EVO HEAT Edge-i Series Side Discharge Inverter Pool Heater Instruction Manual

June 13, 2024
EVO HEAT

EVO HEAT Edge-i Series Side Discharge Inverter Pool Heater

Product Information

Model| kW Range| Normal Running Current (A)| Power Supply| Connection Type| Fan Quantity| Fan Speed (RPM)| Air Flow (m3/h)| Noise at 1M (dB)| Noise at 1M (Silent Mode) (dB)| Refrigerant Gas| PVC Water Connection (mm)| Water Flow Volume (L/min)| Water Pressure Drop (Max) (kPa)| Net Dimensions L/W/H (mm)| Net Weight (kg)
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Edge-i 7| 3.26-7.45| 1.57-5.35| 220-240/1/50| 10amp| 1| 600-800| 2000| 40-46.5| 40| R32| 40| 66.67| 3.2| 1034 / 450 / 626| 67
Edge-i 9| 3.26-9.17| 1.57-7.00| 220-240/1/50| 10amp| 1| 600-800| 2000| 40-46.5| 40| R32| 40| 66.67| 3.2| 1034 / 450 / 626| 67
Edge-i 13| 3.6-11.47| 0.8~8.6| 15amp| 1| 500-900| 2300| 43-50| 43| R32| 40| 76.67| 4| 1034 / 450 / 626| 67
Edge-i 17| 6.6-16| 2.40-12.89| hardwired| 1| 500-800| 3800| 43-53| 43| R32| 39.5| 115| 7.5| 1040 / 490 / 768| 87
Edge-i 20| 6.57-18.10| 2.48-12.9| hardwired| 1| 500-850| 4000| 39.5-52.5| 39.5| R32| 115| 128.33| 8.8| 1171 / 510 / 858| 98

Product Usage Instructions

Pre-Installation:

  1. Position the heater on a level pad in the desired location on the pool water return line.
  2. Install the supplied antivibration rubber pads under the feet of the unit.
  3. Install the supplied condensation barb to the underside of the unit and direct the condensation to an appropriate drainage point.

Airflow Clearances:

Ensure the heater is installed in a well-ventilated area with plenty of fresh air. Maintain a minimum gap of 1500mm between walls/fences on the sides and 500mm overhead clearance.

Plumbing Installation:

Note: Evo heat pumps standard plumbing fitting size can accept 32mm or 50mm NB PVC pipe for connection to the pool or spa filtration plumbing.

  1. Attach the supplied barrel unions to the cold inlet and hot outlet (hand tighten).
  2. Use plumbing tape and ensure the ‘O’ ring is in position when sealing.
  3. Install a 3-way valve at the cold-water inlet and create a bypass by connecting a T piece to the heated line.
  4. Make the plumbing connections and brace pipework where necessary.

Introduction

This manual contains information relating to the installation, troubleshooting, operation, and maintenance of this EvoHeat unit. Instructions in this manual must always be followed. Failure to comply with these recommendations will invalidate the warranty. Should you have any questions or require technical support, call the EvoHeat office on 1300 859 933 to speak to our team.

The Evo Edge-i inverter heat pump is our latest innovation in domestic pool and spa heating and cooling. Thanks to its unique rear intake and side discharge design, the Evo Edge-i can be installed almost anywhere! Designed with our latest stepless full DC inverter compressors, fans, and control systems – all working in perfect harmony to provide optimised year round heating and cooling with the lowest operating costs.

Heating Output

(27°C Air/26°C Water)

|

kW

|

3.26-7.45

|

3.26-9.17

|

3.6-11.47

|

6.6-16

|

6.57-18.10

---|---|---|---|---|---|---
Heating Output

(15°C Air/26°C Water)

|

kW

|

2.09-5.34

|

2.09-6.62

|

1.77-8.55

|

3.62-11.38

|

4.45-13.20

C.O.P. at 27°C Air| | 11.24~6.07| 11.24~5.73| 12.19~5.69| 12.0~5.43| 11.53~6.11
Consumed Power at 27°C Air|

kW

|

0.29-1.227

|

0.29-1.6

|

0.295-2.016

|

0.55-2.95

|

0.57-2.96

Normal Running Current| A| 1.57-5.35| 1.57-7.00| 0.8~8.6| 2.40-12.89| 2.48-12.9
Power Supply| | 220-240/1/50
Connection Type| | 10amp| 10amp| 15amp| hardwired| hardwired
Fan Quantity| | 1| 1| 1| 1| 1
Fan Speed| RPM| 600-800| 600-800| 500-900| 500-800| 500-850
Air Flow| m3h| 2000| 2000| 2300| 3800| 4000
Noise at 1M| dB(A)| 40-46.5| 40-46.5| 43-50| 43-53| 39.5-52.5
Noise at 1M (Silent Mode)| | 40| 40| 43| 43| 39.5
Refrigerant Gas| | R32
PVC Water Connection| mm| 40
Water Flow Volume| L/min| 66.67| 66.67| 76.67| 115| 128.33
Water Pressure Drop (Max)| kPa| 3.2| 3.2| 4| 7.5| 8.8
Net Dimensions L/W/H| mm| 1034 / 450 / 626| 1034 / 450 / 626| 1034 / 450 / 626| 1040 / 490 / 768| 1171 / 510 / 858
Net Weight| kg| 67| 67| 67| 87| 98

