Package Content
9/R 160-500 9/R 160-700|
036765 039891
| | 4
---|---|---|---
e²| 039993| | 5
e²kurz| 040003| | 6
e²60| 041157| | 6
e²60kurz| 040150| | 8
Electrical connection| | | 9
Notes| | | 10
11
DIMENSIONS
BOX CONTENTS
DIMENSIONS
BOX CONTENTS
DIMENSIONS
Unit voltage | 12 V DC SELV, max. 12,6 V |
---|---|
Dimensions (Ø x l) | Ø 154 mm, 243 mm |
Protection class | IP 22 |
Volume flow | 15 – 38 m³/h |
Sound power level | 29 – 49 dB (A) |
Sound pressure level 1 m | 21 – 41 dB(A) |
Heat recovery rate | 88% |
Specific power consumption | 0,08 W/m³/h |
Energy efficiency class | A+ |
DIBt approval | Z-51.3-450 |
BOX CONTENTS
DIEMSIONS
Unit voltage | 12 V DC SELV, max. 12,6 V |
---|---|
Dimensions (Ø x l) | Ø 154 mm, 165 mm |
Protection class | IP 22 |
Volume flow | 15 – 38 m³/h |
Sound power level | 29 – 49 dB (A) |
Sound pressure level 1 m | 21 – 41 dB(A) |
Heat recovery rate | 80% |
Specific power consumption | 0,08 W/m³/h |
Energy efficiency class | A+ |
DIBt approval | – |
BOX CONTENTS
DIMENSIONS
Unit voltage | 12 V DC SELV, max. 12,6 V |
---|---|
Dimensions (Ø x l) | Ø 154 mm, 243 mm |
Protection class | IP 22 |
Volume flow | 5 – 60 m³/h |
Sound power level | 18 – 56 dB(A) |
Sound pressure level 1 m | 10 – 48 dB(A) |
Heat recovery rate | 83% |
Specific power consumption | 0,05 W/m³/h |
Energy efficiency class | A+ |
DIBt approval | Z-51.3-450 |
BOX CONTENTS
DIMENSIONS
Unit voltage | 12 V DC SELV, max. 12,6 V |
---|---|
Dimensions (Ø x l) | Ø 154 mm, 165 mm |
Protection class | IP 22 |
Volume flow | 5 – 60 m³/h |
Sound power level | 18 – 56 dB(A) |
Sound pressure level 1 m | 10 – 48 dB(A) |
Heat recovery rate | 81% |
Specific power consumption | 0,05 W/m³/h |
Energy efficiency class | A+ |
DIBt approval | – |
WIRING
About this manual
- Read this manual carefully and completely before assembly! Always observe the general safety instructions and the safety symbols with information in the text.
- Hand out this manual to the user (tenants, proprietors, property management etc.) after completing assembly.
Disposal
The packaging must be sorted before disposal. If you wish to dispose of the device, observe the currently applicable regulations. The municipal office in charge will provide information.
Installation position
Do not position the device above sensitive furniture, surfaces or pictures;
the wall beneath the device should remain unused.
Do not position the device above or near room thermostats.
Electrical connection
Caution! Any assembly work (connection to power supply and setting of the
miniature switches) may only be carried out after disconnecting the supply
voltage.
Make sure that the supply voltage of all connection lines is voltage-free
(dead). (Separation from the power supply with a minimum contact opening of 3
mm, e.g. electric fuse).
Each electric circuit of this ventilation system must be fitted with a
residual current protection (e.g. FI switch/RCCB).
Electric connection only by a specialist.
Additional installations and electrical components in the ventilation unit are
not allowed. Connection diagrams for further fan functions upon request.
Use the following cables for the electric connection:
- Cable to the ventilation units: e.g. J-Y(St)Y(2x2x0,8), min. 0,5 mm², max. 1,5 mm²
- Cable for the supply voltage of the power supply unit e.g. NYM 3 x 1,5 mm²
Note regarding LUNOS outer covers
The solid plastic outer covers provided by LUNOS ensure high resistance to
driving rain and can be used in Stress Group III pursuant to DIN 4108-3
(2012-04). Metal or metal-coated covers can be used in Stress Group I pursuant
to DIN 4108-3 (2012-04).
In the case of buildings exposed to wind or the risk of strong winds and rain
to the outer covers, further measures of weather protection may be required.
Filter replacement
Check the filter (1) every 3 months for contamination. Clean or replace, if
required. After inserting the filter, snap the design screen into place in
“open position“.
The ventilation openings must not be covered or obstructed.
Note: Alternative inner screens are supplied with the corresponding
instructions on filter replacement.
Partel Ireland
Website: www.partel.ie
Email: sales@partel.ie
Phone: 0818333355
Partel UK
Website: www.partel.co.uk
Email: sales@partel.co.uk
Phone: 02037401918
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>