AMPCONTROL OTS-EL Outlet Test System Earth Leakage Only User Manual
- June 13, 2024
- Ampcontrol
Table of Contents
- Symbols
- Copyright Notice
- Disclaimer
- Before You Begin
- SAFETY AND OTHER WARNINGS
- RECEIVING AND STORAGE
- PRODUCT OVERVIEW
- INSTALLATION
- PRODUCT OPERATION
- OPERATIONAL INTERFACE
- SERVICE, MAINTENANCE & DISPOSAL
- SPECIFICATIONS
- EQUIPMENT LIST
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AMPCONTROL OTS-EL Outlet Test System Earth Leakage Only
Symbols
WARNING The warning symbol highlights a potential risk of injury or
death.
Please share these warnings with other operators.
CAUTION! The caution symbol highlights a potential risk of damage to
equipment.
Please share these cautions with other operators.
NOTE The note symbol highlights key information.
Please share these notes with other operators.
ENVIRO The enviro (environmental) symbol highlights areas which may have an impact on the surrounding fauna and/or flora.
Copyright Notice
The Ampcontrol Outlet Test System – Earth Leakage (OTS-EL) described in this
document is the property of AMPCONTROL PTY LTD. It is furnished under a
license agreement and is to be used only in accordance with the terms of the
agreement.
No part of the hardware or documentation may be reproduced, transmitted,
transcribed, stored in a retrieval system, or translated into any language or
computer language, in any form or by any means, without prior written
permission of AMPCONTROL PTY LTD.
Disclaimer
While every effort has been made to assure the accuracy and clarity of this document, AMPCONTROL PTY LTD assumes no liability resulting from any omissions in this document, or from misuse of the information obtained herein. The information in this document has been carefully checked and is believed to be entirely reliable with all of the necessary information included. AMPCONTROL PTY LTD reserves the right to make changes to any products described herein to improve reliability, function, or design, and reserves the right to revise this document and make changes from time to time in content hereof with no obligation to notify any persons of revisions or changes. AMPCONTROL PTY LTD does not assume any liability arising out of the application or any use of any product or circuit described herein; neither does it convey license under its patent rights or the rights of others.
Before You Begin
Thank you for purchasing the Ampcontrol OTS-EL.
WARNING In the interests of safety and correct equipment operation, please take the time to read and understand the content in this manual.
Ampcontrol Contact Details
7 Billbrooke Close, Cameron Park, NSW, 2285
P +61 1300 267 373 | F +61 2 4903 4888
EMAIL:
customerservice@ampcontrolgroup.com
WEB: ampcontrolgroup.com
SAFETY AND OTHER WARNINGS
For safety reasons, the OTS-EL must be installed, operated and serviced only
by competent personnel.
Please read and understand this instruction manual completely before
installing, operating or servicing this equipment. Failure to install or
operate this instrument in accordance with the instructions contained in this
manual may create hazardous operating conditions.
Safe Use of Equipment
The equipment supplied has been designed and manufactured to ensure safe
operation. The equipment must only be used within the design parameters.
The instructions within this manual must be observed as an aid towards
achieving the safest possible installation.
Persons responsible for installation, maintenance, or operation, must observe the following instructions:
Changes to Equipment
Changes in the design and modifications to the equipment are not permitted.
Unauthorised changes made to the hardware or operating firmware will void the
manufacturer’s warranty, and may compromise the integrity of the system into
which it is installed and other connected equipment.
Equipment Knowledge
Experience with, or understanding of, this equipment is essential for the safe
installation and removal of the equipment. Therefore, please read and
understand this manual prior to use. Competency based training courses are
recommended and are available on request.
Manual Handling
Precautions have been taken to ensure all equipment is safe to handle and free
from sharp edges.
However, care should always be taken when handling enclosures and gloves
should be worn.
Installation
Correct operation and safety depend on the Outlet Test System and associated
equipment being installed correctly. Mechanical and or electrical installation
and maintenance of plant and equipment must only be carried out by
appropriately qualified personnel and must be tested thoroughly prior to
operation.
Operation
The OTS-EL is not a primary safety device: it is periodically operated to
ensure the correct operation of the primary earth leakage protection on an
outlet. It is therefore necessary that it is operated only by trained and
competent personnel who can correctly interpret and verify the test results
obtained through the use of the OTS-EL.
RECEIVING AND STORAGE
Receiving
All possible precautions are taken to protect the equipment against damage or
losses during shipment; however, before accepting delivery, check all items
against the packing list or bill of loading. If there is evidence of physical
damage, notify Ampcontrol immediately.
Notify Ampcontrol immediately in the case of any discrepancies to the packing
list. Keep a record of any claims and correspondence. Photographs are
recommended.
Where practicable do not remove protective covers prior to installation unless
there are indications of damage. Boxes opened for inspection and inventory
should be carefully repacked to ensure protection of the contents or else the
parts should be packaged and stored in a safe place. Examine all packing
boxes, wrappings and covers for items attached to them, retain and store any
approval documentation for your safety file as applicable prior to wrapping
being discarded.
Inspection
Equipment that is found to be damaged or has been modified away from its published specifications must not be used. Please contact Ampcontrol if the equipment is suspected to be different than that ordered or if it does not match the published specifications.
Storage after Delivery
When the equipment is not to be installed immediately, proper storage is
important to ensure protection of equipment and validity of warranty.
All equipment should be stored indoors between 0-40˚C, preferably on shelves
and protected from moisture and sunlight.
Unpacking of Equipment
The method of packing used will depend on the size and quantity of the equipment. The following cautions should be interpreted as appropriate.
CAUTION Take care when unpacking crates as the contents may have shifted during transport.
ENVIRO The disposal of packaging materials, replaced parts, or components
must comply with environmental restrictions without polluting the soil, air or
water.
Ensure that any timber and cardboard used as packaging is disposed of in a
safe and environmentally responsible manner.
Where possible, dispose of all waste products i.e. oils, metals, plastic and
rubber products by using an approved recycling service centre.
PRODUCT OVERVIEW
Description
The Ampcontrol Outlet Test System – Earth Leakage (OTS-EL) provides a fully
automated outlet earth leakage testing facility. The OTS-EL completely
eliminates paper-based record keeping by concurrently updating a historical
database with the latest test data.
The OTS-EL is comprised of an OTS-EL module, embedded within the outlet
electrics, and an OTS Comms Module, mounted on the door to provide Bluetooth
connectivity to the outlet tester.
All tests are initiated wirelessly via the OTS Application Software, which is
installed on compatible Bluetooth enabled devices. Each outlet is able to be
individually targeted.
All local test records are managed within the OTS Application Software until
the tablet performs an authorised sync with the AWARE cloud storage. When this
occurs all local test reports are uploaded to the cloud, and then all Assets
and Users are refreshed for selected site. All OTS test records can be
accessed by anyone with internet access and authorisation (user account).
The OTS-EL will measure both the contactor opening time in addition to the
true earth leakage clearing time (time for back EMF voltages to fall below
ELV).
Key Features
The OTS-EL has the following key features:
- Fully automated, outlet protection function testing
- Wireless outlet testing
- Earth Leakage (EL) protection testing (contactor operating and back EMF clearing times)
- Test data logging (Uploads to cloud storage)
- DIN rail mounted
Application
The OTS-EL System can be installed into Ampcontrol Substations, Distribution Boards and Outlet Control Boxes. The OTS-EL greatly simplifies the statutory testing process, performing a hands-free, automated testing function whilst simultaneously providing a comprehensive record management tool.
Supplementary Documents
The OTS-EL User Manual is expected to be read in conjunction with the following documents:
- MAG-199 OTS Application User Manual
- MAG-204 OTS Dashboard User Manual
INSTALLATION
General Warnings
These instructions have been designed to assist users of the OTS-EL with
installation.
Before the OTS-EL can be installed, there are a number of things that need to
be considered and understood to prevent incorrect or unsafe operation of the
OTS-EL or the system into which it is installed.
Along with relevant competence, and an understanding of the target
application, the following points should be considered:
Ensure that the information provided in this user manual is fully
understood.
It is extremely important that the limitations and functionality of the OTS –
EL are understood to prevent incorrect installation or use, creating a
potentially dangerous risk. If in doubt as to the nature of the limitations or
their implication, consult a competent authority such as a supervisor or
Ampcontrol technical representative.
Ensure that the application into which the OTS-EL is being installed has
been properly defined, designed and approved.
Any system intended to mitigate the risk of injury needs to be properly
designed and implemented.
Such a system must be the result of structured risk analysis with the outcomes
used to define the system requirements. These requirements, in turn, will
guide the choice of instrumentation, logic solvers and actuators needed to
implement the system. Understanding the needs of the system will ensure proper
selection of equipment.
Ensure that the OTS-EL will properly perform the required functions within
the system design.
It is important to understand how the OTS-EL is intended to interact with
other equipment within a system. For safe and reliable use, it is crucial that
neither the OTS-EL logical operation nor its signalling be compromised by
incompatibilities with connected equipment.
Modifications of any form to the Outlet Test System are prohibited.
If modifications of any form are made to the OTS-EL, the equipment may no
longer be fit for use. If any modifications or damage to the OTS-EL is
evident, do not use the equipment and contact Ampcontrol for advice.
Mandatory Installation Practices
The following information must be adhered to when installing the OTS-EL.
Failure to adhere to this information may give rise to unsafe operation.
Using the OTS-EL in a manner that exceeds its electrical or functional
specifications, or in a way that is contrary to its operating restrictions,
may create risks to personnel and/or equipment resulting in injury or death.
- The OTS-EL must be supplied by a regulated voltage within the specified range.
- The installation of the OTS-EL must be carried out by suitably trained and qualified personnel.
- Identification labels fixed to the OTS-EL must not be damaged, removed or covered.
- The installation is to be in accordance with the relevant installation Standards/Codes of Practice.
- Modifications must not be made to any part of the OTS-EL. Modifications to its construction will render the unit non-compliant.
- Complete and accurate records of the installation must be retained for warranty purposes.
Mechanical Installation Information
The OTS-EL is comprised of an OTS-EL Test module and an OTS Comms Module.
Figure 4.1: OTS-EL System Overview
OTS-EL Mechanical Installation Information
Figure 4.2: OTS-EL Dimensions
The OTS-EL Test module performs all the test actuation and measurements. It is a DIN Rail mounted unit that interfaces with the outlet electrics. The terminal layout and description is shown in Figure 4.3 and Table 1 respectively.
Figure 4.3: OTS-EL Terminal Layout
Table 1: OTS-EL Terminal Designators
Number | Designator | Number | Designator | |
---|---|---|---|---|
1 | Vs + | 12 | MC AUX – | |
2 | Vs – | 13 | SPARE | |
3 | Earth | 14 | SPARE | |
4 | EL Test 1 | 15 | SPARE | |
5 | EL Test 2 | 16 | SPARE | |
6 | SPARE | 17 | SPARE | |
7 | SPARE | 18 | SPARE | |
8 | MC AUX 110V A | 19 | SPARE | |
9 | MC AUX 110V N | Ua | Barrier Connection | |
10 | SPARE | Ub | Barrier Connection | |
11 | MC AUX + | Uc | Barrier Connection |
OTS Comms Module Mechanical Installation Information
Figure 4.4: OTS Comms Module
The Comms module provides Bluetooth connectivity to the Tester. It is intended
to be mounted onto the back of an outlet door or enclosure, covering a 22.5mm
OD hole. The hole needs to align with the PCB aerial on the Comms module.
Without this hole, the steel of the enclosure would form a shield, preventing
Bluetooth communications to the tester. To improve the connectivity of the
Bluetooth device, the hole in the enclosure should be positioned such that it
faces the location where the testing officer is most likely to stand when
initiating the test procedure.
The Communications Module must be oriented with the RJ45 port pointing
downwards to ensure both LEDs on the Comms Module align with their
corresponding position on the external label.
To install the Comms Module, simply pull the plastic off of the high strength
adhesive tape and stick it to the back of the door, aligning the circle on the
PCB with the hole in the enclosure.
To maintain the IP rating of the enclosure the included label must be placed
externally over the hole.
The location of the two LEDs on the OTS Comms Module can be seen in Figure
4.5.
Figure 4.5: OTS Comms Module and External Label
Electrical Installation Information
A typical installation diagram of the OTS-EL is shown below, Figure 4.6. The following sub-sections provide a more detailed description of each of the individual circuit elements.
Figure 4.6: Electrical Connections – OTS-EL Circuit Diagram
Power Supply (Terminals 1, 2 & 3)
The OTS-EL requires a regulated 24VDC or 24VAC power supply.
Figure 4.7: Electrical Connections – OTS-EL Power Supply
Line Connections (Terminals Ua, Ub & Uc)
The OTS-EL contains an internal high voltage barrier that allows the OTS-EL to
directly interface with the phase conductors.
The high voltage connections from the OTS-EL must be made on the load side of
the outlet’s contactor / breaking device.
Figure 4.8: Electrical Connections: Internal HV Barrier
Comms Module Connections (RJ45 Port)
The OTS-EL interfaces with the user’s compatible tablet via the OTS Comms
Module. The Comms Module is connected to the OTS-EL via a standard CAT5 or
CAT6 cable (straight-through RJ45 termination).
CAUTION! This Comms Module Connection Ports are not standard Ethernet ports. These cores carry voltages that will damage an incompatible device if connected.
Figure 4.9: Electrical Connections: Comms Module
EL Test Connections (Terminals 4 & 5)
The Earth Leakage Test works by closing an internal normally open contact for
the duration of the test.
This contact is intended to be wired in parallel to an existing earth leakage
test circuit that passes an AC current through the outlet’s earth leakage
toroid.
NOTE The installer is responsible for ensuring that the test resistance
is of a suitable magnitude to provide a meaningful test.
It is recommended that the resistance value is chosen such that the test
current is between 110% and 120% of the trip level of the earth leakage
protection relay (AS/NZS 2081 Appendix E4, AS/NZS 4871.1:2012 Clause 2.6.2.4).
Figure 4.10: Electrical Connections – EL Test
MC Auxiliary Input Connections (Terminals 8 & 9 or 11 & 12)
The MC Auxiliary Input provides feedback to the OTS-EL on the current position
of the outlet’s contactor / breaking device. The OTS-EL provides two options
for monitoring the MC Auxiliary. The first option is used in 110VAC control
circuits, as shown in Figure 4.11. The second option is to use the MC AUX 24V
input, as shown in Figure 4.12. This input is used with 24VDC or 24VAC control
supplies.
The MC AUX 110V and the MC AUX 24V input do not require a load to be present;
the voltage input can connect directly to the input (via the contactor’s
auxiliary contact).
Figure 4.11: Electrical Connections – MC Auxiliary Input (Option 1)
Figure 4.12: Electrical Connections – MC Auxiliary Input (Option 2)
NOTE Either the 110V or 24V auxiliary inputs should be used – not both at the same time.
PRODUCT OPERATION
All tests are initiated wirelessly through Bluetooth from the AmpINTEL
PowerSAFE OTS software. The AmpINTEL PowerSAFE OTS Application software is
compatible with Android versions 4.3 and above.
As the OTS application has been developed and tested on the Samsung Galaxy Tab
A with Android version 6.0.1, Ampcontrol can only guarantee compatibility with
this device.
CAUTION! Ampcontrol cannot guarantee correct operation of the AmpINTEL PowerSAFE OTS application if a non-compatible smart device is utilised.
During a test, the results will be displayed on the tablet and a report will
be generated upon completion.
These test reports are stored on the tablet until the tablet gains network
access. At this point the test reports are uploaded to the dashboard, a site
specific cloud based storage platform.
Once these reports have been uploaded, all reports except for the most recent
will be removed from the tablet. The most recent report is saved on the tablet
because, at the beginning of each new connection, the OTS-EL will check to
make sure there are no discrepancies between the results obtained from the
last test and those stored on the tablet. If there are any differences the
test report will be updated to those stored in the OTS-EL. If the reports are
different (i.e. the last test was conducted on a different device) a new test
report will be generated with the data stored on the OTS-EL. This is of
particular use if there were any issues with the tablet or Bluetooth
connection during testing.
For more information on the operation on the OTS-EL Android Application or the
Dashboard please refer to the relevant user manual.
NOTE The Bluetooth range is limited to a maximum of approximately three metres (3m). This distance is an advised maximum, various factors will influence the connection distance.
Earth Leakage Protection Function Test
The Earth Leakage test can only be initiated with the outlet energised. When the EL test is initialised, the OTS-EL will energise the existing external EL test circuit. This simulates an EL current to be detected by the outlet’s earth leakage toroid.
NOTE The OTS itself does not generate the test current; it operates in parallel to the existing manual EL test circuit.
Once the earth leakage test is initiated, the OTS-EL will measure the time
taken for the outlet to open its contactor or breaking device. In addition,
the OTS-EL will also monitor the voltage on the load side of this breaking
device to determine the time that it takes for the back EMF generated by the
connected load to subside to extra low voltage (<50VAC). This represents the
true clearing time following an earth leakage fault.
The magnitude of the current that flows through the earth leakage toroid is
determined by the design of the test circuit installed. It is the
responsibility of the installer to ensure that this current is sized to
provide meaningful results when the earth leakage test is conducted by the
OTS.
NOTE The installer is responsible for ensuring that the EL test current
is of a suitable magnitude to provide a meaningful test.
It is recommended that the circuit design is chosen such that the test current
is between 110% and 120% of the trip level of the earth leakage protection
relay (AS/NZS 2081 Appendix E4, AS/NZS 4871.1:2012 Clause 2.6.2.4).
OPERATIONAL INTERFACE
This section will give an explanation of the physical location and the operational characteristics of the OTS-EL’s interface elements.
OTS-EL Operational Interface
The OTS-EL has two LEDs and a RJ45 connection port (identified in Figure 6.1). The operation of the LED’s is detailed in Table 2.
Figure 6.1: OTS-EL Operational Interface
Table 2: OTS-EL Fascia LED Operation
LED | Behaviour |
---|---|
Name | Colour |
Status | Green |
Comms | Blue |
Connected to the Tablet
The RJ45 port is designed to connect the OTS-EL to the Comms Module via a straight through CAT5 or CAT6 cable.
CAUTION! The Comms Module Connection Ports are not standard Ethernet ports. These cores carry voltages that will damage an incompatible device if connected.
OTS Comms Module Operational Interface
If the OTS Comms Module is installed correctly, the two LEDs identified on the left in Figure 6.2, will line up with the label that is installed over the hole on the outside of the enclosure. These LEDs are the Paired LED (left) and the Testing LED (right). The operation of the LEDs is detailed in Table 3.
Figure 6.2: Comms Module Operational Interface
Table 3: OTS-EL Comms Module LED Operation
LED | Behaviour |
---|---|
Name | Colour |
Paired | Blue |
Connected to the Tablet
Testing| Red| No Testing in Progress| Testing in Progress| Testing Completed
SERVICE, MAINTENANCE & DISPOSAL
Equipment Service
A number of external system based checks should be completed on a regular basis. These ‘routine inspections’ must be carried out by suitably trained people with knowledge of the Outlet Test System and the systems into which it is fitted. Routine inspections may take the form of either visual-only checks, or visual and ‘hands-on’ checks.
Visual Only Inspections
A basic visual inspection focuses on looking at the installation for signs of
physical damage, water or dust ingress and the condition of cables and labels.
This type of inspection may involve opening cabinets to gain access to the
OTS-EL and other equipment. This level of inspection may also include cleaning
display windows that have become obscured by dirt.
Observations would typically be:
- Check that equipment enclosures, cable trays, conduits, etc. are in good order with no physical damage.
- Check that sealed wall boxes are free from water and dust ingress internally. Door seals are in good condition.
- Check that connected cables are free from cuts, abrasions and obvious signs of damage. Cable restraints are in good order and correctly fitted.
- Check that labels on equipment, wall boxes and cables are present and in good condition (especially certification labels).
- Check that no modifications have been carried out to installed equipment.
Hands-On (Detailed) Inspections
A more detailed inspection would include all of the elements of a visual
inspection, plus some checks that cover the integrity of connections, fixtures
and fittings.
In addition to basic visual observations, more detailed integrity checks would
involve:
-
Verify that equipment housings, wall boxes and other mechanical fixtures are secured in place.
This includes terminal box lids, tightness of cable glands, integrity of wall- box mountings, security of equipment fixing to walls/DIN rails etc. -
Verify all electrical connections are secure with no loose screw terminals or DIN rail terminals not fitted to rails etc.
Equipment Maintenance
WARNING! The OTS-EL has no user-serviceable parts.
All repairs must be carried out by Ampcontrol only.
If a fault develops, return the unit to Ampcontrol for repair. It is essential
that no attempt be made to repair the unit as any attempt to dismantle or
repair the unit can seriously compromise the safety of the unit and voids
product warranty.
Disposal
ENVIRO The electronic equipment discussed in this manual must not be treated as general waste. By ensuring that this product is disposed of correctly you will be helping to prevent potentially negative consequences for the environment which could otherwise be caused by incorrect waste handling of this product.
SPECIFICATIONS
Specifications
Supply
Regulated Voltage| 24V DC or 24V AC (50Hz) ±20%
Power Supply Requirement| 5VA
Dimensions
OTS-EL (mm)| 91 x 100 x 110
Comms Module (mm)| 86 x 54 x 21
Earth Leakage Test
Test Interface| Current injected through the earth leakage toroid
Measured Entities| Elapsed time between trip initiation and outlet
contactor opening and,
Elapsed time between trip initiation and the back EMF falling below ELV (true clearing time).
Find Out More
For more information on this product, contact Ampcontrol Customer Service on
+61 1300 267 373 or
customerservice@ampcontrolgroup.com or visit the Ampcontrol website: www.ampcontrolgroup.com
EQUIPMENT LIST
Part Number | Description |
---|---|
175461 | MODULE OTS TESTER |
179019 | MODULE OTS2 TESTER |
175463 | MODULE OTS COMMS |
176536 | MODULE OTS EL-ONLY TESTER |
180264 | MODULE OTS EL-ONLY TESTER Version 2 |
175462 | MODULE OTS EXTERNAL EL/EC BARRIER |
176852 | OTS TESTERS TABLET 8” (LTE) C/W SOFTWARE AND CASE |
177451 | OTS TESTERS TABLET 8” (NON-LTE) C/W SOFTWARE AND CASE |