TRANE FIAECON303 Packaged Rooftop Units Instruction Manual

June 13, 2024
Trane

TRANE-LOGO

TRANE FIAECON303 Packaged Rooftop Units

TRANE-FIAECON303-Packaged-Rooftop-Units-PRODUCT

Product Information

  • Product Name: 0 to 100% Horizontal Dry Bulb Economizer
  • Model Number: FIAECON303*
  • Compatible with: T/YS180-300, T/YH180-300, T/YZ*150-300, W/D/G**150-300
  • Product Type: Packaged Rooftop Units
  • Tonnage: 12.5 to 25 Tons
  • Manufacturer: Trane
  • Publication Date: April 2023
  • Document Number: ACC-SVN233B-EN

Product Usage Instructions

  1. Safety Warning: Only qualified personnel should install and service the equipment. Improper installation or alteration by an unqualified person can result in death or serious injury. Observe all precautions mentioned in the literature and on the equipment.
  2. Introduction: Read the manual thoroughly before operating or servicing the unit.
  3. Warnings, Cautions, and Notices: Safety advisories are provided throughout the manual. Strictly follow these precautions for personal safety and proper operation of the machine.
  4. Important Environmental Concerns: The product emphasizes responsible refrigerant practices for environmental safety.
  5. Proper Field Wiring and Grounding: All field wiring must be performed by qualified personnel. Failure to follow the code could result in death or serious injury. Refer to NEC and your local/state/national electrical codes for proper installation and grounding.
  6. Personal Protective Equipment (PPE) Required: Technicians must wear proper PPE to protect themselves from potential hazards. Follow the precautions mentioned in the manual, tags, stickers, and labels.
  7. Follow EHS Policies: Failure to follow EHS policies could result in death or serious injury.
  8. Inspection: Unpack all components of the kit.
  9. Check carefully for shipping damage. If any damage is found, report it immediately, and file a claim against the transportation company.

Note: This is a partial extract from the user manual. Please refer to the complete user manual for detailed instructions and information.

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and require specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

  • WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
  • CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
  • NOTICE: Indicates a situation that could result in equipment or property damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released into the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact tonthe environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING Proper Field Wiring and Grounding Required!

Failure to follow the code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

WARNING : Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut-resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS  (Global Harmonized System of Classification andLabeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE by OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.

NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR THE INTENDED VOLTAGE.

WARNING: Follow EHS Policies!

Failure to follow the instructions below could result in death or serious injury.

  • All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • NNon-ranepersonnel should always follow local regulations.

Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History
Added T/YH180-300, T/YZ150-300 Used With information on the front cover

Inspection

  1. Unpack all components of the kit.
  2. Check carefully for shipping damage. If any damage is found, report it immediately, and file a claim against the transportation company.
  3. Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
  4. If concealed damage is discovered, stop unpacking the shipment.
  5. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
  6. Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.

Note : Do not attempt to repair any damaged parts until the parts are inspected by the carrier’s representative.

Parts List
Each economizer ships partially assembled. The steps for installation are illustrated throughout this guide. Refer to the figures as the steps are performed.

Figure 1 illustrates the major components of the economizer when shipped for field installation. As the economizer is not created, locate the following parts:

Item Description Qty
1 Outdoor air damper assembly 1
2 Installation Instruction manual 1
3 Block-off 1
4 Connecting rod assembly 1

5

| Plastic bag of miscellaneous parts:

•    Screws

•    Installation Instruction manual

|

The following parts are used for shipping only and can be discarded:

Installation

WARNING: Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

WARNING: Proper Field Wiring and Grounding Required!

Failure to follow the code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

  1. Remove the filter/fan compartment access panel and the unit end panel (evaporator end).
  2. Attach block-off (3) to the unit by using four screws.
  3. Attach block-off (3) to the unit by using four screws.
  4. Attach connecting rod assembly (4) to outdoor damper using two screws
  5. Attach return air damper assembly (2) to the top and bottom flanges of the return opening using six screws.
  6. Attach connecting rod to return air damper using three screws.
  7. Attach the side panel back to the unit.
  8. Install the rain diverter as shown in Figure 10. Use the four screws provided.
  9. Apply silicone or weather resistance sealant (field supplied) between the unit and edges of the side triangular block-offs and lower brackets.

Minimum Position Setting

To adjust the minimum position setting and check out the economizer, the power must be connected.

  1. Close the unit disconnect and place the zone sensor fan selector in the fan ON position and the heat/cool selector in the OFF This will place the damper in the minimum ventilation position.
  2. To adjust the minimum position setting for the required ventilation air, use the Symbio™ Service and Installation mobile app or Symbio™ 700 on-board UI to adjust the economizer minimum position setpoint BAS in the Fresh/ Return Air settings menu. The damper will open to this setting each time the blower circuit is
  3. When adjusting the minimum position, the damper may move to the new setting in several small steps. Once the damper has remained in position for 10–15 seconds without movement, it can be assumed it is at the new position.
  4. Replace the filter and access the panel.
  5. The damper will close when the blower circuit is de-energized.

Dry Bulb Settings
Standard economizer dry bulb changeover is field selectable and has a range of 50ºF–140ºF.

Reference Enthalpy Settings
Economizer enthalpy changeover is field selectable and has a range of 50ºF–140ºF. The default is 60ºF. This selection can be made using the Symbio™ Service and Installation mobile app or Symbio™ 700 on-board UI.

Table 1. Precedent economizer control options

Control Option Enable Conditions Optional Sensors Required

Comparative Enthalpy

| Outside Air Enthalpy < Return Air Enthalpy – Econ Enthalpy Offset and Outside Air Temperature < Economizer Dry Bulb Setpoint – Econ Dry Bulb Offset| Outdoor Air Temperature Sensor Outdoor Air Humidity Sensor Return Air Temperature Sensor Return Air Humidity Sensor

Reference Enthalpy

| Outside Air Enthalpy < Reference Enthalpy Setpoint – Econ Enthalpy Offset and Outside Air Temperature < Economizer Dry Bulb Setpoint – Econ Dry Bulb Offset|

Outdoor Air Temperature Sensor Outdoor Air Humidity Sensor

Dry Bulb

| Outside Air Temperature < [Economizer Outdoor Air Enable

Setpoint BAS – Economizer Dry Bulb Enable Offset]

|

Outdoor Air Temperature Sensor

Differential Dry Bulb

| Outside Air Temperature < RA Temp – Economizer Dry Bulb

Enable Offset – Economizer Dry Bulb Disable Return Air Offset

|

Outdoor Air Temperature Sensor Return Air Temperature Sensor

Wiring Connections

  1. Use the supplied harness to connect PPF87 to the actuator connector.
  2. Route harness to fresh air options module located in the return section and connect to FAOM-J11. Refer to Figure 11.
  3. After installation is complete, Sthe ymbio™ 700 UC unit configuration will need to be updated to reflect the installed option.

Refer to main unit schematic sheet 6 for electrical connections to the fresh air module located in the return section control box. See Figure 11.

Trane and American Standard create comfortable, energy-efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

ACC-SVN233B-EN 15 Apr 2023 Supersedes ACC-SVN233A-EN (Aug 2022)

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals