BEG PD2N-BMS-DALI-2-FP multicapteur faux Plafond Instruction Manual

June 13, 2024
BEG

BEG PD2N-BMS-DALI-2-FP multicapteur faux Plafond

BEG-PD2N-BMS-DALI-2-FP-multicapteur-faux-Plafond-
product

Product Information

The product is a DALI-2 multisensor designed as an input device. It performs mixed light measurements using both internal and external light sensors. The device is powered via the DALI bus. It is addressable and usable according to IEC 62386 Part 103 as a control device.

Instance 0 of the device provides information regarding occupancy and movement for the DALI bus according to IEC 62386 Part 303. Instance 1 provides LUX values ​​for the DALI bus according to IEC 62386 Part 304. The parameterization of the device is possible via a mandatory Multimaster- Application-Controller of any manufacturer that supports IEC 62386 Parts 101/103/303/304.

Safety Instructions

  • Work on the main supply may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
  • Disconnect the supply before installing! This device is not to be used to isolate other equipment from the main supply.

Mounting Instructions
When replacing the cover, please take care that the opening for light sensor 1 is placed on the same.

Initial Operation
The device can be put into service directly after mounting, following the software instructions from the relevant controller manufacturer.

Safety instructions

  • Work on the main supply may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
  • Disconnect the supply before installing! This device is not to be used to isolate other equipment from the main supply.
  • DALI is not SELV – the installation instructions for low voltage apply. The DALI screw clamps must not be connected to 230 VAC!
  • Read this supplementary sheet and the operating instructions before putting the device into operation. Knowledge of these documents is part of the intended use!

Function

  • DALI-2 multisensor (Input Device). Mixed light measurement with internal and external light sensors. Powered via DALI bus.
  • Addressable according to IEC 62386 Part 103 (control device). Instance 0 provides information regarding occupancy and movement for the DALI bus according to IEC 62386 part 303. Instance 1 provides LUX values for the DALI bus according to IEC 62386 part 304. Parameterization is possible via the mandatory Multimaster-Ap-plication-Controller of any manufacturer. This controller must support IEC 62386 parts 101/103/303/304.

Mounting

Mounting hints
When replacing the cover, please take care that the opening for light sensor 1 is placed on the same.

Initial operation

General:
The device can be put into service directly after mounting, following the software instructions from the relevant controller manufacturer.

Exclude sources of interference
In case the detection area of the detector is too large or areas are being covered that should not be monitored, the range can be reduced or limited by using the enclosed blinds.

Self-test cycle
During the first 20 sec after connecting to the DALI bus power, the product will enter a self-test cycle. During this time the device does not respond to movement.

BEG-PD2N-BMS-DALI-2-FP-multicapteur-faux-Plafond-fig-
\(1\)

LED function indicators

  • Shortly on:
    • A Green Movement
    • B Red –
    • C White –
  • Flashing:
    • A Green Localisation
    • B Red Initialisation
    • C White Localisation
    • D Red Localisation

Technical data

  • Settings: via an application that supports DALI multisensors (IEC 62386 parts 101/103/303/304).

  • DALI-BUS max. 22.5 V == Voltage

  • 7 mA Typ. power input

  • 0.5 – 2.5mm2 10mm

    • Terminal clamps:
      for solid one-wire conductors
  • 360° Area of coverage

  • 2 m/5 m/2.5 m Mounting height min./max./recommended

  • 2.5 m Range of coverage at mounting height

  • 18°C Ambient temperature

1. = Ø 10m across
2. = Ø 6m towards
3. = Ø 4m seated activities **Fig. 4**
  • 79m2 Monitored surface, when the detector is mounted at 2.5 m mounting height and for tangential approach
  • II/IP20 Class/Degree of protection
  • Ø 83 x 55 mm Dimensions
  • -25°C – +50°C Ambient temperature
  • 0 – 4095 Lux Measured light output

Schematic Diagram

Schematic diagram – when connecting the detector, please respect the labeling of the terminal connections at the device!

BEG-PD2N-BMS-DALI-2-FP-multicapteur-faux-Plafond-fig-
\(6\)

Declaration of conformity

UK Declaration of Conformity

This product respects the directives concerning

  1. Electrical Equipment Safety Regulation 2016
  2. Electromagnetic Compatibility Regulation 2016
  3. The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulation 2012

Contact
B.E.G. UK Ltd., Apex Court – Grove House • Camphill Road • West Byfleet, Surrey KT14 6SQ.

Accessory

  • Wire basket BSK (Ø 200 x 90 mm)

Troubleshooting

  1. Power consumption on the DALI line is too high
    Please be aware of the total power consumption of all the DALI units in your system.

  2. Heat sources in the vicinity
    If, for example, the detector is located in the immediate vicinity of ventilation slits or a projector, the warm air currents can trigger motion detection. Place the detector at a sufficient distance from potential sources of interference such as ventilation slits, projectors, beamers, etc.

Product page on the internet

Contact Information

Brück Electronic GmbH

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BEG User Manuals

Related Manuals