Specifications

Supply voltage 12 – 24 Vdc
Self consumption 150mW
Control system Wireless  IEC62386-104 over Thread
Radio support IEEE 802.15.4
Frequency band 2.4 GHz
Max radio tx power +8 dBm
Output load 6A total 0 – 6A per channel
Output load type LED only
Independant channels 4
Bus unit configurations 4 x DT6, 2 x DT8-TC, DT8-RGBW (see bus unit

configuration table)
Wiring| 0.2 – 1.5 mm²
Strip 6 – 7 mm
Operating temperature| 0 to 55°C
Material| PC
Classification| Class III
Ingress protection| IP20

Safety information

  • There are no user serviceable parts, attempting to service any part of the product will void the warranty
  • As the installer, it is your responsibility to ensure you comply to all relevant building and safety codes. Refer to applicable standards for the relevant rules.
  • When the installation is complete, leave this manual with the building’s owner for future reference.

Wiring diagram

zencontrol zc pwm iot 4ch 6a Smart 6A PWM Controller - Wiring
diagram

Wire preparation

Dimensions

Mounting options Inbuilt
Dimensions 80 / 16 / 30 mm

zencontrol zc pwm iot 4ch 6a Smart 6A PWM Controller -
Dimensions

System overview: modes

104 mode is enabled after the device has been added to a 104 application controller such as zc-iot-fc.

zencontrol zc pwm iot 4ch 6a Smart 6A PWM Controller -
overview

Installation

Remove the product from the box and inspect it for any damage. If you believe the product to be damaged or otherwise unsound, do not install the product. Please pack it back into its box and return it to the place of purchase for replacement.
If the product is satisfactory, proceed with the installation:

  1. Ensure safety warnings are adhered to.
  2. Wire according to wiring diagram, as shown in fig 1.
  3. Optional: Break off back tab, and align front tab to case, to install inside field mount case, per fig 2.
  4. Optional: Mount inside mains rated enclosure, such as a luminaire, using mounting tabs, per fig 3.

zencontrol zc pwm iot 4ch 6a Smart 6A PWM Controller -
Installation

Bus unit configurations

Bus unit config. No. of ECG Channel 1 Channel 2 Channel 3 Channel 4
192 (default) 4-Jan ECG index 0
DT6 (LED) ECG index 1
DT6 (LED) ECG index 2
DT6 (LED) ECG index 3

DT6 (LED)
193| 2-Jan| ECG index 0
DT8-TC (cool)| ECG index 0
DT8-TC (warm)| ECG index 1
DT8-TC (cool)| ECG index 1
DT8-TC (warm)
194| 1| ECG index 0
DT8-RGBW (red)| ECG index 0
DT8-RGBW (green)| ECG index 0
DT8-RGBW
(blue)| ECG index 0
DT8-RGBW
(white)

Note: Bus unit configuration RGBW can be set using the zencontrol commissioning application. See support.zencontrol.com for more information.

© zencontrol
zencontrol.com

Documents / Resources

| zencontrol zc-pwm-iot-4ch-6a Smart 6A PWM Controller [pdf] Owner's Manual
zc-pwm-iot-4ch-6a Smart 6A PWM Controller, zc-pwm-iot-4ch-6a, Smart 6A PWM Controller, 6A PWM Controller, PWM Controller
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals