VALLOX 096 MV Plastic Heat Recovery Cell User Manual

June 13, 2024
VALLOX

096 MV Plastic Heat Recovery Cell

Product Information

Product Name: Vallox Ventilation Units

Model Numbers: Vallox 096 MV, Vallox 110 MV,
Vallox 145 MV

Type: A3722 (Vallox 096 MV), A3702 (Vallox 110
MV), A3712-1 (Vallox 145 MV)

Document: D5326

Valid from: 15.10.2021

Updated: 15.05.2023

Product Usage Instructions

Installation

Installation and setup of the Vallox ventilation units should be
carried out only by qualified experts. Electrical installations and
connections must be carried out only by an electrician and in
compliance with local regulations.

Maintenance

Before beginning maintenance work

Before starting any maintenance work, ensure that the power
supply to the unit is switched off.

Changing the filters

To maintain optimal performance, regular filter changes are
necessary. Follow these steps to change the filters:

  1. Switch off the power supply to the unit.
  2. Open the unit cover.
  3. Remove the old filters.
  4. Insert new filters according to the instructions provided.
  5. Close the unit cover.
  6. Switch on the power supply to the unit.

Cleaning the heat recovery cell

To ensure efficient heat recovery, periodic cleaning of the heat
recovery cell is required. Follow these steps to clean the heat
recovery cell:

  1. Switch off the power supply to the unit.

  2. Remove the unit cover.

  3. Carefully clean the heat recovery cell using a soft brush or
    vacuum cleaner.

  4. Replace the unit cover.

  5. Switch on the power supply to the unit.

Condensing water

Condensing water may accumulate in the unit over time. Follow
these steps to remove condensing water:

  1. Switch off the power supply to the unit.
  2. Remove the unit cover.
  3. Drain the condensing water from the designated outlet.
  4. Replace the unit cover.
  5. Switch on the power supply to the unit.

Cleaning the fans

To ensure proper airflow, periodic cleaning of the fans is
necessary. Follow these steps to clean the fans:

  1. Switch off the power supply to the unit.

  2. Remove the unit cover.

  3. Clean the supply air fan and extract air fan using a soft brush
    or vacuum cleaner.

  4. Replace the unit cover.

  5. Switch on the power supply to the unit.

Cleaning the supply air fan

To clean the supply air fan, follow these steps:

  1. Switch off the power supply to the unit.

  2. Remove the unit cover.

  3. Clean the supply air fan using a soft brush or vacuum
    cleaner.

  4. Replace the unit cover.

  5. Switch on the power supply to the unit.

Cleaning the extract air fan

To clean the extract air fan, follow these steps:

  1. Switch off the power supply to the unit.

  2. Remove the unit cover.

  3. Clean the extract air fan using a soft brush or vacuum
    cleaner.

  4. Replace the unit cover.

  5. Switch on the power supply to the unit.

Technical Specifications

For detailed technical specifications, refer to the document
provided with the Vallox ventilation unit.

Note: You can register your Vallox MV
ventilation unit with the MyVallox Cloud service and sign in to
your MyVallox Cloud account at www.myvallox.com.

Important: In order to ensure that the indoor
air presents no harm to health and remains optimal for the
building’s structures, it is recommended to keep the ventilation
turned on without disruptions. This includes leaving ventilation on
during long holidays to keep the indoor air fresh, prevent humidity
from condensing, and reduce the risk of moisture damage.

MANUAL

Manual

Model Vallox 096 MV Vallox 110 MV Vallox 145 MV
Type A3722 A3702 A3712-1

Document D5326
Valid from 15.10.2021
Updated 15.05.2023

Ventilation units

INTRODUCTION

CONTENTS

INTRODUCTION 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Guarantee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Disposal of the ventilation unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety signs used in the instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Differences between the models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ventilation unit control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ventilation unit control options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Filter reminder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ventilation unit setup without a MyVallox control panel . . . . . . . . . . 5 Connecting the ventilation unit to the cloud service . . . . . . . . . . . . . 5 Main parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Vallox 096 MV, Vallox 110 MV, and Vallox 145 MV . . . . . . . . . . . . . . . 6
INSTALLATION 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vallox 096 MV, Vallox 110 MV, and Vallox 145 MV. . . . . . . . . . . . . . . . . 7 Mounting on the wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Mounting on the ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mounting the ceiling mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Installing the ventilation unit to the ceiling mounting plate . . . . . . . 8 Attic floor penetration plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Vallox 145 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Mounting on a base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Measuring and adjusting the air flows of the ventilation unit . . . . . . . 9 Removal of condensing water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Dimensioning figure and space required for installation of the Vallox Silent Klick siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Space required by the alternative Vallox Silent Klick siphon installation method (elbow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Vallox 096 MV, Vallox 110 MV, and Vallox 145 MV. . . . . . . . . . . . . . . . 10 Dimensions and duct outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Vallox 096 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Vallox 110 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Vallox 145 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

MAINTENANCE 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before beginning maintenance work. . . . . . . . . . . . . . . . . . . . . . . . . 14 Changing the filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Cleaning the heat recovery cell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Condensing water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Cleaning the fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Cleaning the supply air fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Cleaning the extract air fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TECHNICAL SPECIFICATIONS . . 19
Internal electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Vallox 096 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Vallox 110 MV, and Vallox 145 MV . . . . . . . . . . . . . . . . . . . . . . . . . . 23
External electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 External electrical connection for controlling the MLV duct radiator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Duct radiator operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Duct radiator operation chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
In the outdoor air duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 In the supply air duct. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Exploded view and parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Vallox 096 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Vallox 110 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 Vallox 145 MV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 Conformity certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
NOTE You can register your Vallox MV ventilation unit with the MyVallox Cloud service and sign in into your MyVallox Cloud account at www.myvallox.com.

2

SAFETY
Safe and appropriate handling requires knowledge of the basic safety regulations, and of the intended use of the ventilation system. Read this manual before operating the ventilation unit. Retain the manual for later reference. If you lose the manual, it can be downloaded from our website. This user manual contains all the information necessary for safe operation of the system. All persons who operate and maintain the ventilation system must follow the instructions provided in this manual. Furthermore, all local accident prevention regulations must be observed.
Installation
Installation and setup should be carried out only by qualified experts. Electrical installations and connections must be carried out only by an electrician and in compliance with local regulations.
GUARANTEE
The guarantee and liability exclude damage resulting from: · Inappropriate use of the ventilation system or the control unit · Incorrect or inappropriate installation, setup or use · Neglect of instructions concerning transportation, installation,
use, or maintenance · Structural or electronic modifications or changes made to the
software
INTENDED USE
All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to maintain structures in good condition.
IMPORTANT In order to ensure that the indoor air presents no harm to health and remains optimal also for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.
DISPOSAL OF THE VENTILATION UNIT
Do not dispose of electronic devices with household waste. Follow local laws and regulations on safe and ecological disposal of the product.
3

NOTE For further information, go to www.vallox.com
WARNING The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit. Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety. Children must be supervised and not be allowed to play with the device.
© Vallox Oy – All rights reserved

INTRODUCTION

INTRODUCTION

SAFETY SIGNS USED IN THE INSTRUCTIONS

DANGER Indicates a hazard that will result in death or serious injury if not avoided.

WARNING Indicates a hazard that can result in death or serious injury if not avoided.

CAUTION Indicates a hazard that can result in minor or moderate injury if not avoided.

IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided.

NOTE Indicates essential information about the product.

TIP Provides additional information about the use of the product and its benefits.

DIFFERENCES BETWEEN THE MODELS
· Power · Size and weight · Vallox 096 MV does not have an additional heater. Vallox 110 MV and
Vallox 145 MV have an additional heater. · In Vallox 096 MV, there is a sealing tape at the bottom of the heat
recovery cell. In other models, there is a separate sealing bar under the heat recovery cell.
INSTALLATION OPTIONS
· Models Vallox 096 MV and Vallox 110 MV can be mounted either on the wall, or on the ceiling by using a mounting plate (optional).
· Vallox 145 MV can be mounted either on the wall, or on the floor by using a floor rack (optional).
· Vallox 245 MV must always be installed on the floor by using a floor rack.

NOTE The standard equipment and available accessories vary from country to country.

SYSTEM DESCRIPTION
1. Internet 2. WLAN 3. Router 4. WLAN/LAN 5. Additional switch 6. Sensors

MyVallox Cloud 1
2 3

4 MyVallox Home
4

Vallox MV

5 6

KNX bus module

Modbus

KNX

MyVallox control panel

VENTILATION UNIT CONTROL
Ventilation unit control options
Operation of the Vallox ventilation unit can be controlled by the following means: · Through the MyVallox control panel installed in the building. · Through the MyVallox Home local area network connection and
the MyVallox Home/Cloud user interface. · Through the MyVallox Cloud service and the MyVallox Home/
Cloud user interface. · Through a remote monitoring service or building automation
that uses voltage signals or Modbus messages.
In addition to the integrated humidity and carbon dioxide sensor, ventilation can also be adjusted automatically by using the optional carbon dioxide, humidity, or VOC (air quality) sensor. When these are used, ventilation remains optimal even when the dwelling is unoccupied. Each user can use the week clock to adjust the ventilation to fit their individual lifestyle.
Filter reminder
The unit reminds the user of the need to change the filters through the MyVallox control panel and the MyVallox Home/Cloud user interface, as well as by changing the relay status, if a signal light has been connected to the relay connectors of the unit.
The filter reminder can be acknowledged: · From the MyVallox control panel · From the MyVallox Home/Cloud user interface · From the Vallox Delico PTD EC and Vallox Capto PTC EC
control hoods — Damper closed, then open-closed-openclosed. Press at a less than 1 second interval.
Ventilation unit setup without a MyVallox control panel
The ventilation unit setup can also be completed without a MyVallox control panel. For instructions, please go to https://vallox.techmanuals.info/ValloxMV/ENG/help/webhelp
See instructions provided in the section Connecting the ventilation unit to the computer.
Connecting the ventilation unit to the cloud service
The ventilation unit can be connected to the MyVallox Cloud service. The cloud service allows for controlling ventilation remotely also, using e.g. a smartphone or tablet. Also the unit software is updated automatically through the cloud service. To connect to the cloud service, the ventilation unit must be connected to the Internet via LAN and registered with the cloud service. At the same time you create a MyVallox Cloud account for yourself. Read more about the service at www.myvallox.com.
5

NOTE For the MyVallox Cloud/ Home instructions, please go to vallox.techmanuals.info/ ValloxMV/ENG/help/ webhelp
IMPORTANT Prolonged overpressure can result in damage to the structures of the building.
IMPORTANT Apartment-specific ventilation units allows residents to adjust the ventilation efficiency. Ventilation is controlled based on the need e.g. through the cooker hood, ventilation control panel, or a separate control centre. In order to ensure that the indoor air presents no harm to health and remains optimal also for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.
© Vallox Oy – All rights reserved

INTRODUCTION

RATING OF EXTRAC
INTRODUCTION

MAIN PARTS
Vallox 096 MV, Vallox 110 MV, and Vallox 145 MV
15
10 9 8 2 7

ERY

A

T AIR HEAT RECOV

NNUAL EFFICIENCY
A+
6 3 1 5

4 11
12 13 14

R model in the figure

Extract air fan (behind the protective cover)
1
Supply air fan (behind the protective cover)
2
Fine filter for supply air
3
Heat recovery cell
4
Bypass damper of the HR cell
5
Coarse filter for supply air
6
Coarse filter for extract air
7
Post-heating resistor (behind the extract air duct)
8
6

Safety switch
9
Internal humidity sensor
10
Internal carbon dioxide sensor
10
Control panel
11
Humidity sensor (optional)
12
Carbon dioxide sensor (optional)
13
VOC sensor (Optional)
14
Ceiling bushing for electric wires
15

INSTALLATION

INSTALLATION

MOUNTING ON THE WALL
NOTE Avoid mounting the unit on a hollow, echoing partition wall or on a bedroom wall, or prevent the conduction of sound. The minimum distance between the top of the unit and the finished ceiling surface is 30 mm. Note that during mounting the unit rises 10 mm higher than the final height. Mount the ventilation unit onto the wall with a mounting plate (optional), as shown in the figures below. Make sure that the unit is horizontally level after mounting.
MOUNTING ON THE CEILING
Vallox 096 MV and Vallox 110 MV can be equipped with an optional ceiling mount plate. To attach the ceiling mounting plate: · On rafter frames or other frame structure with M8 thread bars so
that they withstand the weight of the unit. · Ensure that the installation plate is horizontally level, as this
determines the position of the unit. · The top edge of the white covering strip of the ceiling mounting
plate can be installed against the ceiling. Alternatively, a concealed mounting method can be used, in which case the ceiling can be 20 mm below the top of the white covering strip. Insulate the ducts against condensation also between the unit and the ceiling mounting plate.
Mounting the ceiling mounting plate
1. Fasten the thread bars on the rafter frames or other frame structure, and screw the nuts onto the bars.
2. Lift the ceiling mounting plate in place. 3. Push a rubber damper and a washer onto each thread bar, and ensure
that they touch the bottom of the cups of the plate (Vallox 096 MV). 4. Turn the nuts to make sure that the unit is horizontally level. 5. Shorten the lower ends of the thread bars so that they will be at no
more than 10 mm from the lower surface of the ceiling mounting plate. CAUTION The ventilation unit is very heavy. Do not perform this procedure alone.
7

NOTE When installing the unit, reserve a sufficient space in front of the unit for servicing purposes. Mount the ventilation unit in a place where the temperature does not fall below +10°C. Vallox 096 MV: The service space in front of the unit must be at least 400 mm. Vallox 110 MV: The service space in front of the unit must be at least 450 mm. Vallox 145 MV: The service space in front of the unit must be at least 550 mm.
© Vallox Oy – All rights reserved

INSTALLATION

Installing the ventilation unit to the ceiling
mounting plate
1. Install the ceiling mounting plate with M8 thread bars so that it is horizontally level.
NOTE The end of the thread bars must be 5 mm or less below the fastening nut. Do not fasten the ceiling mounting plate too tight to the ceiling. Ensure that the sliding bars move and restore to their original position by pulling from the operating levers (A). The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling. Alternatively, a concealed mounting method can be used, in which case the ceiling can be 20 mm below the top of the white covering strip.
2. 096 – Install the insulation washers into the outlet collars of the ventilation unit. 110 – Ensure that the insulation washers are in place in the outlet collars below the ceiling mounting plate.
3. Remove the door before installing the ventilation unit to the ceiling mounting plate.
4. Lift the ventilation unit close to the ceiling mounting plate and feed the cables and the connection box through the hole in the ceiling mounting plate on top of the ceiling.

A
A
a
3

NOTE Remember to make a service door in the ceiling so that the cables and the connection box can be accessed. The distance between the service door and the ceiling mounting plate must be around 500 mm.
Alternatively, the cables can be fed between the ceiling mounting plate and the ventilation unit to the rear wall. When the ventilation unit is lifted against the ceiling mounting plate, the unit locks in place. Where needed, guide the mounting hooks on the ceiling mounting plate (B) to the grooves on the side panels of the ventilation unit. There are operating levers (A) on the front bottom corners of the ceiling mounting plate. When the levers have been restored to the same level with the white covering strip of the ceiling mounting plate, the unit has been locked in place.
5. Where required, the unit can be detached from the ceiling mounting plate. Remove the door of the unit. Lift the unit slightly upwards and pull simultaneously from both operating levers (A) of the ceiling mounting plate to detach the unit from the ceiling mounting plate.

Attic floor penetration plate
The attic floor penetration plate (F) is optional. When an attic floor penetration plate is used, the tightness of the vapour barrier has to be ensured.
The minimum distance of the attic floor penetration plate from the rear wall is 5mm. The minimum distance of the attic floor penetration plate from the side walls is 15mm.

B
F
1 B
b
2
4 5
NOTE Mount the ventilation unit in a place where the temperature does not fall below +10°C.
TIP You can detach the unit from the ceiling mounting plate by pulling the springloaded moulding to the direction shown by the arrow (more detailed information provided with the ceiling mounting plate).

8

INSTALLATION

MOUNTING ON A BASE

NOTE Vallox 145 MV must always be installed on a base on the floor, or on the wall using a mounting plate.
The base is optional. Adjust the base with adjusting legs to level it. Remove the (4 pcs) rubber plugs at the bottom of the unit. Place the unit on top of the base so that the bars of the base fit in the holes at the bottom of the unit. Mount the ventilation unit on the wall with a mounting plate, as shown in the adjacent figure. Make sure that the unit is horizontally level after mounting.

A Thread bar M8 x 35, shorter thread upward B The length of the adjusting screw is 37mm.
Ø 22 Ø 8

8

80

23 min.

133 min.

685

A

625

30 30

465

435

495

30
B

655

NOTE Mount the ventilation unit in a place where the temperature does not fall below +10°C.

Ø6

MEASURING AND ADJUSTING THE AIR FLOWS OF THE VENTILATION UNIT
The accessories delivered with the unit include four (4) air flow measuring tubes. These can be inserted in the ducts to allow for easier ventilation adjustment.
92 1
16
9

© Vallox Oy – All rights reserved

INSTALLATION

REMOVAL OF CONDENSING WATER
NOTE The Vallox Silent Klick siphon package is delivered with the unit. Installation instructions for the siphon are enclosed with the packaging, and can also be found online at www.vallox. com. When the alternative siphon installation method is used, the ring seal and the locking part must be moved to the pipe connection part that is mounted on the wall.

Dimensioning figure and space required for installation of the Vallox Silent Klick siphon

Vallox 096 MV

Vallox 110 MV

Vallox 145 MV

143 143 141 141 141 141
75

L

R

L

R

121

121

140

140

L

R

180

180

55 43 43

Space required by the alternative Vallox Silent Klick siphon installation method (elbow)

Vallox 096 MV

Vallox 110 MV

Vallox 145 MV

38 28 28

10

INSTALLATION

DIMENSIONS AND DUCT OUTLETS

Vallox 096 MV

Main parts

9

6

8

3

2

1

7 5

Dimensions and duct outlets

Dimensions

600

430 407
298 545
102 38 583

R model in the figure.

4

In the L model, the parts are mirrored

1. Extract air fan

5. Bypass damper of the HR cell

(behind the protective cover) 6. Coarse filter for supply air

2. Supply air fan

7. Coarse filter for extract air

(behind the extract air duct) 8. Post-heating resistor

3. Fine filter for supply air

(behind the extract air duct

4. Heat recovery cell

9. Safety switch

Air flow measurement points

A

B
A Supply air B Extract air
Measurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.

Locations of supports for HR cell

R model

L model

2

1

1

2

3

3

4

4

R

600

363

93

1

3

125

2

4

141 459

L

600

363

93

430 407
298 102

3

1

125

4

2

141 459

6

424

380

3
1. Supply air 2. Extract air 3. Coarse filter

3

5

5

4. Fine filter 5. Upper support for HR cell

143
Duct outlets
Inner diameter of the outlet collar: 125mm 1. Supply air from the unit to the apartment 2. Extract air from the apartment to the unit 3. Exhaust air flowing outdoors from the unit 4. Outdoor air to the unit

11

© Vallox Oy – All rights reserved

INSTALLATION

Vallox 110 MV
Main parts
9 8 2 7 10

Dimensions and duct outlets

Dimensions

638

6 3 1

678

5

28 706

4
R model in the figure. In the L model, the parts are mirrored

1. Extract air fan

6. Coarse filter for supply air

(behind the protective cover) 7. Coarse filter for extract air

2. Supply air fan

8. Post-heating resistor

(behind the extract air duct)

(behind the extract air duct)

3. Fine filter for supply air

9. Safety switch

4. Heat recovery cell

10. Additional heating resistor

5. Bypass damper of the HR cell

(behind the extract air duct)

Air flow measurement points

A

B
A Supply air B Extract air

Measurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.

Locations of supports for HR cell

R model

L model

2

1

1

2

3

3

4

4

R
638 390 112

111

325

455

472

1

3

160

2

4

160 478

L
638 390 112

472 455
325 111

3

1

160

4

2

160 478

4

473

429

3
1. Supply air 2. Extract air 3. Coarse filter

5

5

3

6

6

4. Fine filter 5. Upper support for HR cell 6. Lower support for the HR cell

12

142
Duct outlets Inner diameter of the outlet collar: 160mm 1. Supply air from the unit to the apartment 2. Extract air from the apartment to the unit 3. Exhaust air flowing outdoors from the unit 4. Outdoor air to the unit

INSTALLATION

Vallox 145 MV
Main parts
9 8 2 7 10

Dimensions and duct outlets

25

Dimensions

717

6 3 1

748

5

42

R model in the figure.

4

In the L model, the parts are mirrored

1. Extract air fan

6. Coarse filter for supply air

(behind the protective cover) 7. Coarse filter for extract air

2. Supply air fan

8. Post-heating resistor

(behind the extract air duct)

(behind the extract air duct)

3. Fine filter for supply air

9. Safety switch

4. Heat recovery cell

10. Additional heating resistor

5. Bypass damper of the HR cell (behind the extract air duct)

Air flow measurement points

A

B
A Supply air B Extract air

Measurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.

Locations of supports for HR cell

R model

L model

2

1

1

2

3

3

4

4

R

717

455

125

578 560 491
411 127

1

3

200

2

4

180 313 405 537

L

717

455

125

578 560 491
411 127

3

1

200

4

2

180 313 405 537

5

574

529

3
1. Supply air 2. Extract air 3. Coarse filter

5

5

3

6

6

4. Fine filter 5. Upper support for HR cell 6. Lower support for the HR cell

13

Duct outlets

142

Inner diameter of the outlet collar: 200mm

1. Supply air from the unit to the apartment 2. Extract air from the apartment to the unit 3. Exhaust air flowing outdoors from the unit 4. Outdoor air to the unit

© Vallox Oy – All rights reserved

MAINTENANCE

MAINTENANCE
BEFORE BEGINNING MAINTENANCE WORK
The safety switch (S) automatically turns off the power when the door of the unit is opened.
WARNING Always disconnect the power plug before starting the ventilation unit maintenance. There are two unit models, left- (L) and right-handed (R). The figure shows the right-handed model.
CHANGING THE FILTERS
When the maintenance reminder becomes activated, check the cleanliness of the filters and replace them if required. The Vallox ventilation unit has three air filters: · Coarse filter for supply air filters insects, heavy pollen
and other relatively large foreign objects out of the outdoor air. · Fine filter for supply air filters microscopic pollen and dust particles out of the supply air. · Coarse filter for extract air filters the extract air and keeps the heat recovery cell clean.
The filter replacement interval depends on the ambient particle concentration. It is recommended that the filters be replaced every spring and autumn, or at the very least once a year.
To replace the filters: 1. Disconnect the ventilation unit from the mains
electricity supply. 2. Lift the latch to open the door of the Vallox ventilation
unit. 3. Lift the door off.
CAUTION The door is heavy. 4. Remove the old filters (A, B, C) and discard them. 5. Install the new filters (A, B, C). 6. Close the door of the unit. Ensure that the safety switch catch of the door is touching the safety switch, allowing the unit to be turned on. 7. Plug the ventilation unit back into the mains.
The filters have now been successfully replaced.
14

IMPORTANT If the power cord is damaged, the manufacturer, its service representative or other person with similar qualifications must replace it to avoid danger.
TIP Using original Vallox filters ensures that the ventilation unit remains in top condition, giving the best results. To select and order filter packages, please go to: filters.vallox.com
NOTE Vallox 096 MV: The service space in front of the unit must be at least 400 mm. Vallox 110 MV: The service space in front of the unit must be at least 450 mm. Vallox 145 MV: The service space in front of the unit must be at least 550 mm.

CLEANING THE HEAT RECOVERY CELL
Check that the heat recovery cell is clean roughly once a year, or whenever the filters are being replaced. Clean by washing as required.
To check and clean the heat recovery cell: 1. Disconnect the ventilation unit from the mains electricity
supply. 2. Open the Vallox ventilation unit door by first lifting the latch
fully up and then lowering it back a little way. 3. Lift the door off.
CAUTION The door is heavy. 4. Remove the filters (A, B, C). 5. Remove the sealing strip (E) above the cell in the direction of the arrow. 6. Lift and pull the cell (D) out of the unit.
IMPORTANT Handle the cell carefully! For example, do not lift the cell by the layers. The cell layers are very thin and easily damaged. 7. If the cell is dirty, clean it by immersing it in warm water, to which a small amount of a mild detergent has been added. 8. Rinse the cell clean with a water spray. Do not use a highpressure cleaner. 9. When all the water has drained from between the layers, reassemble the ventilation unit in the reverse order. 10. When reassembling Vallox 096 MV, check that the sealing strip below the cell is pressed against the bottom of the unit. 11. Close the door. Ensure that the safety switch catch of the door is touching the safety switch. 12. Plug the ventilation unit back into the mains.
The heat recovery cell has now been checked and cleaned.
CONDENSING WATER
In the heating season, the extract air humidity condenses to water. In new buildings, condensation runoff can form rapidly. Condensed water must be able to freely leave the unit.
At some time before the heating season begins (e.g. during autumn maintenance), check that the siphon or the condensing water outlet in the bottom pool are not clogged. To check this, pour some water into the pool. Clean as required.
15

NOTE Some condensing water may have accumulated in the bottom pool of the unit; this is normal and requires no corrective action.
WARNING Water must at all times be kept out of the electrical system.
© Vallox Oy – All rights reserved

MAINTENANCE

MAINTENANCE

CLEANING THE FANS
Check the cleanliness of the fans when servicing the filters and the heat recovery cell. Clean the fans as required. You can clean the fan blades with compressed air (wear protective goggles) or by brushing them gently. Do not remove or move the fan blade balancing weights.
Cleaning the supply air fan
To clean the supply air fan: 1. Disconnect the ventilation unit from the mains electricity
supply. 2. Lift the latch to open the door of the Vallox ventilation unit. 3. Lift the door off.
CAUTION The door is heavy.
4. Remove the extract air filter (C), the cell top bracket (E) and the heat recovery cell (D). See chapters “Replacing the filters” and “Cleaning the heat recovery cell”.
5. Pull out the temperature sensor (figure 1) located at the top of the extract air duct (G). Remove the stopper screw (I) at the bottom of the duct. The extract air duct now comes out by turning and pushing it downwards simultaneously (figure 2).
6. Remove the temperature sensor from the resistor support (figure 4).
7. Remove the additional and post-heating resistor support, which is attached by two wing nuts (Vallox 110 MV and Vallox 145 MV) or screws (Vallox 096 MV) from below (figure 5).

IMPORTANT The fans are extremely sensitive to external shocks. It is recommended that the fans be cleaned in place, i.e. without attempting to remove them.
Handle the fan blades carefully. Do not remove or move the fan blade balancing weights.

