EPSOLAR EPIPDB-COM 10A Duo Battery Charging Solar Controller Instruction Manual
- June 13, 2024
- EPSOLAR
Table of Contents
INSTRUCTION MANUAL
———- Duo-battery charging solar controller, For RVs, Caravans, and
boats
———-EPIPDB-COM series
EPIPDB-COM 10A Duo Battery Charging Solar Controller
RATINGS (12/24VDC Auto)
EPIPDB-COM, 10A, 12/24VDC Auto
EPIPDB-COM, 20A, 12/24VDC Auto
NOTES: For use with solar panels only
TECHNICAL INFORMATION
Setpoint| Sealed
battery| Gel
battery| Flooded
battery
---|---|---|---
Equalize charging voltage| 14.6V| –| 14.8V
Boost charging voltage| 14.4V| 14.2V| 14.6V
Float charging voltage| 13.8V| 13.8V| 13.8V
Maximum solar voltage| 30V ( 12V System )
55V ( 24V System )
Battery voltage range| 8 15V
Boost time| 120 minutes
Self-consumption| 4mA at night. 10mA at charging
Meterbus connection| 8- PIN RJ-45
Temp. compensation| -5mV/ c /2V
Terminals| 4mm2
Temperature| -35 C +55 C
Net weight| 250g
Note: all the data is for 12V, for 24V, please use 2x.
Major feature of duo-battery controller
(Note: connect the components as the 1-6)
| Connect with the battery #1
---|---
| Connect with the battery #2
| Connect with the PV.
Remote temp. sensor
A connection point for RTS(option) to remotely monitor battery temperature
Local temp. sensor
Measures ambient temperature. Battery regulation is adjusted accordingly
For battery 1
Provides charging & battery status and errors
For battery 2
Provides charging & battery status and errors
Remote meter connection
A communication port for the remote meter
Note: where is no RTS, the controller calculate the data which got from the
local temp. sensor. The controller will come to RTS automatically when the RTS
was connected.
SETTING MODE
![]()
Three leds flashing, each LED express different specifications, choose the LED first according to the following information, and then press the switch for 5 seconds until the number flashing, choose one number as you need, and leave it and the number you set will be saved.
- 1 st led is the battery type setting.
Number shows| Battery type
---|---
1| Sealed battery
2| Gel battery
3| Flooded battery - nd 2 led is for charging priority, only set the percentage you want for battery #1, the controller will automatically calculate the rest for battery #2.
Number shows| Battery #1 charging| Battery # 2 charging
---|---|---
0| 0%| 100%
1| 10%| 90%
2| 20%| 80%
3| 30%| 70%
4| 40%| 60%
5| 50%| 50%
6| 60%| 40%
7| 70%| 30%
8| 80%| 20%
9| 90%(pre-set)| 10%
Note: in the normal charging status, the controller will divide the charging
as the setting. While battery #1 is fully charged, more charge current will be
diverted to battery #2, and return to the setting charging automatically when
the battery #1 is in low voltage.
When the controller detects there is only battery #1, all the charging will go
to the battery #1 automatically.
- rd 3. 3 led is for charging frequency.
Number shows| PWM Charging frequency
---|---
0| 25Hz(pre-set)
1| 50Hz
2| 100Hz
TROUBLESHOOTING
- LED blinking, short circuit, check the PV and battery, and make sure that they are in correct connection
- LED slowly flashing, fully charged
- LED ON, on charging
- LED frequent flashing, with battery, no charging
- LED OFF, no battery or over voltage