FRICO Elztrip EZ100 Panel Heaters Instruction Manual
- June 13, 2024
- FRICO
Table of Contents
Original instructions
Elztrip EZ100
Elztrip EZ100 Panel Heaters
Elztrip EZ100
Ecodesign Regulation (EU) 2015/1188 concerning local space heaters does not
apply to all application areas.
The Regulation applies when an installation is intended to provide thermal
comfort for people in the premises. The Regulation does not apply to heating
installations of a more technical nature e.g. in engineering/utility rooms, in
production processes, frost protection, etc. The Regulation also does not
apply to installations in vehicles, offshore or outdoors.
Many of Frico’s products can be used as both local space heaters (as defined
in (EU) 2015/1188) and for technical heating purposes. It is up to the
installer responsible for the installation to assess whether the Ecodesign
Regulation is applicable or not. Control solutions for installations not
covered by the Ecodesign Regulation are listed in a separate table.
| L
[mm]| A
[mm]
---|---|---
EZ106N| 870| 655
EZ111N| 1470| 1252
EZ115N| 1950| 1731
Fig.1. Ceiling mounting| Fig.2. Wall mounting
---|---
|
Fig.3. Positioning Fig.4. Minimum distances
| EZ100
[mm]
---|---
A| 50
B| 50
C| 50
D| 500
E| 1800
Accessories
Item number | Type |
---|---|
10004 | EZMVK (2x) |
Controls
Item number | Type | HxWxD [mm] |
---|---|---|
92790 | TAP16R | 87x87x53 |
205540 | TEP44 | 87x87x55 |
93044 | RTX54 | 82x88x25 |
205550 | SKG30 | 115x85x40 |
211780 | PDK65 | 102x70x50 |
Controls for installations not covered by the Ecodesign Regulation (EU) 2015/1188
Item number | Type | HxWxD [mm] |
---|---|---|
5999 | KRT1900 | 165x57x60 |
10214 | KRTV19 | 165x57x60 |
Elztrip EZ100 (IP44)
Item number| Type| Heat output [W]| Voltage [V]| Amperage [A]| Max. surface
temperature [°C]| Dimensions LxHxW [mm]| Weight [kg]
---|---|---|---|---|---|---|---
14894| EZ106N| 600| 230V~| 2,6| 320| 870x50x150| 3,2
14895| EZ111N| 1100| 230V~| 4,6| 320| 1470x50x150| 5,4
14896| EZ115N| 1500| 230V~| 6,5| 320| 1950x50x150| 7,0
- Heat output
- Voltage
- Amperage
- Max. surface temperature
- Weight
Wiring diagrams
Controls for installations not covered by the Ecodesign Regulation (EU) 2015/1188
Installation and operating instructions
General provisions
Please read these instructions carefully before installation and operation.
Save these instructions for possible calls to future.
The equipment can be used only for the intended purpose specified in this
Instructions. The warranty applies on installations made and used in in
accordance with the requirements and regulations of this Instruction.
Purpose and scope
The appearance of the device is compatible with any interiors and systems
lighting.Infrared heaters EZ100 intended for general or local heating rooms up
to 4 m high. They used in retail, office and residential premises, exhibition
halls, medical institutions, etc.
Recommended heater installation height indicated on the initial pages of the
instructions.
Protection class: IP44.
Purpose and principle of operation
Radiating surfaces have a temperature up to 320 °C. Energy is transferred to
others objects in the form of radiation, heating them.
Maximum ambient temperature +30 °C.
Installation
Elztrip devices are installed horizontally on the ceiling on mounting
brackets, cable guy wires, on supporting guides suspended ceilings, etc.
Mounting brackets for mounting to the ceiling included in the kit supplies. If
the device is hung on cables, then use 4 suspension points as in mounting
brackets. Wall Mounting Brackets fastenings must be ordered separately.
Distance there should not be any between cassette modules greater distance to
the floor; that is, less height H, see the figure at the beginning of the
Instructions.
Minimum installation distances see the picture at the beginning of the
instructions. Elements ceiling mount and screws are in terminal box.
Ceiling installation
- Install the ceiling mount brackets.
- Bend the mounting plates, located on the top panel of the device and hang it on the ceiling elements fastenings Fig.1. To fix the heater in a horizontal position, make sure that the guide pins are inserted into corresponding holes.
- When the incline is selected, tighten the screws securely.
Wall installation
Wall Mount Mounting Brackets must be ordered separately. (EZMVK)
- Install the wall brackets on the wall in in accordance with the dimensional drawing.
- Bend the mounting plates, located on the top panel of the device and hang it on the wall brackets fastenings Fig.2. To fix the heater in a horizontal position, make sure that the guide pins are inserted into corresponding holes.
- When the incline is selected, tighten the screws securely.
Electrical connection
The connection is made permanently based on an all-pole circuit breaker with
an air gap of at least 3mm. Nests terminal boxes suggest the possibility daisy
chain connection of a group of devices.
Maximum cable cross-section when connecting – 4 x 2.5 mm² + ground.
