ALDERON Industries CKIT1S Check It Simplex Pump Station Control Panel Instructions
- June 13, 2024
- ALDERON Industries
Table of Contents
ALDERON Industries CKIT1S Check It Simplex Pump Station Control Panel
Instructions
Introduction
Product Overview
The Check It™ Simplex control panel is designed to operate a single sewage pump in demand dose applications. It supports both 120VAC and 230VAC pumps within specified FLA ranges and has a Type 4X (indoor/outdoor) enclosure.
The panel offers up to four float inputs: low level alarm, stop level, start level, and high alarm or high alarm/start level. The pump starts when the liquid level rises and activates the start level switch, and runs until the pump stop switch is deactivated, ending the cycle. If the low level float deactivates, a low level alarm will be triggered and the pump will turn off. The high level float will trigger a high level alarm when activated.
Product Highlights
Below is a list of highlighted features of the Check It™ Simplex system. For
further details on each feature, please see the rest of this document.
Power Inputs
- 120 VAC Board Power Input
- 120/230 VAC Pump Power Input
Sensor Inputs
- Four Float Inputs
- Low Level, Stop, Lead, and Alarm
- Seal Fail Sensor Input (Optional)
- With Sensitivity Adjustment Between 10K and 100K
User Inputs
- Test/Silence Switch
- Test/Config Switch (For Changing Field Settings)
- Hand-Off-Auto Control
Outputs
- Pump Contactor With Specified FLA Ranges
- One Auxiliary Dry Contact Output
Indications
- Red/Green Beacon for System Normal, Pump Run, and Alarm Indication
- Indicator LEDs for Each Sensor Input
- Pump Run Indicator LED
Field Configurations
- Input Error Detection
- Automatic Alarm Reset
- High Float Redundant Start Enable
- Seal Fail Pump Stop Enable
- Seal Fail Buzzer Enable
- Green System Normal Beacon Enable
Before Installation
Before proceeding with the installation or operation of the control panel read
all instructions thoroughly, as well as comply with all Federal, State and
Local Codes, Regulations and Practices. The control panel must be installed by
qualified personnel familiar with all applicable local electrical and
mechanical codes. Refer to the National Electrical Code (NFPA 70). Failure to
properly install and test this product can result in personal injury or
equipment malfunction. All conduit connected to the panel must be sealed with
conduit sealant to prevent moisture or gases from entering the panel. NEMA 1
enclosures are for indoor use only while NEMA 4X panel enclosures may be used
indoor or outdoor. Refer to panel model name plate on inside of door for
enclosure rating.
Note: If options are ordered that affect the number of floats, refer to
the panel schematic for complete information.
Safety Guidelines
- DO NOT USE WITH FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE, ETC. DO NOT USE IN EXPLOSIVE ATMOSPHERES. CONTROL PANEL SHOULD ONLY BE USED IN WATER AND WASTEWATER APPLICATIONS THAT ARE NOT RATED AS A HAZARDOUS LOCATION.
- DO NOT WORK ON THE CONTROL PANEL WITH LIVE VOLTAGE APPLIED TO THE CONTROL PANEL WITH WET HANDS OR WHEN STANDING ON A WET SURFACE.
- DISCONNECT ALL ELECTRICAL SERVICE BEFORE WORKING ON OR HANDLING THE CONTROL PANEL
- INCOMING VOLTAGE MUST MATCH THE CONTROL PANEL VOLTAGE. REFER TO THE PANEL SCHEMATIC FOR COMPLETE INFORMATION
Description of Product Interface
The following sections will describe all of the interface points with the Check It™, including all buttons, indicator outputs, and sensor inputs for the system.
Outside of the Panel
Each Check It™ panel is equipped with a test/silence switch, an Red-Green (RG) indicator LED, and a buzzer. The test/silence switch is used to activate an indicator test routine to verify the beacon, buzzer, and LED indicators are all functioning properly. The Red-Green beacon will by default be illuminated green while the system is normal and monitoring, will blink green while the pump is running, and will blink red when there is an alarm. If both an alarm and a pump run event are happening simultaneously, the beacon will alternate between Red and Green. If the pump is not enabled (set to OFF mode), the beacon will blink a yellow warning to the user.
Inside of the Panel
HOA Switch
The Check It™ features a Hand-Off-Auto (HOA) selector switch. When set all the
way up, the pump will enter hand mode and the contactor output from the Check
It™ will activate. When in the middle, the pump will be in OFF mode and will
not activate during pump starting events. When set all the way down, the pump
will be in auto mode and will be turned on during pump start events. Note that
if the pump is set to OFF, the RG beacon will blink yellow to warn the user
that the system will be unable to activate the pump.
Test/Config Button
The Test/Config button is used to activate the indicator test routine, to
clear active alarms, and the modify the system settings. See the “How To Clear
an Alarm” section for details on alarm clearing and the “How to View and
Change Settings” section for details on configuring the device.
Indicator LEDs
The Check It™ features indicator LEDs for each sensor input as well as an
indicator LED for the pump. The F1 through F4 LEDs indicate the state of the
float inputs. the S1 LED indicates if the seal fail sensor input is tripped or
not. The Pump Run LED indicates whether or not the pump is running. Note that
if the Pump Run LED is blinking, that means that pump’s seal fail sensor has
been tripped.
Auxiliary Dry Contact
The Check It™ features a single auxiliary dry contact alarm output with both
normally open and normally closed connections. This dry contact output will
activate during any alarm condition. Additionally, the contact will be active
when the product loses power, allowing for power loss detection and alarming
when connected to building automation systems.
Sensor Connections
Float Sensors
The F1 through F4 inputs are designed for standard signal level gold contact
floats. They are powered by an isolated 3.3 Volt low power and touch safe
power source generated by the Check It™ circuit board.
Seal Fail Sensors
The S1input is a water detecting probe circuit designed for use with stainless
steel pump seal fail probes. Itis powered by an isolated 12 Volt alternating,
low power and touch safe power source generated by the Check It™ circuit
board. Next to the seal fail sensor input, there is a “SEAL SENSITIVITY”
adjustment potentiometer. This can be used to adjust the trip point of the
seal fail probe between 10 and 100 Kilo-Ohms of equivalent resistance through
water. 100 K is the most sensitive setting, and 10 K is the least sensitive.
How To Clear an Alarm
If automatic alarm reset is disabled, the user must manually clear all alarm events. To do this, activate and hold the Test/Silence switch on the side of the panel or the Test/Config button on the product chassis for 5 seconds. This will reset all active alarms. Note that if the alarm immediately re-activates and the buzzer activates again, this means that the alarm condition is still present and the system cannot clear the alarm. If this happens, check for the source of the alarm.
Settings
The Check It™ panel has several settings that the user can use to customize the panel for the application. This section will describe how to change the settings and provide a list of the available settings.
How to View and Change Settings
Press and hold the test/configure pushbutton on the Check It™ chassis to begin the setting viewing and changing routine. The system will immediately begin a test blinking pattern of all indicator outputs. After holding for 5 seconds, the setting viewing and changing routine will begin. The routine is as follows:
- LED Test Pattern; Press and hold the Test/Config button.
- The LED indicator outputs, buzzer, and beacon will all begin blinking in a test pattern.
- View Settings; Hold the Test/Config button for 5 seconds.
- The test blinking pattern will stop and the indicator LEDs will display the current system settings.
- If an indicator LED is ON, that means the setting is enabled. Otherwise, the setting is disabled.
- See the “Available Settings” section for a summary of the configs and which LED they are indicated by.
- Toggle Settings; Hold the Test/Config button for another 5 seconds to change a setting.
- A fastblinking pattern will begin to move through the indicator LEDs from left to right and then up to the green beacon.
- This fast blinking pattern indicates which setting is currently selected.
- Totoggle a setting, release the Test/Config button while the desired Setting Indicator LED is blinking.
- After releasing the Test/Config button, a medium blinking pattern will confirm which setting was toggled, after which the system will display the new system settings followed by a burst of fast blinks before the system returns to normal operation..
- Exit Without Saving; To exit without changing any settings, keep holding the Test/Config button until the fast blinking pattern moves through all of the indicator LEDs and the system returns to the test blinking pattern. The Test/Config button can now be released without changing any settings.
Automatic Low-Alarm Enable
The low alarm input of the Check It™ is disabled by default to remove the need for installing jumpers on panels that do not use it. However, the system will automatically enable this input if it detects a closed float connected to it for at least 30 seconds.
Available Settings
Name | Indicator LED | Factory Defaut | Description |
---|---|---|---|
Input Error . . Detect | F1LED | Enabled | Enables input sequence error |
detection. If the floats activate out of sequence (e.g., the high level float
activates before the start float) the system will alarm.
Automatic Alarm Reset| F2 LED| Enabled| Enables automatic alarm resetting. If
enabled, the R system will automatically stop alarming once the alarm
condition is resolved. If disabled, the user must manually clear each alarm by
holding the test/silence switch.
High Redundant Start Enable| F3 LED| Enabled| fInat Enables es redundant
redundant pump tarting sarting on on the the high high alarm
Seal Fail Pump Stop Enable| F4 LED| Disabled| If enabled, this will cause the
pump to stop when the seal fail input has been triggered.
Seal Fail Buzzer Enable| S1LED| Enabled| If enabled, the buzzer will enunciate
when the seal fail input is triggered. If disabled, only the beacon will
activate.
Green System Normal Beacon Enable| Breen Beacon| Enabled| If enabled, the
beacon will be illuminated green when the system is normal. If disabled, the
green beacon will only activate when one of the pumps are running.
© 2023 Alderon Industries. All rights reserved. | Powered by Wiki.js
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>