Carrier 42LSA12 Console Underceiling Indoor Unit User Manual
- June 13, 2024
- Carrier
Table of Contents
- 42LSA12 Console Underceiling Indoor Unit
- Product Information
- Product Usage Instructions
- 41 COOLING/HP 16,5
- 52 COOLING & 45 HP # 52 COOLING & 51 HP
- 61 COOLING/HP 28,5
- 68 COOLING/HP 39,5
- 74 COOLING & 72 HP # 81 COOLING & 78 HP # 88 COOLING & 84 HP
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
42LSA12 Console Underceiling Indoor Unit
Product Information
The Console Underceiling is a cooling and heating unit
manufactured by CARRIER. It is designed for installation and
maintenance by authorized and properly trained installers. The unit
comes in various capacities ranging from 12,000 BTU/h to 60,000
BTU/h. It can be controlled using either a wired or wireless remote
control. The nominal frequency options are 6 – 60 Hz or 5 – 50 Hz,
and the nominal tension is 208/230V.
Product Usage Instructions
-
Installation: Only authorized staff trained by CARRIER should
install the Console Underceiling unit. Follow the installation
procedures outlined in the manual to ensure proper setup. -
Maintenance: Authorized personnel should conduct any repairs or
services to the unit. Do not attempt to perform maintenance if you
are not authorized or properly trained. -
Safety Precautions: Always observe safety warnings and wear
appropriate personal protective equipment when working with the
unit. Keep a fire extinguisher nearby and regularly check its
condition. Turn off the power supply before working on the
unit. -
Reception and Inspection: Do not remove the unit’s packing
until it has reached the installation site. Handle the unit
carefully to avoid damages during transportation. Lift and carry
the unit by holding onto the metal parts, not the plastic side
parts. -
Transportation: Do not shake the outdoor unit during
transportation and avoid inclining it more than 15 degrees
vertically. Take precautions to prevent labor accidents and
promptly move the unit to the installation site or a safe
place.
If you require additional information or have any questions,
please contact us.
Console Underceiling
4
Installation and Service Manual 42 LS
ENGLISH/ESPAÑOL NOTA : Las Instrucciones en Español Empiezan en la Página 20.
1. INTRODUCTION
This manual is addressed to CARRIER authorized and properly trained installers
with the purpose of helping in installation and maintenance procedures.
It is important to stress that any repairs or services can be dangerous if
accomplished by unauthorized personnel. Only authorized staff trained by
CARRIER should install, start up and give any maintenance to the equipment
mentioned on this manual.
If after the reading, shall you still need additional information just get in
contact with us!
2. NOMENCLATURE
42 LS A 18 22 6 C W
EVAPORATING UNIT
CONSOLE MODULE & UNDERCEILING UNIT
INDENTIFICATION IN THE PROJECT CHANGES (VERSION)
12 = 12.000 BTU/h 24 = 24.000 BTU/h 36 = 36.000 BTU/h 48 = 48.000 BTU/h
18 = 18.000 BTU/h 30 = 30.000 BTU/h 42 = 42.000 BTU/h 60 = 60.000 BTU/h
WS – WIRED REMOTE CONTROL .
WITH AIR SWEEP
.
W – WIRED REMOTE CONTROL L
L – WIRELESS REMOTE CONTROL
C – COOLING
G
Q – COOLING AND HEATING
NOMINAL FREQUENCY 6 – 60 Hz 5 – 50 Hz
NOMINAL TENSION 22 – 208/230V
1
3. SAFETY INSTRUCTIONS
The new indoor units 42 LS were projected to offer you a safe and reliable
service when operated within the specifications foreseen in project.
However, due to this same conception, aspects regarding installation, start up
and maintenance should be strictly observed.
WARNING
- Always maintain the fire extinguisher close to the working place. Check the extinguisher periodically to certify it is completely loaded and working perfectly.
- When working in the equipment always observe the safety warnings in the labels attached to the units.
- Always follow all the applicable norms of safety and use clothes and equipment of personal protection. Wear gloves and protection glasses when handling the units or the system refrigerant.
WARNING - Verify the weights and dimensions of the units (see item 13) to guarantee an appropriate and safe handling.
- Learn how to handle the oxyacetylene equipment safely. Leave the equipment in the vertical position inside the vehicle and also in the working place.
- Use dry nitrogen to pressurize and to check the system for leaks. Use a good regulator. Be careful not to exceed 200 psig of test pressure in the rotary compressors.
- Before working in any one of the units always turn off the power supply unplugging the indoor unit from the wall outlet.
- Never introduce the hands or any other object inside the units while the fan is working.
4. RECEPTION AND INSPECTION OF THE UNITS - To avoid damages during handling or transport, don’t remove the unit’s packing until arrive to the defined place of installation.
- Prevent strings, chains or other devices from touching the units.
WARNING - Never lift or carry the evaporator unit by the plastic side parts. Hold it on the metal parts, as shown on figure 1.
FIGURE 1 – HANDLING OF 42 LS UNITS.
- Observe the limit of suitable piling up indicated in the units’ packing.
- Don’t shake the outdoor unit during transportation nor incline more than 15o in the vertical.
- Avoid exposing the machine labor accidents, seeing to it that it is immediately carried to the installation site or a safe place.
- When removing the units from the package and removing the expanded polystyrene protections don’t discard them immediately because they may be useful eventually as protection against dust, or other noxious agents until the building and/or installation is complete and system ready to operate.
5. INSTALLATION
5.1 USEFUL TIPS
First, consult the norms or codes applicable to the installation of the equipment in the selected place, to make sure the system is in accordance to them.
Make also a careful planning of the unit location to avoid interference with any type of existing (or planned) facilities, such as electrical installation, water piping, sewer, etc.
Install the units so that they are free from any type of obstruction from the taking of return air or airflow.
Choose places with enough clearance for repairs or services of any kind and also to make the piping easier(copper tubes that interconnect the units, electrical wiring and drain).
Remember that the units should be leveled after their installation.
Verify if the external place is free of dust or other particles that might obstruct the condenser coil.
2
It is indispensable that the indoor unit possesses hydraulic line for drainage of the condenser. This hydraulic line should not have a diameter less then 1/2″ and should have, right after the exit, a siphon to guarantee a perfect fall and isolation of air. At the start up, this siphon should be filled in with water to avoid taking air from the drainage line. The drainage in the outdoor unit is indispensable only when installed in the high and causing leak risk.
5.2 BASIC PROCEDURES FOR INSTALLATION
- INDOOR UNIT 42 LS
ò CHOICE OF LOCATION ò CHOICE OF POSITION FOR INSTALLATION
ò HOLE IN THE WALL (Ø10cm)
POSITION OF
ò INTERCONNECTION PIPING
INSTALLATION OF HYDRAULIC
ò PIPING FOR THE DRAIN ASSEMBLY
*OUTDOOR UNIT 38RC/38RQ/38NX/38NW/38MS/38CK/ 38YC/38HC/38QC/38HD/38QD
ò CHOICE OF LOCATION
INSTALLATION OF HYDRAULIC
ò PIPING FOR THE DRAIN
ASSEMBLY
*INTERCONNECTION
CONNECTION TO
ò INTERCONNECTION PIPING ò ELECTRICAL CONNECTIONS
FINAL DETAILS
3
5.3 EVAPORATING UNIT INSTALLATION 5.3.1 – GENERAL RECOMMENDATIONS
WRONG
Before installing, read this instructions carefully to get familiar with the unit’s features. Sizes and weights can be found on item 14 on this manual. The following rules apply to all installations.
CORRECT
a) Plan the units’ placement carefully to avoid occasional interference with any existing (or planned) installations, such as electrical installation, water piping, drain, etc.
b) Install the unit so that it is free from any type of obstruction on the air flow, both on the air outflow and air intake.
FIGURE 2 – EVAPORATING UNIT POSITION IN ROOM
c) Choose an installation place with enough clearance for maintenance and general repair.
d) The place should allow for the passage of piping (system pipes, electric wires and drain).
e) The unit should be leveled after installation.
WRONG
5.3.2 – POSITIONING
a) The unit should only be installed horizontally Underceiling, vertically on the floor (console mode) or on the wall (see fig. 4 and 5)
634.3
b) The unit comes with two (2) brackets for Underceiling or on the wall installation. There is also a brace for assembly of the remote control.
c) Fig. 20 indicates the positioning of the screws on the
C
brackets.
d) Install the brackets (figure 3) underceiling by using the screws, nuts and washers.
e) The unit should be positioned so as to distribute the air flow uniformly in the room.
166
278
Capacity (BTU/h)
A
12 and 18.000 1000
24 and 30.000 1380
36 and 42.000 1760
48 and 60.000 2140
B
822 1202 1582 1962
C
792 1172 1552 1932
FIGURE 3 – SIZES FOR EVAPORATING UNIT INSTALLATION
4
300mm MINIMUM
300mm MINIMUM
FIGURE 4 – UNDERCEILING INSTALLATION
FIGURE 5 – CONSOLE ASSEMBLY (ON THE FLOOR) SEE DETAIL A
DETAIL A SCALE 1:4
FIGURE 6 – BRACKET ASSEMBLY
5
5.3.3 – CONDENSATE DRAIN According to the type of installation (console or
under
ceiling), there are two positions on the side plastic parts where the drain
and interconnection pipes must pass through. The following picture shows where
the cover must be broken.
CONSOLE MODE
FIGURE 9 – INEFFECTIVE DRAINING SCENARIO
UNDERCEILING MODE
FIGURE 7 – POSITION WHERE COVERS MUST BE BROKEN
a) Make sure that the unit is leveled, with a slight slant towards the drain
so as to assure a proper draining.
b) Connect the 1/2″ PVC piping to the drain connection (Figure 8).
c) The unit uses drain by gravity. The drain pipes should have declivity,
though. Avoid scenarios like the ones indicated on Fig. 9.
WARNING
When connecting the PVC hose to the machine, do not do it with sudden
movements or too much force, as this may cause leaks. If necessary, heat the
PVC before connecting it or use a flexible hose.
FIGURE 8
6
6. INTERCONNECTION PIPING
6.1. SUSPENSION AND FIXATION OF INTERCONNECTION PIPES
Always try to fasten the interconnection piping in a convenient way through
brackets or porches, preferably both together.
Seal them with circular neoprene bushing and then pass finish ribbon around.
Test all the welded and flared connections looking for leaks (maximum tested
pressure: 200 psig). Use pressure regulator in the Nitrogen cylinder. If
necessary, pass the electric interconnection by the copper tube, as shown on
Figure 10.
LIQUID LINE
TAPE
ELECTRICAL INTERCONNECTION DUCT (OPTIONAL)
SUCTION LINE
ISOLATION
6.2. EVACUATION OF INTERCONNECTION PIPING
TUBES
ISOLATION
The outdoor unit is shipped with enough refrigerant charge for use in a system
with interconnection piping up to 3m, that is, charge for the outdoor unit,
charge for the indoor unit and the necessary charge for an interconnection
piping up to 3m. Since the interconnection pipes are provided in the field,
you should proceed with the evacuation of the lines and of the indoor unit.
The access points are the service valves close to the outdoor unit.
The valves come shut from the plant to retain the refrigerant in the outdoor
unit.
To do the evacuation, maintain the valve shut and connect one side of the
manifold hose to the vent’s valve and the other to the vacuum pump. It is
recommended to proceed the evacuation through both connections of the service
valves simultaneously. The range to be reached should stay between 250 and 500
microns.
OBS: After doing the evacuation, add positive pressure with R-22 so that the
vacuum is broken (see fig. 4).
TAPE
FIGURE 10 – INTERCONNECTION PIPES
To proceed with the refrigerant charge, just maintain the service valve in the
original position (shut) and connect the manifold hose to the vent (valve
Schrader) of the service valve.
OBS: Do not forget to purge the air from the hose. WARNING
For all the necessary information about diameter, charge and connections, see topics 14 and 15.
Before turning on the equipment and after completing the refrigerant charge (if necessary), open the service valves close to the outdoor unit.
CAUTION
Never carry liquid in the suction service valve. Whenever you want to do it,
use the service valve of the liquid line.
7
7 – ELECTRIC INTERCONNECTIONS 7.1 – 42 LS COMMAND 220 V ELECTRIC CHART
8
NEUTRAL 1 POWER
SUPPLY 220 VAC
PHASE
2
GROND 3
COMPRESSOR 4 5
RV 6
TERMINAL BLOCK
CAUTION
On condensors that operate on cooling with the reversion valve energized, the
electric interconnection must be made between P9 and P10 of the Printed
Circuit Board and the reversion valve.
SEE NOTE 1
WHITE BLACK
P 1
NEUTRAL P 2
PHASE
DISPLAY
DISPLAY (FOR UNITS WITH REMOTE WIRELESS CONTROL)
FAN CAPACITOR
FAN
CAPACITOR
RED
P 3
BLUE
P 4
BLACK
P 5
BLACK
P 6
ORANGE
P 7
YELLOW
P 8
FREEZE
LOW
MEDIUM FAN
HIGH COMMON
ROOM
FREEZE
ROOM SENSOR
COMPRESSOR
SEE NOTE 3
P 9
NC
SEE NOTE 2 ORANGE P 10
RV
NO
SEE NOTE 2
VIOLET
P 11
SWP
SWEEP MOTOR
BLACK BLUE
P 12 P 13
MAIN BOARD
SWEEP
(FOR UNITS WITH REMOTE WIRED CONTROL)
CAPTION – – – – LOCALLY MADE WIRING
FACTORY MADE WIRING RV – REVERSION VALVE
1 – MOTOR USED ONLY IN 36, 42, 48, 60K MACHINES 2 – USED ONLY IN QL AND QW MACHINES 3 – MOTOR USED ONLY IN QL, CWS, CL MACHINES
7.2 – 42 LS COMMAND 24 V ELECTRIC CHART
9
NEUTRAL 1
POWER SUPPLY
PHASE 2 GROUND 3 COMPRESSOR 4 RETURN 5
RV 6
TERMINAL BLOCK
TFX
BLUE
WHITE
SEE NOTE 1
FAN MOTOR
CAPACITOR
WHITE
P 1
BLACK
P 2
WHITE
FAN MOTOR
CAPACITOR
RED
P 3
BLUE
P4
BLACK
P 5
BLACK
P 6
SEE NOTE 4
ORANGE
P 7
YELLOW
P 8
NEUTRAL PHASE
DISPLAY
DISPLAY (FOR UNITS WITH REMOTE WIRELESS CONTROL)
FREEZE
LOW
MEDIUM FAN
HIGH COMMON
ROOM
FREEZE
ROOM SENSOR
COMPRESSOR
SEE NOTE 4
SEE NOTE 2
VIOLET
P 9
NC
SEE NOTE 2
ORANGE P 10
RV
NO
P 11
(FOR UNITS
BLACK
P 12
SWEEP
WITH REMOTE WIRED CONTROL)
WHITE
SWP
BLUE
P 13
SEE NOTE 3
SWEEP MOTOR
MAIN BOARD
CAUTION
On condensors that operate on cooling with the reversion valve energized, the
electric interconnection must be made between P9 and P10 of the Printed
Circuit Board and the reversion valve.
CAPTION – – – – LOCALLY MADE WIRING
FACTORY MADE WIRING TFX – 220/24 V TRANSFORMER RV – REVERSION VALVE
1 – MOTOR USED ONLY IN 36, 42, 48, 60K MACHINES 2 – USED ONLY IN QL AND QW MACHINES 3 – MOTOR USED ONLY IN QL, CWS, CL MACHINES 4 – WHEN USING 38NX/NW/RC/RQ CONDENSERS IT IS NECESSARY TO DISCONNECT THE ORANGE CABLE(S) FROM THE TRANSFORMER AND CONNECT IT (THEM) TO TERMINAL 2 ON THE TERMINAL BLOCK
8. INITIAL START – UP
9. COOLING SYSTEM
Before turn the unit on, check the conditions above and the following items: *
Verify the appropriate fixation of all the electrical
connections;
- Make sure there is no refrigerant leakage;
- Make sure the power supply is compatible with the electrical characteristics of the unit;
- Make sure the compressors can move freely on the vibration insulators of the outdoor unit;
- Make sure that all the service valves are in the correct operation position;
- Make sure the area around the outdoor unit is free of any obstruction in the taking or discharge of the airflow;
9 .1 – EXPANSION SYSTEM
The evaporator units are factory-equipped with a system for refrigerant gas
expansion called piston.
As shown below, this system has a small piece with a fixed, calibrated, easily
removable hole inside a nipple to connect a 3/8″ flare nut on the liquid line.
The piston application properties include a more accurate refrigerant gas flow
into the evaporator compared, for instance, with the capillary system.
Besides, pistons are easy to handle.
On reverse cycles (heating and cooling), the piston system requires a by-pass
system, that is, two pieces are placed inside the nipple, one performing the
expansion process and the other as a by-pass and vice-versa according to the
gas flow direction (cooling or heating mode).
- Make sure to have a perfect drainage and no blockage in the drain’s hose of the unit;
EXPANSION DIRECTION
- When the outdoor temperature is too low, there will be a risk of freezing the indoor unit if the operation speed was adjusted to the minimum condition (cooling mode).
CAUTION
The fan motors of the units are lubricated in the plant. Dont lubricate when
installing the units. Before turning on the motor, make sure the propeller or
turbine fan is not loose.
BY – PASS DIRECTION
10
10. MAINTENANCE
10.1 GENERALITIES CAUTION
If, however, the residual pressure is too low, a nitrogen cylinder should be connected to the system (use one of the service valves existent in the units).
Before executing any maintenance services turn off the power that feeds the
unit through the indoor unit.
To avoid unnecessary repair services, check the following points carefully:
- Is the unit correctly connected to the main power, with the entire manual and/or automatic devices of control/ protection of the circuit appropriately connected, without any interruptions such as: burned fuse, open switches, etc.?
- Is the thermostat correctly adjusted for the desired conditions?
- Is the fan’s switch button in the correct position?
10.2 PREVENTIVE MAINTENANCE
Then, pressurize the unit up to 200 psig. Depending on the method to be used,
a small amount of refrigerant should be added to the system. Add refrigerant
first, then the Nitrogen.
10.4.1 METHODS DETECTION
- Electronic Detector (refrigerant + Nitrogen)
Search the leakage, passing the sensor of the unit close to the connections, welding and other possible leak points. Use low speed when moving the sensor. The equipment emits a sound or a luminous sign when passing by the leak point.
CLEANING – Clean the outdoor unit with a soft brush, if necessary use also a
vacuum cleaner to remove the dirt. After this operation, use a comb for fins,
upwards, in order to smooth then out. The dust accumulation obstructs and
reduces the airflow resulting in capacity loss.
Clean the casings with a flannel or soft cloth soaked in warm water and
neutral soap. DO NOT USE solvents, carbon tetrachloride, waxes containing
solvent or alcohol to clean the plastic parts.
WIRING – Check all the cables looking for deterioration and all the electrical
connections for squeeze and corrosion.
ASSEMBLAGE Make sure the units are installed firmly.
CONTROLS – Make sure that all the controls are working correctly and that the
units operation is normal. Vibrations can cause undesirable noises.
DRAIN – Verify blockages or creases in the drain’s hose. This can cause an
overflow in the base pan and consequent leakage of the condensed water.
10.3 CORRECTIVE MAINTENANCE
- Halide – Light Detector (refrigerant + Nitrogen)
Similar procedure to the previous one, but in this case the sensor is replaced by a hose that is connected to a flame. Upon reaching a halogen refrigerant (R11, R12, R22, etc.) this flame turns green.
CAUTION Do not inhale the resulting gases from the refrigerant burn because they are highly toxic. - Solution of water and soap
Prepare a solution with soap or detergent and spread it on the connections, welds and other possible leak points.
Wait at least 1 minute to check where a bubble may form.
CAUTION
When in external environment, the wind can make the search difficult. A very poor soap solution is also inadequate because it wont form bubbles.
It should be done in situations where a component
obstructs the perfect operation of one or both the units. * Method of Immersion On these occasions, it is necessary to consult the wiring
diagrams fixed in the units.
The Method of Immersion in tank could be used for
10.4 DETECTION OF LEAKAGE
inspection in separated components of the unit (especially coils). In this case, the component should be pressurized
to 200 psig.
When there is suspicion leakage on the cooling mode,
you should proceed as follows: In case there is still enough pressure of refrigerant in
WARNING
the system, you may go straight to the detection the leakage Do not mistake air bubbles between the fins for leakage.
through one of the processes indicated below.
11
10.4.2 REPAIRING THE LEAKAGE
After locating the leakage, mark the place appropriately and remove the
pressure of the system by eliminating the refrigerant and/or Nitrogen, which
might exist.
Prepare to do the welding (use Phoscopper weld or silver weld), proceeding it
with passage of Nitrogen inside the tube (during the welding and at low
pressure), avoiding the formation of oxides inside the tube.
Make sure the repair was successful, pressurizing and testing the unit again.
10.5 PROCEDURE OF VACUUM AND REFRIGERANT CHARGE
remain steady either the system still contains humidity or there must be a leakage. Always verify all the connections (points 1, 3 and valves).
- High Vacuum Method
It is applied with a vacuum pump capable to reach vacuum lower than 200 microns in only one evacuation.
Proceed as follows: 1. Turn on the vacuum pump, then open valve 1 (fig 19). Later on, isolate the vacuum pump and open the valve. 2. When a reading lower than 200 microns is obtained (try to reach the lowest possible value), the vacuum procedure will have been completed.
10.5.1 DEHYDRATION
Every system that has been exposed to the atmosphere should be properly
dehydrated. That is possible if we accomplish appropriate evacuation.
To make a proper evacuation, it is necessary to have a VACUUM PUMP (not
compressor) and a vacuum gauge.
The procedure is the following: First the access points to the system must
be defined. Use the service valves in the outdoor unit on both the drop and
the discharge sides (liquid line). That is, high-pressure valve connected to
the piping of smaller diameter and the low-pressure valve connected in the
piping of larger diameter. Only then is it possible to evacuate the system.
Basically, we can do in two ways:
- Method of Dilution
Turn on the vacuum pump and make the vacuum in the pump (valve 1 shut – fig. 18).
Open valve 1 and let the system evacuate until it reaches at least 500 microns. To obtain the measure, close valve 1 and open valve number 2, allowing the vacuum gauge to feel the system pressure. After reaching 500 microns, isolate the vacuum pump and open valve 3, letting the Nitrogen in to break the vacuum. Isolate the Nitrogen cylinder.
Purge the Nitrogen through the connection that links the copper passage to valve 3.
Repeat the procedure at least twice, doing in the last stage the third evacuation.
At the end of this process, at least 200 microns should be obtained.
CAUTION
Never disconnect the copper tube of valve 3; just loosen the connection to purge the Nitrogen
WARNING
The pump oil should be replaced periodically in order to guarantee the vacuum
efficiency.
10.5.2 REFRIGERANT CHARGE
After evacuating the system appropriately, close the valves of the manifold
and isolate the vacuum pump, the vacuum gauge and the Nitrogen cylinder.
To do the refrigerant charge, replace the Nitrogen cylinder shown in Fig. 18
with a refrigerant cylinder. Purge the hose that links the cylinder to the
service valve.
Open the service valve which gives access to the refrigerant cylinder and then
the high-pressure valve of the manifold.
To load the system appropriately, verify in the identification labels of the
units the amount of refrigerant that should be added to the system (see item
6.4 of this manual).
Remember that the charge varies according to the interconnection piping length
of the units.
With the system shut down, load the refrigerant in liquid form through the
service valve of liquid line (smaller diameter).
For help, use a scale (if not using a graduate cylinder). Allow at least 10
minutes before turning the unit back on.
Close the discharge valve of the manifold, open the suction valve and with the
system in operation complete the charge with refrigerant in gas form (between
5% and 20% the total). Check in the scale the refrigerant weight added to the
system. When the charge is complete close the suction valve of the manifold,
disconnect the suction and discharge hoses.Close the cylinder valve.
The charge procedure will be complete.
In order to obtain a precise reading of vacuum one should isolate the vacuum pump from the system. Close valve 1 and wait about 5 to have a precise measure. If the reading doesn’t
Note: The total refrigerant charge is the sum of the charges of the indoor and outdoor units plus the interconnection piping. See item 13 for estimated charge values.
12
10.6 INTERNAL CLEANING OF THE SYSTEM
The burn of an electrical motor is recognized by the characteristic smell.
When a motor of a hermetic compressor burns, the stator winding seal forms
carbon and acid mud, in this case, clean the refrigerant circuit before
installing a new compressor. Install a new capillary tube and out door
condenser filter.
10.8 GENERAL CARE
- Maintain the casing and the grills as well as the area around the unit as clean as possible.
- Periodically clean the coils with a soft brush. If the fins are too dirty, use a jet of compressed air or water at low pressure in the opposite direction of the airflow. Be careful not to damage the fins.
10.7 REFRIGERANT WITHDRAWAL
- Verify the tightness of the connections, flanges and other fixations, preventing the occurrence of vibrations, leakage or noises.
If for any reason there is need to remove/lose refrigerant, the service valves of these units allow to remove refrigerant from the system into the outdoor unit.
Make sure that the insulation of the metallic parts and pipes are in the correct place and in good conditions.
Procedure:
Step 1: Connect manifold hoses to the vents of the outdoor unit service valves.
Step 2: Close the service valve of 1/4″ liquid line.
Step 3: Turn on the unit in cooling mode until that the system pressure reaches 2 psig. Then, close the service valve of the suction line 3/8 ” so that the refrigerant gas remains withdrawn.
GAS OUTFLOW FAUCET
CHARGE CYLINDER
CHARGE VIEWER
3
GAS OUTFLOWN
FAUCET
1
3
2
VACUUMMETER
VACUUM PUMP
NITROGEN CYLINDER WITH PRESSURE REGULATOR
HIGH PRESSURE MANOMETER LOW PRESSURE MANOMETER
EVAPORATOR
SUCTION LINE LIQUID LINE
CONNECTIONS
FIGURE 11 – CHART FOR OBTAINING VACUUM AND FOR REFRIGERANT CHARGING. 13
CONDENSER
11. TROUBLESHOOTING GUIDE
Table guide of possible occurrences in the air conditioning equipment, with the possible causes and the corrections to be done.
OCCURENCE
POSSIBLE CAUSES
SOLUTIONS
Compressor and motors of the outdoor and indoor units work but the room is not efficiently refrigerated.
Thermal capacity of the unit is insufficient for the room.
Incorrect or bad installation.
Evaluate the thermal load and instruct the customer to change the unit to
another model of higher capacity, if necessary.
Check the installation place observing height, location, sun rays in the
outdoor unit, curtains in front of the unit etc.. Reinstall the unit.
Leakage of gas.
Detect the leakage, repair it and reset the unit.
Coil obstructed with dirt.
Remove obstructions from the indoor and outdoor units
Low operation voltage.
Voltage supplied below the minimum tension
Compressor without compression. Low fan speed. Filter and/or capillary tube obstructed. Thermostat and switch button. Service valve shut or partially shut.
Replace the compressor.
Check the capacitor phase of the fan motor and the fan motor itself, replacing
it if necessary.
Replace the filter and capillary. In this case the indoor unit generally gets
blocked with ice.
Adjust the thermostat and the switch correctly, according to instructions of
the owners guide.
Open the valve(s).
Compressor doesnt Power cord unplugged or with bad
work
contact.
Low or high voltage.
Defective switch button/remote control.
Defective Thermostat.
Blocked compressor.
Overloaded circuit causing a breakdown on tension.
Excess of refrigerant.
Defective thermal protector of the compressor (open).
Incorrect electrical connections or broken wires.
Place the power cord appropriately in the power supply.
See item 7.2. An automatic stabilizer with potency in Watts appropriate for
the unit can be used.
Use an ohmmeter to detect the defect. If necessary, change the switch
button/remote control.
Replace the thermal protector.
Proceed the compressors start up, according to instructions in the Service
Manual of the Training Section (AT-MS-B-03/89), in case it doesnt work,
replace it.
The unit should be connected to an exclusive wall receptacle.
Check it and purge if necessary.
Replace the thermal protector.
Check the wiring, repair or replace it. See the units wiring diagram.
14
OCCURENCE
Fan motors dont work
POSSIBLE CAUSES
Power cord unplugged or with bad contact.
Defective fan motor.
Defective Capacitor.
Defective switch button/remote control.
Compressor doesnt operate on heating mode
Incorrect electrical connections or broken wires.
Propeller or blower wheel loose or blocked Defective solenoid of reversing
valve (burned).
Defective defrost thermostat (open).
SOLUTIONS
Place power cord appropriately in the power supply.
Proceed the direct start up of the fan motor, in case it doesnt work, replace
it. Use an ohmmeter to detect the defect and if necessary, change the
capacitor. Use an ohmmeter to detect the defect, if necessary change the
switch button/remote control. Check the wiring, repair or replace it. See the
units wiring diagram. Check, fastening it correctly.
Replace the solenoid.
Replace the reversing valve.
Defective switch button/remote control. Incorrect connections or broken wires. Thermostat button settled on cooling.
Use an ohmmeter to detect the defect. If necessary, change the switch
button/remote control.
Check the wiring, repair or replace it. See the units wiring diagram.
Adjust the thermostat correctly.
Evaporator bloked by ice.
Excessive noise during the operation.
Bloked piston.
Start the unit again, opening the nipple. It is advisable to clean the components with liquid R22 or R-11 jets.
Leakage of gas.
Eliminate the leakage and change all the refrigerant.
Gaps in the axis/bearings of the fan motors.
Vibrating piping.
Loose parts.
Replace the fan motor.
Check the place where the noise comes from and eliminate it. Check and wedge
or fix them correctly.
Broken internal suspensions spring of Replace the compressor. compressor.
Propeller or blower wheel uneven or broken.
Replace it.
Incorrect installation. Normal.
Improve installation (reinforce the pieces that have fragile structure).
Teach the customer.
15
12. SCHEDULE OF PREVENTIVE MAINTENANCE
ITEM
SERVICES DE SCRIPTION
General inspection in the equipment installation, short circulation of air, distribution
1º
of the airflow of the units, blockage in the entrance and exit of air from the outdoor
unit, exposure to thermal load.
2º Check electrical installation.
3º Wash and dry the air filter.
4º Measure tension and operation current and compare then to the nominal one.
5º
Measure tension with blocked rotor and watch for tension decrease till the protector turns off.
6º
Check tightness of all the electrical terminals of the units, avoiding possible bad contacts.
7º
Check dirt obstruction and kneaded fins.
8º
Check possible blockages or creases in the drain hose.
9º
Clean of the casings.
10º Measure temperature differentia.
11º Check for gaps in the axis of the electrical motors.
12º Check positioning, fixation and evening of the propeller or blower wheel.
13º Check thermostat operation, switch button.
14º Measure balance pressures
15º Measure operation pressures
Frequency code: A – monthly B – quartely C – twice a year
FREQUENCY ABC
16
13. TECHNICAL FEATURES
MODELS
NOMINAL CAPACITY
(BTU/h)
42LSA12 12000
SUPPLY
(V-Ph-Hz)
208/230-1-60
FULL CHARGE
CURRENT MOTOR
0,6
FULL CHARGE
CURRENT MOTOR
100
START-UP CURRENT MOTOR
BREAKER REFRIGERANT EXPANSION SYSTEM (PISTON) NET WEIGHT (KG) SIZES 42 (mm) LxAxP DRAIN DIAMETER (IN)
FAN FINS
TYPE QUANTITY OUTFLOW (m3/h) SURFACE AREA (m²)
ND 10
41 COOLING/HP 16,5
1000 X635 X265
02 578 0,18
42LSA18 18000
208/230-1-60
0,7
42LSA24 24000
208/230-1-60
0,83
130
160
1,31
1,48
15
15
R – 22
52 COOLING & 45 HP # 52 COOLING & 51 HP
22
28,5
1000 X 635 X 265
1380 X 635 X 265
1/2
CENTRIFUGAL
02
02
850
1215
0,18
0,28
42LSA30 30000
208/230-1-60 0,79
160
1,57 20
61 COOLING/HP 28,5
1380 X 635 X 265
02 1255 0,28
MODELS
NOMINAL CAPACITY
(BTU/h)
SUPPLY
(V-Ph-Hz)
FULL CHARGE CURRENT MOTOR
FULL CHARGE CURRENT
MOTOR
START-UP CURRENT
MOTOR
BREAKER
REFRIGERANT
EXPANSION SYSTEM (PISTON)
NET WEIGHT (KG)
SIZES 42 (mm) LxAxP
DRAIN DIAMETER (IN)
TYPE
FAN
QUANTITY
OUTFLOW (m3/h)
FINS
SURFACE AREA (m2)
42LSA36 36000
208/230-1-60 1,5
320
1,9 20
68 COOLING/HP 39,5
1760 X635 X265
04 1761 0,38
42LSA42 42000
208/230-1-60
1,7
42LSA48 48000
208/230-1-60
1,7
42LSA60 60000
208/230-1-60
1,7
360
360
300
ND
2,62
2,62
25
25
ND
R – 22
74 COOLING & 72 HP # 81 COOLING & 78 HP # 88 COOLING & 84 HP
39,5
47
47
1760 X 635 X 265
2140 X 635 X 265
1/2
2140 X 635 X 265
CENTRIFUGAL
04 1827 0,38
04 2167,5
0,47
04 2167,5
0,47
14. GENERAL INSTALLATION TIPS
CAPACITY BTU/h
SUCTION CONNECTIONS DIAMETER
42LS
12K
1/2
18K
5/8
24K
5/8
30K
3/4
36K
3/4
42K
7/8
48K
7/8
60K
7/8
-
FOR GREATER LENGTHS THAN THE INDICATED ONES, CONSULT CARRIER.
-
UNITS AND EVAPORATORS HAVE FLARE-NUT TYPE VALVES. 17
LIQUID CONNECTIONS DIAMETER
42LS 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>