Installation must connect to the network via omnipolar circuit breaker with
air gap is not less than 3mm. All work must be carried out qualified
specialist with compliance with applicable rules and regulations.
To access the terminal box, unscrew screws and remove the end section.
Junction box on top panel the device has four inputs (2 x Ø21 mm) for electric
cable, two of them are equipped cable seals. Cable entry into the housing is
carried out through rubber bushings so that to ensure the declared protection
class.
Control
In accordance with Ecodesign (EU) requirements 2015/1188 when using the device
for periodic local heating, it must be equipped with one of the following
control devices.
-
TAP16R, electronic thermostat, has the following functions:
– Electronic room control temperature plus weekly timer
– Room temperature control in combinations with open window sensor -
TAP16R and SKG30, black ball sensor, have the following functions:
– Electronic room control temperature plus weekly timer
– Room temperature control in combinations with open window sensor
– Black ball sensor -
TAP16R and PDK65 presence sensor, have the following functions:
– Electronic room control temperature plus weekly timer
– Room temperature control in combinations with open window sensor
– Room temperature control combinations with presence sensor
The device can be controlled in another way, for example, a common dispatch system building (BMS), but in this case the responsibility for that the control system is programmed in accordance with Ecodesign (EU) requirements 2015/1188., lies with the installation specialist organizations.
Launch
When you turn it on for the first time after a long time there may be some
smoke during the break or there is a smell from burning dust on heating
elements. These manifestations quite acceptable even after a short using the
device they disappear.
Service
Any maintenance and repair work devices should only be produced after disconnecting from the network. wait until complete cooling of the device. The device has no movable parts, so maintenance needs minimal. It is necessary to maintain the device clean, promptly removing dirt and dust.
- When using the machine for the first time, due to shrinkage of the surface coating of panels A rattling sound may be heard.
- During operation of electric heating appliances heating surfaces and elements cases heat up and cool down, which can accompanied by slight clicks.
- Install and operate the device Clean gloves are required. Make sure clean the device before turning it on.
- Presence of residues of aerosols, varnish, solvents, dust, etc. may cause to the formation of plaque on the product and its discoloration.
- Slight color change heating surface of the device with flow time is normal.
Incorrect or unusual installation high ambient temperatures can lead to increased discoloration. Is not affects the declared power device.
Residual current device (RCD)
If the device is connected to the network through a residual current device
(RCD), operating on leakage current and when turned on it is triggered, it may
occur due to insulation moisture heating elements. This is usually result of
long-term storage in damp conditions.
This cannot be considered as malfunction and is eliminated temporarily turning
on the device without an RCD. Drying may take from several hours to several
days. To avoid moisture accumulation during prolonged periods We recommend
periodic breaks during work. turn on the device for a short time.
Residual current device (RCD) In the event that the device is connected to the
network through a residual current device (RCD), operating according to
leakage current and when turned on when it triggers, this may occur due to the
moisture in the insulation of the heating elements. This is usually the result
of prolonged storage in humid conditions.
This cannot be considered a malfunction and can be eliminated by temporarily
turning on the device without an RCD. Drying may take from several hours to
several days.
To avoid moisture accumulation during long breaks in operation, we recommend
periodically turning on the device for a short time.
Factory packaging
The materials used for packaging are selected with the environment in mind and
must therefore be recyclable and recyclable.
Disposal of the device at the end of its useful life
This device may contain substances that are necessary for its operation but
may be potentially hazardous to the environment. The device must not be
recycled with household waste; it must be taken to a special environmental
disposal point. Please contact your local authority for more information about
your nearest designated waste collection point.
Safety
- To protect against electric shock, electrically heated devices can be equipped with an RCD with a leakage current of 300 mA.
- To avoid overheating and fire hazard, the device must not be completely or partially covered with any objects or materials!
- The device must not be located near a socket!
- If the equipment or power cord is damaged, use of the device is not permitted. Risk of injury!
- The cable and plug must not be exposed to radiant heat.
- This appliance can only be used by children over 8 years of age or by persons with reduced capacity or lack of experience and knowledge if they have been given supervision or instruction concerning use of it by personnel responsible for their safety. Children must not be allowed to play with the device. If children are involved in cleaning or maintenance of the appliance, strict supervision is required by a person responsible for their safety.
- Children under 3 years of age should not have access to the device without constant adult supervision.
- Children aged 3 to 8 years can only turn on/off the appliance if it is installed for its intended purpose in a normal operating position and the children are supervised by an adult or have been instructed in how to use the appliance and understand that its improper use is life-threatening.
- Children aged 3 to 8 years should not plug the device into an electrical outlet, adjust its operation, or clean or perform maintenance on it.
WARNING – Some parts of this device may become very hot during operation
and cause burns.
Particular attention should be paid to children and vulnerable groups.
Main office
Frico AB
Industrivägen 41
SE-433 61 Sävedalen
Sweden
Tel: +46 31 336 86 00
mailbox@frico.se
www.frico.net
For latest updated information and information
about your local contact:www.frico.net
Art.no 208956, 2022-07-14 HH/CH
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>