BEG LUXOMAT PD3N-1C Micro Instructions

June 13, 2024
BEG

PD3N-1C Micro
92219

LUXOMAT PD3N-1C Micro

Code 92219

Safety instructions

| Work on the mains supply may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
| Read this supplementary sheet before putting the device into operation.
Knowledge of this document is part of the intended use.
|

Function

| The device is a remote controlcapable motion detector for ceiling mounting (interior applications) having a circular detection area, with integrated acoustic sensor.
| Motion detectors automatically control the light, based on people being present (motion) and on the ambient light level. The detector switches the light on if the ambient light level is below a switch-on threshold (which can be set on the device) and movement is detected. The light remains switched on as long as the detector detects movement (independent of the lighting level) plus followup time. In addition, the device has an adjustable acoustic sensor. The follow-up time is automatically extended by detected movement as well as detected noises. However, a recognized movement is required for switching on the lighting. Within 9 sec. after the end of the follow-up time the lighting can be switched on automatically by means of noises.
| Further functions can be accessed with our remote control (see accessories).

BEG LUXOMAT PD3N-1C Micro - fig1

Exclude sources of interference

In case the detection area of the detector is too large or areas are being covered that should not be monitored, the range can be reduced or limited by using the enclosed blinds (e).
Self-test cycle
The product enters an initial 60-second self-test cycle when the supply is first connected (LEDs flash). During this time the device does not respond to movement.

LED function indicators after each mains recovery
Standard mode

  • Detector programmed – red flashes quickly (2x/sec.)
  • Detector not programmed – red flashes (1x/sec.)

Motion detection – red flashes
Acoustic detection – red flashes (LED Mic)
Impulse mode active  – red and green flash one time all 4 sec.

Hardware Reset

| Reset: The setting of the potentiometers to “test” and “sun” from any other position causes a reset of the device. That means all other settings are reset to factory settings (fast flashing of all LEDs for 5 sec.).
---|---

UK declaration of conformity

| This product respects the directives concerning
1. Electrical Equipment Safety Regulation 2016
2. Electromagnetic Compatibility Regulation 2016
3. The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulation 2012 Contact
B.E.G. UK Ltd., Apex Court – Grove House • Camphill Road • West Byfleet, Surrey KT14 6SQ
---|---

 Technical data

110-240 V ~, 50/60 Hz Voltage
ca./approx. 0.5 W Power input
Terminal clamps: for solid one-wire conductors
360° Area of coverage
2.5 m Recommended mounting height
Range of coverage at

mounting height
Ambient temperature
1 accross
2 towards
3 seated
II / IP44| Class / Degree of protection
Ø 106 x 53 mm| Dimensions
-25°C – +50°C| Ambient temperature
C1
μ – NO
2300 W cosφ = 1
1150 VA cosφ=0.5| Relay contact
tungsten pre-make contact Switching capacity
lp (20ms) = 165 A| max. inrush peak current (relay)
| Settings via potentiometers
Follow-up time
Switch-on threshold
Sensitivity of acoustic sensor
***| Schematic diagram
Schematic diagram – when
connecting the detector, please
respect the labelling of the terminal connections at the device!
BEG LUXOMAT PD3N-1C Micro - fig11
T1/T2| button, manual switching on
T1
+ manual switching off
S1| Switch for permanent light
E1| Lamp
RC| Arc extinction kit if requiredPart no. 10880
SCT1| Light control with staircase
timer model
SCT1 – Part no. 92655
92159| Accessory
92105| Remote control IR-PD-Mini
93067| Remote control IR-PD3N
10880| BLE-IR-Adapter
92199| RC-Arc extinction kit
Wire basket BSK
(Ø 200 x 90 mm)

Trouble shooting

****| 1. Lamp does not light up
• Lamp may be defect: Replace lamp
• No mains connection/power: Check connection and mains fuse by qualified electrician
• Incorrect setting of switch-on threshold:
Correct setting of threshold (potentiometer)
• Lens of sensor unit obstructed by dirt or other objects: Clean lens
---|---
2. Lamp turns ON too late or detection range too small
• The detector is mounted too high:
Correct mounting height if required.
• Incorrect setting of switch-on threshold:
– Correct setting of threshold (potentiometer) – Correct the detection sensitivity
3. Lamp stays ON continuously
• Continuous thermal activity detected within detection area:
Remove heat source. Check proper function of the detector by covering the lens. After expiry of the follow-up time, the detector has to turn OFF lighting.
• The detector is connected in parallel to a manual override switch:
Connect switch correctly
• The acoustic sensor is set too sensitive (LED Mic lights up): – Correct the sensitivity of acoustic sensor
4. Unintended switching of light
• Movement of heat sources within detection area:
– Do not install the detector in the vicinity of radiators, fans or air vents.
– Animals are detected as moving heat sources, too.

https://www.beg-luxomat.com/qr.php?prtno=92219

| Product page on the internet

Brück Electronic GmbH I Gerberstr. 33 I 51789 Lindlar I GERMANY I
Phone: +49 (0) 2266 90121-0 I
Fax: +49 (0) 2266 90121-50 I
[email protected]
I beg-luxomat.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BEG User Manuals

Related Manuals