1

1 det

2

3

4

5

6

7

16

MAINTENANCE

8. Pull the radiator and the support out of the unit (figures 6 and 7) and remove the quick connector of the radiator

8

wires.

CAUTION Before removing the resistor from the unit, make sure it is not hot.

9. The fan can now be cleaned in place. It is

recommended that the fan be cleaned in place, i.e.

without attempting to remove it.

10. To remove the fan for cleaning: a. If necessary, remove the arm pins. Use pliers to

9

press the pins straight, so that they are easier to

install back later.

b. Push the fan gently upward (figure 9).

c. Pry the plastic lock to the right of the fan with a

screwdriver, for example (figure 10).

d. The fan falls downwards.

e. Pull the fan out of the unit (figure 11).

f. Disconnect the fan wire quick connector (figure 12).

The fan has now been removed for cleaning.

10

11. To reassemble the ventilation unit, follow the above

steps in reverse order.

TIP

When you re-install the temperature sensor,

position it with the tip upward and pointing at the

wall in such a way that it does not get squeezed

between the HR cell bypass damper or lean against

the radiator frame.

12. Close the door. Ensure that the safety switch catch of

11

the door is touching the safety switch.

13. Plug the ventilation unit back into the mains.

The fan has now been checked and cleaned.

12

17

© Vallox Oy – All rights reserved

MAINTENANCE

Cleaning the extract air fan
To clean the extract air fan, proceed as follows:
1. Disconnect the ventilation unit from the mains electricity supply. 2. Lift the latch to open the door of the Vallox ventilation unit. 3. Lift the door off.
CAUTION The door is heavy.
4. Remove the filters (C), the cell top support (E) and the heat recovery cell (D). See chapters “Replacing the filters” and “Cleaning the heat recovery cell”.
5. Open the four screws (figure 1) on the extract air fan cover and remove the cover (figure 2). The fan can now be cleaned in place.
6. To remove the fan for cleaning: a. Push the fan gently upward (figure 3). b. Pry the plastic lock to the right of the fan with a screwdriver, for example (figure 4). c. The fan falls downwards (figure 5). d. Pull the fan out of the unit. e. Disconnect the fan wire quick connector (figure 6).
7. Clean the fan. 8. To reassemble the ventilation unit, follow the above steps in reverse
order. 9. Close the door and plug the unit back into the mains.
The extract air fan has now been checked and cleaned.

1

2

3

4

5

6

18

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

Product title

Vallox 096 MV R Vallox 096 MV L

Product number 3474450 3474550

Air volumes Supply air Extract air

84 dm3/s, 100 Pa 88 dm3/s, 100 Pa

Fans Supply air Extract air

Post-heating

Electrical resistor, 900 W

Electrical connection

Pre-heating

­

Enclosure protection class

Additional heating

­

Heat recovery bypass

Filters Supply air Extract air

ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %

Specific energy consumption (SEC)

in a cold climate

A+

in a temperate climate

A

Operating efficiencies* Annual efficiency Supply air efficiency Specific Fan Power (SFP)

Dimensions (w x h x d)

600 x 545 x 428 mm

Weight

*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.

0.119 kW 0.9 A EC 0.119 kW 0.9 A EC 230 V, 50 Hz, 5.1 A power plug IP34 Automatic
77 % 86 % 1.33 kW/m3/h (59 dm3/s) 53 kg

FAN INPUT POWER

SUPPLY/EXTRACT AIR VOLUMES

Power (W)
200

180

160

140

120

100

80

60

40

20

0

0

10

0

36

Pressure loss in ducts. Total pressure (Pa)

100 %

90 %

300

80 % 250

70 %

200

100 % 80 %
L 70 %
60 %

60 %

150

50 %

50 %

100

40 %

40 % 30 % 20 % 10 %

dm³/s

30 % 50 20 %
10 %
0

SFP 1,0

SFP 1,5 SFP 1,2

dm³/s

20 30 40 50 60 70 80 90 100 (l/s)

0

10

20

30 40 50 60 70 80 90 100 (l/s)

72 108 144 180 216 252 288 324 360 m³/h

0

36

72 108 144 180 216 252 288 324 360 m³/h

Volume flow rate

Volume flow rate (dm3/s)

SFP =

Input power (total) (W) Air flow (max) (dm3/s)

SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s)

extract air supply air

SOUND VALUES

Sound power level in the supply air duct (one duct) by octave band Lw, dB Adjustment position

Sound power level in the extract air duct (one duct) by octave band Lw, dB Adjustment position

Adjustment position (%) 10 20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100

Medium frequency of the octave band Hz

63 125 250 500 1000

54 64 69 74 76 80 84 87 87 86 51 56 63 66 70 73 76 78 79 79 50 56 62 66 70 73 77 80 82 81 43 46 52 55 60 63 66 68 71 71 46 54 59 63 66 69 72 75 77 77 33 38 44 47 51 55 58 61 63 63 40 48 54 57 61 63 66 68 70 71 29 38 44 47 51 54 57 59 61 61 34 44 51 55 60 62 64 66 68 68 24 32 38 42 46 49 52 55 57 57

2000

21 35 44 49 54 57 61 63 66 66 13 17 24 29 33 36 39 42 44 44

4000

17 23 34 41 47 51 55 58 61 61 17 17 18 20 23 26 29 32 34 34

8000

21 21 26 34 42 47 52 56 59 59 21 21 21 21 21 22 23 25 27 27

LW,dB LWA, dB(A)

56 65 70 75 78 81 85 88 89 88 52 56 64 66 71 74 76 79 80 80 42 50 57 61 64 67 70 73 75 75 33 39 45 48 52 55 58 61 63 63

Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)

Adjustment position

Adjustment position (%)

10

20

30

40

50

60

70

80

90

100

LpA, dB (A)

24

28

34

33

37

41

44

46

48

48

You can calculate the sound values for each operating point with the Vallox MySelecta software.

19

© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

Product title

Vallox 110 MV R Vallox 110 MV L

Product number 3446650 3446750

Air volumes Supply air Extract air

96 dm3/s, 100 Pa 103 dm3/s, 100 Pa

Fans Supply air Extract air

Post-heating

Electrical resistor, 900 W

Electrical connection

Pre-heating

­

Enclosure protection class

Additional heating

Electrical resistor, 900 W

Heat recovery bypass

Filters Supply air Extract air

ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %

Specific energy consumption (SEC)

in a cold climate

A+

in a temperate climate

A

Operating efficiencies* Annual efficiency Supply air efficiency Specific Fan Power (SFP)

Dimensions (w x h x d)

638 x 678 x 472 mm

Weight

*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.

0.119 kW 1.0 A EC 0.119 kW 1.0 A EC 230 V, 50 Hz, 8.5 A power plug IP 34 Automatic
79 % 86 % 1.15 kW/m3/h (71 dm3/s) 64 kg

FAN INPUT POWER
Power (W)

SUPPLY/EXTRACT AIR VOLUMES
Pressure loss in ducts. Total pressure (Pa)

SFP =

Input power (total) (W) Air flow (max) (dm3/s)

Volume flow rate
SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s)

Volume flow rate (dm3/s) extract air supply air

SOUND VALUES

Sound power level in the supply air duct (one duct) by octave band Lw, dB
Adjustment position

Sound power level in the extract air duct (one duct) by octave band Lw, dB
Adjustment position

Adjustment position (%) 10

Medium 63

53

frequency of the

125

48

octave 250

46

band Hz

500

40

1000

31

2000

18

4000

17

8000

21

LW,dB

55

LWA, dB(A)

41

20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100 60 67 71 74 78 82 83 84 84 54 46 62 65 69 72 75 77 79 79 56 61 66 70 74 76 78 80 80 42 44 50 53 58 61 64 66 68 68 53 58 62 65 69 71 74 76 76 34 41 46 50 53 56 60 62 64 64 48 56 57 60 62 65 67 68 69 26 35 40 43 46 49 52 55 57 57 42 50 55 58 61 64 65 67 67 18 28 34 38 41 45 47 50 52 51 32 40 46 52 56 60 62 64 64 13 17 24 29 33 36 39 42 44 44 20 30 38 44 49 53 56 59 59 17 17 18 19 21 24 27 31 33 33 21 25 34 42 48 53 57 59 60 21 21 21 21 21 22 24 26 29 29 62 69 73 76 80 83 85 86 86 55 57 62 66 70 72 75 78 79 79 49 56 60 63 67 69 72 73 73 33 38 43 46 50 53 56 59 60 60
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)

Adjustment position

Adjustment position (%)

10

20

30

40

50

60

70

80

90

100

LpA, dB (A)

21

24

30

32

35

39

42

45

47

47

You can calculate the sound values for each operating point with the Vallox MySelecta software.

20

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

Product title

Vallox 145 MV R Vallox 145 MV L

Product number 3475650 3475750

Air volumes Supply air Extract air

150 dm3/s, 100 Pa 155 dm3/s, 100 Pa

Fans Supply air Extract air

Post-heating

Electrical resistor, 900 W

Electrical connection

Pre-heating

­

Enclosure protection class

Additional heating

Electrical resistor, 1500 W

Heat recovery bypass

Filters Supply air Extract air

ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %

Specific energy consumption (SEC)

in a cold climate

A+

in a temperate climate

A

Operating efficiencies* Annual efficiency Supply air efficiency Specific Fan Power (SFP)

Dimensions (w x h x d)

717 x 748 x 578 mm

Weight

*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.

0.175 kW 1.25 A EC 0.175 kW 1.25 A EC 230 V, 50 Hz, 11.9 A power plug IP 34 Automatic
79 % 85 % 1.33 kW/m3/h (109 dm3/s) 88 kg

FAN INPUT POWER

SUPPLY/EXTRACT AIR VOLUMES

Power (W)
350

Pressure loss in ducts. Total pressure (Pa)
450

300

100 %

400

90 %

100 %

80 %

350

80 %

250

70 %

300

L

70 %

200

250

150

60 %

60 % 200

100

50 %

150

50 %

40 %

50

30 %

20 %

10 % 0

dm³/s

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 (l/s)

0 36 72 108 144 180 216 252 288 324 360 396 432 468 504 540 576 612 m³/h

40 % 100
30 %

SFP 1,8

50 20 %
10 % 0

SFP 1,0

SFP 1,5

dm³/s

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 (l/s)

Volume flow rate

0 36 72 108 144 180 216 252 288 324 360 396 432 468 504 540 576 612 m³/h
Volume flow rate (dm3/s)

SFP =

Input power (total) (W) Air flow (max) (dm3/s)

SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s)

extract air supply air

SOUND VALUES

Sound power level in the supply air duct (one duct) by octave band Lw, dB
Adjustment position

Sound power level in the extract air duct (one duct) by octave band Lw, dB
Adjustment position

Adjustment position (%) 10 20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100

Medium 63

frequency of the

125

octave 250

band Hz

500 1000

55 66 73 76 80 83 85 86 87 87 53 58 63 67 73 78 78 79 80 79 50 58 64 68 72 76 80 83 84 84 45 50 56 61 65 69 73 75 75 75 52 57 63 65 68 72 74 77 78 78 40 39 44 49 54 57 60 63 64 64 41 48 53 57 61 64 67 70 71 71 30 37 43 47 50 53 56 58 59 59 53 47 52 57 60 64 65 67 68 68 32 33 36 41 44 48 50 52 53 53

2000

23 34 43 48 53 58 62 64 66 66 15 22 30 34 38 42 45 48 49 49

4000

18 23 36 44 50 55 59 62 63 63 17 17 19 23 27 31 35 38 39 39

8000

21 22 28 39 47 54 58 62 63 63 21 21 21 22 24 28 32 35 36 36

LW,dB LWA, dB(A)

59 68 74 77 81 84 86 88 90 89 54 59 64 68 74 79 79 80 81 81 53 52 58 62 66 69 72 75 76 76 37 40 45 50 54 58 60 63 63 63

Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)

Adjustment position

Adjustment position (%)

10

20

30

40

50

60

70

80

90

100

LpA, dB (A)

28

27

32

35

39

43

46

48

49

49

You can calculate the sound values for each operating point with the Vallox MySelecta software.

21

© Vallox Oy – All rights reserved

YEGN YEGN YEGN YEGN
BN YEGN
BU WT GN YE
BN YEGN
BU WT GN YE
TECHNICAL SPECIFICATIONS

INTERNAL ELECTRICAL CONNECTION
Vallox 096 MV

TK
LL
NN

230V 50Hz

BN BU L N L N BN BU BN BU BN BU
2 3 1

T1 T2
130°C 90°C

A

AHS %RH %RH CO2

B
123456

1

C

2 3

4

5

T

P R1

M

MB_A MB_B
+24V RS_A RS_B GND

MB_A MB_B
+24V RS_A RS_B GND

TESTER

NTC GND +24V +24V RS_A RS_A RS_B RS_B GND GND +11V1 +24V AN/I D/I1 GND +24V RM/I D/I2 RM/O

D

A Motherboard

1. Extract air fan tacho (WT)

2. GND (GN)

B

3. Extract air fan PWM (YE) 4. Supply air fan tacho (WT)

5. GND (GN)

6. Supply air fan PWM (YE)

1. Extract air

2. Outdoor air

C 3. Supply air

4. Exhaust air

5. Supply air from the HR cell

D LAN

CABLE COLOURS

BK

Black

BU

Blue

BN

Brown

WT

White

GY

Grey

YE

Yellow

YEGN Yellow-green

MB_A MB_B +24V GND RS_A RS_B NTC D/I1 D/I2 11V1 AN/I

External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC

RM/I RM/O T P M TK AHS %RH
%RH CO2

24V relay input 24V relay output Supply air fan Extract air fan Damper motor Safety switch Post-heating control Internal humidity sensor Internal humidity and carbon dioxide sensor

R1

Post-heating resistor with 90°C and 130°C overheating protection

22

TECHNICAL SPECIFICATIONS

Vallox 110 MV, and Vallox 145 MV

TK 230V 50Hz
LL NN
BN BU L N L N BN BU BN BU BK
2 BN 3 1

T1 T2

T1 T2

130°C 90°C 130°C 90°C

T

P R1 R2

M

YEGN YEGN
YEGN YEGN YEGN

A

AHS %RH %RHCO2

B
123456

1

2

C

3

4

5

MB_A MB_B
+24V RS_A RS_B GND

MB_A MB_B
+24V RS_A RS_B GND

TESTER

NTC GND +24V +24V RS_A RS_A RS_B RS_B GND GND +11V1 +24V AN/I D/I1 GND +24V RM/I D/I2 RM/O

D

BN YEGN
BU WT GN YE
BN YEGN
BU
WT GN YE

A Motherboard

1. Extract air fan tacho (WT)

2. GND (GN)

B

3. Extract air fan PWM (YE) 4. Supply air fan tacho (WT)

5. GND (GN)

6. Supply air fan PWM (YE)

1. Extract air 2. Outdoor air C 3. Supply air 4. Exhaust air 5. Supply air from the HR cell

D LAN

CABLE COLOURS

BK

Black

BU

Blue

BN

Brown

WT White

GY

Grey

YE

Yellow

YEGN Yellow-green

MB_A MB_B +24V GND RS_A RS_B NTC D/I1 D/I2 11V1 AN/I RM/I RM/O

External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output

T

Supply air fan

P

Extract air fan

M

Damper motor

TK

Safety switch

AHS

Post-heating control

%RH

Internal humidity sensor

%RH CO2

Internal humidity and carbon dioxide sensor

R1

Post-heating resistor with 90°C and 130°C overheating protection

R2

Additional heating resistor with 90°C and 130°C overheating protection

23

© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

EXTERNAL ELECTRICAL CONNECTION

MyVallox

VOC

2 W

sensor

MyVallox %RH sensor

0.3W

2x2x0,5+0,5

MyVallox CO2 sensor

1.2W

2x2x0,5+0,5

REMOTE MONITORING Modbus RTU 2x2x0,5+0,5

MyVallox control panel

7028350 2014-08-29 JS
1W

2x2x0,5+0,5

MyVallox control panel
1W

2x2x0,5+0,5

External temperature sensor NTC 4K7

2×0,5

2×0,5

2×0,5

Digital input 1 8 different functions

Digital input 2 8 different functions

Ethernet connection on top of the unit

CAT RJ45 female

VENTILATION UNIT INTERNAL ELECTRICAL CONNECTION

2×0,5

Analog input two different functions

2×0,5

Potential-free contact data 24VDC can be programmed to display information such as errors or to control the valve and pump of the MLV radiator.

Plug connection 1.2 m on top of the unit
3×1,5S

POWER SUPPLY
Maximum MyVallox Control MyVallox Touch MyVallox %RH sensor MyVallox CO2 sensor MyVallox VOC sensor Voltage

6W 1W 0.5 W. 0.3W 1.2W 2W 24 VDC

MB_A MB_B +24V GND RS_A RS_B NTC

External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector

D/I1 D/I2 11V1 AN/I RM/I RM/O

Digital input 1 Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output

24

TECHNICAL SPECIFICATIONS

EXTERNAL ELECTRICAL CONNECTION FOR CONTROLLING THE MLV DUCT RADIATOR

External temperature sensor NTC 4K7
Ethernet connection on top of the unit
RJ45 Female

CAT

2×0,5

24 VDC relay/ contactor for controlling the pump and solenoid valve

Distribution board
LN

2×0,5

GND

VENTILATION UNIT INTERNAL ELECTRICAL CONNECTION

+24VDC

L N1 2

P

V

MLV control

Plug connection 1.2 m on top of the unit

3×1,5S

MB_A MB_B +24V GND RS_A RS_B NTC D/I1

External Modbus A signal External Modbus B signal +24V voltage (DC) Digital and analog ground potential Local hardware Modbus A signal Local hardware Modbus B signal External temperature sensor connector Digital input 1

D/I2 11V1 AN/I RM/I RM/O P V

Digital input 2 11.1 V operating voltage Analog input 0-10VDC 24V relay input 24V relay output Circulation pump Solenoid valve

25

© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

DUCT RADIATOR OPERATION
Always follow first and foremost the connection diagram provided by the HVAC designer or heat pump manufacturer. Also read the duct radiator manual.
The accompanying figure shows an example of the arrangement for connecting the heating/cooling radiator unit to the heat collection circuit.
Connect the radiator output pipe to the heat collection circuit return pipe. Direct the fluid returning from the radiator unit to the heat collection circuit return pipe. If you know that there is a large loss of internal pressure inside the heat pump, the heat pump should be bypassed. If this is done, the fluid circuit will come into operation when the heat pump comes to a halt. When this happens the pressure loss in the one-way bypass valve Y2 must be lower than the pressure loss in the heat pump.
Heating: The pump starts when the outdoor air temperature drops below the winter limit value set at the factory (-5 °C).
Cooling The supply air setpoint value for the active mode (for example, At home) controls the pump start-up. The pump starts when the supply air setting is below the temperature of the supply air that is blown into the apartment.
The duct radiator can be installed in both the supply air duct and the outdoor air duct. If the radiator is installed in the outdoor air duct, it can be used for both preheating and cooling. If the radiator is installed in the supply air duct, it can be used for heating or for cooling only.
The duct radiator can be set to function either automatically or manually.
· Automatic – In summer, the supply air temperature will be maintained at the level specified in the temperature setting. In winter, the duct radiator will turn on, when the outdoor temperature falls below the winter setting.
· Manual – In summer, the duct radiator will turn on, when the outdoor temperature rises above the summer setting. In winter, the duct radiator will turn on, when the outdoor temperature falls below the winter setting.
To prevent the risk of condensation in the supply air duct, you can set the adjustment of the supply air limit to automatic or manual.
· Automatic – The supply air limit is adjusted automatically based on the dew point of the extract air. When the supply air temperature falls too low, the duct radiator will turn off.
· Manual – The supply air limit can be set manually. When the supply air temperature falls down to the set value, the duct radiator will turn off.
If an external sensor is in use, it is selected from the settings of the external sensor whether it is used to control the outdoor air duct radiator or the supply air duct radiator. The temperature of the external sensor can be read from the service menu: menu > service menu > unit information page 5 “External sensor”.
26

NOTE: If the duct radiator is used in the supply air duct, it can only be used for cooling.
NOTE: When used to control the outdoor air duct radiator, the external NTC sensor is installed in the outdoor air duct before the radiator. When used to control the supply air duct radiator, the external NTC sensor is installed after the radiator.
NOTE: When selecting the relay (C), take account of the maximum allowed combined power supply (6W) of the circuit board in the external MV electrical box, if the relay power supply comes from the circuit board’s +24V connector.
NOTE: Due to the risk of humidity damage, in a duct that has not been insulated for condensation the supply air temperature must not fall below +16 … 20 °C.

TECHNICAL SPECIFICATIONS

DUCT RADIATOR OPERATION CHART

In the outdoor air duct

E IP F

B

C

S

N

A

D

K C

G

V

P

Y

Y2

H

In the supply air duct

E

F

IP

B

C

NN

S

A

K

C

D

G

V

P

Y2

Y

H
A Ventilation unit B Supply air C Outdoor air D Feed from the distribution board E Air extraction F Duct radiator (reverse connection) G Heat pump H Heat collection circuit N External NTC sensor

Circulation pump. Not included in the delivery. The pump should be suited to pumping P liquid colder than the surrounding air, due to risk of condensation (for example, Grundfos
Magna 1 25-80).

V

Solenoid valve. Not included in the delivery. The valve that is chosen must be compatible with the heat collection circuit fluid (for example, Danfoss 032U161431).

K Condensing water tube. Not included in the delivery.

IP De-aerator. Not included in the delivery.

S External electrical junction box for the MV

N External NTC sensor for Vallox MV ventilation units

C

24 VDC relay/contactor for controlling the pump and the solenoid valve. Not included in the delivery. (For example, ABB CR-P024DC2)

Y One-way valve. Not included in the delivery.

Y2

One-way valve. Not included in the delivery. The pressure loss must be less than the pressure loss of the heat pump.

27

© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

EXPLODED VIEW AND PARTS LIST
Vallox 096 MV

3

2

1

28

19

16

12

20 21

13 12 11

10

9

8

18
14
22 23
4 15
5 17
6
16

25
7
26
27

NO. PART

CODE NO. PART

CODE NO. PART

CODE

Supply / extract air fan (with a hood)

1108800

HR cell bypass damper assembly

Post-heating resistor 900W (R and L models)

942210

2. Fan

935365

R model

3491200 20. Door

3475200

Wall mounting plate (optional)

3080700

L model

3491201 21. Door latch

3355900

4. Siphon Vallox Silent Klick 3494701 12. Damper motor

930620 22. NTC sensor kit

3480500

5. Coarse filter for supply air 978044 13. Extract air outlet

985026

Glass tube fuse 63mA slow 5x20mm

952490

6. Fine filter for supply air

978220

Internal humidity and carbon dioxide sensor

4107982

MyVallox Control panel MyVallox Touch control panel

949033 949090

HR cell (aluminium) HR cell (enthalpy)

933260 933153

15. Motherboard

949032-1 25.

MyVallox humidity sensor (optional)

946149

8. Upper support for HR cell 3467200 16. Safety switch

948377

MyVallox carbon dioxide sensor (optional)

949111

9. Filter stand

3464500 17. Connection box

3526700 27. MyVallox VOC sensor (optional) 949112

Coarse filter for extract air 978045

18. RJ45 extension cable 952196

Ceiling bushing for electric wires 950445

Ceiling feed-through seal

950446

28

TECHNICAL SPECIFICATIONS

Vallox 110 MV

3

2

1

30

20

21

17

12

22 23

14 13 12

11

10

9

19

15
24
25 4
16 5

6

18

26

27

8

7

28

29

NO. PART

CODE

Supply / extract air fan

1108800

2. Fan

935415

Wall mounting plate (optional)

3080700

Siphon Vallox Silent Klick

3494701

Coarse filter for supply air

978042

Fine filter for supply air

978157

Lower support for HR cell

3450100

HR cell (aluminium) 933160 HR cell (enthalpy) 933170

Upper support for HR cell

3426600

10. Filter stand

3426800

Coarse filter for extract air

978043

NO. PART
12. Bypass duct assembly R model L model

13. Damper motor

14. Extract air outlet

Internal humidity and carbon dioxide sensor

16. Motherboard

17. Safety switch

18. Connection box

19. RJ45 extension cable

Post-heating resistor 900W

R model

L model

CODE NO. PART

CODE

21. 3447200

Additional heating resistor 900W
R model

3447201

L model

942210 942211

930620 22. Door

3447300

985025 23. Door latch

3355900

4107982 24. NTC sensor kit

3457900

949032-1 25. 948377 26. 3526700 27. 952196 28.

Glass tube fuse 63mA slow 5x20mm
MyVallox Control panel MyVallox Touch control panel
MyVallox humidity sensor (optional)
MyVallox carbon dioxide sensor (optional)

952490 949033 949090 946149
949111

29. MyVallox VOC sensor (optional) 949112

942211 942210

Ceiling bushing for electric wires 950445

Ceiling feed-through seal

950446

29

© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

Vallox 145 MV

3

2

1

30

22 23

21

20

17

14

13 12

11

10

9

12

19

15
24
25 4
16 5

6

18

26

27

8

7

28

29

NO. PART

CODE NO. PART

CODE NO. PART

CODE

Supply / extract air fan (with a hood)

1109200

HR cell bypass damper assembly

21. Post-heating resistor 900W

2. Fan

935530

R model

3475900

R model

942211

Wall mounting plate (optional)

3482100

L model

3475901

L model

942210

4. Siphon Vallox Silent Klick 3494701 13. Damper motor

930620 22. Door

3476000

5. Coarse filter for supply air 978046 14. Extract air outlet

985035 23. Door latch

3355900

6. Fine filter for supply air

978158

Internal humidity and carbon dioxide sensor

4107982

NTC sensor kit

3482300

7. Lower support for HR cell 3469000 16. Motherboard

949032-1 25.

Glass tube fuse 63mA slow 5x20mm

952490

HR cell (aluminium) HR cell (enthalpy)

933270 933154

17. Safety switch

948377

MyVallox Control panel MyVallox Touch control panel

949033 949090

9. Upper support for HR cell 3468900 18. Connection box

3526700 27.

MyVallox humidity sensor (optional)

946149

10. Filter stand

3466500 19. RJ45 extension cable 952196

MyVallox carbon dioxide sensor (optional)

949111

Coarse filter for extract air

978047

Additional heating resistor 1500W

942220 29. MyVallox VOC sensor (optional) 949112

Ceiling bushing for electric wires 950445

Ceiling feed-through seal

950446

30

CONFORMITY CERTIFICATES

D5326/10.05.2023FIN/15.05.2023ENG/PDF

www.vallox.com Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals