Vallox 99 MV CF Ventilation Unit User Manual

June 13, 2024
VALLOX

99 MV CF Ventilation Unit

Product Information

Model: Vallox 99 MV CF

Type: 3756

Document: D11218

Valid from: 01.01.2022

Updated: 19.06.2023

Product: Ventilation unit

Introduction

  • Safety
  • Installation
  • Ventilation unit control options
  • Filter reminder
  • Ventilation unit setup without a MyVallox control panel
  • Connecting the ventilation unit to the cloud service
  • Main parts

Installation

  • Mounting on the wall
  • Mounting on the ceiling

Maintenance

  • Cleaning of the anemometer

Technical Specifications

  • In the outdoor air duct
  • In the supply air duct
  • Exploded view and parts list
  • Conformity certificates

Important Safety Information

Installation and setup should only be carried out by a qualified
specialist. Electrical installations and connections must be
carried out only by an electrician and in compliance with local
regulations.

Warranty Information

The product is covered by warranty. Please refer to the warranty
document for more details.

Intended Use

All Vallox ventilation units are designed to provide appropriate
and continuous ventilation to maintain indoor air quality and the
condition of the building structures.

Disposal

Do not dispose of the ventilation unit with household waste.
Follow local laws and regulations for safe and ecological disposal
of electronic devices.

MANUAL

Manual

Model Vallox 99 MV CF
Type 3756

Document D11218
Valid from 01.01.2022
Updated 19.06.2023

Ventilation unit

INTRODUCTION

CONTENTS
INTRODUCTION 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Disposal of the ventilation unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Safety signs used in the instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Installation options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Ventilation unit control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Ventilation unit control options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Filter reminder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Ventilation unit setup without a MyVallox control panel . . . . . . . . . . . .5 Connecting the ventilation unit to the cloud service . . . . . . . . . . . . . . .5 Main parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
INSTALLATION 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting on the wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Mounting on the ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mounting the ceiling mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Installing the ventilation unit to the ceiling mounting plate . . . . . . . . .8 Attic floor penetration plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Removal of condensing water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Dimensioning figures and space required for installation of the Vallox Silent Klick siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Space required by the alternative Vallox Silent Klick siphon installation method (elbow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Measuring and adjusting the air flows of the ventilation unit . . . . . . . . . .9 Dimensions and duct outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
MAINTENANCE 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before beginning maintenance work. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Replacing the filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Cleaning the heat recovery cell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Condensing water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Cleaning the fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cleaning of the anemometer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
TECHNICAL SPECIFICATIONS . . . . . . . 15
Internal electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 External electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 External electrical connection for controlling the MLV duct radiator. . . 18 Duct radiator operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Duct radiator operation chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
In the outdoor air duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 In the supply air duct. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Exploded view and parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Conformity certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2

NOTE You can register your Vallox MV ventilation unit with the MyVallox Cloud service and sign in into your MyVallox Cloud account at www.myvallox.com.

INTRODUCTION

SAFETY
Safe and appropriate handling requires knowledge of the basic safety regulations, and of the intended use of the ventilation system. Read this manual before operating the ventilation unit. Please keep the manual for later reference. If you lose the manual, it can be downloaded from our website. This user manual contains all the information necessary for safe operation of the system. All persons who operate and maintain the ventilation system must follow the instructions provided in this manual. Furthermore, all local accident prevention regulations must be observed.
Installation
Installation and setup should only be carried out by a qualified specialist. Electrical installations and connections must be carried out only by an electrician and in compliance with local regulations.
WARRANTY
The guarantee and liability exclude damage resulting from: · Inappropriate use of the ventilation system or the control unit · Incorrect or inappropriate installation, setup or use · Neglect of instructions concerning transportation, installation, use,
or maintenance · Structural or electronic modifications or changes made to the
software
INTENDED USE
All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to maintain structures in good condition.
IMPORTANT In order to ensure that the indoor air presents no harm to health and remains optimal also for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.
DISPOSAL OF THE VENTILATION UNIT
Do not dispose of electronic devices with household waste. Follow local laws and regulations on safe and ecological disposal of the product.

NOTE For further information, go to www.vallox.com
WARNING The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit. Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety. Children must be supervised and not be allowed to play with the device.

3

© Vallox Oy – All rights reserved

INTRODUCTION

SAFETY SIGNS USED IN THE INSTRUCTIONS

DANGER Indicates a hazard that will result in death or serious injury if not avoided.
IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided.

WARNING Indicates a hazard that can result in death or serious injury if not avoided.
NOTE Indicates essential information about the product.

CAUTION Indicates a hazard that can result in minor or moderate injury if not avoided.
TIP Provides additional information about the use of the product and its benefits.

INSTALLATION OPTIONS
· Vallox 99 MV can be mounted either on the wall, or on the ceiling by using a mounting plate (optional).

NOTE The standard equipment and available accessories vary from country to country.

SYSTEM DESCRIPTION

1. Internet 2. WLAN 3. Router 4. WLAN/LAN 5. Additional switch 6. Sensors

MyVallox Cloud 1

2 3

Vallox MV

5 6

MyVallox Home

4
4

KNX bus module

Modbus

KNX

MyVallox control panel

VENTILATION UNIT CONTROL
Ventilation unit control options
Operation of the Vallox ventilation unit can be controlled by the following means: · Through the MyVallox control panel installed in the building. · Through the MyVallox Home local area network connection and
the MyVallox Home/Cloud user interface. · Through the MyVallox Cloud service and the MyVallox Home/
Cloud user interface. · Through a remote monitoring service or building automation
that uses voltage signals or Modbus messages.
In addition to the integrated humidity and carbon dioxide sensor, ventilation can also be adjusted automatically by using the optional carbon dioxide, humidity, or VOC (air quality) sensor. When these are used, ventilation remains optimal even when the dwelling is unoccupied. Each user can use the week clock to adjust the ventilation to fit their individual lifestyle.
Filter reminder
The unit reminds the user of the need to change the filters through the MyVallox control panel and the MyVallox Home/Cloud user interface, as well as by changing the relay status, if a signal light has been connected to the relay connectors of the unit.
The filter reminder can be acknowledged: · From the MyVallox control panel · From the MyVallox Home/Cloud user interface · From the Vallox Delico PTD EC and Vallox Capto PTC EC
control hoods — Damper closed, then open-closed-openclosed. Press at a less than 1 second interval.
Ventilation unit setup without a MyVallox control panel
The ventilation unit setup can also be completed without a MyVallox control panel. For instructions, please go to https://vallox.techmanuals.info/ValloxMV/ENG/help/webhelp
See instructions provided in the section Connecting the ventilation unit to the computer.
Connecting the ventilation unit to the cloud service
The ventilation unit can be connected to the MyVallox Cloud service. The cloud service allows for controlling ventilation remotely also, using e.g. a smartphone or tablet. Also the unit software is updated automatically through the cloud service. To connect to the cloud service, the ventilation unit must be connected to the Internet via LAN and registered with the cloud service. At the same time you create a MyVallox Cloud account for yourself. Read more about the service at www.myvallox.com.
5

NOTE For the MyVallox Cloud/ Home instructions, please go to vallox.techmanuals.info/ ValloxMV/ENG/help/ webhelp
IMPORTANT Prolonged overpressure can result in damage to the structures of the building.
IMPORTANT Apartment-specific ventilation units allows residents to adjust the ventilation efficiency. Ventilation is controlled based on the need e.g. through the cooker hood, ventilation control panel, or a separate control centre. In order to ensure that the indoor air presents no harm to health and remains optimal also for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.
© Vallox Oy – All rights reserved

INTRODUCTION

RATING O F EXTRAC
INTRODUCTION

MAIN PARTS

12
11 10 8 7
4 2

ERY

A

T AIR HEAT REC OV

NNUAL EFFIC IENC Y
A
6 9 3 5 1

13

14

15

16

R model in the figure

Extract air fan Supply air fan Fine filter for supply air Heat recovery cell Bypass damper of the HR cell Coarse filter for supply air Coarse filter for extract air Post-heating resistor
(in front of the supply air fan)

1 2 3 4 5 6 7 8
6

Additional heating resistor
9
Safety switch
10
Internal carbon dioxide and humidity sensor
11
Ceiling bushing for electric wires
12
Control panel
13
Carbon dioxide sensor (optional)
14
Humidity sensor (optional)
15
VOC sensor (Optional)
16

INSTALLATION

INSTALLATION

MOUNTING ON THE WALL
NOTE Avoid mounting the unit on a hollow, echoing partition wall or on a bedroom wall, or prevent the conduction of sound.
The minimum distance between the top of the unit and the finished ceiling surface is 30 mm. Note that during mounting the unit rises 10 mm higher than the final height.
Mount the ventilation unit onto the wall with a mounting plate (optional), as shown in the figures below. Make sure that the unit is horizontally level after mounting.

NOTE When installing the unit, reserve a space of at least 500 mm in front of the unit for servicing purposes.
NOTE Mount the ventilation unit in a place where the temperature does not fall below +10°C.

MOUNTING ON THE CEILING
Vallox 99 MV can be equipped with an optional ceiling mounting plate. To attach the ceiling mounting plate: · On rafter frames or other frame structure with M8 thread bars so
that they withstand the weight of the unit. · Ensure that the installation plate is horizontally level, as this
determines the position of the unit. · The top edge of the white covering strip of the ceiling mounting
plate can be installed against the ceiling. Alternatively, a concealed mounting method can be used, in which case the ceiling can be 30 mm below the top of the white covering strip.
Insulate the ducts against condensation also between the unit and the ceiling mounting plate.
Mounting the ceiling mounting plate
1. Fasten the thread bars on the rafter frames or other frame structure, and screw the nuts (E) onto the bars.
2. Lift the ceiling mounting plate in place. 3. Push a rubber damper (F) and a washer (G) to each thread bar. 4. Adjust the nuts so that the ceiling mounting plate is level. 5. Shorten the lower ends of the thread bars so that they are no more
than 5 mm below the nuts.
CAUTION The ventilation unit is very heavy. Do not perform this procedure alone.
7

© Vallox Oy – All rights reserved

INSTALLATION

Installing the ventilation unit to the ceiling mounting plate

1. Install the ceiling mounting plate with M8 thread bars so that it is horizontally level.
NOTE The end of the thread bars must be 5 mm or less below
the fastening nut. Do not fasten the ceiling mounting plate A too tight to the ceiling. Ensure that the sliding bars move and restore to their original position by pulling from the operating levers (A).

The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling. Alternatively, a concealed mounting method can be used, in which case the ceiling can be 30 mm below the top of the white covering strip.

2. Ensure that the insulation washers are in the outlet collars

below the ceiling mounting plate.

3. Remove the door before installing the ventilation unit to the

ceiling mounting plate.

4. Lift the ventilation unit close to the ceiling mounting plate

A

and feed the cables and the connection box through the

hole in the ceiling mounting plate on top of the ceiling.

NOTE Remember to make a service door in the ceiling so that the cables and the connection box can be accessed. The distance between the service door and the ceiling mounting plate must be around 500 mm.
Alternatively, the cables can be fed to the rear wall between the ceiling mounting plate and the ventilation unit. When the ventilation unit is lifted against the ceiling mounting plate, the unit locks in place. Where needed, guide the mounting hooks on the ceiling mounting plate (B) to the grooves on the side panels of the ventilation unit.
There are operating levers (A) on the front bottom corners of the ceiling mounting plate. When the levers have been restored to the same level with the white covering strip of the ceiling mounting plate, the unit has been locked in place.
5. Where required, the unit can be detached from the ceiling mounting plate. Remove the door of the unit. Lift the unit slightly upwards and pull simultaneously from both operating levers (A) of the ceiling mounting plate to detach the unit from the ceiling mounting plate.

Attic floor penetration plate
The attic floor penetration plate (D) is optional. When an attic floor penetration plate is used, the tightness of the vapour barrier has to be ensured.
The attic floor penetration plate can be fastened on the finished rear wall. The minimum distance of the attic floor penetration plate from the finished side walls is 15 mm.

8

B
D
1 B
2 4 5
3

INSTALLATION

466 Ø6

REMOVAL OF CONDENSING WATER

Dimensioning figures and space required for installation of the Vallox Silent Klick siphon

L

R

7 5

466

132

132

598

NOTE The Vallox Silent Klick siphon package is delivered with the unit. Installation instructions for the siphon are enclosed with the packaging, and can also be found online at www.vallox.com. When the alternative siphon installation method is used, the ring seal and the locking part must be moved to the pipe connection part that is mounted on the wall.

