ELMEKO THRV 22 Double-Thermostat Owner’s Manual

June 13, 2024
ELMEKO

ELMEKO THRV 22 Double-ThermostatTHRV 22 DOUBLE TEMPERATURE CONTROLLER

APPLICATION

This double thermostat monitors the temperature in the switching cabinet. It was specially developed to control the combination of fan and heater. It is two independently switching thermostats with a high switching capacity in a compact housing.

FEATURES

  • Temperature controller for fan and heater
  • 1x NC contact at rising temperature to control the heater
  • 1x NO contact at rising temperature for regulation of the fan
  • High power capacity
  • Adjustable temperature 0 – 60 °C
  • Mounting on DIN rail
  • 10 A switching capacity at 250 V AC

TECHNICAL DATA

Type THRV 22
Part number 15 THRV 022
Perm. operating voltage 12 V DC– 48 V DC

125 V AC – 250 V AC
Output switch contact| 1x NC; 1x NO
Sensor switching system| Bimetall intern
Switsching contact resistance| < 10 mOHM
Switching difference (hysteresis)| 7 K
Switching precision| ± 4 K
Switching capacity| max. 10 A (1,6 A) @ 250 V AC
max. 15 A (2,5 A
) @ 125 V AC
Switching power| 30 W @ 48 V DC
Control range| 0 °C … +60 °C
Protection class| 0
Degree of protection| IP20
Operating temperature| -25°C… +80°C
Storage temperature| -45°C… +80°C
Admissible degree of humidity| max. 95% r.h., non-condensing
Electrical connections| terminal 0,5 … 2,5 mm²
Housing material and colour| PA6, UL94 V0 self-extinguishing, light grey RAL 7035
Service life| > 1000.000 switching cycles
Weight| 80 gr.
Way of installation| on 35 mm standard rail
Approval| CE

Inductive load

DIMENSIONED DRAWING

ELMEKO THRV 22 Double-Thermostat - DRAWING

CONNECTION DIAGRAM

ELMEKO THRV 22 Double-Thermostat - DRAWING 2

FUNCTION

ELMEKO THRV 22 Double-Thermostat - Switch

Contact status

SP| Set point (thermostat value set)
ON| Switching point (contact closing temperature)
ti| Negative tolerance of set point
TL| Positive tolerance of set point
H| Hysteresis
OFF| Switching point (contact opening temperature)

ACCESSORIES

 Type Description Part number
HAL 51 Installation set with 2 screws 19 HAL 051

MOUNTING/INSTALLATION

The controller is mounted on a 35 mm DIN standard rail. For this purpose, the controller is hooked in with the upper hooks and then snapped onto the standard rail by pressing. To remove the controller from the standard rail, first pull it down and unhook it from the front.
The THRV 22 has internal sensors. In order to record the actual internal temperature of the control cabinet, it must not be directly exposed to cold or heat sources, unless it is the assembly to be protected. After mounting, the controller must be wired as shown in the wiring diagram.
After installation, therefore, the correct operating direction and proper functioning of the control must be checked. The switching point is set with a slotted screwdriver.

Mounting

  1. Hook up at the top
  2. Snap on below

Removal

  1. Pull downward
  2. Unhook inclined manner

ELMEKO GmbH + Co. KG Graf-Zeppelin-Str. 5 56479 Liebenscheid Germany
Tel. +49/2736/509748-0 info@elmeko.de www.elmeko.de