zencontrol zc-smart-relay-vf Wired / Wireless Relay Controller User Guide

June 1, 2024
zencontrol

Inline relay zc-smart-relay-vf

zencontrol zc-smart-relay-vf Wired Wireless Relay
Controller

Product range

Order code Description
zc-smart-relay-vf Wired / wireless relay controller, field mount, dry contact

/ volt free

Specifications

Supply voltage 230 V ~ 50 Hz
Control system Wired  DALI-2 Wireless  IEC62386-104 over Thread
Radio support IEEE 802.15.4
Frequency band 2.4 GHz
Max radio tx power +8 dBm
DALI line current 2 mA
Output load AC 10 A resistive 6 A inductive
Output voltage rating AC 0 – 240V ~ 50 Hz
Max. in-rush AC 165 A   20ms

492 A   1.5ms
Output rating DC| 0 – 25V 3A resistive
25 – 240V 200mA resistive
Output type| Volt free / dry contact
Min. rated relay operations| 40 000
Contact rating| 100mΩ max. (at 1A 6V dc)
Max. operations per hour| 360
Relay type| Non-latching normally open
Wiring| 1 – 4 mm2 Strip 6 – 7 mm
Operating temperature| 0 to 55°C
Material| PC
Classification| Class III
Ingress protection| IP20

Safety information

■ This product must only be installed by a licensed electrician.
■ Before commencing installation turn off and isolate the electrical supply.
■ There are no user serviceable parts, attempting to service any part of the product will void the warranty
■ DALI is not SELV and as such should be treated as LV.
■ As the installer, it is your responsibility to ensure you comply to all relevant building and safety codes. Refer to applicable standards for the relevant rules.

Dimensions

Mounting options Independently mounted control for surface mounting
Fixing centres 125 mm
Dimensions 148 / 44.5 / 30 mm

Installation

Remove the product from the box and inspect it for any damage. If you believe the product to be damaged or otherwise unsound, do not install the product. Please pack it back into its box and return it to the place of purchase for replacement.

If the product is satisfactory, proceed with the installation:

  1. Ensure safety warnings are adhered to.
  2. Release the two end covers using a flatblade screwdriver fig 1.
  3. Mount driver, fig 2 ,and wire the as per the wiring diagram in fig 3.
  4. Replace end covers to ensure adequate strain relief.

Note relay must have an appropriate MCB to protect the load circuit.

zencontrol zc-smart-relay-vf Wired Wireless Relay Controller - Fig
2

Wiring diagram

zencontrol zc-smart-relay-vf Wired Wireless Relay Controller - Fig
3

System overview: modes

  1. 104 mode is enabled after the device has been added to a 104 application controller such as zc-iot-fc. zencontrol zc-smart-relay-vf Wired Wireless Relay Controller - Fig 4
  2. 104 + 101 Bridge mode is enabled after the device has been added to a 104 controller and a 101 power supply has been connected to the DALI terminals.zencontrol zc-smart-relay-vf Wired Wireless Relay Controller - Fig 5
  3. 101 mode is enabled after a 101 power supply has been connected to the DALI terminal and the device has not been added to a 104 application controller.

zencontrol zc-smart-relay-vf Wired Wireless Relay Controller - Fig
7

Notice

For more information on compliant software see our website zencontrol.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>