The data above is based on the Evo heat pump only, it does not include auxiliary devices. Product specification information provided above is correct at the date of printing, this data may change without notice. Please speak with an EvoHeat Specialist for the most current product specifications.

Dimensions

IMPORTANT THINGS TO NOTE

  • Ensure you meet the minimum clearances and recommended installation locations as outlined in the manual.
  • All heat pump accessories are contained in a plastic bag inside the packaging of your heat pump unit.

PRE-INSTALLATION

  1. Position the heater on a level pad in the desired location on the pool water return line (as shown in the example image below).
  2. Install the supplied antivibration rubber pads under the feet of the unit.
  3. Install the supplied condensation barb to the underside of the unit and direct the condensation to an appropriate drainage point.

AIRFLOW CLEARANCES
Ensure the heater is installed in a well-ventilated area with plenty of fresh air, a minimum gap between walls/fences etc of 1500mm on the sides and 500mm overhead clearance.

PLUMBING INSTALLATION
NOTE: Evo heat pumps standard plumbing fitting size can accept 32mm or 50mm NB PVC pipe for connection to the pool or spa filtration plumbing.

  1. Attach the supplied barrel unions to the cold inlet and hot outlet (hand tighten).
  2. Use plumbing tape and ensure the ‘O’ ring is in position when sealing.
  3. Install a 3-way valve at the cold-water inlet and create a bypass by connecting a “T” piece to the heated line.
  4. Make the plumbing connections and brace pipework where necessary.

ELECTRICAL CONNECTION
NOTE: Electrical connection should only be completed by licenced personnel and in accordance with all relevant Australian Standards, applicable laws and local legislations.

  1. Remove the external cover to the electrical terminal by removing the screws and the terminal cover panel.
  2. Feed the electrical cable in through the conduit nipple and attach the electric supply wires to the applicable Active Neutral and Earth connections located in the electrical terminal.
  3. To complete the electrical connection, install electrical conduit, UF cable or other suitable means as specified (as permitted by local electrical authorities) and connect the cable to a dedicated power supply branch circuit equipped with the appropriate size circuit breaker, or time delay fuse protection.

INITIAL STARTUP & COMMISSIONING
NOTE: The water pump must be running and water circulating through the heat pump for the system to operate.

  1. Turn on your water filter pump and check for water leaks and verify flow to and from the pool.
  2. Turn on the electrical power supply to the EvoHeat unit
  3. Press the ON/OFF button of the controller so that the outlet temperature is displayed on screen, the unit will start within 60 seconds.
  4. Press the MODE button to select a mode, continue pressing the button until the small sun icon appears for heating.
  5. Go back to the main menu, press the UP or DOWN arrow keys to adjust the target temperature settings. Leave the new temperature idle on the screen for 5 seconds to automatically save the adjustment.
  6. After the system has been running for approximately 5 minutes, check the Temperature Differential (TD) of the entering cold water to the exiting heated water.
    • a. On the main screen, the larger numbers on the display refer to the outlet water temperature. The smaller numbers below this refer to the inlet water temperature.
    • b. Review the inlet and outlet water temperatures and adjust the water flow by opening or closing the 3-way valve installed at the cold-water inlet to achieve a target TD of approximately 2°C (ex. 26°C inlet water and 28°C outlet water).
  7. If there is any interruption to water flow (i.e. when the water pump is turned off), the unit will automatically turn off and display an E03 error code – no water flow. This is normal and the system will restart once water flow is reinstated.

INITIAL HEAT UP TIME
Initial heat up times will vary depending on the size of your pool, environmental conditions and the capacity of the system installed. After installation please allow the unit and pool pump to run continuously until the desired pool water temperature is reached (it may take several days for the pool to initially reach the set temperature). Once the pool water reaches the desired set temperature, the unit will shut off. The unit will automatically restart (provided your pool pump is running) when the pool temperature falls more than 1°C below the desired set temperature.

Safety Instructions

Installation, repair, or relocations must only be done by a fully qualified technician. If done incorrectly there is a number of hazards that can occur including fire, electric shock, water leakage and injury.

  • A circuit breaker must be installed for the unit.
  • Ensure the unit has a good power connection and earthing to avoid the risk of electrical shocks.
  • Do not use any means to accelerate the defrosting processor or to clean other than those recommended by EvoHeat.
  • The unit must be stored in a room without any continuously operating ignition sources (for example: open flames, an operating gas appliance)
  • Do not pierce or burn the unit.
  • If the supply cord is damaged, it must be replaced by a qualified service agent.
  • This appliance must be installed in accordance with national wiring regulations.
  • Before obtaining access to terminals all supply circuits must be disconnected.
    The unit is equipped with an over-load protection system. After a previous stoppage, the unit will not start for at least 3 minutes.
    Be aware that refrigerants may not contain an odour.

An all-pole disconnection device must be incorporated which as at least 3mm clearances in all poles, a leakage current that may exceed 10mA, residual current device (RCD) having a rated residual operating current not exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.

WARNING

  • THIS PRODUCT CONTAINS A BUTTON BATTERY
  • If swallowed, a lithium button battery can cause severe or fatal injuries within 2 hours.
  • Keep batteries out of reach of children.
  • If you think batteries may have been swallowed or placed inside any part of the body, seek immediate medical attention.

Installation

  • The unit should be installed, operated and stored in a room with a floor area larger than 30m2.
  • The installation of pipe-work should be kept to a minimum 30m2
  • Spaces where refrigerant pipes are present must comply with national gas regulations.
  • Use supply wires suitable for 75°C

Transport

When transporting equipment containing flammable refrigerants:

  • Comply with transport & local regulations
  • Equipment must be stored safely in accordance with the instructions within this manual.
  • Abide by any signage on the packaging
  • The unit must be protected from damage and potential leak of the refrigerant charge.

*Caution: Single wall heat exchanger, not suitable for potable water connection.

Installation

System Installation
Upon receiving the unit, check the packaging for any obvious signs of damage. Inform EvoHeat immediately if there is any evidence of rough handling. When the heater has been removed from the packaging check the refrigerant gauge on the front panel of the unit. The gauge should be showing a pressure of approx. 10 – 20 on the outside red band – any less than this figure means there may be a leak in the refrigerant system, and you should immediately contact your EvoHeat Dealer.

Only the main unit and the water unit in the illustration are provided; the other items are necessary spare parts for the water system that are to be provided by customer or the installer.

When starting for the first time:

  1. Open valve and charge water.
  2. Make sure that the pump and the water-in pipe have been filled with water.
  3. Close the valve and start the unit.
    The schematic diagram is for reference only. Please check the water inlet/outlet label on the heat pump while plumbing the unit.

IMPORTANT: EvoHeat heat pumps MUST be connected by a licensed electrician. Under no circumstances should an unlicensed person attempt to install or repair an EvoHeat heat pump themselves. Heater electrical installation undertaken by an unlicensed installer will void the warranty. Correct installation is required to ensure safe and efficient operation of your pool heater.
Before installation it is very important to ensure 5 variables are carefully checked to allow the unit to operate correctly.

  • Heater Condition
  • Location
  • Clearances & Air Flow
  • Adequate water flow & plumbing
  • Correct electrical connection & supply

Location of Installation
Evo recommend the heat pump should ONLY be installed in an outdoor location with appropriate ventilation. Installing the heater indoors without adequate ventilation, or in a poorly ventilated enclosed space, will result in very poor performance and can, in extreme cases, damage the heater.

The Evo unit should be installed:

  • At least 3.5m away from the water’s edge.
  • No greater than 7.5m from the water’s edge (to avoid heat loss from the piping).
  • No greater than 5m below the water level of the pool/spa.

Make sure the heat pump is not located where large amounts of water may run- off from a roof into the unit. Sharp sloping roofs without gutters will allow excessive amounts of rainwater mixed with debris from the roof to be forced through the unit. A water deflector may be needed to protect the heat pump. Ensure the heat pump is not installed close to harsh or corrosive chemicals. The heat pump should be installed on a flat level surface. If a suitable outdoor location is unavailable please contact EvoHeat for specialist technical advice.

Airflow Clearances

Ensure the heater is installed in a well-ventilated area with plenty of fresh air, a minimum gap between walls/fences etc of 1500mm on the sides and 500mm overhead clearance. At minimum gap of at least 50mm is required at the rear of the unit.
Leave sufficient space for unobstructed airflow into and out of the heater. Do not locate the heater in an enclosed area, or the discharged cold air will recirculate into the unit and consequently lower the heating efficiency as well as possibly icing up.
If the installation location does not comply with these suggested clearances, contact EvoHeat’s Tech Support to discuss possible solutions.

Adequate Water Flow
All EvoHeat heat pumps have a factory pre-set internal water flow switch. If there is insufficient water flow the unit will not operate.
It is VITAL that that there is sufficient water flow to the unit. Incorrect water flow can cause a loss of efficiency and possible damage to the unit. Optimal water flow rates are listed within this manual. It is imperative that water flow is kept as close as possible to these flow rates. Before connecting the heater to the plumbing all piping must be thoroughly flushed to ensure no debris can enter the heater. Failure to remove pipe debris can jam or damage the flow switch and may cause damage to the heater. When cleaning the pool, it is advisable to turn off your heater as restricted water flow may cause the heater to shut down and indicate low water flow fault (E03 error) or high pressure fault (E01 Error).
A Variable speed pump or bypass valve and plumbing MUST be fitted to allow water flow to be adjusted through the heater. Do not direct connect a water pump with higher flow than required to the heat pump.

Rubber Feet
All EvoHeat units are provided with rubber feet which we highly recommend being installed. The rubber feet help reduce vibration of the unit and provide a space below the heat pump to install the drainage barbs.

Condensate Drain Barb

Fit the condensate drain barb into the 2 holes under the unit if you need to direct water away from the heater. If the barb is too stiff, place it in hot water to soften.

Drainage & Condensation

During operation, water in the air condenses on the fins of the evaporator. In high humidity, the condensate may be several litres per hour, giving the impression that the unit is leaking. This process is a normal function of heat pumps.

The heater will automatically activate reverse cycle or de-icing mode when required which also increases condensate discharge. This normally occurs at temperatures below 8˚C. The condensate water will discharge through the base of the heater. As an option, a 20mm clear vinyl tube pipe can be connected by hand to the drain on the base of the unit to direct condensate water to an appropriate location.

NOTE
A quick way to verify that the water is condensation is to shut off the unit and keep the pool pump running. If the water stops running out of the base pan, it is condensation. Another method is to test the drain water for chlorine – if the is no chlorine present, then it’s condensation

Plumbing
The unit’s exclusive rated flow titanium heat exchanger requires no special plumbing arrangements except bypass (set the flow rate according to the nameplate). The water pressure drop is less than 10kPa at max.

Flow Rate
Since there is no residual heat or flame temperatures the unit does not need copper heat sink piping. PVC pipe can be run straight into the unit.

Location
Connect the unit in the pool pump discharge (return) line downstream of all filter and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

  • Standard models have slip glue fittings which accept 32mm or 50mm PVC pipe for connection to the pool or spa filtration piping. By using a 50NB to 40NB you can plumb 40NB.
  • Consider adding a quick coupler fitting at the unit’s inlet & outlet to allow easy draining of the unit and to provide easier access should servicing be required.
  • Ensure pipework connecting to the inlet/outlet unions is appropriately supported, any movement in this pipework can caused the rubber O-ring to pinch and leak.

Electrical Connection

Always use a suitably qualified Electrician to perform any electrical work, they must read the manual before connecting.

Ensure all cabling, circuit breakers, and protections are of a suitable size and specification in accordance with electrical wiring legislation for the heater being installed. Ensure to check that there is adequate voltage and current available at the heater connection to run the unit. Voltage range should be 220-240 volts for single phase, and 380-415 volts for 3 phase units. Voltage ranges outside these parameters will cause heater damage and void your warranty.

  1. Ensure power is disconnected during installation or service.
  2. Always comply with the national and local electrical codes and standards.
  3. Ensure the electrical cable size is adequate for heater requirements at the installation location.
  4. The heater must be equipped with a circuit breaker and isolation device.
  5. The circuit breaker must be installed between the heater and the water circulation pump if the water pump is hard-wired into the heater. Please note recommended circuit breaker sizes make no allowance for a water pump hard wired into the heater.
  6. The unit must be well earthed. Remove the front panel to access the electrical connection terminals of the heater. The electrical wiring diagram is affixed to the inside of the front panel or at the back of this manual.

Initial Start-Up
For the unit to heat the pool or spa, the filter pump MUST be running to circulate water through the heat exchanger.

  1. Turn on the filter pump. Check for water leaks and verify there is flow both to and from the pool.
  2. Turn of the unit’s electrical power supply, then press the ON/OFF button on the unit to start it.
  3. After a few minutes of running, make sure the air leaving the unit is roughly between 5-10°C cooler.
  4. With the unit in operation, turn the filter pump off. The unit should then turn off automatically.
  5. Allow the unit and the pool pump to run for at least 24 hours a day until the desired temperature is reached. Once this temperature is reached, the unit will periodically slow down and turn off if the temperature is maintained for at least 45 minutes. The unit will automatically restart (as long as the pool pump is running) when the pool temperature drops more than 0.2°C below set temperature.

Operation

The Controller

Operating Functions

Startup & Shutdown
To turn the unit on or off, press the ON/OFF button. When the unit is on, the outlet water temperature will appear on the screen instead of ‘Off’.

When the screen has not been touched for over a minute, the screen will go to sleep. Press any key to re-wake the screen.

Setting the Mode
In the main menu, press the MODE button to switch between the modes: Heating, Cooling & Automatic.
Once you have selected your desired mode, leave the control panel idle for a few seconds to automatically apply the changes.

Setting a Target Temperature

To change the set temperature of your unit, press either the UP or DOWN arrow key from the main menu. When you are altering the set temperature value, it will begin flashing to indicate it is being edited.
To save the changes either press the MODE button or leave the screen idle for 5 seconds. The controller will automatically save and return back to the main menu.

System Time Settings
The system time is the clock that is displayed on your unit. We recommend you adjust this to your local time if your unit is not aligned with this.
From the main menu, press the CLOCK button to enter into the system time settings for your unit. Once the system time begins flashing, this indicates you can now edit it.
With the entire time flashing, press the CLOCK button again to begin altering the hour value of the time. Use the arrow keys to adjust the hour value as desired and then press CLOCK to save and begin altering the minute value.
Use the arrow keys again to adjust the minute value and press CLOCK to save and return to the main menu. If at any point you would like to cancel any adjustments, press the POWER button to cancel and return.

On-Off Timer
The On-Off Timer allows you to specify a timing period that the unit will startup and shutdown.
From the main menu, hold down the CLOCK button for up to 5 seconds until a small alarm clock symbol displays and is flashing. Press the CLOCK button to enter into the ON/OFF Timer settings.

Use the arrow keys to select either an ON timer or an OFF timer (you need to set both for this function to operate). Press CLOCK to begin adjusting the hour value, once adjustments have been made to the hour value, press CLOCK to adjust the minute value and continue pressing CLOCK once you’ve made any changes.

Mute Timer
The Mute Timer is a function that will allow you to operate the unit at reduced noise levels for a specified time period.
Note: When silent mode is active it locks the compressor into a lower speed, reducing the available full heating capacity
From the main menu, hold down the CLOCK button for up to 5 seconds until a small alarm clock symbol displays and is flashing. Use the arrow key to select the MUTE option, then press the CLOCK button to enter into the settings.

Use the same steps to alter the mute timer as the ‘On Off Timer’.

Locking the Keyboard
Lock the keyboard to prevent accidental or unauthorised changes to the unit’s operation. When the screen is locked, a small lock symbol will appear at the bottom right of the screen.
To unlock or relock the screen, simply hold down the POWER button for 5 seconds.

Fault Interface
If your unit experiences a fault, a flashing warning symbol will appear to the left of the screen. While this warning is flashing, press the POWER button for half a second to view the fault/s. The main value on the fault screen is a code which refers to what issu
the unit is experiencing. The smaller number below the fault code refers to how many errors have occurred. If you have more than one error, use the arrow keys to browse them.

Troubleshooting

Electronic Control Fault Table

Protect/Fault| Fault Display| Reason| Elimination Methods
---|---|---|---
Standby| Non|  |
Normal boot| Non|  |
Inlet Temp. Sensor Fault| P01| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Outlet Temp. Sensor Fault| P02| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Ambient Temp. Sensor Fault| P04| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Coil1 Temp. Sensor Fault| P05| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Coil2 Temp. Sensor Fault| P15| The temp. sensor is broken or short circuit| Check or change the temp. sensor
Suction Temp. Sensor Fault| P07| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Discharge Temp. Sensor Fault| P81| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
High Pressure Prot.| E01| The high-pressure switch is broken| Check the pressure switch and cold circuit
Low Pressure Prot.| E02| Low pressure1 protection| Check the pressure switch and cold circuit
Flow Switch Prot.| E03| No water/little water in water system| Check the pipe water flow and water pump
Anti-freezing Prot.| E07| Water flow is not enough| Check the pipe water flow and whether water system is jammed or not
Primary Anti-freezing Prot.| E19| The ambient temp. Is low|
Secondary Anti-freezing Prot.| E29| The ambient temp. Is low|


Inlet and outlet temp. too big

| ****

E06

| Water flow is not enough and low differential pressure| Check the pipe water flow and whether water system is jammed or not
Low temperature protection| Non| The environment temp. is low|
Comp. Overcurrent Prot.| E51| The compressor is overload| Check whether the system of the compressor running normally
Exhaust Air over Temp Prot.| P82| The compressor is overload| Check whether the system of the compressor running normally


Communication Fault

| ****

E08

| Communication failure between wire controller and mainboard| Check the wire connection between remote wire controller and main board


Antifreeze Temp. Sensor Fault

| ****

P09

| Antifreeze temp sensor is broken or short circuited| ****

check and replace this temp sensor

Waterway Anti-freezing Prot.| E05| Water temp. or ambient temp. is too low|
EC fan feedback Fault| F51| There is something wrong with fan motor and fan motor stops running| Check whether fan motor is broken or locked or not
Pressure sensor Fault| PP| The pressure Sensor is broken| Check or change the pressure sensor or pressure


Fan Motor1 Fault

| ****

F31

| 1.  Motor is in locked-rotor state

2.  The wire connection between DC-fan motor module and fan motor is in bad contact

| ****

1.  Change a new fan motor

2.  Check the wire connection and make sure they are in good contact

Low AT Protection| TP| Ambient temp is too low|



Fan Motor2 Fault

| ****


F32

| 1.  Motor is in locked-rotor state

2.  The wire connection between DC-fan motor module and fan motor is in bad contact

| ****

1.  Change a new fan motor

2.  Check the wire connection and make sure they are in good contact.

Communication Fault (speed control module)| E81| Speed control module and main board communication fail| Check the communication connection

Frequency Conversion Board Fault Table

Protect/Fault| Fault Display| Reason| Elimination Methods
---|---|---|---
Drv1 MOP alarm| F01| MOP drive alarm| Recovery after the 150s


Inverter offline

| ****

F02

| Frequency conversion board and main board communication failure| ****

Check the communication connection

IPM protection| F03| IPM modular protection| Recovery after the 150s


Comp. Driver Failure

| ****

F04

| Lack of phase, step or drive hardware damage| Check the measuring voltage check frequency conversion board hardware


DC Fan Fault

| ****

F05

| Motor current feedback open circuit or short circuit| ****

Check whether current return wires connected motor


IPM Overcurrent

| ****

F06

| ****

IPM Input current is large

| ****

Check and adjust the current measurement


Inv. DC Overvoltage

| ****

F07

| DC bus voltage>Dc bus over-voltage protection value| ****

Check the input voltage measurement


Inv. DC Lessvoltage

| ****

F08

| DC bus voltage<Dc bus over-voltage protection value| ****

Check the input voltage measurement


Inv. Input Lessvolt.

| ****

F09

| The input voltage is low, causing the input current to be high| ****

Check the input voltage measurement


Inv. Input Overvolt

| ****

F10

| The input voltage is too high, more than outage protection current RMS|


Check the input voltage measurement

Inv. Sampling Volt| F11| The input voltage sampling fault| Check and adjust the current measurement
Comm. Err DSP-PFC| F12| DSP and PFC connect fault| Check the communication connection
Input Over Cur.| F26| The equipment load is too large|
PFC Fault| F27| The PFC circuit protection| Check the PFC switch tube short circuit or not
IPM Over heating| F15| The IPM module is overheat| Check and adjust the current measurement
Weak Magnetic Warn| F16| Compressor magnetic force is not enough|
Inv. Input Out Phase| F17| The input voltage lost phase| Check and measure the voltage adjustment
IPM Sampling Cur.| F18| IPM sampling electricity is fault| Check and adjust the current measurement
Inv. Temp Probe Fail| F19| Sensor is short circuit or open circuit| Inspect and replace the sensor
Inverter Overheating| F20| The transducer is overheat| Check and adjust the current measurement
Inv. Overheating Warn| F22| Transducer temperature is too high| Check and adjust the current measurement
Comp. Overcur. Warn| F23| Compressor electricity is large| The compressor over-current protection
Input Over Cur. Warn| F24| Input current is too large| Check and adjust the current measurement
EEPROM Error Warn| F25| MCU error| Check whether the chip is damaged Replace the chip
V15V over/undervoltage fault| ****

F28

| ****

The V15C is overload or undervoltage

| ****

Check the V15V input voltage in range 13.5v~16.5v or not

Appendix

Controller Interface Diagram

No. Sign Meaning
01 P10-1/2/3(U/V/W) Compressor
02 P13(L)/P14(L) Resistance
03 CN97 DC motor
04 RS485-2 The port for centralized control
05 RS485 Colour line controller communication/Wi-Fi
06 OT Water output temperature
07 ET System exhaust temperature
08 IT Water input temperature
09 SUT System suction temperature
10 CT System fan coil temperature
11 AT Ambient temperature
12 HP System high pressure
13 LP System low pressure
14 FS Water flow switch
15 MODE Mode switch
16 REMOTE Emergency switch
17 CN11 4-way valve
18 CN13 Reserved
19 CN18 Water pump
20 CN66 Compressor signal
21 CN99 Low pressure sensor
22 CN15 Electronic expansion valve
23 CN10 Program port
24 P00 Grounding
25 P1 Live wire
26 P2 Neutral wire

Parameter List

Meaning Default Remarks
Refrigeration target temperature set point 27°C Adjustable
Heating the target temperature set point 27°C Adjustable
Automatic target temperature set point 27°C Adjustable

Cable Specifications

Single Phase Unit

Nameplate maximum current| Phase line| Earth line| MCB| Creepage Protector| Signal Line
No more than 10A| 2 x 1.5mm2| 1.5mm2| 20A| ****







30mA less than 0.1 sec

| ****







n x 0.5mm2

10~16A| 2 x 2.5mm2| 2.5mm2| 32A
16~25A| 2 x 4mm2| 4mm2| 40A
25~32A| 2 x 6mm2| 6mm2| 40A
32~40A| 2 x 10mm2| 10mm2| 63A
40~63A| 2 x 16mm2| 16mm2| 80A
63~75A| 2 x 25mm2| 25mm2| 100A
75~101A| 2 x 25mm2| 25mm2| 125A
101~123A| 2 x 35mm2| 35mm2| 160A
123~148A| 2 x 50mm2| 50mm2| 225A
148~186A| 2 x 70mm2| 70mm2| 250A
186~224A| 2 x 95mm2| 95mm2| 280A
Three Phase Unit

Nameplate maximum current| Phase line| Earth line| MCB| Creepage Protector| Signal Line
No more than 10A| 3 x 1.5mm2| 1.5mm2| 20A| ****







30mA less than 0.1 sec

| ****







n x 0.5mm2

10~16A| 3 x 2.5mm2| 2.5mm2| 32A
16~25A| 3 x 4mm2| 4mm2| 40A
25~32A| 3 x 6mm2| 6mm2| 40A
32~40A| 3 x 10mm2| 10mm2| 63A
40~63A| 3 x 16mm2| 16mm2| 80A
63~75A| 3 x 25mm2| 25mm2| 100A
75~101A| 3 x 25mm2| 25mm2| 125A
101~123A| 3 x 35mm2| 35mm2| 160A
123~148A| 3 x 50mm2| 50mm2| 225A
148~186A| 3 x 70mm2| 70mm2| 250A
186~224A| 3 x 95mm2| 95mm2| 280A

Maintenance

F.A.Q

  • DO I NEED TO GET MY UNIT SERVICED?
    It is recommended that you get your EvoHeat unit serviced once a year by your local certified air conditioning or refrigeration technician. If your unit is located in a coastal area, more frequent maintenance may be necessary. During the service, they will check the operational pressures of the refrigeration system and give the unit and fins a good clean to ensure maximum performance.

  • DO WE HAVE RECOMMENDED SERVICE AGENTS?
    EvoHeat have a large database of recommended service agents. Please contact EvoHeat tech support on 1300 859 933 for your local service agent details.

  • SHOULD I CHECK MY UNIT REGULARLY?

    • We recommend you check your unit regularly to avoid potential issues and damage to your heat pump.
    • Check the water inlet/outlets often for leaks. You should avoid the condition of no water or air entering into the system, as this will influence unit’s performance and reliability.
    • You should clear the pool/spa filter regularly to avoid damage to the unit as a result of the dirty of clogged filter.
    • The area around the unit should be dry, clean and well-ventilated. Make sure there is nothing blocking the airflow of the heater e.g. Leaf litter.
  • WHAT SHOULD I BE CHECKING REGULARLY?

    • Discharge all water in the water pump and water system, so that freezing of the water in the pump or water system does not occur. You should discharge the water at the bottom of water pump if the unit will not be used for an extended period. You should check the unit thoroughly and fill the system with water fully before using it for the first time after a period of time.
    • Check the power supply and cable connection often, should the unit begin to operate abnormally, switch it off and contact the qualified technician

Advanced

  • CHECK THE AREA
    Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. a prolonged period of no usage.

  • PRESENCE OF FIRE EXTINGUISHER
    If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging

  • CHECKING FOR PRESENCE OF REFRIGERANT
    The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

  • CABLING
    Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also consider the effects of aging or continual vibration from sources such as compressors or fans.

  • REPAIR TO INTRINSICALLY SAFE COMPONENTS
    Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
    Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

  • GENERAL WORK AREA
    All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

  • WORK PROCEDURES
    Work shall be undertaken under a controlled procedure to minimize the risk of flammable gas or vapor being present while the work is being performed.

  • VENTILATED AREA
    Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. prolonged period of no usage.

  • DETECTION OF FLAMMABLE REFRIGERANTS
    Under no circumstances shall potential sources of ignition be used in the search for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

  • LABELLING
    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

NO IGNITION SOURCES

No person carrying out work in relation to a refrigeration system that involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removal, and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.

CHARGING PROCEDURES

In addition to conventional charging procedures, the following requirements shall be followed.

  • Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.
  • Cylinders shall be kept upright.
  • Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
  • Label the system when charging is complete (if not already).
  • Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site. The safety wire model is 5*20_5A/250VAC, and must meet the explosion- proof requirements.

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:

CHECKS TO THE REFRIGERATION EQUIPMENT

  • The charge size is in accordance with the room size within which the refrigerant-containing parts are installed;
  • The ventilation machinery and outlets are operating adequately and are not obstructed; If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
  • Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
  • Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant-containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

CHECKS TO ELECTRICAL DEVICES

Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment, so all parties are advised.

Initial safety checks shall include:

  • That capacitors are discharged: this shall be done in a safe manner to avoid the possibility of sparking;
  • That there no live electrical components and wiring exposed while charging, recovering or purging the system;
  • That there is continuity of earth bonding

REPAIRS TO SEALED COMPONENTS

  1. During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
  2. Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.

Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to.

LEAK DETECTION METHODS

  • The following leak detection methods are deemed acceptable for systems containing flammable refrigerants.
  • Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
  • Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
  • If a leak is suspected, all naked flames shall be removed/extinguished.
  • If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

REMOVAL AND EVACUATION

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:

Remove refrigerant;
Purge the circuit with inert gas; Evacuate;
Purge again with inert gas; Open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available. working on them.

RECOVERY

  • When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
  • When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut- off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
  • The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
  • The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
  • If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

DECOMMISSIONING

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.

  • a) Become familiar with the equipment and its operation.

  • b) Isolate system electrically.

  • c) Before attempting the procedure ensure that:
    – Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
    – All personal protective equipment is available and being used correctly;
    – The recovery process is always supervised by a competent person;
    – Recovery equipment and cylinders conform to the appropriate standards.

  • d) Pump down refrigerant system, if possible.

  • e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.

  • f) Make sure that cylinder is situated on the scales before recovery takes place.

  • g) Start the recovery machine and operate in accordance with manufacturer’s instructions.

  • h) Do not overfill cylinders. (No more than 80 % volume liquid charge).

  • i) Do not exceed the maximum working pressure of the cylinder, even temporarily.

  • j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.

  • k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

Warranty

Refer to the EvoHeat website for warranty details

  1. Warranty terms are from date of purchase.
  2. This warranty excludes any defect or injury caused by or resulting from misuse, abuse, neglect, accidental damage, improper voltage, vermin infestation, incompetent installation, any fault not attributable to faulty manufacture or parts, any modifications which affect the reliability or performance of the unit.
  3. This warranty does not cover the following:
    • a. Natural Disasters (hail, lightening, flood, fire etc.)
    • b. Rust or damage to paintwork caused by a corrosive atmosphere
    • c. When serviced by an unauthorized person without the permission of Evo Industries
    • d. When a unit is installed by an unqualified person
    • e. Where a unit is incorrectly installed
    • f. When failure occurs due to improper or faulty installation
    • g. Failure due to improper maintenance (refer Operating Instructions)
    • h. ‘No Fault Found’ service calls where the perceived problem is explained within the operation instructions.
    • i. Costs associated with delivery, handling, freighting, or damage to the product in transit.
  4. If warranty service is required, you should:
    • a. contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site
    • b. provide a copy of your receipt as proof of purchase
    • c. have completed the online Warranty Registration Form
  5. Onsite technical service is available within the normal operating area of your Evo Authorised Service Agents. Service outside this area will incur a traveling fee.
  6. Unless otherwise specified to the purchaser, the benefits conferred by this express warranty and additional to all other conditions, warranties, rights and remedies expressed or implied by the Trade Practices Act 1974 and similar consumer protection provisions contained in legislation of the States and Territories and all other obligations and liabilities on the part of the manufacturer or supplier and nothing contained herein shall restrict or modify such rights, remedies, obligations or liabilities.

REGISTER YOUR WARRANTY

EvoHeat highly recommend customers complete their warranty details online to ensure efficient warranty claim processing.
To register your warranty, scan our QR Code or head to our website and fill in the Warranty Registration Form: https://evoheat.com.au/warranty- registration/

info@evoheat.com.au
1300 859 933
www.evoheat.com.au

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals