EVO HEAT Evo Max Series Commercial Hot Water Heat Pump User Manual

June 9, 2024
EVO HEAT

EVO HEAT Evo Max Series Commercial Hot Water Heat Pump

Introduction

This manual contains information relating to the installation, troubleshooting, operation, and maintenance of this EvoHeat unit. Instructions in this manual must always be followed. Failure to comply with these recommendations will invalidate the warranty. Should you have any questions or require technical support, call the EvoHeat office on 1300 859 933 to speak to our team.

The data and information contained in this manual is correct at the time of publishing and is subject to change without notice. For the most up to date manual, contact EvoHeat directly.

The Evo Max is ideal for commercial water heating applications that need high temperature hot water of up to 80°C. It is ideal for hospitals, nursing homes, hotels and motels, food preparation and sanitation, sterilization, industrial and laundry applications. With a higher C.O.P than traditional boilers, cutting edge technology, green refrigerants, high efficiency heat exchanger and a circulating heating method, the Evo Max can help end users save significantly on their annual hot water operating costs.

TECHNICAL DATA| | Evo Max 19| Evo Max 35| Evo Max 70| Evo Max 135|
---|---|---|---|---|---|---

Hot Water

| Heating Capacity| kW| 19| 35| 70| 135|
Power Input| kW| 5.3| 9.2| 19| 38.6|
Conditions:|
Air 20°C,|
Water 65°C|
C.O.P| | 3.58| 3.68| 3.68| 3.5|

Hot Water

| Heating Capacity| kW| 16| 29.5| 58.9| 113.7|
Power Input| kW| 6| 10.8| 21.5| 43.7|
Conditions:|
Air 20°C,|
Water 80°C| C.O.P| | 2.67| 2.74| 2.74| 2.6|
Max. Running Current| A| 14.3| 32.2| 64.6| 108.5|
Max. Power Input| kW| 7.5| 18.1| 36.2| 64.4|
Voltage/Phase| | 380-415V/3/50| 380-415/3/50| 380-415/3/50| 380-415/3/50|
Noise| dB(A)| 58| 65| 68| 70|
Air Discharge Type| | Horizontal| Horizontal| Vertical| Vertical|
Fan No.| | 2| 1| 2| 2|
Compressor No.| | 1| 1| 2| 4|
Refrigerant Type| | R134A| R134A| R134A| R134A|
Operation Range| ° C| -7 to 45| -7 to 45| -7 to 45| -7 to 45|
Hot Water Volume| L/hr| 326| 602| 1204| 2321|
Water Pressure Drop| kPa| 25| 38| 42| 45|
Water Connection| inch| DN32 Flange| DN40 Flange| DN65 Flange| DN80 Flange|
Max. Water Temp.| ° C| 80| 80| 80| 80|
Net Weight| kg| 238| 468| 600| 1050|
Net Dimensions (L/W/H)| mm| 1175 / 400 / 1605| 1195 / 980 / 1900| 1930 / 1050 / 1980| 2350 / 1150 / 2370|

Dimensions

EVO-HEAT-Evo-Max-Series-Commercial-Hot-Water-Heat-
Pump-1

Evo Max| A (L)| B (W)| C (H)| D| E| F| G| H| I
---|---|---|---|---|---|---|---|---|---
19| 1175| 400| 1605| 1267| 725| 694| 402| 215| 107

EVO-HEAT-Evo-Max-Series-Commercial-Hot-Water-Heat-
Pump-2

Evo Max| A (L)| B (W)| C (H)| D| E| F| G| H
---|---|---|---|---|---|---|---|---
35| 1195| 980| 1900| 925| 598| 517| 516| 360

EVO-HEAT-Evo-Max-Series-Commercial-Hot-Water-Heat-
Pump-3

Evo Max| A (L)| B (W)| C (H)| | D| | | E| | | F| | G| | | H
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
70| 1930| 1050| 1980| | 1170| | | 998| | | 539| | 530| | | 170
135| 2350| 1150| 2370| | 1590| | | 1098| | | 614| | 575| | | 164

Safety Instructions

  • Installation, repairs and maintenance of this unit must be performed by a qualified technician.
  • Any wiring must comply with local electrical regulations.
  • If any abnormal instances occur or a strange smells, the unit must be shut off by the power supply.
  • Do not put fingers or objects into the fans or evaporator of the unit.
  • The unit must be earthed to avoid any risk caused by insulation defects.
  • No wiring must come into contact with the heat source or the rotating fan parts.
  • The unit must be handled and lifted with appropriate equipment in correlation with the unit’s size and weight.
  • Electrical power must be switched off before any work is started on the unit.
  • Do not expose the unit to or install near any flammable gases.
  • Ensure there is a circuit breaker for this unit.
  • Copper and iron can not be used as a fuse.
  • The unit is equipped with an over-load protection system. After a previous stoppage, the unit will not start for at least 3 minutes.
  • If the supply cord is damaged, it must be replaced by the manufacturer, our service agent or a similarly qualified person in order to avoid a hazard.
  • USE SUPPLY WIRES SUITABLE FOR 75℃.
  • Caution: Single wall heat exchanger, not suitable for potable water connection.

Installation

Transit
When transporting the unit, ensure the unit is kept standing upright. Laying the unit down may damage internal parts.
If the unit needs to be hung up (such as for lifting with a crane) use the special lifting hole (hook) on the base of the unit with an 8 metre cable. Ensure there is some kind of padding between the cable and the unit to prevent damage to the heat pump cabinet.

Location of Installation
The unit can be installed in any outdoor area which can carry the weight of heavy machinery, such as a terrace, rooftop, the ground etc.

  • The location must have adequate ventilation and be free from strong winds.
  • The installation location must be free from heat radiation and fire hazards.
  • Ensure there are no obstacles near the air inlet and outlet of the heat pump.
  • There must be a water channel around the heat pump to drain condensing water.
  • Ensure that there is enough space around the unit for maintenance.
  • The heat pump can be installed onto the concrete basement using expansion screws, or onto a steel frame with rubber feet which can be placed on the ground or rooftop. Ensure the unit is placed horizontally.

Airflow Clearances

EVO-HEAT-Evo-Max-Series-Commercial-Hot-Water-Heat-
Pump-5

Plumbing

  • Try to reduce the resistance to the water from the piping.
  • The piping must be clear and free from dirt and blockage. A water leakage test must be carried out to ensure that there is no water leaking before the installation can be made.
  • The pipe must be tested by pressure separately. DO NOT test it together with the unit.
  • There must be an expansion tank on the top point of the water loop, and the water level inside the tank must be at least 0.5meters higher than the top point of the water loop.
  • The flow switch is installed inside of the heat pump, check to ensure that the wiring and action of the switch is normal and controlled by the controller.
  • The connection between the heat pump and the construction is best to be of a flexible type to avoid vibration transfer. The support to the water pipe must be separate, but not rely on the heat pump unit.
  • Try to avoid any air from being trapped inside the water pipe, there must be an air vent on the top point of the water loop.
  • There must be a thermometer and pressure meter at the water inlet and outlet for easy inspection during running.
  • There must be drainage on the low points of the water system, and there is already drainage on the chassis of the heat pump. The water in the system must be drained out during winter if the heat pump is not to be used.

Electrical Connection

  • Open the panel and open the power line hole
  • Thread the power line though the hole and connect it to the power line terminal. The three-core control line of the remote controller shall be plugged with the three-core signal line on the main board according to the wiring diagram.
  • For an external water pump, thread the power line of the water pump through the hole and connect it to the water pump terminals.
  • If an additional auxiliary heater is needed to be to be controlled by the heat pump controller, the relay (or power) of the aux-heather must be connected to the relevant output of the controller.

ATTENTION:

  • The unit should use an independent power supply, see wiring in 8.4 Cable Specifications. Power supply voltage must be in line with the rated voltage.
  • The power supply circuit must be equipped with an All-pole disconnect device and have at least 3mm contact opening distance.
  • The wiring must be completed by a professional technician in accordance with the circuit diagram.
  • Power supply circuit must have earth wire; the earth wire of power should be connected with an external earth wire safely. The external earth wire must be in order.
  • The creepage protection device must be settled in accordance with the relevant national technical standards for electronic equipment.
  • The power wire and signal wire should be neatly arranged. High voltage wires and low voltage wires must be separated and free from any interference. These wires must also be free from any pipes or valves on the unit.
  • When all wiring is completed, the power should only be connected after a thorough double check.
Initial Start-Up

Prior To:

  • Check the indoor unit, make sure that the pipe connection is done correctly and that the relevant valves are open.
  • Check the water loop to ensure that there is enough water inside of the expansion tank, that the water supply is good and that the water loop has no air in it and is full of water. Make sure there in good insulation for the water pipe.
  • Check the electrical wiring. Make sure that the power voltage is normal, the screws are fastened, the wiring is made in line with the diagram and the earthing is connected.
  • Check that the heat pump, including all the screws and different parts are in good order. When the power is on, review the indicator on the controller to see if there is any failure indications. The gas gauge can be connected to the check valve to see the high pressure (or low pressure) of the system during trial running.

Trial Operation:

  • Start the heat pump and check whether the water pump is running, if it is running normally there will be 0.2MPa on the water pressure meter.
  • When the water pump runs for 1 minute, the compressor will start. Hear whether there is a strange sound coming from the compressor. If an abnormal sound occurs, please stop the unit and check the compressor. If the compressor runs well, look for the pressure meter of the refrigerant.
  • Check whether the power input and running current is in line with the manual. If not stop the unit and check for why this may be occurring.
  • Adjust the valves on the water loop to make sure that the hot (cool) water supply to each door is good and meets the requirement of heating (or cooling).
  • Review whether the outlet water temperature is stable.

Operation

The Controller

| ****

ON/OFF

| Turn the unit on or off. When the unit is on, the button will be red.
---|---|---
| MODE| Switch modes
| TEMP. SETTING| Enter the temperature setting menu.
| FAST HEATING| Press this to begin rapid heating.
| TIMER| Set a unit on/off timer. When a timer is on, this icon will be green.
| SETUP| Check the unit status, time, factory parameters, temp. curve, timer & mute settings.
| | |
---|---|---|---
FAULT| DEFROSTING| HOT WATER MODE| HEATING MODE
When an error occurs this icon will flash at the top right of the screen. Tap the icon to see a record of failures.| When this icon is shown the unit is in defrosting mode.| When this icon is shown the unit is in hot water mode.| When this icon is shown the unit is in heating mode.

Operating Functions

Start-up & Shutdown
To turn the unit on or off, press ON/OFF button. The icon will be grey when the unit is off, and green when it is on.

Mode Switch
From the main menu there are five different operating modes that can be chosen from. Press MODE to select from the options:
Hot Water, Heating, Cooling, Hot Water & Heating or Hot Water & Cooling
Note: If you have purchased a heating-only model (with no cooling functions) “cooling” mode will not appear.

Setting the Target Temperature

Press the TEMP. SETTING button to change the set temperature values of heating and/or cooling mode.
Press the temperature value to alter the value, then press ‘Enter’ to save and return to the main menu.

Fast Heating Mode

While the unit is in heating mode, press the FAST HEATING button to enable the rapid heating function.

Setting a Timer

You can set a customised start-up and shutdown timer for your unit. Press the TIMER button on the main menu and enter your desired ‘ON’ & ‘OFF’ times.
Press the On/Off button to the left of each time to toggle the start/end timers. When they are not on the button will be grey instead of coloured.
Example: The unit will turn on at 17:10 and shut down at 20:10.

Fault Interface

Press the FAULT ****icon on the main menu to display a record of all failures that have occurred.
After faults have been reviewed and corrected, press the top right ‘Clear’ button to wipe the records.

Colour Display Calibration
Keep clicking quickly at the blank area on any interface till you hear a long beep. You will then enter the calibration interface.
Click “+” to start calibration. When you hear the beep again, you will have finished calibration and can exit.

Troubleshooting

Protect/fault Fault Display Reason Elimination methods
Inlet Temp Sensor Fault P01 The temp. Sensor is broken or short circuit

Check or change the temp. sensor
Outlet Temp Sensor Fault| P02| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Water Tank Temp Sensor| P03| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
AT Sensor Fault| P04| The ambient temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Coil temp1 Sensor| P153| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Coil temp2 Sensor| P154| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Suction temp Sensor| P17| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Antifreeze Sensor1(US)| P191| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Antifreeze Sensor2(US)| P193| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Antifreeze Sensor4(HSS)| P195| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Inlet Sensor(EVI)| P101| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Outlet Sensor(EVI)| P102| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Exhaust temp Sensor| P181| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Pressure Sensor fault| PP11| The system 1 pressure Sensor is broken or short circuit| Check or change the pressure sensor or pressure
Syst2:Coil temp Sensor| P25| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Suction temp Sensor| P27| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Antifreeze Sensor1(US)| P291| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Antifreeze Sensor2(US)| P293| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Antifreeze Sensor1(HSS)| P292| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Antifreeze Sensor2(HSS)| P296| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Exhaust Temp Sensor| P281| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Pressure Sensor fault| PP21| The system 2 pressure Sensor is broken or short circuit| Check or change the pressure sensor or pressure
Syst2:Inlet Sensor(EVI)| P201| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Outlet Sensor(EVI)| P202| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst1:Exhaust Overtemp| P182| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Syst2:Exhaust Overtemp| P282| The temp. Sensor is broken or short circuit| Check or change the temp. sensor
Low ATProtection| TP| The ambient temp. is low|


Fan Motor1 Fault

| ****

F031

| 1. Motor is in locked-rotor state 2.The wire connection between DC-fan motor module

and fan motor is in bad contact

| 1.  Change a new fan motor

2.  Check the wire connection and make sure they are in good contact


Fan Motor2 Fault

| ****

F032

| 1. Motor is in locked-rotor state 2.The wire

connection between DC-fan motor module and fan motor is in bad contact

| 1.  Change a new fan motor

2.  Check the wire connection and make sure they are in good contact

Communication Fault (speed control module)| E081| Speed control module and main| Check the communication connection
Communication Fault| E08| Communication failure between wire controller and mainboard| Check the wire connection between remote wire controller and main board
Syst1:Comp Overcurrent| E101| The compressor is overload| Check if system of compressor running normally
Syst2:Comp Overcurrent| E201| The compressor is overload| Check if system of compressor running normally
Syst1: HP Protection| E11| The high-pressure switch is broken| Check the pressure switch and cold circuit
Syst2: HP Protection| E21| The high-pressure switch is broken| Check the pressure switch and cold circuit
Syst1: LP Protection| E12| The high-pressure switch is broken| Check the pressure switch and cold circuit
Syst2: LP Protection| E22| The high-pressure switch is broken| Check the pressure switch and cold circuit
Flow Switch Protection| E032| No water/little water in water system| Check the pipe water flow and water pump


Aux Superheat Protection

| ****

E04

| ****

Electric-heater protection switch is broken

| Check to see if the electric heater has been running under the temperature over 150 for a long

time

Prim Anti-freezing Prot| E19| The ambient temp. is low|
Secondary Anti-freezing Prot| E29| The ambient temp. is low|


Syst1:Antifreeze(US)

| ****

E171

| ****

Use side water system temp. is low

| 1. Check US water temp. or change temp. sensor 2.Check pipe water flow and whether water system is jammed or not


Syst2:Antifreeze(US)

| ****

E271

| ****

Use side water system temp. is low

| 1. Check US water temp. or change temp. sensor 2.Check pipe water flow and whether water system is jammed or not


Syst1:Antifreeze(HSS)

| ****

E172

| ****

Heat side water system temp. is low

| 1. Check HSS water temp. or change temp. sensor 2.Check pipe water flow and whether water system

is jammed or not


Syst2:Antifreeze(HSS)

| ****

E272

| ****

Heat side water system temp. is low

| 1. Check HSS water temp. or change temp. sensor 2.Check pipe water flow and whether water system

is jammed or not

Syst1:Exhaust Overtemp| E182| The compressor is overload| Check whether the system of the compressor running normally
Syst2:Exhaust Overtemp| E282| The compressor is overload| Check whether the system of the compressor running normally
Excess Water Temp Diff| E06| Water flow is not enough and low pressure difference| Check pipe water flow & if water system is jammed

Appendix

Parameter List

Meaning Default Remarks
Cooling target temperature set point 12°C Adjustable
Heating the target temperature set point 40°C Adjustable
Hot Water target temperature set point 55°C Adjustable

Cable Specifications

|
---|---
Nameplate maximum current| Phase line (Single Phase)| Phase Line (Three Phase)| Earth line| MCB| Creepage Protector| Signal Line
No more than 10A| 2 x 1.5mm2| 3 x 1.5mm2| 1.5mm2| 20A| ****






30mA less than 0.1 sec

| ****






n x 0.5mm2

10~16A| 2 x 2.5mm2| 3 x 2.5mm2| 2.5mm2| 32A
16~25A| 2 x 4mm2| 3 x 4mm2| 4mm2| 40A
25~32A| 2 x 6mm2| 3 x 6mm2| 6mm2| 40A
32~40A| 2 x 10mm2| 3 x 10mm2| 10mm2| 63A
40~63A| 2 x 16mm2| 3 x 16mm2| 16mm2| 80A
63~75A| 2 x 25mm2| 3 x 25mm2| 25mm2| 100A
75~101A| 2 x 25mm2| 3 x 25mm2| 25mm2| 125A
101~123A| 2 x 35mm2| 3 x 35mm2| 35mm2| 160A
123~148A| 2 x 50mm2| 3 x 50mm2| 50mm2| 225A
148~186A| 2 x 70mm2| 3 x 70mm2| 70mm2| 250A
186~224A| 2 x 95mm2| 3 x 95mm2| 95mm2| 280A

Wire Control Interface Diagram

Sign Meaning
V 12v (power +)
R No Use
T No Use
A 485A
B 485B
G GND (power-)

Controller Interface Diagram

EVO-HEAT-Evo-Max-Series-Commercial-Hot-Water-Heat-
Pump-24

No. Sign Meaning
01 AI/DI01 Water input temperature
02 AI/DI02 Water output temperature
03 AI/DI03 System 1 coil temperature
04 AI/DI04 Ambient temperature
05 AI/DI05 System 1 suction temperature
06 AI/DI06 System 1 antifreeze 1 temperature/ system 1 coil temperature 2
07 AI/DI07 System1 Antifreeze 2 Temperature
08 AI/DI08 Water tank Temperature
09 AI/DI09 System1 Antifreeze 4 Temperature
10 AI/DI10 Temperature of the EVI inlet of system 1
11 AI/DI11 Temperature of the EVI outlet of system 1
12 AI/DI12 The high-pressure switch 1
13 AI/DI13 The low-pressure switch 1
14 AI/DI14 Water flow switch protection
15 AI/DI15 Emergency switch output
16 AI/DI16 Mode switch
17 AI17 (50K) Overload switch of electric heater
18 AI18 (50k) System Exhaust temperature 1
19 0~5V_IN1 System 1 compressor current detection
20 0~5V_IN2 Water level sensor
21 0~5V_IN3 pressure sensor 1
22 PWM_IN1 System flow meter (reserved)
23 PWM_IN2 No use
24 PWM_OUT1 AC Fan control output
25 PWM_OUT2 No use
26 0~10V OUT1 No use
27 0~10V OUT2 No use
28 +5V 5V output
29 +12V 12V output
30 CN1 Communication ports on the expansion board
31 CN2 Centralized control port
32 CN4 Electronic expansion valve 1
33 CN5 Colour line controller
34 CN8 Electronic expansion valve of EVI in system 1
35 CN15 DTU
36 RO11 Electromagnetic three-way valve 2
37 RO10 Electromagnetic three-way valve 1
38 RO09 Hot water pump
39 RO08 Alarm output
40 RO07 AUX superheat
41 RO06 4-way valve
42 RO05 Water pump
43 RO04 Fan 2 / Fan low speed
44 RO03 Fan 1 / Fan high speed
45 RO02 Compressor 2
46 RO01 Compressor 1

Maintenance

DO I NEED TO GET MY UNIT SERVICED?
It is recommended that you get your EvoHeat unit serviced once a year by your local certified air conditioning or refrigeration technician. If your unit is located in a coastal area, more frequent maintenance may be necessary. During the service, they will check the operational pressures of the refrigeration system and give the unit and fins a good clean to ensure maximum performance.

DO WE HAVE RECOMMENDED SERVICE AGENTS?
EvoHeat have a large database of recommended service agents. Please contact EvoHeat tech support on 1300 859 933 for your local service agent details.

SHOULD I CHECK MY UNIT REGULARLY?
We recommend you check your unit regularly to avoid potential issues and damage to your heat pump.
Check the water inlet/outlets often for leaks. You should avoid the condition of no water or air entering into the system, as this will influence unit’s performance and reliability.
The area around the unit should be dry, clean and well ventilated. Make sure there is nothing blocking the airflow of the heater e.g. Leaf litter. Clean the heat exchanger every few months to keep a good heat exchange rate and save energy.

WHAT SHOULD I BE CHECKING REGULARLY?

You should discharge the water at the bottom of the water pump if the unit will not be used for an extended period. Discharge all water in the water pump and water system so that freezing of the water in the pump or water system does not occur. Check the unit thoroughly and fill the system with water fully before using it for the first time after a period of time.

Check the power supply and cable connection often, should the unit begin to operate abnormally, switch it off and contact the qualified technician
Clean the water filter periodically to maintain good water quality. Lack of water and dirty water can damage the unit. The heat pump will start the water every 72 hours when it is not running to avoid freezing.

The water loop of the heat pump MUST be protected from freezing in winter. Do not shut off the power supply to the heat pump in winter. When the air temperature is below 0°C, if the inlet water temperature is above 2°C and below 4°C the water pump will begin freezing protection. If the inlet water is lower than 2°C, the heat pump will begin heating.

Warranty

Refer to the EvoHeat website for warranty details

  1. Warranty terms are from date of purchase.
  2. This warranty excludes any defect or injury caused by or resulting from misuse, abuse, neglect, accidental damage, improper voltage, vermin infestation, incompetent installation, any fault not attributable to faulty manufacture or parts, any modifications which affect the reliability or performance of the unit.
  3. This warranty does not cover the following:
    • Natural Disasters (hail, lightening, flood, fire etc.)
    • Rust or damage to paintwork caused by a corrosive atmosphere
    • When serviced by an unauthorized person without the permission of Evo Industries
    • When a unit is installed by an unqualified person
    • Where a unit is incorrectly installed
    • When failure occurs due to improper or faulty installation
    • Failure due to improper maintenance (refer Operating Instructions)
    • ‘No Fault Found’ service calls where the perceived problem is explained within the
    • Costs associated with delivery, handling, freighting, or damage to the product in transit.
  4. If warranty service is required, you should:
    • contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site
    • provide a copy of your receipt as proof of purchase
    • have completed the online Warranty Registration Form
  5. Onsite technical service is available within the normal operating area of your Evo Authorised Service Agents. Service outside this area will incur a traveling fee.
  6. Unless otherwise specified to the purchaser, the benefits conferred by this express warranty and additional to all other conditions, warranties, rights and remedies expressed or implied by the Trade Practices Act 1974 and similar consumer protection provisions contained in legislation of the States and Territories and all other obligations and liabilities on the part of the manufacturer or supplier and nothing contained herein shall restrict or modify such rights, remedies, obligations or liabilities.

REGISTER YOUR WARRANTY

EvoHeat highly recommend customers complete their warranty details online to ensure efficient warranty claim processing.
To register your warranty, scan our QR Code or head to our website and fill in the Warranty Registration Form: https://evoheat.com.au/warranty- registration/

EVO-HEAT-Evo-Max-Series-Commercial-Hot-Water-Heat-
Pump-25

info@evoheat.com.au
1300 859 933
www.evoheat.com.au

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals