Carrier 50ZHK-01SI Package RTU Heat Pump Instruction Manual
- June 13, 2024
- Carrier
Table of Contents
50ZHK
Single-Packaged Heat Pump System
With Puron® (R-410A) Refrigerant
Single Phase
2 to 5 Nominal Tons (Sizes 024-060)
Installation Instructions
50ZHK-01SI Package RTU Heat Pump
IMPORTANT: Effective January 1, 2015, all split system and packaged air
conditioners must be installed pursuant to applicable regional efficiency
standards issued by the Department of Energy.
NOTE: Read the entire instruction manual before starting the
installation.
NOTE: Installer: Make sure the Owner’s Manual and Service Instructions
are left with the unit after installation.Certified to leak 2% or less of
nominal air conditioning CFM delivered when pressurized to 1-in. W.C. with all
present air inlets, air outlets, and condensate drain port(s) sealed.
Safety Considerations
Installation and servicing of this equipment can be hazardous due to
mechanical and electrical components. Only trained and qualified personnel
should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning
and replacing air filters. All other operations must be performed by trained
service personnel. When working on this equipment, observe precautions in the
literature, on tags, and on labels attached to or shipped with the unit and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses, protective clothing, and work
gloves. Use quenching cloth for brazing operations. Have fire extinguisher
available. Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult local
building codes, the current editions of the National Electrical Code (NEC)
NFPA 70 and NFPA 90B-Installation Warm Air Heating and A/C Systems
(Residential). In Canada refer to the current editions of the Canadian
Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol **. When you
see this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury. Understand these signal words: DANGER, WARNING,
and CAUTION. These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices which may result
in minor personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation, reliability,
or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system
and install lockout tag. There may be more than one disconnect switch. Turn
off accessory heater power switch if applicable.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate
protective clothing, safety glasses and gloves when handling parts and
servicing.
WARNING**
PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to relieve system pressure
could result in personal injury and/or death.
- Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves.
- Federal regulations require that you do not vent refrigerant into the atmosphere. Recover during system repair or final unit disposal.
WARNING
PERSONAL INJURY AND PROPERTY DAMAGE HAZARD
For continued performance, reliability, and safety, the only approved
accessories and replacement parts are those specified by the equipment
manufacturer. The use of non-manufacturer approved parts and accessories could
invalidate the equipment limited warranty and result in fire risk, equipment
malfunction, and failure. Please review manufacturer’s instructions and
replacement part catalogs available from your equipment supplier.
Introduction
This packaged heat pump is fully self-contained and designed for outdoor installation (See Fig. 2). Standard units are shipped in a horizontal- discharge configuration for installation on a ground-level slab or directly on the ground if local codes permit. Standard units can be converted to downflow (vertical) discharge configurations for rooftop applications with a field supplied plenum.
Receiving and Installation
Step 1 – Check Equipment
Identify Unit
The unit model number and serial number are printed on the unit informative
plate. Check this information against shipping papers.
Inspect Shipment
Inspect for shipping damage while unit is still on shipping pallet. If unit
appears to be damaged or is torn loose from its anchorage, have it examined by
transportation inspectors before removal. Forward claim papers directly to
transportation company. Manufacturer is not responsible for any damage
incurred in transit. Check all items against shipping list. Immediately notify
the nearest equipment distribution office if any item is missing. To prevent
loss or damage, leave all parts in original packages until installation.
Step 2 – Provide Unit Support
For hurricane tie downs, contact distributor for details and PE (Professional
Engineering) Certificate, if required.
Slab Mount
Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102
mm) thick with 2 in. (51 mm) above grade. The slab should extend approximately
2 in. (51 mm) beyond the casing on all 4 sides of the unit. Do not secure the
unit to the slab except when required by local codes. A 6-in. (152 mm) wide
gravel apron should be used around the flat surface to prevent airflow
blockage by grass or shrubs. The unit should be level within 1/4 in. (6 mm).
This is necessary for the unit drain to function properly.
Ground Mount
The unit may be installed either on a slab or placed directly on the ground if
local codes permit. Place the unit on level ground prepared with gravel for
condensate discharge.
Step 3 – Provide Clearances
The required minimum service clearances are shown in Fig. 5 – Fig. 6. Adequate
ventilation and outdoor air must be provided.
The outdoor fan draws air through the outdoor coil and discharges it through
the top fan grille. Be sure that the fan discharge does not recirculate to the
outdoor coil. Do not locate the unit in either a corner or under an overhead
obstruction. The minimum clearance under a partial overhang (such as a normal
house overhang) is 48 in. (1219 mm) above the unit top. The maximum horizontal
extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the
outdoor-air inlet or the fan discharge may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will
damage or flood the unit. Do not install the unit on carpeting or other
combustible materials. Slab-mounted units should be at least 4 in. (102 mm)
above the highest expected water and runoff levels. Do not use unit if it has
been under water.
Step 4 – Place Unit
Unit can be moved with the rigging holds provided in the unit base. Refer to
Table 1 for operating weights. Use extreme caution to prevent damage when
moving the unit. Unit must remain in an upright position during all moving
operations. The unit must be level with in 1/4 in. (6 mm) for proper
condensate drainage; the ground-level pad must be level before setting the
unit in place. When a field-fabricated support is used, be sure that the
support is level and that it properly supports the unit.
Step 5 – Select and Install Ductwork
The design and installation of the duct system must be in accordance with the
standards of the NFPA for installation of non-residence type air conditioning
and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local
codes and ordinances.
Select and size ductwork, supply-air registers, and return air grilles
according to ASHRAE (American Society of Heating, Refrigeration, and Air
Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply- and return-air openings on the
side of the unit. See Fig. 5 – Fig. 6 for connection sizes and locations. The
14-in. (356 mm) round or 14 x 20 in. (356 x 508 mm) rectangular duct collars
are shipped inside the unit attached to the base pan in the indoor blower
compartment. They are field-installed and must be removed from the indoor
blower compartment prior to start-up, even if they are not used for
installation. If a corrugated shipping block is used under the blower housing,
remove and discard the block and label.
When designing and installing ductwork, consider the following:
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components. When
connecting ductwork to units, do not drill deeper than 3/4 in. (19 mm) in
shaded area shown in Fig. 3 or coil may be damaged.
-
All units should have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1.
-
Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24-in. (610 mm) from electric heater element. -
Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
-
Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
-
Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof according to good construction practices.
Fig. 7 shows a typical duct system with unit installed.
Installing factory-supplied duct flanges;
For 24, 30, and 36 sizes:
- Two round 14-in. (356 mm) duct collars are factory supplied.
- Line up the 6 holes in the duct collar with the pre-drilled holes in the side panel.
- Fasten duct collar to side panel using field-supplied screws. For 42, 48 and 60 sizes (See Fig. 4):
- One round 14-in. (356 mm) duct collar for the supply air connections and two “L” brackets for the 14-in. x 20-in. (356 x 508 mm) return air connection are factory-supplied.
- Line up the 6 holes in the supply duct collar with the pre-drilled holes in the side panel. Fasten duct collar to side panel using field-supplied screws.
- For the return, remove the 4 screws on the left side of the return and install one of the “L” flanges on the left side by replacing the 4 screws. Using the 2 dimples below the return, align the bottom of the “L” flange with the two dimples and attach using filed-supplied thread-cutting screws.
For the second “L” flange, align flange with the three dimples to the right of the return and the two dimples above the return and attach using field- supplied thread-cutting screws.
NOTE: The factory-installed screws to the right of the return should not be removed in this process.
* Table 1 – Physical Data
UNIT SIZE | 024 | 030 | 036 | 042 | 048 | 060 |
---|---|---|---|---|---|---|
NOMINAL CAPACITY (ton) | 2 | 2.5 | 3 | 3.5 | 4 | 5 |
SHIPPING WEIGHT (lb)
(kg)| 312
142| 333
151| 334
152| 388
177| 407
185| 475
215
COMPRESSOR TYPE| SCROLL
REFRIGERANT| R-410A
REFRIGERANT QUANTITIY (lb)
QUANTITY (kg)| 6.3
2.9| 9.8
3.1| 6.8
3.1| 7.7
3.5| 9.0
4.1| 12.0
5.4
OUTDOOR METERING DEVICE| TXV| Piston| TXV| Piston
ORIFICE ID (in.)
(mm)| –
–| 0.055
1.397| 0.057
1.448| 0.059
1.499| –
–| 0.070
1.778
OUTDOOR COIL
ROWS…FINS/in. FACE AREA (sq. ft)| 1…20
9.1| 1…20
9.1| 2…20
9.1| 2…20
10.2| 2…20
13.0| 2…20
15.5
OUTDOOR FAN
NOMINAL AIRFLOW (CFM) DIAMETER (in.) DIAMETER (mm)
MOTOR HP (RPM)| 2000
20
508
1/8 (825)| 2000
20
508
1/8 (825)| 2800
20
508
1/4 (1100)| 3100
20
508
1/4 (1100)| 3100
20
508
1/4 (1100)| 3300
20
508
1/3 (1100)
INDOOR METERING DEVICE| Piston| TXV| TXV
ORIFICE ID (in.) (mm)| 0.057
1.448| 0.063
1.600| 0.067
1.702| 0.076
1.930| –
–| –
–
INDOOR COIL
ROWS…FINS/in. FACE AREA (sq. ft)| 2…12
4.3| 3…15
4.3| 3…15
4.3| 3…15
4.9| 3…15
4.9| 3…15
6.1
INDOOR BLOWER
NOMINAL COOLING AIRFLOW (CFM) NOMINAL SIZE D x L (in.) (mm)
MOTOR (HP)| 800
8 x 11
254 x 203
1/3| 1000
8 x 11
254 x 203
1/2| 1200
9 x 12
279 x 229
1/2| 1400
9 x 12
279 x 229
1/2| 1600
11 x 12
279 x 229
3/4| 1850
11 x 12
267 x 305
1
HIGH-PRESSURE SWITCH (psig)
CUTOUT RESET (AUTO)| 650 +/- 15
420 +/- 25
LOW-PRESSURE SWITCH (psig)
CUTOUT RESET (AUTO)| 20 +/- 5
45 +/- 10
RETURN-AIR FILTERS* THROWAWAY (in.)
(mm)| 20x20x1
508x508x25| 20x24x1
508x610x25| 24x30x1
610x762x
25| 24x36x1
610x914x25
*. Required filter sizes shown are based on the AHRI (Air Conditioning, Heating & Refrigeration Institute) rated airflow at a velocity of 300 ft/min (91 m) for throwaway type or 450 ft/min (137 m) for high capacity type. Recommended filters are 1-in. (25 mm) thick.
Table 2 – Minimum Airflow for Safe Electric Heater Operation
HP Unit Size | Minimum Airflow (CFM) |
---|---|
5 kW | 7.5 kW |
24 | 750 |
30 | 750 |
36 | 750 |
42 | 750 |
48 | 750 |
60 | 750 |
X = Not Approved Combination
Configuring Units for Downflow (Vertical) Discharge
Units are dedicated side supply products. They are not convertible to vertical
air supply. A field-supplied plenum must be used to convert to vertical air
discharge.
Step 6 – Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to comply with
local codes and restrictions.
Unit removes condensate through a 1-3/64 in. (27 mm) ID hole (using 3/4-in.
(19 mm) ID piping or tubing) which is located at the end of the unit. See Fig.
5 – Fig. 6 for location of condensate connection.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground level
installations. Install a field-supplied condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of the trap is
at least 1 in. (25 mm) lower than the drain pan condensate connection to
prevent the pan from overflowing (See Fig. 8 and Fig. 9). When using a gravel
apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit,
install a 2-in. (51 mm) trap using a 3/4-in. (19 mm) ID tubing or pipe. (See
Fig. 8 and Fig. 9.) Make sure that the outlet of the trap is at least 1 in.
(25 mm) lower than the unit drain-pan condensate connection to prevent the pan
from overflowing. Prime the trap with water. Connect a drain tube using a
minimum of 3/4-in. (19 mm) PVC, 3/4-in. (19 mm) CPVC, or 3/4-in. copper pipe
(all field supplied). Do not undersize the tube. Pitch the drain tube downward
at a slope of at least 1 in. (25 mm) for every 10 ft (3 m) of horizontal run.
Be sure to check the drain tube for leaks. Prime trap at the beginning of the
cooling season start-up. Allowable glues for condensate trap connection are:
Standard ABS, CPVC, or PVC cement.Step 7 – Install Electrical Connections
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. The
unit cabinet must have an uninterrupted, unbroken electrical ground to
minimize the possibility of personal injury if an electrical fault should
occur. This ground may consist of an electrical wire connected to the unit
ground screw in the control compartment, or conduit approved for electrical
ground when installed in accordance with NEC, ANSI/NFPA 70 American National
Standards Institute/ National Fire Protection Association (latest edition) (in
Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
CAUTION
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being
installed.
- Make all electrical connections in accordance with NEC ANSI/NFPA 70 (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
- Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
- Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.
- Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
- Route field power supply(s) away from areas that could be damaged by lawn and garden equipment or other accidental damage.
High-Voltage Connections
The unit must have a separate electrical service with a field-supplied,
waterproof disconnect switch mounted at, or within sight from the unit. Refer
to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker
size and minimum circuit amps (ampacity) for wire sizing.
The field-supplied disconnect may be mounted on the unit over the high-voltage
inlet hole when the standard power and low-voltage entry points are used. See
Fig. 10 and Fig. 11 for acceptable location.
Operation of unit on improper line voltage constitutes abuse and may cause
unit damage that could affect warranty.
Routing Power Leads into Unit
Use only copper wire between disconnect and unit. The high-voltage leads
should be in a conduit until they enter the unit; conduit termination at the
unit must be watertight. Run the high-voltage leads through the hole on the
control box side of the unit (See Fig. 10). When the leads are inside the
unit, run leads to the control box (See Fig. 11). Connect leads to the black
and yellow wires (See Fig. 12). Connecting Ground Lead to Unit Ground
Connect the ground lead to the chassis using the unit ground in the control
box (See Fig. 11 and Fig. 12).
Routing Control Power Wires (24-V)
Form a drip-loop with the thermostat leads before routing them into the unit.
Route the thermostat leads through grommeted hole provided in unit into unit
control box (See Fig. 10). Connect thermostat leads and unit power leads as
shown in Fig. 12 – Fig. 15.
The unit transformer supplies 24-v power for complete system including
accessory electrical heater. Transformer is factory wired for 230-v operation.
Unit main harness contains a 3 amp automotive style replaceable fuse. If
transformer secondary voltage is not available at red and brown leads in unit
low voltage box, check fuse in red lead near transformer. Replace with
Littelfuse brand, part number 257003.
Unit main harness also contains a 1k ohm, 3 watt load resistor wired across
low voltage leads “G” and “C”. Purpose of resistor is to provide a small
electrical load for the indoor thermostat fan circuit to ensure reliable
operation.
Accessory Electric Heat Wiring
Refer to accessory electric heat installation instructions for information on
installing accessory electric heat. Accessory electric heat wiring is shown in
Fig. 14 – Fig. 16.
NOTE: When installing an accessory electric heater, the high voltage wire
harness pass-through must be sealed with silicone or equivalent at the
partition in order to comply with the 2% or less air leakage certification.
Pre-Start-up
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or
property damage.
- Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
- Relieve and recover all refrigerant from system before touching or disturbing compressor plug if refrigerant leak is suspected around compressor terminals.
- Never attempt to repair soldered connection while refrigerant system is under pressure.
- Do not use torch to remove any component. System contains oil and refrigerant under pressure.
- To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power to unit and install lockout tag.
b. Relieve and reclaim all refrigerant from system using both high- and low- pressure ports.
c. Cut component connecting tubing with tubing cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to inspect and prepare the unit for initial start-up:
-
Remove all access panels.
-
Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with unit.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to relieve system pressure could result in personal injury and/or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerant. Keep torches and other ignition sources away from refrigerants and oils. -
Make the following inspections:
a. Inspect for shipping and handling damages, such as broken lines, loose parts, disconnected wires, etc.
b. Inspect all field- and factory-wiring connections. Be sure that connections are completed and tight.
c. Ensure wires do not touch refrigerant tubing or sharp sheet metal edges.
d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb. -
Verify the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned in fan orifice. See Outdoor Fan Adjustment section.
b. Make sure that air filter is in place.
c. Make sure that condensate drain pan and trap are filled with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts have been removed.
Start-up
Step 1 – Check for Refrigerant Leaks
Proceed as follows to locate and repair a refrigerant leak and to charge the
unit:
-
Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high- and low-pressure ports.
-
Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for repair. -
Add a small charge of Puron (R-410A) refrigerant vapor to system and leak-test unit.
-
Recover refrigerant from system and evacuate to 500 microns if no additional leaks are found.
-
Charge unit with Puron (R-410A) refrigerant, using an accurate scale. Refer to unit rating plate for required charge.
Step 2 – Start-Up Cooling and Make Adjustments
Complete the required procedures given in the Pre-Start-Up section before
starting the unit. Do not jumper any safety devices when operating the unit.
Do not operate the unit in cooling mode when the outdoor temperature is below
40°F (4.4°C) (unless accessory low-ambient kit is installed). Do not rapid
cycle the compressor. Allow 5 min. between “on” cycles to prevent compressor
damage.
Checking Cooling and Heating Control Operation
Start and check the unit for proper cooling control operation as follows:
- Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down within 60 sec. when FAN switch is placed in AUTO position.
- Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set control below room temperature. Observe that compressor, outdoor fan, and indoor blower motors start and that reversing valve shifts. Observe that cooling cycle shuts down when control setting is satisfied. Reversing valve (RV) remains energized.
- Place system switch in HEAT position. Observe that compressor, indoor fan and outdoor fan energize (Reversing Valve is deenergized in heat pump heating mode). Set control above room temperature. Observe that heating cycle shuts down when control setting is satisfied.
- When using an automatic changeover room thermostat, place both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to call for Cooling (below room temperature), and unit operates in Heating mode when temperature control is set to call for Heating (above room temperature).
Step 3 – Refrigerant Charge
Refrigerant Charge — The refrigerant system is fully charged with Puron
(R-410A) refrigerant and is tested and factory sealed. Amount of refrigerant
charge is listed on unit nameplate and in Table 1. Unit must operate a minimum
of 15 minutes before checking charge.
NOTE: Adjustment of the refrigerant charge is not required unless the
unit is suspected of not having the proper Puron (R-410A) charge.
NOTE: Unit sizes 024-042 have fixed orifice refrigerant metering devices.
There is a different charging procedure for both expansion devices. Refer to
the correct procedure for your unit.
No Charge
Use standard evacuating techniques. After evacuating system, weigh in the
specified amount of refrigerant (refer to Table 1).
Low Charge Cooling
024-042 Units, Fixed Indoor Metering Device:
- Operate unit a minimum of 10 minutes before checking charge.
- Measure suction pressure by attaching an accurate gauge to compressor suction side service port.
- Measure suction side temperature by attaching an accurate thermisitor type or electronic thermometer to suction line about 10 in. from compressor.
- Measure outdoor air dry-bulb temperature with thermometer.
- Measure indoor air (return air) wet-bulb temperature with a sling psychrometer or electronic equivalent.
- Using Superheat Charging Table (Table 3) find outdoor temperature and indoor air wet-bulb temperature. At this intersection note superheat. Where a dash (–) appears on table do not attempt to charge unit under these conditions or refrigerant slugging may occur. In this situation refrigerant must be evacuated and weighed in. See rating plate for charge quantity.
- Refer to Required Suction Tube Temp. Table (Table 3). Find superheat temperature located in Step 6 and suction pressure. At this intersection note suction line temperature.
- If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
- If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature is reached.
- If outdoor air temperature or pressure at suction port changes, charge to new suction line temperature indicated on chart.
048-060 Units, Indoor TXV
- Measure Discharge line pressure by attaching a gauge to the service port.
- Measure the Liquid line temperature by attaching a temperature sensing device to it.
- Insulate the temperature sensing device so that the Outdoor Ambient doesn’t affect the reading.
- Refer to the required Subcooling in Table 4 based on the model size and the Outdoor Ambient temperature.
- Interpolate if the Outdoor ambient temperature lies in between the table values.
- Find the Pressure Value in the table corresponding to the measured Pressure of the Compressor Discharge line.
- Read across from the Pressure reading to obtain the Liquid line temperature for a required Subcooling.
- Add Charge if the measured temperature is higher than the table value.
- Remove charge if the measured temperature is lower than the table value.
Heating Mode Charge
Do not attempt to adjust charge by cooling methods while in heat pump heating
mode. Recover refrigerant and weigh in according to unit data plate
refrigerant data.
Table 3 – Superheat Charging A12098
COOLING ONLY CHARGING PROCEDURE
- Operate unit a minimum of 10 minutes before checking charge.
- Measure suction pressure by attaching an accurate gauge to compressor suction side service port.
- Measure suction side temperature by attaching an accurate thermisitor type or electronic thermometer to suction line about 10 inches from compressor.
- Measure outdoor air dry-bulb temperature with thermometer.
- Measure indoor air (return air) wet-bulb temperature with a sling psychrometer or electronic equivalent.
- Using Superheat Charging Table find outdoor temperature and indoor air wet-bulb temperature. At this intersection note superheat. Where a dash (–) appears on table do not attempt to charge unit under these conditions or refrigerant slugging may occur. In this situation refrigerant must be evacuated and weighed in. See rating plate for charge quantity.
- Refer to Required Suction Tube Temp. table. Find superheat temperature located in step 6 and suction pressure. At this intersection note suction line temperature.
- If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
- If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature is reached.
- If outdoor air temperature or pressure at suction port changes, charge to new suction line temperature indicated on chart.
Table 4 – Required Subcooling
Required Subcooling °F(°C)
Model Size| Outdoor Ambient Temperature °F(°C)
75 (24)| 85 (29)| 95 (35)| 105 (41)| 115 (46)
| | | | |
24| 0 (0)| 0 (0)| 0 (0)| 0 (0)| 0 (0)
30| 0 (0)| 0 (0)| 0 (0)| 0 (0)| 0 (0)
36| 0 (0)| 0 (0)| 0 (0)| 0 (0)| 0 (0)
42| 0 (0)| 0 (0)| 0 (0)| 0 (0)| 0 (0)
48| 14 (7.5)| 13 (7.3)| 13 (7.2)| 12 (6.9)| 12 (6.7)
60| 13 (6.9)| 12 (6.8)| 12 (6.6)| 11 (6.3)| 11 (6.1)
Charging Procedure
- Measure Discharge line pressure by attaching a gauge to the service port.
- Measure the Liquid line temperature by attaching a temperature sensing device to it.
- Insulate the temperature sensing device so that the Outdoor Ambient doesn’t affect the reading.
- Refer to the required Subcooling in the table based on the model size and the Outdoor Ambient temperature.
- Interpolate if the Outdoor ambient temperature lies in between the table values.
- Find the Pressure Value in the table corresponding to the the measured Pressure of the Compressor Discharge line.
- Read across from the Pressure reading to obtain the Liquid line temperature for a required Subcooling
- Add Charge if the measured temperature is higher than the table value.
- Remove charge if the measured temperature is lower than the table value.
Required Liquid Line Temperature for a Specific Subcooling (R-410A)
Pressure| Required Subcooling (°F)| | Pressure| Required
Subcooling (°C)
| | | | | | | | |
(psig)| 5| 10| 15| 20| 25| (kPa)| 3| 6| 8| 11| 14
189| 61| 56| 51| 46| 41| 1303| 16| 13| 11| 8| 5
196| 63| 58| 53| 48| 43| 1351| 17| 15| 12| 9| 6
203| 66| 61| 56| 51| 46| 1399| 19| 16| 13| 10| 8
210| 68| 63| 58| 53| 48| 1448| 20| 17| 14| 11| 9
217| 70| 65| 60| 55| 50| 1496| 21| 18| 15| 13| 10
224| 72| 67| 62| 57| 52| 1544| 22| 19| 16| 14| 11
231| 74| 69| 64| 59| 54| 1593| 23| 20| 18| 15| 12
238| 76| 71| 66| 61| 56| 1641| 24| 21| 19| 16| 13
245| 77| 72| 67| 62| 57| 1689| 25| 22| 20| 17| 14
252| 79| 74| 69| 64| 59| 1737| 26| 23| 21| 18| 15
260| 81| 76| 71| 66| 61| 1792| 27| 25| 22| 19| 16
268| 83| 78| 73| 68| 63| 1848| 29| 26| 23| 20| 17
276| 85| 80| 75| 70| 65| 1903| 30| 27| 24| 21| 19
284| 87| 82| 77| 72| 67| 1958| 31| 28| 25| 22| 20
292| 89| 84| 79| 74| 69| 2013| 32| 29| 26| 23| 21
300| 91| 86| 81| 76| 71| 2068| 33| 30| 27| 24| 22
309| 93| 88| 83| 78| 73| 2130| 34| 31| 28| 26| 23
318| 95| 90| 85| 80| 75| 2192| 35| 32| 29| 27| 24
327| 97| 92| 87| 82| 77| 2254| 36| 33| 31| 28| 25
336| 99| 94| 89| 84| 79| 2316| 37| 34| 32| 29| 26
345| 101| 96| 91| 86| 81| 2378| 38| 35| 33| 30| 27
354| 103| 98| 93| 88| 83| 2440| 39| 36| 34| 31| 28
364| 105| 100| 95| 90| 85| 2509| 40| 38| 35| 32| 29
374| 107| 102| 97| 92| 87| 2578| 41| 39| 36| 33| 30
384| 108| 103| 98| 93| 88| 2647| 42| 40| 37| 34| 31
394| 110| 105| 100| 95| 90| 2716| 44| 41| 38| 35| 32
404| 112| 107| 102| 97| 92| 2785| 45| 42| 39| 36| 33
414| 114| 109| 104| 99| 94| 2854| 46| 43| 40| 37| 34
424| 116| 111| 106| 101| 96| 2923| 47| 44| 41| 38| 35
434| 118| 113| 108| 103| 98| 2992| 48| 45| 42| 39| 36
444| 119| 114| 109| 104| 99| 3061| 48| 46| 43| 40| 37
454| 121| 116| 111| 106| 101| 3130| 49| 47| 44| 41| 38
464| 123| 118| 113| 108| 103| 3199| 50| 48| 45| 42| 39
474| 124| 119| 114| 109| 104| 3268| 51| 48| 46| 43| 40
484| 126| 121| 116| 111| 106| 3337| 52| 49| 47| 44| 41
494| 127| 122| 117| 112| 107| 3406| 53| 50| 47| 45| 42
504| 129| 124| 119| 114| 109| 3475| 54| 51| 48| 46| 43
514| 131| 126| 121| 116| 111| 3544| 55| 52| 49| 46| 44
524| 132| 127| 122| 117| 112| 3612| 56| 53| 50| 47| 45
534| 134| 129| 124| 119| 114| 3681| 56| 54| 51| 48| 45
A220232
50VL500323 REV 2.0
Step 4 – Indoor Airflow and Airflow Adjustments
WARNING
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
For cooling operation, the recommended airflow is 350 to 450 cfm for each
12,000 Btuh of rated cooling capacity.
Table 5 shows wet coil air delivery for horizontal discharge units.
NOTE: Be sure that all supply- and return-air grilles are open, free from
obstructions, and adjusted properly.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before
changing blower speed.
Blower speed tap can be changed by replacing the factory installed blue low
speed tap wire (cooling) with the unused black high speed wire in unit control
box. The red medium speed wire is factory installed to operate with a call for
supplemental electric heat. See unit wiring diagram.
Be sure new airflow meets the range noted above and minimum electric heat CFM,
if equipped. Refer to Table 2 and Table 5.
All model sizes are factory wired or rated airflow operation.
Step 5 – Sequence of Operation
Fan Operation
The FAN switch on the thermostat controls indoor fan operation. When the FAN
switch is placed in the ON position, the indoor (evaporator) fan motor (IFM)
is energized through the G terminal on the thermostat. The motor’s internal
logic then provides power to the indoor (evaporator) fan motor (IFM). The IFM
will run continuously when the FAN switch is set to ON.
When the FAN switch is set to AUTO, the thermostat deenergizes the IFM
(provided there is not a call for cooling). The contacts open and the IFM is
deenergized. The IFM will be energized only when there is a call for cooling,
in heat pump heating mode or if the unit is equipped with accessory electric
heat, the indoor-fan motor will also run while the accessory electric heat is
energized.
NOTE: Motors on this product are programmed for 60 second time delay on
tap 1 and 30 second time delay on tap 2. There is no time delay on tap 3. The
indoor fan will remain ON for the set time delay after G or W2 is de-
energized.
Cooling Operation
With a call for cooling (Y), the compressor, outdoor fan, and indoor fan start
immediately. When the cooling demand is met, Y de-energizes, shutting the
compressor, indoor fan and the outdoor fan.
Heating Operation
With a call for heating (Y), the compressor, outdoor fan, and indoor fan start
immediately. If Y cannot satisfy the heating demand, the auxiliary or backup
heat (W2) energizes. In case of staged heating, W3 is energized if the demand
is not met. When heating demand is met, W3, W2 and Y sequentially de-energize
shutting the compressor, indoor fan and the outdoor fan.
Continuous Fan
With the continuous indoor fan option selected on the thermostat, G is
continuously energized. The continuous fan speed will be the same as the
cooling fan speed.
Demand Defrost Mode
The defrost mode is factory set to an initial 60-minute time interval. It may
also be adjusted to an initial interval of 30, 90, or 120 minutes. During
operation, the control optimizes current defrost time based on the previous
defrost interval and previous defrost period. If the previous defrost period
is less than 2 minutes for two consecutive defrost cycles the control will
lengthen the defrost interval by 15 minutes, up to a maximum of 120 minutes or
30 minutes greater than the original setpoint, whichever comes first. If the
previous defrost period is more than 5 minutes for two consecutive defrost
cycles the control will shorten the defrost interval by 15 minutes, down to a
minimum of 30 minutes or 30 minutes from the original setpoint, whichever is
first.
After the defrost condition is satisfied, or after a maximum of 10 minutes in
defrost mode, the unit will resume normal heating operation.
ELECTRIC RESISTANCE HEATING
If accessory electric heaters are installed, on a call for “Emergency Heat”
the thermostat energizes W which energizes the heater relay and in turn
energizes the electric heaters. The IFM is energized which starts the indoor-
fan motor. If the heaters are staged, W2 is energized when the second stage of
heating is required. When the need for heating is satisfied, the heater and
IFM are de-energized. **Table 5 – Wet Coil Air Delivery ***
UNIT SIZE| SPEED TAP| TAP COLOR| AIR DELIVERY †|
EXTERNAL STATIC PRESSURE (in. W.C.)
---|---|---|---|---
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7|
0.8| 0.9| 1
24| 1| BLU| SCFM| 905| 695| 635| 580| 515| 445| 385| 345| 310| 275
2| PNK| SCFM| 920| 830| 770| 740| 690| 640| 565| 505| 455| 400
3| RED‡| SCFM| 1015| 990| 935| 890| 845| 800| 760| 720| 665| 635
4| ORN| SCFM| 1060| 1030| 975| 930| 890| 845| 805| 760| 705| 670
5| BLK| SCFM| 1165| 1130| 1085| 1045| 1005| 965| 925| 890| 850| 810
30| 1| BLU| SCFM| 995| 875| 935| 775| 690| 945| 575| 520| 480| 385
2| PNK| SCFM| 1055| 1005| 960| 915| 855| 775| 735| 685| 655| 610
3| RED‡| SCFM| 1210| 1175| 1135| 1085| 1045| 1005| 925| 880| 840| 780
4| ORN| SCFM| 1225| 1180| 1135| 1095| 1055| 1010| 955| 880| 845| 815
5| BLK| SCFM| 1355| 1335| 1295| 1255| 1215| 1180| 1140| 1100| 1045| 990
36| 1| BLU| SCFM| 1195| 1165| 1120| 1075| 1020| 975| 930| 865| 820| 765
2| PNK| SCFM| 1250| 1210| 1165| 1115| 1070| 1025| 950| 910| 870| 820
3| RED‡| SCFM| 1410| 1370| 1330| 1290| 1245| 1205| 1165| 1120| 1080| 1020
4| ORN| SCFM| 1430| 1380| 1340| 1295| 1255| 1220| 1175| 1135| 1080| 1000
5| BLK| SCFM| 1535| 1495| 1455| 1415| 1375| 1335| 1300| 1260| 1220| 1155
42| 1| BLU| SCFM| 1400| 1360| 1305| 1250| 1200| 1140| 1085| 1035| 985| 885
2| PNK| SCFM| 1455| 1415| 1365| 1315| 1260| 1200| 1155| 1115| 1070| 1020
3| RED| SCFM| 1480| 1425| 1370| 1320| 1265| 1215| 1160| 1105| 1055| 1030
4| ORN| SCFM| 1535| 1505| 1460| 1410| 1360| 1305| 1255| 1210| 1175| 1130
5| BLK‡| SCFM| 1645| 1600| 1555| 1500| 1455| 1410| 1365| 1315| 1255| 1215
48
| 1| BLU| SCFM| 1580| 1545| 1515| 1480| 1440| 1400| 1360| 1345| 1285| 1250
2| PNK| SCFM| 1645| 1610| 1570| 1535| 1500| 1460| 1420| 1380| 1345| 1315
3| RED‡| SCFM| 1750| 1725| 1690| 1655| 1620| 1585| 1550| 1510| 1475| 1440
4| ORN| SCFM| 1780| 1755| 1720| 1690| 1655| 1625| 1590| 1555| 1515| 1480
5| BLK| SCFM| 1905| 1875| 1845| 1815| 1780| 1755| 1720| 1685| 1655| 1625
60| 1| BLU| SCFM| 1705| 1675| 1635| 1600| 1555| 1515| 1470| 1420| 1370| 1320
2| PNK| SCFM| 1755| 1720| 1685| 1645| 1605| 1565| 1525| 1475| 1430| 1380
3| RED‡| SCFM| 1880| 1850| 1815| 1775| 1745| 1705| 1665| 1625| 1590| 1545
4| ORN| SCFM| 1900| 1875| 1840| 1800| 1765| 1730| 1695| 1655| 1620| 1575
5| BLK| SCFM| 2010| 1985| 1950| 1915| 1885| 1850| 1815| 1780| 1745| 1705
*. Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static pressure available for ducting.
†. Standard Cubic Feet per Minute
‡. Factory-shipped cooling speed.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 CFM for
each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur
at airflows below this point.
Table 6 – Filter Pressure Drop (IN. W.C.) Table 7 – Accessory
Electric Heat Pressure Drop (IN. W.C.)
HEATER kW|
---|---
800| 1000| 1200| 1400| 1600| 1800| 2000|
2200
5-20| 0.033| 0.037| 0.042| 0.047| 0.052| 0.060| 0.067| 0.075
Maintenance
To ensure continuing high performance, and to minimize the possibility of
premature equipment failure, periodic maintenance must be performed on this
equipment. This cooling unit should be inspected at least once each year by a
qualified service person. To troubleshoot unit, refer to Table 9,
Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a
maintenance contract.
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and
possible unit component damage.
The ability to properly perform maintenance on this equipment requires certain
expertise, mechanical skills, tools and equipment. If you do not possess
these, do not attempt to perform any maintenance on this equipment, other than
those procedures recommended in the Owner’s Manual.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
- Turn off electrical power to the unit and install lockout tag before performing any maintenance or service on this unit.
- Use extreme caution when removing panels and parts.
- Never place anything combustible either on or in contact with the unit.
WARNING
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Errors made when reconnecting wires may cause improper and dangerous
operation. Label all wires prior to disconnecting when servicing.
The minimum maintenance requirements for this equipment are as follows:
- Inspect air filter(s) each month. Clean or replace when necessary.
- Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
- Inspect blower motor and wheel for cleanliness each cooling season. Clean when necessary.
- Check electrical connections for tightness and controls for proper operation each cooling season. Service when necessary.
- Ensure electric wires are not in contact with refrigerant tubing or sharp metal edges.
Air Filter
IMPORTANT: Never operate the unit without a suitable air filter in the
return-air duct system. Always replace the filter with the same dimensional
size and type as originally installed. See Table 1 for recommended filter
sizes.
Inspect air filter(s) at least once each month and replace (throwaway-type) or
clean (cleanable-type) at least twice during each cooling season and twice
during the heating season if electric heat is installed, or whenever the
filter becomes clogged with dust and lint.
Unit Top Removal
NOTE: When performing maintenance or service procedures that require
removal of the unit top, be sure to perform all of the routine maintenance
procedures that require top removal, including coil inspection and cleaning,
and condensate drain pan inspection and cleaning.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power, and install lockout tag to the unit before
removing top.
Only qualified service personnel should perform maintenance and service
procedures that require unit top removal. Refer to the following top removal
procedures:
- Unplug all three wires from the outdoor fan motor.
- Remove screws on unit top cover flange. (Save all screws.)
- Lift top from unit carefully. Set top on edge and make sure that top is supported by unit side that is opposite duct (or plenum) side.
- Carefully replace and secure unit top to unit, using screws removed in Steps 1 and 2, when maintenance and/or service procedures are completed.
Indoor Blower and Motor
NOTE: All motors are pre-lubricated. Do not attempt to lubricate these
motors.
For longer life, operating economy, and continuing efficiency, clean
accumulated dirt and grease from the blower wheel and motor annually.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power, and install lockout tag to the unit before
cleaning and lubricating the blower motor and wheel.
To clean the blower wheel:
-
Remove the blower housing:
a. Remove the screws on the external side of the duct panel that fasten the housing to the duct panel assembly.
b. Remove the side access panel and unscrew the mounting bracket that fastens the blower housing to the internal partition panel of the control box assembly.
c. Make sure that the blower housing is supported by hand before completely removing the mounting bracket.
d. Slide the blower housing from the rails of the duct panel and place it outside the unit. -
Remove the blower wheel from the housing:
a. Loosen the set screw which secures the wheel to the motor shaft.
b. Loosen the three mounting legs of the motor by removing the bolts that fasten the mounting legs to the housing.
c. Slide out the motor assembly (motor, belly band and the 3 mounting legs) from the hub of the wheel.
d. Remove the filler panel at the discharge end of the blower housing by removing the two screws that fasten it to the housing.
e. Ensure proper reassembly by marking wheel orientation. Remove the wheel from the housing. -
Remove the caked on dirt from the wheel and the motor using a brush.
-
Remove lint and dirt accumulations from the wheel and housing with a vacuum cleaner, using a soft brush attachment.
-
Remove grease and oil with a mild solvent.
-
Reassemble
a. Slip the wheel back in the housing with the hub set screw parented in the correct direction.
b. Install the filler panel.
c. Reinsert the motor assembly in the wheel hub and align the mounting legs with the housing mounting hold locations.
d. Tighten the mounting bolts to fasten the motor assembly with the housing.
e. Center the wheel in the housing by sliding it, align the flat end of the shaft with the set screw and tighten the set screw.
f. Slide back the blower housing into the mounting rails in the duct panel and install the mounting bracket back in its position.
g. Install the screws on the external side of the duct panel to fasten duct panel with the housing.
h. Replace the side access panel.
Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain pan at least
once each year.
The coils are easily cleaned when dry; therefore, inspect and clean the coils
either before or after each cooling season. Remove all obstructions, including
weeds and shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the
coils with a vacuum cleaner, using the soft brush attachment. Be careful not
to bend the fins. If coated with oil or grease, clean the coils with a mild
detergent and water solution. Rinse coils with clear water, using a garden
hose. Be careful not to splash water on motors, insulation, wiring, or air
filter(s). For best results, spray condenser coil fins from inside to outside
the unit. On units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils.
Clean the drain pan and condensate drain by removing all foreign matter from
the pan. Flush the pan and drain trough with clear water. Do not splash water
on the insulation, motor, wiring, or air filter(s). If the drain trough is
restricted, clear it with a “plumbers snake” or similar probe device.
Outdoor Fan Adjustment
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components. Keep
the condenser fan free from all obstructions to ensure proper cooling
operation. Never place articles on top of unit.
- Shut off unit power supply and install lockout tag.
- Remove outdoor-fan assembly (grille, motor, motor cover, and fan) by removing screws and flipping assembly onto unit top cover.
- Inspect the fan blades for cracks or bends.
- If fan needs to be removed, loosen the setscrew and slide the fan off the motor shaft.
- When replacing fan blade, position blade as shown in Fig. 17. Tighten setscrews.
Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn
off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring. Check
all electrical connections for tightness. Tighten all screw connections. If
any smoky or burned connections are noticed, disassemble the connection, clean
all the parts, re-strip the wire end and reassemble the connection properly
and securely.
Check to ensure no wires are touching refrigerant tubing or sharp sheet metal
edges. Move and secure wires to isolate from tubing and sheet metal edges.
After inspecting the electrical controls and wiring, replace all the panels.
Start the unit, and observe at least one complete cooling cycle to ensure
proper operation. If discrepancies are observed in operating cycle, or if a
suspected malfunction has occurred, check each electrical component with the
proper electrical instrumentation. Refer to the unit wiring label when making
these checks. (See Fig. 14 and Fig. 15)
Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil
accumulation annually. Detecting oil generally indicates a refrigerant leak.
WARNING
EXPLOSION, SAFETY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This system uses Puron (R-410A) refrigerant which has higher operating
pressures than R-22 and other refrigerant. No other refrigerant may be used in
this system. Gauge set, hoses, and recovery system must be designed to handle
Puron (R-410A). If you are unsure, consult the equipment manufacturer.
If oil is detected or if low cooling performance is suspected, leak test all
refrigerant tubing using an electronic leak detector, halide torch or liquid-
soap solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.
Indoor Airflow
The airflow does not require checking unless improper performance is
suspected. If a problem exists, be sure that all supply- and return-air
grilles are open and free from obstructions, and that the air filter is clean.
Metering Devices
Refrigerant cooling metering device is a piston located upstream of the indoor
coil distributor assembly. Refrigerant heating mode metering device is a
piston located upstream of the outdoor coil distributor assembly.
High Flow Valves
High flow valves are located on the compressor hot gas and suction tubes.
Large black plastic caps distinguish these valves with O-rings located inside
the caps. Ensure the plastic caps are in place and tight or the possibility of
refrigerant leakage could occur. To replace valve core body without removing
charge, service tool p/n SCFT20A is required.
High Pressure Switch
The high-pressure switch is located in the discharge line and protects against
excessive condenser coil pressure. It opens at 650 psig (4482 kPA). High
pressure may be caused by a dirty condenser coil, failed fan motor, or
condenser air recirculation.
To check switch:
- Turn off all power to unit.
- Disconnect leads on switch.
- Apply ohmmeter leads across switch. You should have continuity on a good switch.
Loss of Charge Switch
The loss of charge switch is located in the liquid line and will protect the
compressor against a loss of charge condition. It opens at 20 psig (138 kPa).
If switch is open check system pressures. If pressures are normal, check
continuity and wiring of switch. Repair or replace as required.
Puron (R-410A) Compressor
The compressor used in this product is specifically designed to operate with
Puron (R-410A) refrigerant and cannot be interchanged.
The compressor is an electrical (as well as mechanical) device. Exercise
extreme caution when working near compressors. Power should be shut off, if
possible, for most troubleshooting techniques. Refrigerants present additional
safety hazards.
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death and/or
property damage.
Wear safety glasses and gloves when handling refrigerants. Keep torches and
other ignition sources away from refrigerants and oils.
Compressors vary in type by unit size. See Table 8 below for compressor type
by size.
Table 8 – Compressor Type
UNIT| COMPRESSOR TYPE| MANUFACTURER SUGGESTED OIL
TYPE
---|---|---
024| Copeland Scroll| 3MAF Polyolester Oil (POE)
030| Copeland Scroll| 3MAF Polyolester Oil (POE)
036| LG Scroll| RB32G Polyolester Oil (POE)
042| LG Scroll| RB32G Polyolester Oil (POE)
048| Copeland Scroll| 3MAF Polyolester Oil (POE)
060| Copeland Scroll| 3MAF Polyolester Oil (POE)
All compressors in these units have internal overload protection. This
protection will interrupt motor current under fault conditions such as running
current overload. The Copeland Scroll compressors also have internal pressure
relief that will relieve from the high side to the low side if the
differential is between 550 and 625 psig.
Refrigerant
CAUTION
EXPLOSION, ENVIRONMENTAL SAFETY HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This system uses Puron (R-410A) refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be used
in this system. Gauge set, hoses, and recovery system must be designed to
handle Puron (R-410A). If you are unsure, consult the equipment manufacturer.
This system uses Puron (R-410A) refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be used
in this system. Gauge set, hoses, and recovery system must be designed to
handle Puron (R-410A). If you are unsure, consult the equipment manufacturer.
Failure to use Puron (R-410A) compatible servicing equipment or replacement
components may result in property damage or injury.
Compressor Oil
Use only manufacturer suggested compressor oil, see Table 8 for correct oil.
NOTE: Alternate manufacturer approved compressor oil for Copeland Scroll
compressor: Uniqema RL32-3MAF, Copeland Ultra 32 CC, Mobil Arctic EAL22 CC,
ICI Emkarate RL22 or ICI Emkarate 32CF. This oil is extremely hygroscopic,
meaning it absorbs water readily. POE/PVE oils can absorb 15 times as much
water as other oils designed for HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.
Servicing Systems on Roofs with Synthetic Materials
POE/PVE (polyolester) compressor lubricants are known to cause long term
damage to some synthetic roofing materials. Exposure, even if immediately
cleaned up, may cause embrittlement (leading to cracking) to occur in one year
or more. When performing any service that may risk exposure of compressor oil
to the roof, take appropriate precautions to protect roofing. Procedures which
risk oil leakage include, but are not limited to, compressor replacement,
repairing refrigerant leaks, replacing refrigerant components such as filter
drier, pressure switch, metering device, coil, accumulator, or reversing
valve.
Synthetic Roof Precautionary Procedure
- Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10 x 10 ft (3 x 3 m) area.
- Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills, prevent run-offs, and protect drop cloth from tears caused by tools or components.
- Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run-offs through the louvered openings in the unit base.
- Perform required service.
- Remove and dispose of any oil contaminated material per local codes.
Liquid Line Filter Drier
The filter drier is specifically designed to operate with Puron (R-410A). Use
only factory-authorized components. Filter drier must be replaced whenever the
refrigerant system is opened. When removing a filter drier, use a tubing
cutter to cut the drier from the system. Do not unsweat a filter drier from
the system. Heat from unsweating will release moisture and contaminants from
drier into system.
Puron (R-410A) Refrigerant Charging
Refer to unit information plate and charging chart. Some Puron (R-410A)
refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow
from cylinder in upright position. For cylinders equipped with a dip tube,
charge Puron (R-410A) units with cylinder in upright position and a commercial
metering device in manifold hose. Charge refrigerant into suction-line.
Troubleshooting
Refer to the Troubleshooting Chart (Table 9) for troubleshooting information.
Start-up Checklist
Use the Start-Up Checklist at the back of this manual.
Table 9 – Troubleshooting Chart
SYMPTOM | CAUSE | REMEDY |
---|---|---|
Compressor and outdoor fan will not start | Power failure | Call power company |
Fuse blown or circuit breaker tripped | Replace fuse or reset circuit breaker |
Defective contactor, transformer, control relay, or high-pressure, loss- of-
charge or low-pressure switch|
Replace component
Insufficient line voltage| Determine cause and correct
Incorrect or faulty wiring| Check wiring diagram and rewire correctly
Thermostat setting too low/too high| Reset Thermostat setting
Compressor will not start but condenser fan runs| Faulty wiring or circuit
Loose connections in compressor| Check wiring and repair or replace
Compressor motor burned out, seized, or| Determine cause
internal overload open| Replace compressor
Defective run capacitor, overload, or PTC (positive temperature coefficient)
thermistor| Determine cause and replace
Low input voltage| Determine cause and correct
Compressor cycles (other than normally satisfying) cooling/heating calls|
Refrigerant overcharge or undercharge| Recover refrigerant, evacuate system,
and recharge to capacities shown on rating plate
Defective compressor| Replace and determine cause
Insufficient line voltage| Determine cause and correct
Blocked outdoor coil| Determine cause and correct
Defective run/start capacitor, overload or start relay| Determine cause and
replace
Faulty outdoor fan motor or capacitor| Replace
Restriction in refrigerant system| Locate restriction and remove
Compressor operates continuously| Dirty air filter| Replace filter
Unit undersized for load| Decrease load or increase unit size
Thermostat temperature set too low| Reset Thermostat setting
Low refrigerant charge| Locate leak, repair, and recharge
Air in system| Recover refrigerant, evacuate system, andrecharge
Outdoor coil dirty or restricted| Clean coil or remove restriction
Excessive head pressure| Dirty air filter| Replace filter
Dirty indoor or outdoor coil| Clean coil
Refrigerant overcharged| Recover excess refrigerant
Air in system| Recover refrigerant, evacuate system, and recharge
Indoor or outdoor air restricted or air short-cycling| Determine cause and
correct
Head pressure too low| Low refrigerant charge| Check for leaks, repair and
recharge
Restriction in liquid tube| Remove restriction
Excessive suction pressure| High Heat load| Check for source and eliminate
Reversing valve hung up or leaking internally| Replace valve
Refrigerant overcharged| Recover excess refrigerant
Suction pressure too low| Dirty air filter| Replace filter
Low refrigerant charge| Check for leaks, repair and recharge
Metering device or low side restricted| Remove source of restriction
Insufficient coil airflow| Check filter–replace if necessary
Temperature too low in conditioned area| Reset Thermostat setting
Outdoor ambient below 55°F (13°C)| Install low-ambient kit
Filter drier restricted| Replace
Start-Up Checklist
(Remove and Store in Job Files)
I. PRELIMINARY INFORMATION
MODEL NO.: ____
SERIAL NO.:
DATE: ____
TECHNICIAN:___
II. PRESTART-UP (Insert check mark in box as each item is completed)
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION
INSTRUCTIONS
( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE
( ) VERIFY THAT UNIT INSTALLATION IS LEVEL
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND
SETSCREW TIGHTNESS
III. START-UP
Supply Voltage: L1-L2
Compressor Amps: L1 (C) ____ L2 (S) __L3(R)____
Indoor (Evaporator Fan Amps __Outdoor Fan Amps_
Temperature-Cooling Mode
Outdoor Air Temperature:____ DB _ WB
Return-Air Temperature:___ DB _ WB
Cooling Supply Air ___ DB _ WB
Pressures – Cooling Mode
Refrigerant Suction ___ psig
Suction Line Temp _
Refrigerant Discharge __ psig
Discharge Temp† _____
Temperature-Heating Mode
Outdoor Air Temperature:_ DB ____ WB
Return-Air Temperature:____ DB ____ WB
Supply Air ___ DB ____ WB
Pressures – Heating Mode
Refrigerant Suction ____ psig
Suction Line Temp ____
Refrigerant Discharge __ psig
Discharge Temp† _____
- Measured at suction inlet to compressor
{Measured at liquid line leaving condenser.
My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses. We believe in providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at www.MLCtraining.com. Please contact us at mylearning@carrier.com with questions.
© 2022 Carrier. All rights reserved.
Edition Date: 03/22
Catalog No: 50ZHK-01SI
Replaces: 50ZHC-05SI
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>