VALLOX 096 MV Plastic Heat Recovery Cell User Manual
- June 13, 2024
- VALLOX
Table of Contents
096 MV Plastic Heat Recovery Cell
Product Information
Product Name: Vallox Ventilation Units
Model Numbers: Vallox 096 MV, Vallox 110 MV,
Vallox 145 MV
Type: A3722 (Vallox 096 MV), A3702 (Vallox 110
MV), A3712-1 (Vallox 145 MV)
Document: D5326
Valid from: 15.10.2021
Updated: 15.05.2023
Product Usage Instructions
Installation
Installation and setup of the Vallox ventilation units should be
carried out only by qualified experts. Electrical installations and
connections must be carried out only by an electrician and in
compliance with local regulations.
Maintenance
Before beginning maintenance work
Before starting any maintenance work, ensure that the power
supply to the unit is switched off.
Changing the filters
To maintain optimal performance, regular filter changes are
necessary. Follow these steps to change the filters:
- Switch off the power supply to the unit.
- Open the unit cover.
- Remove the old filters.
- Insert new filters according to the instructions provided.
- Close the unit cover.
- Switch on the power supply to the unit.
Cleaning the heat recovery cell
To ensure efficient heat recovery, periodic cleaning of the heat
recovery cell is required. Follow these steps to clean the heat
recovery cell:
-
Switch off the power supply to the unit.
-
Remove the unit cover.
-
Carefully clean the heat recovery cell using a soft brush or
vacuum cleaner. -
Replace the unit cover.
-
Switch on the power supply to the unit.
Condensing water
Condensing water may accumulate in the unit over time. Follow
these steps to remove condensing water:
- Switch off the power supply to the unit.
- Remove the unit cover.
- Drain the condensing water from the designated outlet.
- Replace the unit cover.
- Switch on the power supply to the unit.
Cleaning the fans
To ensure proper airflow, periodic cleaning of the fans is
necessary. Follow these steps to clean the fans:
-
Switch off the power supply to the unit.
-
Remove the unit cover.
-
Clean the supply air fan and extract air fan using a soft brush
or vacuum cleaner. -
Replace the unit cover.
-
Switch on the power supply to the unit.
Cleaning the supply air fan
To clean the supply air fan, follow these steps:
-
Switch off the power supply to the unit.
-
Remove the unit cover.
-
Clean the supply air fan using a soft brush or vacuum
cleaner. -
Replace the unit cover.
-
Switch on the power supply to the unit.
Cleaning the extract air fan
To clean the extract air fan, follow these steps:
-
Switch off the power supply to the unit.
-
Remove the unit cover.
-
Clean the extract air fan using a soft brush or vacuum
cleaner. -
Replace the unit cover.
-
Switch on the power supply to the unit.
Technical Specifications
For detailed technical specifications, refer to the document
provided with the Vallox ventilation unit.
Note: You can register your Vallox MV
ventilation unit with the MyVallox Cloud service and sign in to
your MyVallox Cloud account at www.myvallox.com.
Important: In order to ensure that the indoor
air presents no harm to health and remains optimal for the
building’s structures, it is recommended to keep the ventilation
turned on without disruptions. This includes leaving ventilation on
during long holidays to keep the indoor air fresh, prevent humidity
from condensing, and reduce the risk of moisture damage.
MANUAL
Manual
Model Vallox 096 MV Vallox 110 MV Vallox 145 MV
Type A3722 A3702 A3712-1
Document D5326
Valid from 15.10.2021
Updated 15.05.2023
Ventilation units
INTRODUCTION
CONTENTS
INTRODUCTION 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 3 Installation . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Guarantee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 3 Intended use . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Disposal of the ventilation unit . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 3 Safety signs used in the instructions . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 4 Differences between the models . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation
options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 4 System description . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 4 Ventilation unit control . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Ventilation unit control options. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 5 Filter reminder . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 5 Ventilation unit setup
without a MyVallox control panel . . . . . . . . . . 5 Connecting the
ventilation unit to the cloud service . . . . . . . . . . . . . 5 Main parts .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 6 Vallox 096 MV, Vallox 110 MV, and Vallox 145 MV . .
. . . . . . . . . . . . . 6
INSTALLATION 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .
Vallox 096 MV, Vallox 110 MV, and Vallox 145 MV. . . . . . . . . . . . . . . .
. 7 Mounting on the wall . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 7 Mounting on the ceiling . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mounting the ceiling mounting plate . . . . . . . . . . . . . . . . . . . . .
. . . . . . 7 Installing the ventilation unit to the ceiling mounting plate .
. . . . . . 8 Attic floor penetration plate. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 8 Vallox 145 MV . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mounting on a base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 9 Measuring and adjusting the air flows of the
ventilation unit . . . . . . . 9 Removal of condensing water . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 10 Dimensioning figure and
space required for installation of the Vallox Silent Klick siphon . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Space required
by the alternative Vallox Silent Klick siphon installation method (elbow) . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Vallox 096
MV, Vallox 110 MV, and Vallox 145 MV. . . . . . . . . . . . . . . . 10
Dimensions and duct outlets . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 11 Vallox 096 MV . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 11 Vallox 110 MV . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .12 Vallox 145 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .13
MAINTENANCE 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before beginning maintenance work. . . . . . . . . . . . . . . . . . . . . . .
. . 14 Changing the filters . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 14 Cleaning the heat recovery cell . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 15 Condensing water . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cleaning the fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 16
Cleaning the supply air fan . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 16 Cleaning the extract air fan . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 18
TECHNICAL SPECIFICATIONS . . 19
Internal electrical connection . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .22 Vallox 096 MV . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 22 Vallox 110 MV, and Vallox 145 MV . . .
. . . . . . . . . . . . . . . . . . . . . . . 23
External electrical connection. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 24 External electrical connection for controlling the MLV duct
radiator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 25 Duct radiator operation. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 26 Duct radiator operation chart . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 27
In the outdoor air duct . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 27 In the supply air duct. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 27 Exploded view and parts list . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Vallox 096 MV . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Vallox 110 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .29 Vallox 145 MV . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .30 Conformity certificates . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
NOTE You can register your Vallox MV ventilation unit with the MyVallox Cloud
service and sign in into your MyVallox Cloud account at www.myvallox.com.
2
SAFETY
Safe and appropriate handling requires knowledge of the basic safety
regulations, and of the intended use of the ventilation system. Read this
manual before operating the ventilation unit. Retain the manual for later
reference. If you lose the manual, it can be downloaded from our website. This
user manual contains all the information necessary for safe operation of the
system. All persons who operate and maintain the ventilation system must
follow the instructions provided in this manual. Furthermore, all local
accident prevention regulations must be observed.
Installation
Installation and setup should be carried out only by qualified experts.
Electrical installations and connections must be carried out only by an
electrician and in compliance with local regulations.
GUARANTEE
The guarantee and liability exclude damage resulting from: · Inappropriate use
of the ventilation system or the control unit · Incorrect or inappropriate
installation, setup or use · Neglect of instructions concerning
transportation, installation,
use, or maintenance · Structural or electronic modifications or changes made
to the
software
INTENDED USE
All Vallox ventilation units have been designed to provide appropriate and
continuous ventilation so as to present no threat to health and to maintain
structures in good condition.
IMPORTANT In order to ensure that the indoor air presents no harm to health
and remains optimal also for the structures of the building, ventilation must
be kept on without disruptions. It is recommended that ventilation be left
turned on during long holidays also. This keeps the indoor air fresh and
prevents humidity from condensing in the ventilation ducts and structures. It
also reduces the risk of moisture damage.
DISPOSAL OF THE VENTILATION UNIT
Do not dispose of electronic devices with household waste. Follow local laws
and regulations on safe and ecological disposal of the product.
3
NOTE For further information, go to www.vallox.com
WARNING The unit is not intended for use by children under 8 or by persons
with reduced sensory, physical or mental capabilities, or whose lack of
knowledge and experience do not ensure safe operation of the unit. Such
persons can use the unit under supervision, or by following the instructions
of someone who is responsible for their safety. Children must be supervised
and not be allowed to play with the device.
© Vallox Oy – All rights reserved
INTRODUCTION
INTRODUCTION
SAFETY SIGNS USED IN THE INSTRUCTIONS
DANGER Indicates a hazard that will result in death or serious injury if not avoided.
WARNING Indicates a hazard that can result in death or serious injury if not avoided.
CAUTION Indicates a hazard that can result in minor or moderate injury if not avoided.
IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided.
NOTE Indicates essential information about the product.
TIP Provides additional information about the use of the product and its benefits.
DIFFERENCES BETWEEN THE MODELS
· Power · Size and weight · Vallox 096 MV does not have an additional heater.
Vallox 110 MV and
Vallox 145 MV have an additional heater. · In Vallox 096 MV, there is a
sealing tape at the bottom of the heat
recovery cell. In other models, there is a separate sealing bar under the heat
recovery cell.
INSTALLATION OPTIONS
· Models Vallox 096 MV and Vallox 110 MV can be mounted either on the wall, or
on the ceiling by using a mounting plate (optional).
· Vallox 145 MV can be mounted either on the wall, or on the floor by using a
floor rack (optional).
· Vallox 245 MV must always be installed on the floor by using a floor rack.
NOTE The standard equipment and available accessories vary from country to country.
SYSTEM DESCRIPTION
1. Internet 2. WLAN 3. Router 4. WLAN/LAN 5. Additional switch 6. Sensors
MyVallox Cloud 1
2 3
4 MyVallox Home
4
Vallox MV
5 6
KNX bus module
Modbus
KNX
MyVallox control panel
VENTILATION UNIT CONTROL
Ventilation unit control options
Operation of the Vallox ventilation unit can be controlled by the following
means: · Through the MyVallox control panel installed in the building. ·
Through the MyVallox Home local area network connection and
the MyVallox Home/Cloud user interface. · Through the MyVallox Cloud service
and the MyVallox Home/
Cloud user interface. · Through a remote monitoring service or building
automation
that uses voltage signals or Modbus messages.
In addition to the integrated humidity and carbon dioxide sensor, ventilation
can also be adjusted automatically by using the optional carbon dioxide,
humidity, or VOC (air quality) sensor. When these are used, ventilation
remains optimal even when the dwelling is unoccupied. Each user can use the
week clock to adjust the ventilation to fit their individual lifestyle.
Filter reminder
The unit reminds the user of the need to change the filters through the
MyVallox control panel and the MyVallox Home/Cloud user interface, as well as
by changing the relay status, if a signal light has been connected to the
relay connectors of the unit.
The filter reminder can be acknowledged: · From the MyVallox control panel ·
From the MyVallox Home/Cloud user interface · From the Vallox Delico PTD EC
and Vallox Capto PTC EC
control hoods — Damper closed, then open-closed-openclosed. Press at a less
than 1 second interval.
Ventilation unit setup without a MyVallox control panel
The ventilation unit setup can also be completed without a MyVallox control
panel. For instructions, please go to
https://vallox.techmanuals.info/ValloxMV/ENG/help/webhelp
See instructions provided in the section Connecting the ventilation unit to
the computer.
Connecting the ventilation unit to the cloud service
The ventilation unit can be connected to the MyVallox Cloud service. The cloud
service allows for controlling ventilation remotely also, using e.g. a
smartphone or tablet. Also the unit software is updated automatically through
the cloud service. To connect to the cloud service, the ventilation unit must
be connected to the Internet via LAN and registered with the cloud service. At
the same time you create a MyVallox Cloud account for yourself. Read more
about the service at www.myvallox.com.
5
NOTE For the MyVallox Cloud/ Home instructions, please go to
vallox.techmanuals.info/ ValloxMV/ENG/help/ webhelp
IMPORTANT Prolonged overpressure can result in damage to the structures of the
building.
IMPORTANT Apartment-specific ventilation units allows residents to adjust the
ventilation efficiency. Ventilation is controlled based on the need e.g.
through the cooker hood, ventilation control panel, or a separate control
centre. In order to ensure that the indoor air presents no harm to health and
remains optimal also for the structures of the building, ventilation must be
kept on without disruptions. It is recommended that ventilation be left turned
on during long holidays also. This keeps the indoor air fresh and prevents
humidity from condensing in the ventilation ducts and structures. It also
reduces the risk of moisture damage.
© Vallox Oy – All rights reserved
INTRODUCTION
RATING OF EXTRAC
INTRODUCTION
MAIN PARTS
Vallox 096 MV, Vallox 110 MV, and Vallox 145 MV
15
10 9 8 2 7
ERY
A
T AIR HEAT RECOV
NNUAL EFFICIENCY
A+
6 3 1 5
4 11
12 13 14
R model in the figure
Extract air fan (behind the protective cover)
1
Supply air fan (behind the protective cover)
2
Fine filter for supply air
3
Heat recovery cell
4
Bypass damper of the HR cell
5
Coarse filter for supply air
6
Coarse filter for extract air
7
Post-heating resistor (behind the extract air duct)
8
6
Safety switch
9
Internal humidity sensor
10
Internal carbon dioxide sensor
10
Control panel
11
Humidity sensor (optional)
12
Carbon dioxide sensor (optional)
13
VOC sensor (Optional)
14
Ceiling bushing for electric wires
15
INSTALLATION
INSTALLATION
MOUNTING ON THE WALL
NOTE Avoid mounting the unit on a hollow, echoing partition wall or on a
bedroom wall, or prevent the conduction of sound. The minimum distance between
the top of the unit and the finished ceiling surface is 30 mm. Note that
during mounting the unit rises 10 mm higher than the final height. Mount the
ventilation unit onto the wall with a mounting plate (optional), as shown in
the figures below. Make sure that the unit is horizontally level after
mounting.
MOUNTING ON THE CEILING
Vallox 096 MV and Vallox 110 MV can be equipped with an optional ceiling mount
plate. To attach the ceiling mounting plate: · On rafter frames or other frame
structure with M8 thread bars so
that they withstand the weight of the unit. · Ensure that the installation
plate is horizontally level, as this
determines the position of the unit. · The top edge of the white covering
strip of the ceiling mounting
plate can be installed against the ceiling. Alternatively, a concealed
mounting method can be used, in which case the ceiling can be 20 mm below the
top of the white covering strip. Insulate the ducts against condensation also
between the unit and the ceiling mounting plate.
Mounting the ceiling mounting plate
1. Fasten the thread bars on the rafter frames or other frame structure, and
screw the nuts onto the bars.
2. Lift the ceiling mounting plate in place. 3. Push a rubber damper and a
washer onto each thread bar, and ensure
that they touch the bottom of the cups of the plate (Vallox 096 MV). 4. Turn
the nuts to make sure that the unit is horizontally level. 5. Shorten the
lower ends of the thread bars so that they will be at no
more than 10 mm from the lower surface of the ceiling mounting plate. CAUTION
The ventilation unit is very heavy. Do not perform this procedure alone.
7
NOTE When installing the unit, reserve a sufficient space in front of the unit
for servicing purposes. Mount the ventilation unit in a place where the
temperature does not fall below +10°C. Vallox 096 MV: The service space in
front of the unit must be at least 400 mm. Vallox 110 MV: The service space in
front of the unit must be at least 450 mm. Vallox 145 MV: The service space in
front of the unit must be at least 550 mm.
© Vallox Oy – All rights reserved
INSTALLATION
Installing the ventilation unit to the ceiling
mounting plate
1. Install the ceiling mounting plate with M8 thread bars so that it is
horizontally level.
NOTE The end of the thread bars must be 5 mm or less below the fastening nut.
Do not fasten the ceiling mounting plate too tight to the ceiling. Ensure that
the sliding bars move and restore to their original position by pulling from
the operating levers (A). The top edge of the white covering strip of the
ceiling mounting plate can be installed against the ceiling. Alternatively, a
concealed mounting method can be used, in which case the ceiling can be 20 mm
below the top of the white covering strip.
2. 096 – Install the insulation washers into the outlet collars of the
ventilation unit. 110 – Ensure that the insulation washers are in place in the
outlet collars below the ceiling mounting plate.
3. Remove the door before installing the ventilation unit to the ceiling
mounting plate.
4. Lift the ventilation unit close to the ceiling mounting plate and feed the
cables and the connection box through the hole in the ceiling mounting plate
on top of the ceiling.
A
A
a
3
NOTE Remember to make a service door in the ceiling so that the cables and the
connection box can be accessed. The distance between the service door and the
ceiling mounting plate must be around 500 mm.
Alternatively, the cables can be fed between the ceiling mounting plate and
the ventilation unit to the rear wall. When the ventilation unit is lifted
against the ceiling mounting plate, the unit locks in place. Where needed,
guide the mounting hooks on the ceiling mounting plate (B) to the grooves on
the side panels of the ventilation unit. There are operating levers (A) on the
front bottom corners of the ceiling mounting plate. When the levers have been
restored to the same level with the white covering strip of the ceiling
mounting plate, the unit has been locked in place.
5. Where required, the unit can be detached from the ceiling mounting plate.
Remove the door of the unit. Lift the unit slightly upwards and pull
simultaneously from both operating levers (A) of the ceiling mounting plate to
detach the unit from the ceiling mounting plate.
Attic floor penetration plate
The attic floor penetration plate (F) is optional. When an attic floor
penetration plate is used, the tightness of the vapour barrier has to be
ensured.
The minimum distance of the attic floor penetration plate from the rear wall
is 5mm. The minimum distance of the attic floor penetration plate from the
side walls is 15mm.
B
F
1 B
b
2
4 5
NOTE Mount the ventilation unit in a place where the temperature does not fall
below +10°C.
TIP You can detach the unit from the ceiling mounting plate by pulling the
springloaded moulding to the direction shown by the arrow (more detailed
information provided with the ceiling mounting plate).
8
INSTALLATION
MOUNTING ON A BASE
NOTE Vallox 145 MV must always be installed on a base on the floor, or on the
wall using a mounting plate.
The base is optional. Adjust the base with adjusting legs to level it. Remove
the (4 pcs) rubber plugs at the bottom of the unit. Place the unit on top of
the base so that the bars of the base fit in the holes at the bottom of the
unit. Mount the ventilation unit on the wall with a mounting plate, as shown
in the adjacent figure. Make sure that the unit is horizontally level after
mounting.
A Thread bar M8 x 35, shorter thread upward B The length of the adjusting
screw is 37mm.
Ø 22 Ø 8
8
80
23 min.
133 min.
685
A
625
30 30
465
435
495
30
B
655
NOTE Mount the ventilation unit in a place where the temperature does not fall below +10°C.
Ø6
MEASURING AND ADJUSTING THE AIR FLOWS OF THE VENTILATION UNIT
The accessories delivered with the unit include four (4) air flow measuring
tubes. These can be inserted in the ducts to allow for easier ventilation
adjustment.
92 1
16
9
© Vallox Oy – All rights reserved
INSTALLATION
REMOVAL OF CONDENSING WATER
NOTE The Vallox Silent Klick siphon package is delivered with the unit.
Installation instructions for the siphon are enclosed with the packaging, and
can also be found online at www.vallox. com. When the alternative siphon
installation method is used, the ring seal and the locking part must be moved
to the pipe connection part that is mounted on the wall.
Dimensioning figure and space required for installation of the Vallox Silent Klick siphon
Vallox 096 MV
Vallox 110 MV
Vallox 145 MV
143 143 141 141 141 141
75
L
R
L
R
121
121
140
140
L
R
180
180
55 43 43
Space required by the alternative Vallox Silent Klick siphon installation method (elbow)
Vallox 096 MV
Vallox 110 MV
Vallox 145 MV
38 28 28
10
INSTALLATION
DIMENSIONS AND DUCT OUTLETS
Vallox 096 MV
Main parts
9
6
8
3
2
1
7 5
Dimensions and duct outlets
Dimensions
600
430 407
298 545
102 38 583
R model in the figure.
4
In the L model, the parts are mirrored
1. Extract air fan
5. Bypass damper of the HR cell
(behind the protective cover) 6. Coarse filter for supply air
2. Supply air fan
7. Coarse filter for extract air
(behind the extract air duct) 8. Post-heating resistor
3. Fine filter for supply air
(behind the extract air duct
4. Heat recovery cell
9. Safety switch
Air flow measurement points
A
B
A Supply air B Extract air
Measurement points after the outlet collar. The fan curves indicate the total
pressure accounted for by duct losses.
Locations of supports for HR cell
R model
L model
2
1
1
2
3
3
4
4
R
600
363
93
1
3
125
2
4
141 459
L
600
363
93
430 407
298 102
3
1
125
4
2
141 459
6
424
380
3
1. Supply air 2. Extract air 3. Coarse filter
3
5
5
4. Fine filter 5. Upper support for HR cell
143
Duct outlets
Inner diameter of the outlet collar: 125mm 1. Supply air from the unit to the
apartment 2. Extract air from the apartment to the unit 3. Exhaust air flowing
outdoors from the unit 4. Outdoor air to the unit
11
© Vallox Oy – All rights reserved
INSTALLATION
Vallox 110 MV
Main parts
9 8 2 7 10
Dimensions and duct outlets
Dimensions
638
6 3 1
678
5
28 706
4
R model in the figure. In the L model, the parts are mirrored
1. Extract air fan
6. Coarse filter for supply air
(behind the protective cover) 7. Coarse filter for extract air
2. Supply air fan
8. Post-heating resistor
(behind the extract air duct)
(behind the extract air duct)
3. Fine filter for supply air
9. Safety switch
4. Heat recovery cell
10. Additional heating resistor
5. Bypass damper of the HR cell
(behind the extract air duct)
Air flow measurement points
A
B
A Supply air B Extract air
Measurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.
Locations of supports for HR cell
R model
L model
2
1
1
2
3
3
4
4
R
638 390 112
111
325
455
472
1
3
160
2
4
160 478
L
638 390 112
472 455
325 111
3
1
160
4
2
160 478
4
473
429
3
1. Supply air 2. Extract air 3. Coarse filter
5
5
3
6
6
4. Fine filter 5. Upper support for HR cell 6. Lower support for the HR cell
12
142
Duct outlets Inner diameter of the outlet collar: 160mm 1. Supply air from the
unit to the apartment 2. Extract air from the apartment to the unit 3. Exhaust
air flowing outdoors from the unit 4. Outdoor air to the unit
INSTALLATION
Vallox 145 MV
Main parts
9 8 2 7 10
Dimensions and duct outlets
25
Dimensions
717
6 3 1
748
5
42
R model in the figure.
4
In the L model, the parts are mirrored
1. Extract air fan
6. Coarse filter for supply air
(behind the protective cover) 7. Coarse filter for extract air
2. Supply air fan
8. Post-heating resistor
(behind the extract air duct)
(behind the extract air duct)
3. Fine filter for supply air
9. Safety switch
4. Heat recovery cell
10. Additional heating resistor
5. Bypass damper of the HR cell (behind the extract air duct)
Air flow measurement points
A
B
A Supply air B Extract air
Measurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.
Locations of supports for HR cell
R model
L model
2
1
1
2
3
3
4
4
R
717
455
125
578 560 491
411 127
1
3
200
2
4
180 313 405 537
L
717
455
125
578 560 491
411 127
3
1
200
4
2
180 313 405 537
5
574
529
3
1. Supply air 2. Extract air 3. Coarse filter
5
5
3
6
6
4. Fine filter 5. Upper support for HR cell 6. Lower support for the HR cell
13
Duct outlets
142
Inner diameter of the outlet collar: 200mm
1. Supply air from the unit to the apartment 2. Extract air from the apartment to the unit 3. Exhaust air flowing outdoors from the unit 4. Outdoor air to the unit
© Vallox Oy – All rights reserved
MAINTENANCE
MAINTENANCE
BEFORE BEGINNING MAINTENANCE WORK
The safety switch (S) automatically turns off the power when the door of the
unit is opened.
WARNING Always disconnect the power plug before starting the ventilation unit
maintenance. There are two unit models, left- (L) and right-handed (R). The
figure shows the right-handed model.
CHANGING THE FILTERS
When the maintenance reminder becomes activated, check the cleanliness of the
filters and replace them if required. The Vallox ventilation unit has three
air filters: · Coarse filter for supply air filters insects, heavy pollen
and other relatively large foreign objects out of the outdoor air. · Fine
filter for supply air filters microscopic pollen and dust particles out of the
supply air. · Coarse filter for extract air filters the extract air and keeps
the heat recovery cell clean.
The filter replacement interval depends on the ambient particle concentration.
It is recommended that the filters be replaced every spring and autumn, or at
the very least once a year.
To replace the filters: 1. Disconnect the ventilation unit from the mains
electricity supply. 2. Lift the latch to open the door of the Vallox
ventilation
unit. 3. Lift the door off.
CAUTION The door is heavy. 4. Remove the old filters (A, B, C) and discard
them. 5. Install the new filters (A, B, C). 6. Close the door of the unit.
Ensure that the safety switch catch of the door is touching the safety switch,
allowing the unit to be turned on. 7. Plug the ventilation unit back into the
mains.
The filters have now been successfully replaced.
14
IMPORTANT If the power cord is damaged, the manufacturer, its service
representative or other person with similar qualifications must replace it to
avoid danger.
TIP Using original Vallox filters ensures that the ventilation unit remains in
top condition, giving the best results. To select and order filter packages,
please go to: filters.vallox.com
NOTE Vallox 096 MV: The service space in front of the unit must be at least
400 mm. Vallox 110 MV: The service space in front of the unit must be at least
450 mm. Vallox 145 MV: The service space in front of the unit must be at least
550 mm.
CLEANING THE HEAT RECOVERY CELL
Check that the heat recovery cell is clean roughly once a year, or whenever
the filters are being replaced. Clean by washing as required.
To check and clean the heat recovery cell: 1. Disconnect the ventilation unit
from the mains electricity
supply. 2. Open the Vallox ventilation unit door by first lifting the latch
fully up and then lowering it back a little way. 3. Lift the door off.
CAUTION The door is heavy. 4. Remove the filters (A, B, C). 5. Remove the
sealing strip (E) above the cell in the direction of the arrow. 6. Lift and
pull the cell (D) out of the unit.
IMPORTANT Handle the cell carefully! For example, do not lift the cell by the
layers. The cell layers are very thin and easily damaged. 7. If the cell is
dirty, clean it by immersing it in warm water, to which a small amount of a
mild detergent has been added. 8. Rinse the cell clean with a water spray. Do
not use a highpressure cleaner. 9. When all the water has drained from between
the layers, reassemble the ventilation unit in the reverse order. 10. When
reassembling Vallox 096 MV, check that the sealing strip below the cell is
pressed against the bottom of the unit. 11. Close the door. Ensure that the
safety switch catch of the door is touching the safety switch. 12. Plug the
ventilation unit back into the mains.
The heat recovery cell has now been checked and cleaned.
CONDENSING WATER
In the heating season, the extract air humidity condenses to water. In new
buildings, condensation runoff can form rapidly. Condensed water must be able
to freely leave the unit.
At some time before the heating season begins (e.g. during autumn
maintenance), check that the siphon or the condensing water outlet in the
bottom pool are not clogged. To check this, pour some water into the pool.
Clean as required.
15
NOTE Some condensing water may have accumulated in the bottom pool of the
unit; this is normal and requires no corrective action.
WARNING Water must at all times be kept out of the electrical system.
© Vallox Oy – All rights reserved
MAINTENANCE
MAINTENANCE
CLEANING THE FANS
Check the cleanliness of the fans when servicing the filters and the heat
recovery cell. Clean the fans as required. You can clean the fan blades with
compressed air (wear protective goggles) or by brushing them gently. Do not
remove or move the fan blade balancing weights.
Cleaning the supply air fan
To clean the supply air fan: 1. Disconnect the ventilation unit from the mains
electricity
supply. 2. Lift the latch to open the door of the Vallox ventilation unit. 3.
Lift the door off.
CAUTION The door is heavy.
4. Remove the extract air filter (C), the cell top bracket (E) and the heat
recovery cell (D). See chapters “Replacing the filters” and “Cleaning the heat
recovery cell”.
5. Pull out the temperature sensor (figure 1) located at the top of the
extract air duct (G). Remove the stopper screw (I) at the bottom of the duct.
The extract air duct now comes out by turning and pushing it downwards
simultaneously (figure 2).
6. Remove the temperature sensor from the resistor support (figure 4).
7. Remove the additional and post-heating resistor support, which is attached
by two wing nuts (Vallox 110 MV and Vallox 145 MV) or screws (Vallox 096 MV)
from below (figure 5).
IMPORTANT The fans are extremely sensitive to external shocks. It is
recommended that the fans be cleaned in place, i.e. without attempting to
remove them.
Handle the fan blades carefully. Do not remove or move the fan blade balancing
weights.
1
1 det
2
3
4
5
6
7
16
MAINTENANCE
8. Pull the radiator and the support out of the unit (figures 6 and 7) and remove the quick connector of the radiator
8
wires.
CAUTION Before removing the resistor from the unit, make sure it is not hot.
9. The fan can now be cleaned in place. It is
recommended that the fan be cleaned in place, i.e.
without attempting to remove it.
10. To remove the fan for cleaning: a. If necessary, remove the arm pins. Use pliers to
9
press the pins straight, so that they are easier to
install back later.
b. Push the fan gently upward (figure 9).
c. Pry the plastic lock to the right of the fan with a
screwdriver, for example (figure 10).
d. The fan falls downwards.
e. Pull the fan out of the unit (figure 11).
f. Disconnect the fan wire quick connector (figure 12).
The fan has now been removed for cleaning.
10
11. To reassemble the ventilation unit, follow the above
steps in reverse order.
TIP
When you re-install the temperature sensor,
position it with the tip upward and pointing at the
wall in such a way that it does not get squeezed
between the HR cell bypass damper or lean against
the radiator frame.
12. Close the door. Ensure that the safety switch catch of
11
the door is touching the safety switch.
13. Plug the ventilation unit back into the mains.
The fan has now been checked and cleaned.
12
17
© Vallox Oy – All rights reserved
MAINTENANCE
Cleaning the extract air fan
To clean the extract air fan, proceed as follows:
1. Disconnect the ventilation unit from the mains electricity supply. 2. Lift
the latch to open the door of the Vallox ventilation unit. 3. Lift the door
off.
CAUTION The door is heavy.
4. Remove the filters (C), the cell top support (E) and the heat recovery
cell (D). See chapters “Replacing the filters” and “Cleaning the heat recovery
cell”.
5. Open the four screws (figure 1) on the extract air fan cover and remove
the cover (figure 2). The fan can now be cleaned in place.
6. To remove the fan for cleaning: a. Push the fan gently upward (figure 3).
b. Pry the plastic lock to the right of the fan with a screwdriver, for
example (figure 4). c. The fan falls downwards (figure 5). d. Pull the fan out
of the unit. e. Disconnect the fan wire quick connector (figure 6).
7. Clean the fan. 8. To reassemble the ventilation unit, follow the above
steps in reverse
order. 9. Close the door and plug the unit back into the mains.
The extract air fan has now been checked and cleaned.
1
2
3
4
5
6
18
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
Product title
Vallox 096 MV R Vallox 096 MV L
Product number 3474450 3474550
Air volumes Supply air Extract air
84 dm3/s, 100 Pa 88 dm3/s, 100 Pa
Fans Supply air Extract air
Post-heating
Electrical resistor, 900 W
Electrical connection
Pre-heating
Enclosure protection class
Additional heating
Heat recovery bypass
Filters Supply air Extract air
ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %
Specific energy consumption (SEC)
in a cold climate
A+
in a temperate climate
A
Operating efficiencies* Annual efficiency Supply air efficiency Specific Fan Power (SFP)
Dimensions (w x h x d)
600 x 545 x 428 mm
Weight
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.
0.119 kW 0.9 A EC 0.119 kW 0.9 A EC 230 V, 50 Hz, 5.1 A power plug IP34
Automatic
77 % 86 % 1.33 kW/m3/h (59 dm3/s) 53 kg
FAN INPUT POWER
SUPPLY/EXTRACT AIR VOLUMES
Power (W)
200
180
160
140
120
100
80
60
40
20
0
0
10
0
36
Pressure loss in ducts. Total pressure (Pa)
100 %
90 %
300
80 % 250
70 %
200
100 % 80 %
L 70 %
60 %
60 %
150
50 %
50 %
100
40 %
40 % 30 % 20 % 10 %
dm³/s
30 % 50 20 %
10 %
0
SFP 1,0
SFP 1,5 SFP 1,2
dm³/s
20 30 40 50 60 70 80 90 100 (l/s)
0
10
20
30 40 50 60 70 80 90 100 (l/s)
72 108 144 180 216 252 288 324 360 m³/h
0
36
72 108 144 180 216 252 288 324 360 m³/h
Volume flow rate
Volume flow rate (dm3/s)
SFP =
Input power (total) (W) Air flow (max) (dm3/s)
SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s)
extract air supply air
SOUND VALUES
Sound power level in the supply air duct (one duct) by octave band Lw, dB Adjustment position
Sound power level in the extract air duct (one duct) by octave band Lw, dB Adjustment position
Adjustment position (%) 10 20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100
Medium frequency of the octave band Hz
63 125 250 500 1000
54 64 69 74 76 80 84 87 87 86 51 56 63 66 70 73 76 78 79 79 50 56 62 66 70 73 77 80 82 81 43 46 52 55 60 63 66 68 71 71 46 54 59 63 66 69 72 75 77 77 33 38 44 47 51 55 58 61 63 63 40 48 54 57 61 63 66 68 70 71 29 38 44 47 51 54 57 59 61 61 34 44 51 55 60 62 64 66 68 68 24 32 38 42 46 49 52 55 57 57
2000
21 35 44 49 54 57 61 63 66 66 13 17 24 29 33 36 39 42 44 44
4000
17 23 34 41 47 51 55 58 61 61 17 17 18 20 23 26 29 32 34 34
8000
21 21 26 34 42 47 52 56 59 59 21 21 21 21 21 22 23 25 27 27
LW,dB LWA, dB(A)
56 65 70 75 78 81 85 88 89 88 52 56 64 66 71 74 76 79 80 80 42 50 57 61 64 67 70 73 75 75 33 39 45 48 52 55 58 61 63 63
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Adjustment position
Adjustment position (%)
10
20
30
40
50
60
70
80
90
100
LpA, dB (A)
24
28
34
33
37
41
44
46
48
48
You can calculate the sound values for each operating point with the Vallox MySelecta software.
19
© Vallox Oy – All rights reserved
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
Product title
Vallox 110 MV R Vallox 110 MV L
Product number 3446650 3446750
Air volumes Supply air Extract air
96 dm3/s, 100 Pa 103 dm3/s, 100 Pa
Fans Supply air Extract air
Post-heating
Electrical resistor, 900 W
Electrical connection
Pre-heating
Enclosure protection class
Additional heating
Electrical resistor, 900 W
Heat recovery bypass
Filters Supply air Extract air
ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %
Specific energy consumption (SEC)
in a cold climate
A+
in a temperate climate
A
Operating efficiencies* Annual efficiency Supply air efficiency Specific Fan Power (SFP)
Dimensions (w x h x d)
638 x 678 x 472 mm
Weight
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.
0.119 kW 1.0 A EC 0.119 kW 1.0 A EC 230 V, 50 Hz, 8.5 A power plug IP 34
Automatic
79 % 86 % 1.15 kW/m3/h (71 dm3/s) 64 kg
FAN INPUT POWER
Power (W)
SUPPLY/EXTRACT AIR VOLUMES
Pressure loss in ducts. Total pressure (Pa)
SFP =
Input power (total) (W) Air flow (max) (dm3/s)
Volume flow rate
SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s)
Volume flow rate (dm3/s) extract air supply air
SOUND VALUES
Sound power level in the supply air duct (one duct) by octave band Lw, dB
Adjustment position
Sound power level in the extract air duct (one duct) by octave band Lw, dB
Adjustment position
Adjustment position (%) 10
Medium 63
53
frequency of the
125
48
octave 250
46
band Hz
500
40
1000
31
2000
18
4000
17
8000
21
LW,dB
55
LWA, dB(A)
41
20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100 60 67 71 74 78 82
83 84 84 54 46 62 65 69 72 75 77 79 79 56 61 66 70 74 76 78 80 80 42 44 50 53
58 61 64 66 68 68 53 58 62 65 69 71 74 76 76 34 41 46 50 53 56 60 62 64 64 48
56 57 60 62 65 67 68 69 26 35 40 43 46 49 52 55 57 57 42 50 55 58 61 64 65 67
67 18 28 34 38 41 45 47 50 52 51 32 40 46 52 56 60 62 64 64 13 17 24 29 33 36
39 42 44 44 20 30 38 44 49 53 56 59 59 17 17 18 19 21 24 27 31 33 33 21 25 34
42 48 53 57 59 60 21 21 21 21 21 22 24 26 29 29 62 69 73 76 80 83 85 86 86 55
57 62 66 70 72 75 78 79 79 49 56 60 63 67 69 72 73 73 33 38 43 46 50 53 56 59
60 60
Sound pressure level coming through the envelope of the unit in the room in
which it is installed (10m² sound absorption)
Adjustment position
Adjustment position (%)
10
20
30
40
50
60
70
80
90
100
LpA, dB (A)
21
24
30
32
35
39
42
45
47
47
You can calculate the sound values for each operating point with the Vallox MySelecta software.
20
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
Product title
Vallox 145 MV R Vallox 145 MV L
Product number 3475650 3475750
Air volumes Supply air Extract air
150 dm3/s, 100 Pa 155 dm3/s, 100 Pa
Fans Supply air Extract air
Post-heating
Electrical resistor, 900 W
Electrical connection
Pre-heating
Enclosure protection class
Additional heating
Electrical resistor, 1500 W
Heat recovery bypass
Filters Supply air Extract air
ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %
Specific energy consumption (SEC)
in a cold climate
A+
in a temperate climate
A
Operating efficiencies* Annual efficiency Supply air efficiency Specific Fan Power (SFP)
Dimensions (w x h x d)
717 x 748 x 578 mm
Weight
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.
0.175 kW 1.25 A EC 0.175 kW 1.25 A EC 230 V, 50 Hz, 11.9 A power plug IP 34
Automatic
79 % 85 % 1.33 kW/m3/h (109 dm3/s) 88 kg
FAN INPUT POWER
SUPPLY/EXTRACT AIR VOLUMES
Power (W)
350
Pressure loss in ducts. Total pressure (Pa)
450
300
100 %
400
90 %
100 %
80 %
350
80 %
250
70 %
300
L
70 %
200
250
150
60 %
60 % 200
100
50 %
150
50 %
40 %
50
30 %
20 %
10 % 0
dm³/s
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 (l/s)
0 36 72 108 144 180 216 252 288 324 360 396 432 468 504 540 576 612 m³/h
40 % 100
30 %
SFP 1,8
50 20 %
10 % 0
SFP 1,0
SFP 1,5
dm³/s
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 (l/s)
Volume flow rate
0 36 72 108 144 180 216 252 288 324 360 396 432 468 504 540 576 612 m³/h
Volume flow rate (dm3/s)
SFP =
Input power (total) (W) Air flow (max) (dm3/s)
SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s)
extract air supply air
SOUND VALUES
Sound power level in the supply air duct (one duct) by octave band Lw, dB
Adjustment position
Sound power level in the extract air duct (one duct) by octave band Lw, dB
Adjustment position
Adjustment position (%) 10 20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100
Medium 63
frequency of the
125
octave 250
band Hz
500 1000
55 66 73 76 80 83 85 86 87 87 53 58 63 67 73 78 78 79 80 79 50 58 64 68 72 76 80 83 84 84 45 50 56 61 65 69 73 75 75 75 52 57 63 65 68 72 74 77 78 78 40 39 44 49 54 57 60 63 64 64 41 48 53 57 61 64 67 70 71 71 30 37 43 47 50 53 56 58 59 59 53 47 52 57 60 64 65 67 68 68 32 33 36 41 44 48 50 52 53 53
2000
23 34 43 48 53 58 62 64 66 66 15 22 30 34 38 42 45 48 49 49
4000
18 23 36 44 50 55 59 62 63 63 17 17 19 23 27 31 35 38 39 39
8000
21 22 28 39 47 54 58 62 63 63 21 21 21 22 24 28 32 35 36 36
LW,dB LWA, dB(A)
59 68 74 77 81 84 86 88 90 89 54 59 64 68 74 79 79 80 81 81 53 52 58 62 66 69 72 75 76 76 37 40 45 50 54 58 60 63 63 63
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Adjustment position
Adjustment position (%)
10
20
30
40
50
60
70
80
90
100
LpA, dB (A)
28
27
32
35
39
43
46
48
49
49
You can calculate the sound values for each operating point with the Vallox MySelecta software.
21
© Vallox Oy – All rights reserved
YEGN YEGN YEGN YEGN
BN YEGN
BU WT GN YE
BN YEGN
BU WT GN YE
TECHNICAL SPECIFICATIONS
INTERNAL ELECTRICAL CONNECTION
Vallox 096 MV
TK
LL
NN
230V 50Hz
BN BU L N L N BN BU BN BU BN BU
2 3 1
T1 T2
130°C 90°C
A
AHS %RH %RH CO2
B
123456
1
C
2 3
4
5
T
P R1
M
MB_A MB_B
+24V RS_A RS_B GND
MB_A MB_B
+24V RS_A RS_B GND
TESTER
NTC GND +24V +24V RS_A RS_A RS_B RS_B GND GND +11V1 +24V AN/I D/I1 GND +24V RM/I D/I2 RM/O
D
A Motherboard
1. Extract air fan tacho (WT)
2. GND (GN)
B
3. Extract air fan PWM (YE) 4. Supply air fan tacho (WT)
5. GND (GN)
6. Supply air fan PWM (YE)
1. Extract air
2. Outdoor air
C 3. Supply air
4. Exhaust air
5. Supply air from the HR cell
D LAN
CABLE COLOURS
BK
Black
BU
Blue
BN
Brown
WT
White
GY
Grey
YE
Yellow
YEGN Yellow-green
MB_A MB_B +24V GND RS_A RS_B NTC D/I1 D/I2 11V1 AN/I
External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC
RM/I RM/O T P M TK AHS %RH
%RH CO2
24V relay input 24V relay output Supply air fan Extract air fan Damper motor Safety switch Post-heating control Internal humidity sensor Internal humidity and carbon dioxide sensor
R1
Post-heating resistor with 90°C and 130°C overheating protection
22
TECHNICAL SPECIFICATIONS
Vallox 110 MV, and Vallox 145 MV
TK 230V 50Hz
LL NN
BN BU L N L N BN BU BN BU BK
2 BN 3 1
T1 T2
T1 T2
130°C 90°C 130°C 90°C
T
P R1 R2
M
YEGN YEGN
YEGN YEGN YEGN
A
AHS %RH %RHCO2
B
123456
1
2
C
3
4
5
MB_A MB_B
+24V RS_A RS_B GND
MB_A MB_B
+24V RS_A RS_B GND
TESTER
NTC GND +24V +24V RS_A RS_A RS_B RS_B GND GND +11V1 +24V AN/I D/I1 GND +24V RM/I D/I2 RM/O
D
BN YEGN
BU WT GN YE
BN YEGN
BU
WT GN YE
A Motherboard
1. Extract air fan tacho (WT)
2. GND (GN)
B
3. Extract air fan PWM (YE) 4. Supply air fan tacho (WT)
5. GND (GN)
6. Supply air fan PWM (YE)
1. Extract air 2. Outdoor air C 3. Supply air 4. Exhaust air 5. Supply air from the HR cell
D LAN
CABLE COLOURS
BK
Black
BU
Blue
BN
Brown
WT White
GY
Grey
YE
Yellow
YEGN Yellow-green
MB_A MB_B +24V GND RS_A RS_B NTC D/I1 D/I2 11V1 AN/I RM/I RM/O
External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output
T
Supply air fan
P
Extract air fan
M
Damper motor
TK
Safety switch
AHS
Post-heating control
%RH
Internal humidity sensor
%RH CO2
Internal humidity and carbon dioxide sensor
R1
Post-heating resistor with 90°C and 130°C overheating protection
R2
Additional heating resistor with 90°C and 130°C overheating protection
23
© Vallox Oy – All rights reserved
TECHNICAL SPECIFICATIONS
EXTERNAL ELECTRICAL CONNECTION
MyVallox
VOC
2 W
sensor
MyVallox %RH sensor
0.3W
2x2x0,5+0,5
MyVallox CO2 sensor
1.2W
2x2x0,5+0,5
REMOTE MONITORING Modbus RTU 2x2x0,5+0,5
MyVallox control panel
7028350 2014-08-29 JS
1W
2x2x0,5+0,5
MyVallox control panel
1W
2x2x0,5+0,5
External temperature sensor NTC 4K7
2×0,5
2×0,5
2×0,5
Digital input 1 8 different functions
Digital input 2 8 different functions
Ethernet connection on top of the unit
CAT RJ45 female
VENTILATION UNIT INTERNAL ELECTRICAL CONNECTION
2×0,5
Analog input two different functions
2×0,5
Potential-free contact data 24VDC can be programmed to display information such as errors or to control the valve and pump of the MLV radiator.
Plug connection 1.2 m on top of the unit
3×1,5S
POWER SUPPLY
Maximum MyVallox Control MyVallox Touch MyVallox %RH sensor MyVallox CO2
sensor MyVallox VOC sensor Voltage
6W 1W 0.5 W. 0.3W 1.2W 2W 24 VDC
MB_A MB_B +24V GND RS_A RS_B NTC
External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector
D/I1 D/I2 11V1 AN/I RM/I RM/O
Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output
24
TECHNICAL SPECIFICATIONS
EXTERNAL ELECTRICAL CONNECTION FOR CONTROLLING THE MLV DUCT RADIATOR
External temperature sensor NTC 4K7
Ethernet connection on top of the unit
RJ45 Female
CAT
2×0,5
24 VDC relay/ contactor for controlling the pump and solenoid valve
Distribution board
LN
2×0,5
GND
VENTILATION UNIT INTERNAL ELECTRICAL CONNECTION
+24VDC
L N1 2
P
V
MLV control
Plug connection 1.2 m on top of the unit
3×1,5S
MB_A MB_B +24V GND RS_A RS_B NTC D/I1
External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1
D/I2 11V1 AN/I RM/I RM/O P V
Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output Circulation pump Solenoid valve
25
© Vallox Oy – All rights reserved
TECHNICAL SPECIFICATIONS
DUCT RADIATOR OPERATION
Always follow first and foremost the connection diagram provided by the HVAC
designer or heat pump manufacturer. Also read the duct radiator manual.
The accompanying figure shows an example of the arrangement for connecting the
heating/cooling radiator unit to the heat collection circuit.
Connect the radiator output pipe to the heat collection circuit return pipe.
Direct the fluid returning from the radiator unit to the heat collection
circuit return pipe. If you know that there is a large loss of internal
pressure inside the heat pump, the heat pump should be bypassed. If this is
done, the fluid circuit will come into operation when the heat pump comes to a
halt. When this happens the pressure loss in the one-way bypass valve Y2 must
be lower than the pressure loss in the heat pump.
Heating: The pump starts when the outdoor air temperature drops below the
winter limit value set at the factory (-5 °C).
Cooling The supply air setpoint value for the active mode (for example, At
home) controls the pump start-up. The pump starts when the supply air setting
is below the temperature of the supply air that is blown into the apartment.
The duct radiator can be installed in both the supply air duct and the outdoor
air duct. If the radiator is installed in the outdoor air duct, it can be used
for both preheating and cooling. If the radiator is installed in the supply
air duct, it can be used for heating or for cooling only.
The duct radiator can be set to function either automatically or manually.
· Automatic – In summer, the supply air temperature will be maintained at the
level specified in the temperature setting. In winter, the duct radiator will
turn on, when the outdoor temperature falls below the winter setting.
· Manual – In summer, the duct radiator will turn on, when the outdoor
temperature rises above the summer setting. In winter, the duct radiator will
turn on, when the outdoor temperature falls below the winter setting.
To prevent the risk of condensation in the supply air duct, you can set the
adjustment of the supply air limit to automatic or manual.
· Automatic – The supply air limit is adjusted automatically based on the dew
point of the extract air. When the supply air temperature falls too low, the
duct radiator will turn off.
· Manual – The supply air limit can be set manually. When the supply air
temperature falls down to the set value, the duct radiator will turn off.
If an external sensor is in use, it is selected from the settings of the
external sensor whether it is used to control the outdoor air duct radiator or
the supply air duct radiator. The temperature of the external sensor can be
read from the service menu: menu > service menu > unit information page 5
“External sensor”.
26
NOTE: If the duct radiator is used in the supply air duct, it can only be used
for cooling.
NOTE: When used to control the outdoor air duct radiator, the external NTC
sensor is installed in the outdoor air duct before the radiator. When used to
control the supply air duct radiator, the external NTC sensor is installed
after the radiator.
NOTE: When selecting the relay (C), take account of the maximum allowed
combined power supply (6W) of the circuit board in the external MV electrical
box, if the relay power supply comes from the circuit board’s +24V connector.
NOTE: Due to the risk of humidity damage, in a duct that has not been
insulated for condensation the supply air temperature must not fall below +16
… 20 °C.
TECHNICAL SPECIFICATIONS
DUCT RADIATOR OPERATION CHART
In the outdoor air duct
E IP F
B
C
S
N
A
D
K C
G
V
P
Y
Y2
H
In the supply air duct
E
F
IP
B
C
NN
S
A
K
C
D
G
V
P
Y2
Y
H
A Ventilation unit B Supply air C Outdoor air D Feed from the distribution
board E Air extraction F Duct radiator (reverse connection) G Heat pump H Heat
collection circuit N External NTC sensor
Circulation pump. Not included in the delivery. The pump should be suited to
pumping P liquid colder than the surrounding air, due to risk of condensation
(for example, Grundfos
Magna 1 25-80).
V
Solenoid valve. Not included in the delivery. The valve that is chosen must be compatible with the heat collection circuit fluid (for example, Danfoss 032U161431).
K Condensing water tube. Not included in the delivery.
IP De-aerator. Not included in the delivery.
S External electrical junction box for the MV
N External NTC sensor for Vallox MV ventilation units
C
24 VDC relay/contactor for controlling the pump and the solenoid valve. Not included in the delivery. (For example, ABB CR-P024DC2)
Y One-way valve. Not included in the delivery.
Y2
One-way valve. Not included in the delivery. The pressure loss must be less than the pressure loss of the heat pump.
27
© Vallox Oy – All rights reserved
TECHNICAL SPECIFICATIONS
EXPLODED VIEW AND PARTS LIST
Vallox 096 MV
3
2
1
28
19
16
12
20 21
13 12 11
10
9
8
18
14
22 23
4 15
5 17
6
16
25
7
26
27
NO. PART
CODE NO. PART
CODE NO. PART
CODE
Supply / extract air fan (with a hood)
1108800
HR cell bypass damper assembly
Post-heating resistor 900W (R and L models)
942210
2. Fan
935365
R model
3491200 20. Door
3475200
Wall mounting plate (optional)
3080700
L model
3491201 21. Door latch
3355900
4. Siphon Vallox Silent Klick 3494701 12. Damper motor
930620 22. NTC sensor kit
3480500
5. Coarse filter for supply air 978044 13. Extract air outlet
985026
Glass tube fuse 63mA slow 5x20mm
952490
6. Fine filter for supply air
978220
Internal humidity and carbon dioxide sensor
4107982
MyVallox Control panel MyVallox Touch control panel
949033 949090
HR cell (aluminium) HR cell (enthalpy)
933260 933153
15. Motherboard
949032-1 25.
MyVallox humidity sensor (optional)
946149
8. Upper support for HR cell 3467200 16. Safety switch
948377
MyVallox carbon dioxide sensor (optional)
949111
9. Filter stand
3464500 17. Connection box
3526700 27. MyVallox VOC sensor (optional) 949112
Coarse filter for extract air 978045
18. RJ45 extension cable 952196
Ceiling bushing for electric wires 950445
Ceiling feed-through seal
950446
28
TECHNICAL SPECIFICATIONS
Vallox 110 MV
3
2
1
30
20
21
17
12
22 23
14 13 12
11
10
9
19
15
24
25 4
16 5
6
18
26
27
8
7
28
29
NO. PART
CODE
Supply / extract air fan
1108800
2. Fan
935415
Wall mounting plate (optional)
3080700
Siphon Vallox Silent Klick
3494701
Coarse filter for supply air
978042
Fine filter for supply air
978157
Lower support for HR cell
3450100
HR cell (aluminium) 933160 HR cell (enthalpy) 933170
Upper support for HR cell
3426600
10. Filter stand
3426800
Coarse filter for extract air
978043
NO. PART
12. Bypass duct assembly R model L model
13. Damper motor
14. Extract air outlet
Internal humidity and carbon dioxide sensor
16. Motherboard
17. Safety switch
18. Connection box
19. RJ45 extension cable
Post-heating resistor 900W
R model
L model
CODE NO. PART
CODE
21. 3447200
Additional heating resistor 900W
R model
3447201
L model
942210 942211
930620 22. Door
3447300
985025 23. Door latch
3355900
4107982 24. NTC sensor kit
3457900
949032-1 25. 948377 26. 3526700 27. 952196 28.
Glass tube fuse 63mA slow 5x20mm
MyVallox Control panel MyVallox Touch control panel
MyVallox humidity sensor (optional)
MyVallox carbon dioxide sensor (optional)
952490 949033 949090 946149
949111
29. MyVallox VOC sensor (optional) 949112
942211 942210
Ceiling bushing for electric wires 950445
Ceiling feed-through seal
950446
29
© Vallox Oy – All rights reserved
TECHNICAL SPECIFICATIONS
Vallox 145 MV
3
2
1
30
22 23
21
20
17
14
13 12
11
10
9
12
19
15
24
25 4
16 5
6
18
26
27
8
7
28
29
NO. PART
CODE NO. PART
CODE NO. PART
CODE
Supply / extract air fan (with a hood)
1109200
HR cell bypass damper assembly
21. Post-heating resistor 900W
2. Fan
935530
R model
3475900
R model
942211
Wall mounting plate (optional)
3482100
L model
3475901
L model
942210
4. Siphon Vallox Silent Klick 3494701 13. Damper motor
930620 22. Door
3476000
5. Coarse filter for supply air 978046 14. Extract air outlet
985035 23. Door latch
3355900
6. Fine filter for supply air
978158
Internal humidity and carbon dioxide sensor
4107982
NTC sensor kit
3482300
7. Lower support for HR cell 3469000 16. Motherboard
949032-1 25.
Glass tube fuse 63mA slow 5x20mm
952490
HR cell (aluminium) HR cell (enthalpy)
933270 933154
17. Safety switch
948377
MyVallox Control panel MyVallox Touch control panel
949033 949090
9. Upper support for HR cell 3468900 18. Connection box
3526700 27.
MyVallox humidity sensor (optional)
946149
10. Filter stand
3466500 19. RJ45 extension cable 952196
MyVallox carbon dioxide sensor (optional)
949111
Coarse filter for extract air
978047
Additional heating resistor 1500W
942220 29. MyVallox VOC sensor (optional) 949112
Ceiling bushing for electric wires 950445
Ceiling feed-through seal
950446
30
CONFORMITY CERTIFICATES
D5326/10.05.2023FIN/15.05.2023ENG/PDF
www.vallox.com Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND
References
- Vallox Ordering system — Vallox-ilmanvaihtolaitteiden suodattimet
- MyVallox Cloud
- One moment, please...
- Operating, maintenance, and technical instructions for the Vallox ventilation unit
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>