Carrier 38MGR-HB Multi Zone Outdoor Unit Ductless System Installation Guide
- June 13, 2024
- Carrier
Table of Contents
- 38MGR-HB Multi Zone Outdoor Unit Ductless System
- SAFETY CONSIDERATIONS
- GENERAL
- PARTS LIST
- SYSTEM REQUIREMENTS
- WIRING
- DIMENSIONS
- CLEARANCES
- INSTALLATION GUIDE
- OUTDOOR UNIT INSTALLATION
- ELECTRICAL DATA
- CONNECTION DIAGRAMS
- AUTOMATIC WIRING/PIPING CORRECTION
- SYSTEM VACUUM AND CHARGE
- START-UP
- OUTDOOR UNIT DIAGNOSTIC GUIDES
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
38MG(R/H)B
Multi-zone Outdoor Unit Ductless System
Sizes 18R, 24HH, 30HH, 36R, 36HH, 48R and 48HH
Installation Instructions
38MGR-HB Multi Zone Outdoor Unit Ductless System
A220030
NOTE: Read the entire instruction manual before starting the
installation.
Specifications subject to change without notice.
38MGRBQ: Installation Instructions
SAFETY CONSIDERATIONS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 2
PARTS LIST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 3
SYSTEM REQUIREMENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 3
PIPING REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 4
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 5
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 6
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 9
INSTALLATION GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 10
OUTDOOR UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 10
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 12
CONNECTION DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 12
AUTOMATIC WIRING/PIPING CORRECTION . . . . . . . . . . . . . . . 15
SYSTEM VACUUM AND CHARGE. . . . . . . . . . . . . . . . . . . . . . . . . 16
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 17
OUTDOOR UNIT DIAGNOSTIC GUIDES . . . . . . . . . . . . . . . . . . . . 18
Installing, starting up, and servicing air-conditioning equipment can be
hazardous due to system pressures, electrical components, and
equipmentlocation (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install,
start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as coil
cleaning. All other operations should be performed by trained
servicepersonnel.
When working on the equipment, observe precautions in the literature andon
tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep a quenching
cloth and fire extinguisher nearby when brazing. Use care in handling,
rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local building codes
and current editions of the National Electrical Code (NEC) NFPA 70. In Canada,
refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety-alert symbol **. When you
see this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury. Understand these signal words:
DANGER, WARNING, and CAUTION. These words are used with the safety-
alert symbol. DANGER identifies the most serious hazards which will result
in severe personal injury or death. WARNING signifies hazards which could
result in personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and property
damage. NOTE is used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
****WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect
switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and tag switch with a
suitable warning label.
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen for leak testing or operating
refrigerant compressors. Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
CAUTION
EQUIPMENT DAMAGE HAZARD**
Failure to follow this caution may result in equipment damage or improper
operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If
any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to
the valve connections on the outdoor units. If more than the recommended
length is buried, refrigerant may migrate to the cooler buried section during
extended periods of system shutdown. This causes refrigerant slugging and
could possibly damage the compressor at startup.
GENERAL
These instructions cover the installation, start-up and servicing of the
multi-zone outdoor unit connected to up to five indoor fan coil units. For
approved combinations, refer to the product data document.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.
PARTS LIST
Table 1 — Parts List
Part No. | Part Name | Qty |
---|---|---|
1 | Outdoor Unit | 1 |
– | Literature package including installation instructions and warranty | 1 |
– | Vibration Pad | 4 |
– | Drain joint | 1 |
– | Conversion Joints (see Table 4) | – |
NOTES:
– If the outdoor unit is higher than the indoor unit, prevent rain from
flowing into the indoor unit along the connection pipe by making a downward
arc in the connection pipe before it enters the wall to the indoor unit. This
ensures that rain drips from the connection pipe before it enters the wall.
– Piping and the interconnecting wiring are field supplied.
– Figure 4 is only a sketch. Different models may differ slightly.
The units listed in Table 2 are covered in this manual.
Table 2 — Indoor Units
System Tons | kBTUh | V-Ph-Hz | Outdoor Model |
---|---|---|---|
1.5 | 18 | 208/230-1-60 | 38MGRBQ18BA3 |
2.0 | 24HH | 38MGHBQ24CA3 | |
2.5 | 30HH | 38MGHBQ30DA3 | |
3.0 | 36 | 38MGRBQ36DA3 | |
3.0 | 36HH | 38MGHBQ36DA3 | |
4.0 | 48 | 38MGRBQ48EA3 | |
4.0 | 48HH | 38MGHBQ48EA3 |
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and unit service. see Fig. 9 — on page 9
for the minimum required distances between the unit and walls or ceilings.
PIPING REQUIREMENTS
IMPORTANT: Both refrigerant lines must be insulated separately.
The minimum refrigerant line length between the indoor and outdoor units is 10
ft. (3 m). The following lengths are allowed.
Table 3 lists the pipe sizes for the outdoor unit. For the indoor unit pipe
sizes refer to the indoor unit installation instructions.
Table 3 — Piping and Refrigerant
38MG *** BQ Size**
| Standard| High Heat| High Heat| Standard| High
Heat| Standard| High Heat
---|---|---|---|---|---|---|---
18K| 24K| 30K| 36K| 36K| 48K| 48K
(208/230V)| (208/230V)| (208/230V)| (208/230V)| (208/230V)| (208/230V)|
(208/230V)
Min. Piping Length per each indoor unit| ft. (m)| 10 (3)| 10 (3)| 10 (3)| 10
(3)| 10 (3)| 10 (3)| 10 (3)
Standard Piping Length per each indoor unit| ft. (m)| 25 (7.5)| 25 (7.5)| 25
(7.5)| 25 (7.5)| 25 (7.5)| 25 (7.5)| 25 (7.5)
Max. outdoor-indoor height difference| ft. (m)| 49 (15)| 49 (15)| 49 (15)| 49
(15)| 65(20)| 65 (20)| 65 (20)
Max. height difference between indoor units| ft. (m)| 32 (10)| 32 (10)| 32
(10)| 32 (10)| 32 (10)| 32 (10)| 32 (10)
Max. Length per each indoor unit| ft. (m)| 82 (25)| 98 (30)| 115(35)| 115(35)|
115(35)| 115 (35)| 115 (35)
Max. Piping Length with no additional refrigerant charge per System (Standard
Piping length x No. of Zones)| ft. (m)| 50 (15)| 75 (22)| 100 (30)| 100 (30)|
100 (30)| 125 (37.5)| 125 (37.5)
Total Maximum Piping Length per system| ft. (m)| 131(40)| 197(60)| 262(80)|
262(80)| 262 (80)| 328 (100)| 328 (100)
Additional refrigerant charge (between Standard – Max piping length)| ****
Oz/ft (g/m)| 0.16 (15)| 0.16 (15)| 0.16 (15)| 0.16 (15)| 0.16 (15)| 0.16 (15)|
0.16 (15)
Max number of IDU| | 2| 3| 4| 4| 4| 5| 5
Suction Pipe
(size – connection type)
| in| 3/82| 3/83| 1/2 1+ 3/83| 1/2 1+ 3/83| 1/2 2+ 3/82| 1/2 2+
3/83| 1/2 2+ 3/83
(mm)| 9.522| 9.523| 12.71+9.523| 12.71+9.523| 12.72+9.522|
12.72+9.523| 12.72+9.523
Liquid Pipe
(size – connection type)
| in| 1/42| 1/43| 1/44| 1/44| 1/44| 1/45| 1/45
(mm)| 6.352| 6.353| 6.354| 6.354| 6.354| 6.355| 6.355
Refrigerant Type Heat Pump Models Charge Amount| | R410A
Lbs (kg)| 4.08(1.85)| 5.73(2.6)| 8.38(3.8)| 8.38(3.8)| 10.14 (4.6)| 10.14
(4.6)| 10.14(4.6)
NOTE: For piping runs greater than the “Maximum Piping Length with no
additional refrigerant charge per System,” see Additional Refrigerant Charge
(see Table 5).
Refrigerant Piping:
Line sets to be sized based on the connection size of the indoor unit. Each
pipe should be insulated individually.
Conversion Joints: The outdoor unit includes a package of conversion joints to
facilitate installation of the various fan coil sizes. These joints are to be
connected to the outdoor unit as needed to match the line set size.
No. of Zones | Size | Adaptor | Qty. |
---|---|---|---|
2 zone | 18 | 3/8”–1/2” | 2 |
3 zone | 24HH | 3/8”–1/2” | 3 |
4 zone
| ****
30HH 36
| 3/8”–1/2”| 3
1/2”–3/8”| 1
1/4”–3/8”| 1
1/2”–5/8”| 1
4 zone
5 zone
| ****
36HH 48 48HH
| 1/2”–3/8”| 2
1/4”–3/8”| 2
1/2”–5/8”| 2
3/8”–1/2”| 3 (36 only includes 2)
Table 5 — Additional Refrigerant Charge
Unit Size| Min. No. of Zones| Max. No. of Zones| Charge oz.
Lbs (kg)| Additional Charge Required After ft. (m)| Additional
Charge oz./ft. (g/m)| Total Maximum Piping Length ft. (m.)
---|---|---|---|---|---|---
18| 2| 2| 4.08(1.85)| 49 (15)| 0.16 (15)| 131 (40)
24 High Heat| 2| 3| 5.73(2.6)| 74 (22)| 0.16 (15)| 197 (60)
30 High Heat| 2| 4| 8.38(3.8)| 98 (30)| 0.16 (15)| 262 (80)
36| 2| 4| 8.38(3.8)| 98 (30)| 0.16 (15)| 262 (80)
36 High Heat| 2| 4| 10.14 (4.6)| 98 (30)| 0.16 (15)| 262 (80)
48| 2| 5| 10.14 (4.6)| 123 (37.5)| 0.16 (15)| 328 (100)
48 High Heat| 2| 5| 10.14 (4.6)| 123 (37.5)| 0.16 (15)| 328 (100)
Additional Refrigerant Calculation
(Sum Total Liquid Pipe ft. (m) – Additional Charge Required After ft. (m.)) x
Additional Charge oz./ft. (g/m) 0.16 (15)
Adding Refrigerant when using 30 & 36 AHUs
A maximum of two AHUs can be added to the MZ system. Refer to the application
tables in the product data for allowed combinations.
Regardless of size, when two AHUs are connected to any MZ ODU, no other indoor
units can be added to the system.
If a 30k or 36k AHU is connected to a any outdoor unit, 500g (17.6 Oz) of
additional refrigerant charge has to be added to the system.
30k or 36k indoor units are not compatible with phased out models.
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian
Electrical Code) and local codes. See the rating plate and/or the installation
instructions of the compatible outdoor unit for MCA (minimum circuit amps) and
MOCP (maximum over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively.
Recommended Connection Method for Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3
stranded wire with ground with a 600 volt insulation rating,
power/communication wiring from the outdoor unit to indoor unit consists of
four (4) wires and provides the power for the indoor unit. Two wires are line
voltage AC power, one is communication wiring (S) and the other is a ground
wire. Wiring between indoor and outdoor unit is polarity sensitive. The use of
BX wire is NOT recommended.
If installed in a high Electromagnetic field (EMF) area and communication
issues exists, a 14/2 stranded shielded wire can be used to replace L2 and (S)
between outdoor unit and indoor unit landing the shield onto ground in the
outdoor unit only.
WARNING
A listed fitting must be used to securely affix conduit in accordance with NEC
and local codes.
WARNING
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Be sure to comply with local codes while running wire from the indoor unit to
the outdoor unit.
Every wire must be connected firmly. Loose wiring may cause the terminal to
overheat or result in unit malfunction. A fire hazard may also exist. Ensure
all wiring is tightly connected.
No wire should touch the refrigerant tubing, compressor or any moving parts.
Disconnecting means must be provided and shall be located within sight and
readily accessible from the air conditioner.
Follow local codes.
Connecting cable with conduit shall be routed through the hole in the conduit
panel.
DIMENSIONS
Table 6 — Dimensions
System Size
| 18K| 24K High Heat| 30K High Heat| 36K| 36K High
Heat| 48K| 48K High Heat
---|---|---|---|---|---|---|---
(208/230V)| (208/230V)| (208/230V)| (208/230V)|
(208/230V)| (208/230V)| (208/230V)
Height (H)| in (mm)| 26.50(673)| 31.89(810)| 31.89(810)| 31.89(810)|
52.48(1333)| 52.48(1333)| 52.48(1333)
Width (W)| in (mm)| 35.04(890)| 37.24(946)| 37.24(946)| 37.24(946)|
37.48(952)| 37.48(952)| 37.48(952)
Depth (D)| in (mm)| 13.46(342)| 16.14(410)| 16.14(410)| 16.14(410)|
16.34(415)| 16.34(415)| 16.34(415)
Weight -Net| lbs. (kg)| 100.31(45.5)| 139.77(63.4)| 169.09(76.7)|
169.09(76.7)| 223.1(101.2)| 225.5(102.3)| 238.32(108.1)
CLEARANCES
Table 7 — Clearance Values
UNIT | MINIMUM VALUE in. (mm) |
---|---|
A | 24 (609) |
B | 24 (609) |
C | 24 (609) |
D | 4 (101) |
E | 6 (152) |
NOTE: The outdoor unit must be mounted at least 2in (50mm) above the maximum anticipated snow depth.
INSTALLATION GUIDE
Up to five fan coil units can be connected to one outdoor unit. Refer to the
product data for approved combinations.
INSTALLATION TIPS
Ideal installation locations include:
Outdoor Unit
- A location which is convenient to installation and not exposed to strongwinds.
- A location which can bear the weight of the outdoor unit and where theoutdoor unit can be mounted in a level position.
- A location with appropriate clearances as outlined (see Fig. 9 — on page 9).
- Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your Ductless representative.
OUTDOOR UNIT INSTALLATION
- Use a rigid base to support unit in a level position.
- Locate the outdoor unit and connect piping and wiring.
** CAUTION
EQUIPMENT DAMAGE HAZARD**
Failure to follow this caution may result in equipment damage or improper
operation.
Excessive torque can break flare nut depending on installation conditions.
NOTE: Install the outdoor unit on a rigid base to reduce noise levels and
vibration. Determine the optimal air outlet direction to prevent discharged
air from being blocked. If the installation site is exposed to strong winds
such as a coastal areas, ensure the fan’s proper operation by installing the
unit lengthwise along the wall or use dust or shield plates. If the unit needs
to be suspended, the installation bracket should comply with the suspension
requirements in the installation bracket diagram. The installation wall should
be solid brick, concrete or the same intensity construction, or take steps to
reinforce and dampen the support. The connection between the bracket and the
wall as well as the bracket and the air conditioner should be firm, stable and
reliable. Ensure there is no obstacle which may block the radiating air.
MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR UNIT)
IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be
used. Use of other tubing types will void the manufacturer’s warranty.
Piping Guide:
- Do not open service valves or remove protective caps from tubing ends until all the connections are made.
- Bend the tubing with bending tools to avoid kinks and flat spots.
- Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system.
- Avoid sags in the suction line to prevent the formation of oil dams. Insulate each tube with minimum 3/8-in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections saves time and improves installation quality.
1. The unit is equipped with multiple pairs of service valves. Each pair is clearly marked (color and letter) to identify the indoor unit circuits. In the outdoor unit wiring area, each indoor unit interconnecting terminal block is marked (letter) the same as the corresponding pair of service valves. The indoor units must be piped and wired in matched sets (A to A; B to B, etc.).
NOTE: Any size indoor unit can be connected to any port number on the outdoor unit.
2. It is not required to use all of the available fan coil connections if the application does not require them at the current time. The system can be expanded at any time.
3. Conversion joints are supplied with the outdoor unit. They are required for certain fan coil combinations. Connect joints to the outdoor unit as needed to match the line set size.
4. Remove the service connection, if provided with the unit. 5. Remove all the burrs from the cut cross section of the pipe avoiding any burrs inside the tubes.
6. Remove the flare nuts attached to the indoor and outdoor units.
7. Install the correct size flare nut onto the tubing and make a flare connection. Refer to Table 8 for the flare nut spaces.
Table 8 — Flare Nut Spacing** OUTER DIAM. in. (mm)| A in. (mm)
---|---
Max.| Min.**
Ø1/4” (6.35)| .013 (0.34)| .013 (0.33)
Ø3/8” (9.52)| .021 (0.53)| .020 (0.52)
Ø1/2” (12.7)| .026 (0.65)| .025 (0.64)
8. Apply a small amount of refrigerant oil to the flare connection on the
tubing.
9. Align the center of the pipes and/or the service valve.10. Connect both the liquid and gas piping to the indoor
unit.
11. Tighten the flare nut using a torque wrench as specified in Table 9.
12. Complete the installation.
Table 9 — Tightening Torque
Pipe Gauge| ****
Tightening Torque
| Flare Dimension (A) Unit: Inch (mm)| ****
Flare Shape
---|---|---|---
Min.| Max.
Ø1/4 (6.4mm)| 14.8 – 18.4 Ft.- Lbs.
20 to 25 N.M
| 3/8 (8.4)| 3/8 (8.7)| ****
Ø3/8 (9.52mm)| 14.8 – 18.4 Ft.- Lbs.
20 to 25 N.M
| 1/2 (13.2)| 1/2 (13.5)
Ø1/2 (12.7mm)| 18.4 – 22.1 Ft.- Lbs.
25 to 30 N.M
| 5/8 (16.2)| 5/8 (16.5)
INSTALL ALL POWER AND INTERCONNECTING WIRING TO OUTDOOR UNIT
- Mount the outdoor power disconnect.
- Run power wiring from the main box to the disconnect per NEC and local codes.
- Remove the field wiring cover (if available) from the unit by loosening the screws.
- Remove the caps on the conduit panel.
- Connect the conduit to the conduit panel (see Fig. 15).
- Properly connect both the power supply and control lines to the terminal block per the connection diagram.
- Ground the unit in accordance with NEC and local electrical codes.
- Use the lock nuts to secure the conduit.
- Reinstall the field wiring cover.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Be sure to comply with local codes while running wire from indoor unit to
outdoor unit.
Every wire must be connected firmly. Loose wiring may cause the terminal to
overheat or result in unit malfunction. A fire hazard may also exist.
Therefore, ensure all wiring is tightly connected.
No wire should be allowed to touch the refrigerant tubing, compressor or any
moving parts.
Disconnecting means must be provided and shall be located within sight and
readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through hole in the conduit
panel.
WARNING
An approved and listed fitting must be used to securely affix conduit in
accordance with NEC and local codes.
DRAIN CONNECTIONS
Install drains must meet local sanitation codes.
Install the outdoor unit drain joint
Fit the seal into the drain joint, then insert the drain joint into the base
pan hole of the outdoor unit. Rotate 90° to securely assemble them. Connect
the drain joint with an extension drain hose to avoid condensate from draining
off the outdoor unit during the heating mode.
CAUTION
In cold climates, ensure the drain hose is as vertical as possible to ensure
swift water drainage. If water drains too slowly, it can freeze in the hose
and flood the unit.
NOTE: Basepan built-in with multiple holes for proper draining during defrost.
For applications where it is required to seal these holes, and re-direct the
condensate drain, rubber plugs are available through Replacement Components
(RC).
Table 10 — Rubber Plugs
Outdoor Unit| Basepan Base Rubber
Plugs RC Part Number
| Quantity per unit
---|---|---
18K| 12600801A00077| 25
24K High Heat 30K High Heat 36K| ****
12600801A00117
| ****
5
36K High Heat 48K
48K High Heat
| ****
12600801A00118
| ****
5
ELECTRICAL DATA
Table 11 — Electrical Data
UNIT SIZE| SYSTEM VOLTAGE| OPERATING VOLTAGE|
COMPRESSOR| OUTDOOR FAN| MCA| MOCP
---|---|---|---|---|---|---
VOLT / PHASE / HZ| **MAX / MIN*| RLA| FLA| HP| W
18| **
208/230/1/60
| ****
253/187
| 11| 1.0| 0.1| 80| 18| 25
24 High Heat| 14| 1.7| 0.16| 120| 24.5| 30
30 High Heat| 18| 1.0| 0.16| 120| 25| 40
36| 18| 1.0| 0.16| 120| 25| 40
36 High Heat| 24| 2.5| 0.11| 85| 40| 60
48| 24| 2.5| 0.11| 85| 40| 60
48 High Heat| 30| 2.0| 0.11| 85| 40| 60
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA – Full Load Amps
MCA – Minimum Circuit Amps
MOCP – Maximum Overcurrent Protection
RLA – Rated Load Amps
CONNECTION DIAGRAMS
AUTOMATIC WIRING/PIPING CORRECTION
The unit is capable of automatically correcting a wiring/piping error. Indoor
units do not have to be in the run mode. The outdoor temperature should be
above 41°F (5°C) to use this feature. Press SW1 on the outdoor unit PCB board
for 6 seconds until the display shows “CE” (“FA” may appear first – continue
to press SW1).
The outdoor unit takes control of the indoor units and adjust fan speed(s)
according to the program. Setpoint display (if available) will be “76” and
outdoor unit will start the compressor and fan to dispense refrigerant to the
indoor heads to determine piping setup versus physical wiring. When the
controller has adjusted control so that each indoor unit is synced to its
piping port (approximately 5-10 minutes, depending on temperature, unit size,
etc.), “CE” is replaced with “00” on the display and the control program
terminates.
NOTE: The indoor units will not automatically release from the “76”
setting or return to previous control. Use the indoor units’ remote
controllers to restore them to normal function.
SYSTEM VACUUM AND CHARGE
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Never use the system compressor as a vacuum pump.
Refrigerant pipes and indoor unit coils should be evacuated using the
recommended 500 microns deep vacuum method. The alternate triple evacuation
method may be used if the following procedure is followed.
Always break a vacuum with dry nitrogen.
NOTE: All units (except the 18,000 BTU model) have a Master Suction and
Liquid Line Service Valve.
Using Vacuum Pump
-
Completely tighten the flare nuts of the liquid and gas pipes on the indoor and outdoor side (for all fan coils) (see Fig 23 ).
-
For size 18, DO NOT open the Gas or Liquid service valves until the evacuation is complete. For sizes 24-48, fully open all the connected individual service valves (with the line set attached). DONOT open the Master Service Valves until the evacuation is
complete (see Fig 24 ). -
For size 18, connect the manifold gauge (low side hose) to the Individual Service Valve (5/16 port, use the adapter to fit a 1/4in hose) to evacuate each of the circuits. For sizes 24-48, connect the manifold gauge (low side hose) to the Master service valve (5/16 port, use the adapter to fit a 1/4in. hose) to evacuate all circuits at thesame time (see Fig. 26).
-
Connect the charge hose to the vacuum pump.
-
Open (fully) the low pressure valve of the manifold gauge (see Fig. 26 for 18K. Fig. 25 for sizes 24K-48K).
-
Start the vacuum pump.
-
Evacuate using either the deep vacuum or the triple evacuation method (see Fig. 28 and 29).
-
After the evacuation is complete, fully close the low pressure valve of the manifold gauge and stop the vacuum pump operation.
-
Insert a hexagonal wrench into each Gas Side Service Valve for size18 or into the Master Gas Side Service Valve for sizes 24-48 and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system (see Fig. 24).
-
Reference Table 5 on page 5 when additional charge is needed.
-
Disconnect the charge hoses and manifold gauge.
-
Using a hexagonal wrench, fully open all the gas and liquid service valves for the size 18 and all the Master Gas and Liquid service valves for sizes 24-48 (see Fig. 24).
NOTE: The Master Valve utilizes a 5/16-inch port.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of
500 microns and a vacuum gauge capable of accurately measuring this vacuum
depth. The deep vacuum method is the most positive way of assuring a system is
free of air and liquid water (see Fig. 28).
Triple Evacuation Method
The triple evacuation is the recommended method of dehydration.
Refer to Fig. and proceed as follows:
- Pump the system down to 1500 microns and allow the pump to continue operating for an additional 15 minutes.
- Close the service valves and shut off the vacuum pump.
- Connect a dry nitrogen cylinder and regulator to the system and break vacuum until the system reaches 2 psig.
- Close the service valve and allow the system to stand for 1 hr. During this time, the dry nitrogen can diffuse throughout the system absorbing moisture.
- Pump the system down to 1000 microns.
- Break the vacuum with dry nitrogen (2 psig).
- Pump the system down to 500 microns.
- Perform the hold test for 30 minutes.
Final Tubing Check
IMPORTANT: Ensure the factory tubing on both the indoor and outdoor unit
has not shifted during shipment. Ensure tubes are not rubbing against each
other or any sheet metal.
Pay close attention to feeder tubes, making sure wire ties on the feeder tubes
are secure and tight.
START-UP
CAUTION
DO NOT apply power to the outdoor unit if the Master Service Valves are not
fully open. Compressor damage will occur.
TEST OPERATION
Perform a test operation after completing a gas leak and electrical safety
check. Review the indoor unit installation instructions and owner’s manual for
additional start up information.
System Checks
- Conceal the tubing where possible.
- Ensure the drain tube slopes downward along its entire length.
- Ensure all tubing and connections are properly insulated.
- Fasten the tubes to the outside wall, when possible.
- Seal the hole through which the cables and tubing pass.
OUTDOOR UNIT
-
Are there unusual noises or vibrations during operation?
Explain the Following Items to the Customer (with the aid of the Owner’s Manual): -
Explain care and maintenance.
-
Present the installation instructions to the customer.
OUTDOOR UNIT DIAGNOSTIC GUIDES
For ease of service, the systems are equipped with a diagnostic code display
LED on both the indoor and outdoor units. The outdoor diagnostic is displayed
on the outdoor unit microprocessor board. There may be a few error codes
displayed on the indoor unit that might relate to the outdoor unit’s problems.
If possible, always check the diagnostic codes displayed on the indoor unit
first. In standby, the LED displays “- -”. In the compressor operation, the
LED displays the running frequency. In the defrosting mode, the LED displays
“dF” or alternative displays between the running frequency and “dF” (each
appears for 0.5s). During the compressor pre-heating cycle, the LED displays
“PH” or alternative displays between the running frequency and “PH” (each
appears for 0.5s).
During the oil return process, the LED displays “RO” or alternative displays
between the running frequency and “RO” (each appears for 0.5s).
In the low ambient Cooling mode, the LED displays “LC” or alternative displays
between the running frequency and “LC” (each appears for 0.5s).
In the Forced Cooling mode, the LED displays “FC” or alternative displays
between the running frequency and “FC” (each appears for 0.5s).
When PFC module protection occurs three times within 15 minutes, the LED
displays “E6” or alternative displays between the running frequency and “E6”
(each appears for 0.5s).
In protection or malfunction, the LED displays an error code or a protection
code. The diagnostic codes displayed on the outdoor units are listed on Table
12.
Table 12 — Outdoor Unit Error Display
OUTDOOR UNIT DISPLAY | LED STATUS | INDOOR UNIT DISPLAY |
---|---|---|
EC 51 | Outdoor EEPROM malfunction | EC51 |
EL 01 | Communication malfunction between indoor and outdoor units | EL01 |
PC 40 | Communication malfunction between IPM board and outdoor main board | — — |
PC 08 | Outdoor Overcurrent Protection | — — |
PC 10 | Outdoor Unit Low AC Voltage Protection | — — |
PC 11 | Outdoor Unit Main Control Board DC Bus High Voltage Protection | — — |
PC 12 | Outdoor Unit Main Control Board DC Bus High Voltage Protection /341 MCE | |
Error | — — | |
PC 00 | IPM module protection | PC00 |
PC 0F | PFC module protection | — — |
EC 71 | Over current failure of outdoor DC fan motor | — — |
EC 72 | Lack phase failure of outdoor DC fan motor | — — |
EC 07 | Outdoor fan speed has been out of control (only for DC fan motor | |
models) | EC07 | |
PC 43 | Outdoor compressor lack phase protection | — — |
PC 44 | Outdoor unit zero speed protection | — — |
PC 45 | Outdoor unit IR chip drive failure | — — |
PC 46 | Compressor speed has been out of control | — — |
PC 49 | Compressor overcurrent failure | — — |
PC 30 | High pressure protection | — — |
PC 31 | Low pressure protection | — — |
PC 0A | High temperature protection of condenser | — — |
PC 06 | Temperature protection of compressor discharge | — — |
PC 0L | Low ambient temperature protection | PC0L |
PC 02 | Top temperature protection of compressor | PC02 |
EC 52 | Condenser coil temperature sensor T3 is in open circuit or has short | |
circuited | EC52 | |
EC 53 | Outdoor room temperature sensor T4 is in open circuit or has short | |
circuited | EC53 | |
EC 54 | Compressor discharge temperature sensor TP is in open circuit or has | |
short circuited | EC54 | |
EC 55 | Outdoor IPM module temperature sensor TH is in open circuit or has | |
short circuited | EC55 | |
EC 56 | Evaporator coil outlet temperature sensor T2B is in open circuit or has | |
short circuited | EC56 | |
EC 50 | Open or short circuit of outdoor unit temperature sensor(T3,T4.T5) | — — |
EL 16 | Communication malfunction between adapter board and outdoor main | |
control board | — — |
© 2023 Carrier. All rights reserved.
Edition Date: 04/23
Catalog No: IM-38MGRBQ-03
Replaces: IM-38MGRBQ-02
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>