IB500013
Installation Instructions – Caretaker
WARNING
Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation
and maintenance of this product must be performed by a qualified electrician.
This product must be installed in accordance with the applicable installation
code by a person familiar with the construction and operation of the product
and hazards involved.
Risk of Fire and Electric Shock- Make certain power is OFF before starting
installation or attempting any maintenance. Disconnect power at fuse or
circuit breaker.
Risk of Fire- Refer to product label for specific minimum supply conductor
requirements.
Risk of Burn- Disconnect power and allow fixture to cool before handling or
servicing.
Risk of Personal Injury- Fixture may become damaged and/or unstable if not
installed properly.
Failure to comply with these instructions may result in death, serious bodily
injury and property damage.
DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability
for damages or losses of any kind that may arise from the improper, careless,
or negligent installation, handling or use of this product.
NOTICE: Green ground wire provided in proper location. Do not relocate.
ATTENTION Receiving Department: Note actual fixture description of any
shortage or noticeable damage on delivery receipt. File claim for common
carrier (LTL) directly with carrier. Claims for concealed damage must be filed
within 15 days of delivery. All damaged material, complete with original
packing must be retained.
Safety: This fixture must be wired in accordance with the National
Electrical Code and applicable local codes and ordinances. Proper grounding is
required to insure personal safety. Carefully observe grounding procedure
under
installation section.
APPLICATIONS:
This lighting fixture is designed for outdoor lighting services, and should not be used in area of limited ventilation or inside high ambient temperature enclosures. It must be stored in a dry location prior to installation. Do not expose lighting fixture to rain, dust or other environmental conditions prior to installation and insertion of photo control or shorting cap (if so equipped). Best results will be obtained if installed and maintained according to the following recommendations.
Wall/Pole Mount Tools Required
1/2” Socket wrench, 7/16” Socket wrench, drill, 3/16” drill bit.
-
Use a 1/2” socket wrench to remove wall/pole mount bracket from fixture and set aside two fixture mounting bolts and wire shield. Discard pipe clamp bracket. (Figure 1.)
-
Determine mounting surface and pre-drill lag bolt locations.
• Wall/Square Pole Mount: Place bracket (wall/sq pole mount) face against mounting surface with bracket arrow pointing up. (Figure 2.)• Wood Pole Mount: Place bracket (wood pole mount) face against pole with bracket arrow pointing up. (Figure 3.) -
Using 7/16” socket drive four lag bolts (provided) where indicated. Tighten bolts to approx. 6-8 ft-lbs.
Note:Ensure provided lag screws are compatible with anchor material and anchor material is capable of withstanding required torque.
Note: Do not use holes labeled “luminaire” to fasten bracket to mounting surface. -
With supply wires pulled through 1/2” conduit hole 6” to 8”, slide fixture down over bracket and ensure support tab is correctly positioned inside the housing wall cavity.
-
Using 1/2” socket, install wire shield as shown with the two fixture mounting bolts up through the wall/pole bracket and into luminaire. If connection to conduit hole in the bottom of mounting bracket is preferred, remove the knockout tab on the wire shield. Tighten to 6-8 ft-lbs. (Figure 4 & Figure 5.)
Pipe Mount
Tools Required: 1/2” socket wrench.
- Use a 1/2” socket wrench to remove pipe clamp bracket from fixture and set aside two fixture mounting bolts. Discard wall/pole mount bracket and wire shield. (Figure 1.)
- Re-attach pipe clamp bracket leaving enough space to allow the mounting pipe to slide onto desired leveling step.
- With supply wires pulled through mounting pipe 6” to 8”, tighten the two fixture mounting bolts using 1/2” socket. Tighten to 6-8 ft-lbs. (Figure 6.)
Wiring
Tools Required: Philips or Flathead Screwdriver.
- Open fixture using screwdriver and allow access door to hang from ground tether. (Figure 7.)
- Make wiring connections inside the housing. Refer to wiring diagram for power connections. Connect the supply wires to the appropriate luminaire leads with the supplied wire nuts. (Figure 8.)
- Position and secure all wires away from all other electrical components.
- Slide access door tab under optic plate and close access door. Be sure not to pinch any wires. Tighten door screw (25-30 in-lbs).
Photocontrol (Shipped Uninstalled)
Tools Required: Flathead screwdriver.
- Loosen two flathead screws enough to allow rotation of the receptacle.
- Insert screwdriver into center slot and rotate receptacle until indicator arrow points north or desired direction. Tighten screws.
- Insert the photocontrol (or shorting cap) into receptacle and twist into locked position.
FCC Statement
Declaration of Conformity
Note: This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Warranties and Limitation of Liability
Please refer to
www.cooperlighting.com/legal for
our terms and conditions.
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2020 Cooper Lighting Solutions
All Rights Reserved
Publication No. IB500013EN
October 12, 2021
Cooper Lighting Solutions is a registered trademark.
All trademarks are property of their respective owners.
Product availability, specifications, and compliances are subject to change
without notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>