ELMEKO 15 ETUH 022 Hygrostat AC1 Change Over User Manual

June 13, 2024
ELMEKO

ELMEKO - Logo

ELMEKO 15 ETUH 022 Hygrostat AC1 Change Over - Cover

ETUH 22 ELECTRONIC THERMO-HYGROSTAT

APPLICATION

The ETUH 22 thermo-hygrostat monitors the temperature and humidity in the control cabinet. This is because pronounced cold, heat or even humidity, leads to strong loads on the control cabinet components. Even small temperature changes lead to humidity inside the control cabinet. This is because warm air can hold more moisture than cold air. When warm air cools down, moisture can condense, which shows up as condensed water at the coldest points in the control cabinet. Temperature and humidity control in the control cabinet is therefore essential. re essential.

FEATURES

  • Temperature controller for fan and heater
  • CO Changeover contact
  • Adjustable temperature 0 – 60 °C
  • Adjustable humidity 20 – 90 Rh%
  • Mounting on DIN rail
  • 10 A switching capacity at 250 V AC

FUNCTIONAL DESCRIPCION

The ETUH was specially developed to control fan or heater. A connected heater or fan prevents the formation of condensation on electrical components. The CO contact is switched either at high humidity or low temperature. Temperature and humidity are independently adjustable. LEDs signal function and status.

TECHNICAL DATA

Designation Type ETUH 22
Part number 15 ETUH 022
Perm. operating voltage 230 V AC; 50/60 Hz; 20 VA
Output switch contact CO Change over
Sensor switching system Integrated electronic sensor for humidity and

temperature
Switsching contact resistance| < 10 mOHM
Switching difference (hysteresis) temperature / humidity| 2 K / 5 %
Switching precision| ± 1 K
Switching capacity AC max| NO/NC: 10 A @250 V AC – resistive load
NO: 400 VA @240 V AC; 200 VA @120 V AC – inductive load
Switching capacity DC max| NO/NC: 8 A @ 30 V DC – resistive load
Switching power| 30 W @ 48 V DC
Switching reaction time| 60 sec.
Control range temperature / humidity| 0 °C … +60 °C / 20 % … 90 Rh %
Protection class| 0
Degree of protection| IP20
Operating temperature| -40°C… +80°C
Storage temperature| -45°C… +80°C
Admissible degree of humidity| max. 95% r.h., non-condensing
Electrical connections| terminal 0,5 … 2,5 mm²
Housing material and colour| PA6, UL94 V0 self-extinguishing, light grey RAL 7035
Service life| > 1000.000 switching cycles
Weight| 110 gr.
Way of installation| on 35 mm standard rail
Approval| CE

DIMENSIONED DRAWING / CONNECTION DIAGRAM

ELMEKO 15 ETUH 022 Hygrostat AC1 Change Over - ANSCHLUSS
SCHALTBILD

Terminal|
---|---
1-2  input supply| 230 V AC; 50/60 Hz; 20 VA
4-6  output NO contact| NO: 10 A @250 V AC; 50/60 Hz – resistive load
NO: 8 A @ 30 V DC – resistive load
NO: 400 VA @240 V AC; 50/60 Hz –  inductive load
NO: 200 VA @120 V AC; 50/60 Hz –  inductive load
5-6 Output NC contact| NC: 8 A @ 30 V DC –  resistive load

FUNCTION

The presence of the supply voltage is signaled by a green LED. When the changeover contact is switched, a red LED lights up.

  • Contact 4-6 closes (and the contacts 5-6 opens) if humidity rises above humidity set point or if temperature falls below temperature set point.
  • Contacts 5-6 closes (and the contacts 4-6 opens) if temperature rises above temperature set point or if humidity falls below humidity set point.

ACCESSORIES

Type Description Part number
HAL 51 Installation set with 2 screws 19 HAL 051

MOUNTING / INSTALLATION

The Thermo-Hygrostat ETUH must only be used in stationary, closed electric cabinets.
The controller is mounted on a 35 mm DIN standard rail. For this purpose, the controller is hooked in with the upper hooks and then snapped onto the standard rail by pressing. To remove the controller from the standard rail, first pull it down and unhook it from the front.
The ETUH 22 has internal sensors. In order to record the actual internal temperature of the control cabinet, it must not be directly exposed to cold or heat sources, unless it is the assembly to be protected. After mounting, the controller must be wired as shown in the wiring diagram.
After installation, therefore, the correct operating direction and proper functioning of the control must be checked. The switching point is set with a slotted screwdriver.

|
---|---
Mounting
1. Hook up at the top
2. Snap on below| Removal
1. Pull downward
2. Unhook inclined manner

ELMEKO GmbH + Co. KG Graf-Zeppelin-Str. 5 56479 Liebenscheid Germany
Tel. +49/2736/509748-0 info@elmeko.de www.elmeko.de
Rev. 06/2022