495

442

5 3

Space required by the alternative Vallox Silent Klick siphon installation method (elbow)

3 8

MEASURING AND ADJUSTING THE AIR FLOWS OF THE VENTILATION UNIT
The accessories delivered with the unit include four (4) air flow measuring tubes. These can be inserted in the ducts to allow for easier ventilation adjustment.
92 1
16
9

© Vallox Oy – All rights reserved

INSTALLATION

3 5

5 3

DIMENSIONS AND DUCT OUTLETS

Main parts
12

11

6

10

9

8

3

7

5 4

2 1

R model in the figure. In the L model, the parts are mirrored

1. Extract air fan 2. Supply air fan 3. Fine filter for supply air 4. Heat recovery cell 5. Bypass damper of the HR
cell 6. Coarse filter for supply air 7. Coarse filter for extract air

8. Post-heating resistor (in front of the supply air fan)
9. Additional heating resistor
10. Safety switch
11. Internal humidity and carbon dioxide sensor
12. Ceiling bushing for electric wires

Air flow measurement points

A

A

Dimensions and duct outlets

Dimensions

598

495 8 8
442

530

R

598

356

87

210

500

517

625

1 3

125

2

4

86 224 444

L

598

328

105

31

625 517
114 500
9 1

125

4

2

154
374 512

631

6

164

B

B

R model
1. A Supply air 2. B Extract air

L model

Measurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.

10

Duct outlets
Inner diameter of the female collar: 125mm 1. Supply air from the unit to the apartment 2. Extract air from the apartment to the unit 3. Exhaust air flowing outdoors from the unit 4. Outdoor air to the unit

280

MAINTENANCE

MAINTENANCE

BEFORE BEGINNING MAINTENANCE WORK
The safety switch (S) automatically turns off the power when the door of the unit is opened.
WARNING Always disconnect the power plug before starting the ventilation unit maintenance. There are two unit models, left- (L) and right-handed (R). The figure shows the right-handed model.

REPLACING THE FILTERS

When the maintenance reminder becomes activated,

check the cleanliness of the filters and replace them if

A

required.

The Vallox ventilation unit has three air filters:

S

· Coarse filter for supply air filters insects, heavy pollen

C

and other relatively large foreign objects out of the

outdoor air.

B

· Fine filter for supply air filters microscopic pollen and

dust particles out of the supply air.

· Coarse filter for extract air filters the extract air and

keeps the heat recovery cell clean.

The filter replacement interval depends on the ambient particle concentration. It is recommended that the filters be replaced every spring and autumn, or, at the very least, once a year.

To replace the filters:
1. Disconnect the ventilation unit from the mains electricity supply.
2. Open the door of the Vallox ventilation unit by undoing the finger screws.
3. Lift the door off. 4. Remove the old filters (A, B, C) and discard them.
CAUTION The door is heavy.
5. Install the new filters (A, B, C). 6. Close the door of the unit. Ensure that the safety
switch catch of the door is touching the safety switch, allowing the unit to be turned on. 7. Plug the ventilation unit back into the mains.
The filters have now been successfully replaced.

11

IMPORTANT If the power cord is damaged, the manufacturer, its service representative or other person with similar qualifications must replace it to avoid danger.
NOTE The service space in front of the ventilation unit must be at least 500 mm.
TIP Using original Vallox filters ensures that the ventilation unit remains in top condition, giving the best results. To select and order filter packages, please go to: filters.vallox.com
© Vallox Oy – All rights reserved

MAINTENANCE

CLEANING THE HEAT RECOVERY CELL

Check that the heat recovery cell is clean roughly once a year, or whenever the filters are being replaced. Clean by washing as required.
To check and clean the heat recovery cell:
1. Disconnect the ventilation unit from the mains electricity supply.
2. Open the door of the Vallox ventilation unit by undoing the finger screws.
3. Lift the door off.

CAUTION

The door is heavy. B

4. Remove the supply air filter (A).

5. Turn the upper support of the cell (B) to the upper position

(anti-clockwise).

6. Remove the extract air filter (C).

C

7. Lift and pull the HR cell (D) out of the unit.

8. If the cell is dirty, clean it by immersing it in warm water, to

which a small amount of a mild detergent has been added.

9. Rinse the cell clean with a water spray. Do not use a high-

D

pressure cleaner.

10. When all the water has drained from between the layers,

reassemble the ventilation unit as follows:

11. Ensure that the lower support (E) is in place against the

knobs at the bottom of the unit.

12. Lift the HR cell in place.

13. Turn the upper support against the cell. Ensure that the

upper support is properly nestled against the cell (remains

upright).

14. Install the extract air filter (C) and the supply air filters (A) in

place.

15. Close the door. Ensure that the safety switch catch of the

door is touching the safety switch.

E

16. Plug the ventilation unit back into the mains.

The heat recovery cell has now been checked and cleaned.

CONDENSING WATER
In the heating season, the extract air humidity condenses to water. In new buildings, the volume of condensing water can be high. Condensed water must be able to freely leave the unit.
At some time before the heating season begins (e.g. during autumn maintenance), check that the siphon or the condensing water outlet in the bottom pool are not clogged. To check this, pour some water into the pool. Clean as required.

12

IMPORTANT Handle the cell carefully! For example, do not lift the cell by the layers. The cell layers are very thin and easily damaged.
A
NOTE Some condensing water may have accumulated in the bottom pool of the unit; this is normal and requires no corrective action. WARNING Water must at all times be kept out of the electrical system.

MAINTENANCE

CLEANING THE FANS

Check the cleanliness of the fans when servicing the filters and

the heat recovery cell. Clean the fans as required.

A

You can clean the fan blades with compressed air (wear

protective goggles) or by brushing them gently. Do not remove

B

or move the fan blade balancing weights.

To clean the fan:

C

1. Disconnect the ventilation unit from the mains electricity

supply.

D

2. Open the door of the Vallox ventilation unit by undoing the

finger screws.

3. Lift the door off.

CAUTION The door is heavy.

4. Remove the supply air filters (A) and the extract air filter

and turn the upper support of the cell (B) anti-clockwise

against the ceiling. See chapters “Replacing the filters” and

“Cleaning the heat recovery cell”.

5. Remove the support plate (F) by undoing the screws (E).

6. Push the wires of the fan and the rubber feedthrough (K/L)

through the intermediate floor and to the bottom part of the

unit.

7. Remove the plastic screws used to fasten the fans (I) (2 per

fan). Remove the wing screws (J) (2 pcs) of the post-heating

resistor (only when changing the supply air fan) and remove

the cable of the resistor (G) from the connector.

8. Remove the fan from the unit by lowering it before turning

the fan anti-clockwise, whilst tilting it. Remove the control

grille by undoing the screws (4 pcs).

9. You can now clean the fan. Put the control grille (S) back in

place after cleaning.

I

10. Reassemble in reverse order after cleaning. Once the fan

has been installed, ensure that the rubber feedthroughs (M,

K, L) are in place.

11. Close the door. Ensure that the safety switch catch of the

door is touching the safety switch.

12. Plug the ventilation unit back into the mains.

The fan has now been checked and cleaned.

13

© Vallox Oy – All rights reserved

MAINTENANCE

Cleaning of the anemometer
The anemometer in the fan must be cleaned at least every three (3) years. It is recommended to use compressed air for the cleaning.
CAUTION When using compressed air, the arms of the anemometer must not be allowed to rotate freely. This could damage the bearings. CAUTION Cleaning with a brush is not recommended. This could damage the arms.
14

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

Product title

Vallox 99 MV CF R Vallox 99 MV CF L

Product number 4120132 4120133

Air volumes Supply air Extract air

88 dm3/s, 100 Pa 93 dm3/s, 100 Pa

Fans Supply air Extract air

Post-heating

Electrical resistor, 900 W

Electrical connection

Pre-heating

­

Enclosure protection class

Additional heating

Electrical resistor, 900 W

Heat recovery bypass

Filters Supply air Extract air

ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %

Specific energy consumption (SEC)

in a cold climate

A+

in a temperate climate

A

Operating efficiencies* Annual efficiency Supply air efficiency Specific Fan Power (SFP)

Dimensions (w x h x d)

598 x 442 x 625 mm

Weight

*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.

0.085 kW, 0.75 A EC 0.085 kW, 0.75 A EC 230 V, 50 Hz, 8.6 A power plug IP 34 Automatic
76 % 81 % 1.15 kW/m3/h (62 dm3/s) 59 kg

FAN INPUT POWER

SUPPLY/EXTRACT AIR VOLUMES

Power (W)
200 180 160 140 120 100 80 60 40 20
0 0 10 0 36

Pressure loss in ducts. Total pressure (Pa)
350

100 %

300

90 %

250

80 % 200
70 %

150

SFP 1,5

SFP 1,8

60 %
50 % 40 % 30 % 1 % 10 % 20 %
20 30 40 50 60 70 72 108 144 180 216 252

SFP =

Input power (total) (W) Air flow (max) (dm3/s)

dm³/s 80 90 100 (l/s) 288 324 360 m³/h

100
50
0 0 0

SFP 1,0
1 % 10 % 20 % 10 20 30 36 72 108

90 % 100 % 80 % 60 % 70 % 30 % 40 % 50 % 40 50 60 70 80 90 100 144 180 216 252 288 324 360

dm³/s
(l/s) m³/h

Volume flow rate

Volume flow rate (dm3/s)

SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s)

extract air supply air

SOUND VALUES

Sound power level in the supply air duct (one duct) by octave band Lw, dB Adjustment position

Sound power level in the extract air duct (one duct) by octave band Lw, dB Adjustment position

Adjustment position (%)

10 20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100

Medium 63

71 71 71 73 72 76 76 78 75 79 60 63 71 66 69 70 74 75 81 79

frequency

125

69 67 66 66 65 66 66 68 68 68 57 54 53 55 56 58 61 64 66 67

of the 250 70 68 68 67 67 69 68 69 69 69 46 45 47 47 50 51 53 55 57 58

octave 500 64 64 64 65 67 67 70 71 72 72 37 37 39 41 44 49 51 49 52 51

band

Hz

1000 57 58 59 60 62 63 64 65 66 66 33 33 33 35 36 38 40 42 44 45

2000 50 51 52 54 55 57 69 61 62 62 27 27 28 29 31 33 35 37 39 39

4000 42 44 46 47 49 51 53 55 56 56 19 19 20 21 22 24 26 28 30 31

8000 32 34 36 38 40 42 45 47 48 48 21 21 21 21 21 22 22 23 23 24

LW, dB LWA, dB(A)

75 75 74 75 75 78 78 80 78 80 62 63 71 66 69 71 74 76 81 79 65 65 65 66 67 68 70 71 72 72 44 43 47 45 48 50 53 54 57 57

Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)

Adjustment position

Adjustment position (%)

10

20

30

40

50

60

70

80

90

100

LpA, dB (A)

24

27

29

31

34

37

42

41

41

42

You can calculate the sound values for each operating point with the Vallox MySelecta software.

15

© Vallox Oy – All rights reserved

YEGN YEGN YEGN YEGN
BN YEGN BU WT GN YE
BN YEGN BU WT GN YE
TECHNICAL SPECIFICATIONS

INTERNAL ELECTRICAL CONNECTION

TK
LL
NN

230V 50Hz

BN
BU L
N L N BN BU BN BU BN BU BN BU
2 3 1

T1 T2 T1 T2
130°C 90°C 130°C 90°C

T

P R1 R2

M

A

AHS %RH %RH CO2

B
1 2 3 4 5 6

1 2
C3 4 5

MB_A MB_A MB_B MB_B +24V +24V RS_A RS_A RS_B RS_B GND GND
TESTER
NTC GND +24V +24V RS_A RS_A RS_B RS_B GND GND +11V1 +24V AN/I D/I1 GND +24V RM/I D/I2 RM/O
D

A Motherboard

1. Extract air fan tacho (WT)

2. GND (GN)

B

3. Extract air fan PWM (YE) 4. Supply air fan tacho (WT)

5. GND (GN)

6. Supply air fan PWM (YE)

1. Extract air 2. Outdoor air C 3. Supply air 4. Exhaust air 5. Supply air from the HR cell

D LAN

CABLE COLOURS

BK

Black

BU

Blue

BN

Brown

WT White

GY

Grey

YE

Yellow

YEGN Yellow-green

MB_A MB_B +24V GND RS_A RS_B NTC D/I1 D/I2 11V1 AN/I RM/I RM/O

External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output

T

Supply air fan

P

Extract air fan

M

Damper motor

TK

Safety switch

AHS

Post-heating control

%RH

Internal humidity sensor

%RH CO2 R1

Internal humidity and carbon dioxide sensor
Post-heating resistor with 90°C and 130°C overheating protection

R2

Post-heating resistor with 90°C and

130°C overheating protection

16

TECHNICAL SPECIFICATIONS

EXTERNAL ELECTRICAL CONNECTION

MyVallox

VOC

2W

sensor

MyVallox %RH sensor

0.3W

2x2x0,5+0,5

MyVallox CO2 sensor

1.2W

2x2x0,5+0,5

REMOTE MONITORING Modbus RTU 2x2x0,5+0,5

MyVallox control panel

7028350 2014-08-29 JS
1 W

2x2x0,5+0,5

MyVallox control panel
1 W

2x2x0,5+0,5

External temperature sensor NTC 4K7

2×0,5

2×0,5

2×0,5

Digital input 1 8 different functions

Digital input 2 8 different functions

Ethernet connection on top of the unit

RJ45 female

CAT

VENTILATION UNIT INTERNAL ELECTRICAL CONNECTION

2×0,5

Analog input two different functions

2×0,5

Potential-free contact data 24VDC can be programmed to display information such as errors or to control the valve and pump of the MLV radiator.

Plug connection 1.2 m on top of the unit
3×1,5S

POWER SUPPLY
Maximum MyVallox Control MyVallox Touch MyVallox %RH sensor MyVallox CO2 sensor MyVallox VOC sensor Voltage

6W 1W 0.5 W. 0.3W 1.2W 2W 24 VDC

MB_A MB_B +24V GND RS_A RS_B NTC

External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector

17

D/I1 D/I2 11V1 AN/I RM/I RM/O

Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output

© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

EXTERNAL ELECTRICAL CONNECTION FOR CONTROLLING THE MLV DUCT RADIATOR

External temperature sensor NTC 4K7
Ethernet connection on top of the unit
RJ45 Female

CAT

2×0,5

24 VDC relay/contactor for controlling the pump and solenoid valve

Distribution board
LN

2×0,5

GND

VENTILATION UNIT INTERNAL ELECTRICAL CONNECTION

+24VDC

L N1 2

P

V

MLV control

3×1,5S

Plug connection 1.2 m on top of the unit

MB_A MB_B +24V GND RS_A RS_B NTC D/I1

External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1

D/I2 11V1 AN/I RM/I RM/O P V

Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output Circulation pump Solenoid valve

18

DUCT RADIATOR OPERATION
Always follow first and foremost the connection diagram provided by the HVAC designer or heat pump manufacturer. Also read the duct radiator manual.
The accompanying figure shows an example of the arrangement for connecting the heating/cooling radiator unit to the heat collection circuit.
Connect the radiator output pipe to the heat collection circuit return pipe. Direct the fluid returning from the radiator unit to the heat collection circuit return pipe. If you know that there is a large loss of internal pressure inside the heat pump, the heat pump should be bypassed. If this is done, the fluid circuit will come into operation when the heat pump comes to a halt. When this happens the pressure loss in the one-way bypass valve Y2 must be lower than the pressure loss in the heat pump.
Heating: The pump starts when the outdoor air temperature drops below the winter limit value set at the factory (-5 °C).
Cooling The supply air setpoint value for the active mode (for example, At home) controls the pump start-up. The pump starts when the supply air setting is below the temperature of the supply air that is blown into the apartment.
The duct radiator can be installed in both the supply air duct and the outdoor air duct. If the radiator is installed in the outdoor air duct, it can be used for both preheating and cooling. If the radiator is installed in the supply air duct, it can be used for heating or for cooling only.
The duct radiator can be set to function either automatically or manually.
· Automatic – In summer, the supply air temperature will be maintained at the level specified in the temperature setting. In winter, the duct radiator will turn on, when the outdoor temperature falls below the winter setting.
· Manual – In summer, the duct radiator will turn on, when the outdoor temperature rises above the summer setting. In winter, the duct radiator will turn on, when the outdoor temperature falls below the winter setting.
To prevent the risk of condensation in the supply air duct, you can set the adjustment of the supply air limit to automatic or manual.
· Automatic – The supply air limit is adjusted automatically based on the dew point of the extract air. When the supply air temperature falls too low, the duct radiator will turn off.
· Manual – The supply air limit can be set manually. When the supply air temperature falls down to the set value, the duct radiator will turn off.
If an external sensor is in use, it is selected from the settings of the external sensor whether it is used to control the outdoor air duct radiator or the supply air duct radiator. The temperature of the external sensor can be read from the service menu: menu > service menu > unit information page 5 “External sensor”.
19

NOTE: If the duct radiator is used in the supply air duct, it can only be used for cooling.
NOTE: When used to control the outdoor air duct radiator, the external NTC sensor is installed in the outdoor air duct before the radiator. When used to control the supply air duct radiator, the external NTC sensor is installed after the radiator.
NOTE: When selecting the relay (C), take account of the maximum allowed combined power supply (6W) of the circuit board in the external MV electrical box, if the relay power supply comes from the circuit board’s +24V connector.
NOTE: Due to the risk of humidity damage, in a duct that has not been insulated for condensation the supply air temperature must not fall below +16 … 20 °C.
© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

DUCT RADIATOR OPERATION CHART

In the outdoor air duct

E IP F

B

C

S

N

A

D

K C

G

V

P

Y

Y2

H

In the supply air duct

E

F

IP

B

C

NN

S

A

K

C

D

G

V

P

Y2

Y

H
A Ventilation unit B Supply air C Outdoor air D Feed from the distribution board E Air extraction F Duct radiator (reverse connection) G Heat pump H Heat collection circuit N External NTC sensor

Circulation pump. Not included in the delivery. The pump should be suited to pumping P liquid colder than the surrounding air, due to risk of condensation (for example, Grundfos
Magna 1 25-80).

V

Solenoid valve. Not included in the delivery. The valve that is chosen must be compatible with the heat collection circuit fluid (for example, Danfoss 032U161431)

K Condensing water tube. Not included in the delivery.

IP De-aerator. Not included in the delivery.

S External electrical junction box for the MV

N External NTC sensor for Vallox MV ventilation units

C

24 VDC relay/contactor for controlling the pump and the solenoid valve. Not included in the delivery. (For example, ABB CR-P024DC2)

Y One-way valve. Not included in the delivery.

Y2

One-way valve. Not included in the delivery. The pressure loss must be less than the pressure loss of the heat pump.

20

TECHNICAL SPECIFICATIONS

EXPLODED VIEW AND PARTS LIST

27 27

21

20

1

19

2

18 17
16 15 11 12
4
7

5

10

9

8

3 27 27
1 2 14 6 13 22 23 24 25 26

NO. PART 1. Supply / extract air fan

CODE 4115888

NO. PART

Mounting screw of the door

CODE 990712

NO. PART

Internal humidity and carbon dioxide sensor

CODE 4107982

2. Air flow control grille

4114497 11.

Coarse filter for extract air

4114459 20. NTC sensor kit

4115613

Wall mounting plate (optional)

3080700 12. Extract air filter frame 4114315 21. RJ45 extension cable

952196

4. HR cell

933220

HR cell bypass damper assembly

4115315

22. Connection box

3526700

Coarse and fine filter for supply air

4114075

Additional heating resistor

4115412

MyVallox Control panel MyVallox Touch control panel

949033 949090

6. Damper motor

930621 15. Post-heating resistor

4115413

MyVallox humidity sensor (optional)

946149

7. Lower support for HR cell 4114303 16. Safety switch

948377

MyVallox carbon dioxide sensor (optional)

949111

8. Siphon Vallox Silent Klick 3494701 17. Motherboard

949032-1 26.

MyVallox VOC sensor (optional)

949112

9. Door

4116174

Glass tube fuse 63mA slow 5x20mm

952490

27. Plastic screw Vallox 99

950308

21

© Vallox Oy – All rights reserved

CONFORMITY CERTIFICATES

23

© Vallox Oy – All rights reserved

D11218/19.06.2023FIN/19.06.2023ENG/PDF

www.vallox.com Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals