selec RPS60-24-CE Power Supply Unit Instruction Manual
- June 4, 2024
- selec
Table of Contents
OP907-V02
selec
RPS60-24-CE
Operating Instruction
FEATURES
- AC 100-240V Wide-range Input.
- Cost optimized without compromising quality or reliability.
- Full power between -25ºC and +50ºC .
- Compact size.
INTENDED USE
This device is designed for installation in an enclosure and is intended for
the general professional use such as in instrumentation equipment, office,
industrial control communication.
Do not use this power supply in equipment where malfunction may cause severe
personal injury or threaten human life.
INPUT SPECIFICATIONS
INPUT VOLTAGE RANGE | 100 – 240VAC ±10% ; 127 – 370VDC |
---|---|
FREQUENCY RANGE | 50-60Hz |
EFFICIENCY(TYP.) | >87% @ 230VAC |
AC CURRENT(TYP.) | 1.2A @ 115VAC; 0.8A @ 230VAC |
INRUSH CURRENT(TYP.) | <48Amps; Measured at 264VAC, 25°C Ambient, Cold Start |
START UP TIME | <1 Sec@ 230VAC & <3 Sec@115VAC, Full Load |
OUTPUT SPECIFICATIONS
OUTPUT VOLTAGE | 24 – 28VDC |
---|---|
OUTPUT CURRENT | 2.5A at 24V; 2.14A at 28V |
RIPPLE AND NOISE | <1% of Vout ***** |
LINE AND LOAD REGULATION | ±1% |
HOLD UP TIME | ≥60ms at 230VAC & ≥15ms at 115VAC, Full Load |
SERIES OPERATION | Possible for up to two power supplies (with external diode) |
***** Ripple & Noise measured at 20MHz of bandwidth by using 0.1uF & 10uF parallel capacitor.
PROTECTIONS
INPUT FUSED | 2A – 250VAC Internal |
---|---|
OUTPUT OVER LOAD | 110% to 140% of rated output current Protection type : |
Hiccup mode; recovers automatically after fault condition is removed.
OUTPUT SHORT CIRCUIT| Hiccup mode when output is shorted; Recovers
automatically after fault condition is removed.
OUTPUT OVER VOLTAGE| 31.5VDC ± 1VDC
Protection type : Latched; Input AC power has to be recycled to recover the
power supply.
OVER TEMPERATURE| Power supply shuts down when the temperature of PCB below
main transformer reaches typically 120° C; Turns on only after the temperature
falls below 90° C typically and AC power is recycled thereafter .
ENVIRONMENT
OPERATING TEMPERATURE| -25°C to +70°C
*De-rate output power at 1.5W/°C above +50°C Ambient.
---|---
STORAGE TEMPERATURE| -40°C to +85°C.
HUMIDITY| 5 to 95% RH, Non Condensing
ALTITUDE| 2000m
SAFETY & EMC
SAFETY STANDARDS| Designed to meet IEC 62368-1
Processing for UL-508
---|---
DIELECTRIC WITHSTAND VOLTAGE| I/P to Earth : 2500VAC
I/P to O/P : 4000VAC
O/P to Earth : 1500VAC
INSULATION RESISTANCE| 100 MΩ min. (between all outputs and all inputs/ PE
terminals) at 500 VDC
CONDUCTED EMISSION| EN55022 ; Class A
RADIATED EMISSION| EN55022 ; Class A
EMS IMMUNITY| Compliance to IEC61000-4-4,5,11
DIMENSIONAL DIAGRAM
DIMENSION | 43109.8102.7mm (WHD) |
---|---|
WEIGHT | 285 gms |
WIRING DIAGRAM
WIRING INSTRUCTIONS
- To prevent risk of electric shock, power supply equipment must be kept OFF while wiring.
- Terminals and electrically charged parts must not be touched when the power is ON.
- Wiring shall be done strictly according to terminal layout provided in the operating manual.
INSTALLATION INSTRUCTIONS
Fig. 1
Attention:(Fig. 1)
- Do not block the ventilation holes of power supply.
- Keep at least 20mm clearance around the switching power supply.
- The Equipment should not be installed in environmental conditions other than those specified in this manual.
Fig. 2
Mounting:(Fig.2)
- Slightly tilt the unit to engage on the top side of Din Rail mounting.
- Press it downward until it gets locked in Din Rail.
Fig. 3
Removal:(Fig.3)
- Before removing power supply unit from Din Rail ensure that supply has been switched off.
- Unscrew all the wire connections of power supply unit.
- Insert a screw driver into the mounting clamp slot & pull it down to remove the power supply from Din Rail.
WARNING : Risk of electrical shock, fire, personal injury or death.
- Do not use the power supply without proper grounding (Protective Earth).
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Make sure mains power supply is off before wiring the power supply unit. Make sure of correct wiring. Incorrect wiring may cause electrical shock or damage.
- Do not touch the power supply during operation or immediately after turning off because some parts get hot or are at high voltage which may cause burns or electrical shock.
- Do not install the power supply where human body may come into contact while power is supplied to the power supply.
- Do not repair the power supply at user end . Modification or repairing of the power supply by users may cause electrical shocks, damage, & other accidents.
- If damage or malfunction occurs during operation, immediately turn off mains power.
CAUTION
Minor burns may occasionally occur. Do not touch the product while power is
being supplied or immediately after power is turned OFF.|
---|---
If the external breaker or fuse is tripped, the equipment may have been
seriously damaged. Do not turn ON the input again.|
Minor injury due to electric shock may occasionally occur. Do not touch the
terminals while power is being supplied.|
Minor electric shock, fire or product failure may occasionally occur. Do not
allow any pieces of metal or conductors or any clippings or cuttings resulting
from installation work to enter the product.|
MEANING OF PRODUCT SAFETY SYMBOL
| Indicates the possibility of electrical shock under specific conditions
---|---
| Indicates the possibility of injuries by high temperature under specific
condition
| Indicates the instructions of unspecified general action.
SAFETY INSTRUCTIONS
- This manual is meant for personnel involved in wiring installation operation & routine maintenance of the equipment.
- Disconnect power supply of your system before starting any installation operation or wiring.
- Improper installation operation or wiring may impair safety & failure of the unit or electrical shock or damage.
- Connect the ground completely. A protective earthing terminal stipulated in safety standards is used. Electric shock or malfunction may occur if ground is not connected properly.
? SERVICE DETAILS
This power supply is not field serviceable product. In case of failure or
malfunction, send back the power supply to factory.
Please contact service center for repair on the following numbers:
Tel. No. : +91-7498077172;
Email :service@selec.com
NO WARRANTY ON UNIT DAMAGED DUE TO WRONG CONNECTION OF POWER SUPPLY.
(Specifications are subject to change, since development is a continuous process.)
Factory Address :
EL-27/1, Electronic Zone, TTC Industrial Area,
MIDC, Mahape, Navi Mumbai – 400 710, INDIA.
Tel. No. : +91-22-28476443 / 1882
Fax No. : +91-22-28471733 I Toll free : 1800 227 353