TRANE J4HP5_14.3SEER2 Split System Heat Pump Installation Guide
- June 13, 2024
- Trane
Table of Contents
- TRANE J4HP5_14.3SEER2 Split System Heat Pump
- Product Information
- Product Usage Instructions
- SAFETY INSTRUCTIONS
- UNIT LOCATION CONSIDERATIONS
- UNIT PREPARATION
- SETTING UP THE UNIT
- REFRIGERANT LINE CONSIDERATIONS
- REFRIGERANT LINE ROUTING
- REFRIGERANT LINE BRAZING
- REFRIGERANT LINE LEAK CHECK
- EVACUATION
- SERVICE VALVES
- ELECTRICAL – LOW VOLTAGE
- ELECTRICAL – HIGH VOLTAGE
- START UP
- SYSTEM CHARGE ADJUSTMENT
- SYSTEM OPERATION AND TROUBLESHOOTING
- WARRANTY
- Maintenance
- WIRING DIAGRAMS
- MATCHING TABLE AND CHECKOUT PROCEDURES
- Operational and Checkout Procedures
- CONTACT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TRANE J4HP5_14.3SEER2 Split System Heat Pump
Product Information
- Product Name: Installer’s Guide Condensing Units
- Product Type: Split System Heat Pump
- Capacity: 1.5-5 Tons
- SEER Rating: Up to 15.2 SEER
- Refrigerant Type: R410a
Product Usage Instructions
- Before using the unit, read the manual carefully and keep it for future reference.
- Ensure that the installation, adjustment, and operation of the unit are done by qualified service personnel.
- Follow the instructions thoroughly to avoid improper installation, adjustment, service, or maintenance that may result in fire, electrical shock, property damage, personal injury, or death.
- Supervise children to prevent them from playing with the appliance.
- Install only approved matched indoor and outdoor systems for maximum efficiency, optimum performance, and system reliability.
- Follow the key symbols and safety instructions provided in the manual.
- Consider unit dimensions and location restrictions before installation.
- Prepare the unit for installation according to the preinstallation guidelines.
- Install the unit on a pad as per the pad installation instructions.
- Take into account the service valve connection sizes and refrigerant line sizes.
- Adhere to the refrigerant piping limits and required refrigerant line length.
- Insulate the refrigerant lines properly.
- If applicable, consider reusing existing refrigerant lines.
- Follow precautions for refrigerant line routing.
- Braze the refrigerant lines following the provided instructions.
- Perform a leak check to ensure there are no refrigerant line leaks.
- Evacuate the refrigerant lines and indoor coil.
- Open the service valves as instructed.
- Follow the low voltage electrical guidelines for wire length and hook-up diagrams.
- Ensure proper high voltage power supply, disconnect switch, and ground connections.
- Start up the system using the provided instructions.
- Adjust the system charge using either the weigh-in method or suction line pressure charging and refrigerant adjustment in cooling.
- Understand the system operation and troubleshooting guidelines, including information about the compressor crankcase heater, reversing valve, protection function, and defrost mode.
SAFETY INSTRUCTIONS
KEY TO SYMBOLS AND SAFETY INSTRUCTIONS
Key to Symbols
- Warnings in this document are identified by a warning triangle. Keywords at the start of a warning indicate the type and seriousness of the ensuing risks arising from failure to take measures.
- This symbol indicates important informationwhere there is no risk to people or property.
- The following keywords are defined and can be used in this document:
- DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
- WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
- CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury.
- NOTICE is used to address practices not related to personal injury.
Safety
Important – This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
CAUTION
This information is intended for use by individuals possessing adequate
backgrounds of electrical and mechanical experience. Any attempt torepair a
central air conditioning product may result in personal injury and/or property
damage. The manufacturer or seller cannot be responsible for the
interpretation of this information, nor can it assume any liability in
connection with its use.
WARNING
-
HAZARDOUS VOLTAGE! Failure to follow this warning could result in property damage, severe personal injury or death. Disconnect all electric power, including remote disconnects before service. Follow proper lockout /tagout procedures to ensure the power cannot be inadvertently energized.
-
REFRIGERANT OIL! Any attempt to repair a central air conditioning product may result in property damage, severe personal injury, or death. These units use R-410a refrigerant which operates at 50% to 70% higher pressures than R-22. Use only R-410a approved service equipments. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil (VG74 or equivalent) that readily absorbs moisture from the atmosphere. To limit this ‘hygroscopic“ action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement.
-
HIGH CURRENT LEAKAGE!
Failure to follow this warning could result in property damage, severe personal injury, or death. Earth connection is essential before connecting electrical supply. -
SERVICE VALVES!
Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and/or property damage. Extremecaution should be exercised when opening the Liquid Line Service valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. No torque is required. -
BRAZING REQUIRED!
Failure to inspect lines or use proper service tools may result in equipment damage or personal injury. If using existing refrigerant lines make certain that all joints are brazed, not soldered.
CAUTION
CONTAINS REFRIGERANT!
Failure to follow proper procedures can result in personal illness or injury
or severe equipment damage. Systems contain oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure before opening a system.
GROUNDING REQUIRED!
Failure to inspect or use proper service tools may result in equipment damage
or personal injury. Reconnect all grounding devices. All parts of this product
that are capable of conducting electrical current are grounded. If grounding
wires, screws, straps, clips, nuts, or washersused to complete a path to
ground are removed for service, they must be returned to theirB original
position and properly fastened.
HOT SURFACE!
May cause minor to severe burning. Failure to follow this caution could result
in property damage or personal injury. Do not touch the top of the compressor.
UNIT LOCATION CONSIDERATIONS
Unit Dimensions
Unit Dimensions
Model| H(inches)| W(inches)| L(inches)
18| 24-15/16| 23-5/8| 23-5/8
24/30| 24-15/16| 28| 28
36| 33-3/16| 28| 28
42/48/60/61| 33-3/16| 29-1/8| 29-1/8
Table 2-1
The unit’s weight value is on the cardboard box. When mounting the outdoor
unit on a roof, be sure the roof will support the unit’s weight. Properly
selected isolation is recommended to prevent sound or vibration transmission
to the building structure.
Location Restrictions
- Ensure the top discharge area is unrestricted for at least 60 inches above the unit.
- Do not locate outdoor unit near bedrooms since normal operational sounds may be objectionable.
- Position unit to allow adequate space for unobstructed airflow, wiring, refrigerant lines, and serviceability.
- Maintain a distance of 24 inches between units. 24 inches clearance must be provided in front of the control box (access panels) and any other side requiring service.
- Position unit where water, snow or ice from roof or overhang cannot fall directly on unit.
- Position the outdoor unit a minimum of 12″ from any wall or surrounding shrubbery to ensure adequate airflow. See Figure 2-2 and Figure 2-3
- Cold climate considerations (heat pump only)
NOTE: Precautions must be taken for units beinginstalled in areas where snow accumulation and prolonged below-freezing temperatures occur.
- Units should be elevated 3-12 inches above the pad or rooftop, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing.Ensure that drain holes in unit base pan are not obstructed, preventing drainage of defrost water (Fig. 2-4).
- If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow driftbarrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.
UNIT PREPARATION
Preinstallation
- STEP 1 – Check for damage and report promptly to the carrier any damage found to the unit (Fig.3-1).
- STEP 2 – Instruments must be designed to install/serve R410A equipments.
- Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle the POE type oils.
- Manifold sets should be 800 PSIG high side and 250 PSIG low side.
- All hoses must have a 700 PSIG service pressure rating.
- Leak detectors should be designed to detect R410A.
- Recovery equipments (including refrigerant recovery containers) must be specifically designed to handle R410A.
- Do not use a R22 TXV.
SETTING UP THE UNIT
Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following:
- The pad must be at least 1-2″ larger than the unit on all sides.
- The pad must be separate from any structure.
- The pad must be level.
- The pad must be high enough above grade to allow for drainage.
- The pad location must comply with National, State and Local codes.
NOTE: These instructions are intended to provide amethod to tie-down system to concrete slab as a securing procedure for high wind areas. Check Local Codes for tie-down methods and protocols.
REFRIGERANT LINE CONSIDERATIONS
Service Valve Connection Sizes
Models | Suction line connection | Liquid line connection |
---|---|---|
18/24/30/36 | 3/4 | **** |
3/8
42/48/60/61| 7/8
Refrigerant Line Sizes
Models
| Suction Line| Liquid Line
---|---|---
optional| standard| optional| standard
18/24/30/36| 5/8| 3/4| 5/16|
3/8
42/48| 3/4| 7/8| 1/2
60/61| 7/8| 1-1/8| 1/2
Table 5-2
Refrigerant Piping Limits And Required Refrigerant Line Length
Model
| Liquid line (inches)| Total equivalent length(Feet)
---|---|---
25| 50| 75| 100| 125| 150
Maximum vertical length(Feet)
18| 5/16| 25| 50| 60| 60| 40| 30
3/8| 25| 50| 60| 60| 40| 30
24| 5/16| 25| 40| 30| 20| 15| 10
3/8| 25| 50| 60| 60| 40| 30
30| 5/16| 25| 40| 40| 30| 40| 30
3/8| 25| 50| 60| 60| 40| 30
36| 5/16| 25| 50| 40| 30| 10| NA
3/8| 25| 50| 60| 60| 40| 30
42| 5/16| 25| 23| 4| N/A| NA| NA
3/8| 25| 50| 43| 36| 30| 24
48| 1/2| 25| 50| 56| 55| 40| 30
3/8| 25| 46| 38| 30| 22| 15
60/61| 1/2| 25| 50| 60| 60| 40| 30
3/8| 25| 50| 56| 44| 32| 20
Table 5-3 NOTE: Using suction line larger than shown in chart will result in poor oil return and is not recommended.For example: the system capacity published in AHRI is 17800 Btu/h. This data is based on the AHRI test condition and 25 feet line set with standard suction tube size (3/4″ tube). If you need to add the line set more than 25 feet or use the optional suction tube size, you need to recalculate the capacity with the coefficient in the table. For 50 feet line and 5/8″ suction tube, thecapacity will be 17800*0.97=17266 Btu/h.
Determine required line length and lift. You will need this later in Section 14.
- Total Line Length = __ Feet.
- Total vertical Change(Lift) = __ Feet.
Figure 5-2
The coil picture above in figure5-2 represents indoor unit, which includes
J4AH and JMM models.
Refrigerant Line Insulation
NOTE
The suction line must always be insulated. DO NOT allow the Liquid Line and
Suction Line to come in direct (metal to metal) contact.
Reuse Existing Refrigerant Lines
CAUTION
If using existing refrigerant lines make certain that all joints are brazed,
not soldered.
For retrofit applications, where the existing refrigerant lines will be used, the following precautions should be taken:
- Ensure that the size of the refrigerant lines is correct. Refer to Section 5.2 and Table 5-2.
- Ensure that the refrigerant lines are free of leaks, acid, and oil.
NOTE
The manufacturer recommends installing only approved matched indoor and
outdoor systems. All of the manufacturer’s split systems are AHRI certified.
Some of the benefits of installing approved matched indoor and outdoor split
systems are maximum efficiency, optimumperformance and the best overall system
reliability.
REFRIGERANT LINE ROUTING
Precautions
NOTE
- Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines. For example:
- When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
- Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
- Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
- Isolate the lines from all ductwork.
- Minimize the number of 90º turns.
- Use PVC piping as a conduit for all underground installations as shown in Figure 15. Buried lines should be keep as short as possible.
- The lines should not obstruct service access to the coil, air handling system or filter.
- Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.
- Comply with National, State, and Local codes when isolating linesets from joists, rafters, walls, or other structural elements.
REFRIGERANT LINE BRAZING
Braze The Refrigerant Lines
- Remove caps or plugs. Use a deburing tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.
- Remove the pressure tap cap from both service valves.
- Purge the refrigerant lines and indoor coil with dry nitrogen.
- Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge (Fig. 7-4). Braze the refrigerant lines to the service valves. Check liquid line filter drier’s directional flow arrow to confirm correct direction of refrigeration flow (awayfrom outdoor unit and toward evaporator coil) as illustrated. Brazing the filter drier to the Liquid Line. Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
- NOTE: Remove the wet rag before stopping the dry nitrogen purge.
- Replace the pressure tap caps after the service valves have cooled.
- NOTE: Do not over tighten (between 40 and 60 inch-lbs. maximum).
REFRIGERANT LINE LEAK CHECK
Check For Leaks
- Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.
- Check for leaks by using a soapy solution or bubbles at each brazed location.
- Remove nitrogren pressure and repair any leaks before continuing.
EVACUATION
Evacuate the Refrigerant Lines and Indoor Coil
NOTE
Do not open the service valves until there frigerant lines and indoor coil
leak check and evacuation are complete.
- Evacuate until the micron gauge reads no higherthan 350 microns, then close off the valve to the vacuum pump.
- Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
SERVICE VALVES
Open the Service Valves
WARNING
Extreme caution should be exercised when opening the Liquid Line Service
Valve. Turn counterclock wise until the valve stem justtouches the rolled
edge. No torque is required. Failure to follow this warning will result in
abrupt release of system charge and may result in personal injury and /or
property damage.
NOTE
Leak check and evacuation must be completed before opening the service valves.
- Remove Service Valve Cap (Fig. 10-1).
- Fully insert hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge.
- Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
ELECTRICAL – LOW VOLTAGE
Low Voltage Maximum Wire Length
Table 11-1 Defines the maximum total length of low voltage wiring from the outdoor unit to the indoor unit and to the thermostat.
24 Volts – Wire Size | Max. Wire Length |
---|---|
18 AWG | 150 Ft. |
16 AWG | 225 Ft. |
14 AWG | 300 Ft. |
Low Voltage Hook-up Diagrams
Figure 11-2
Notes: “—–”The electric auxiliary heat connection (optional).
- W: Electric auxiliary heat signal.
- W1: The first Electric auxiliary heat signal.
- W2: The second Electric auxiliary heat signal.
Figure 11-3
Notes: “ ” The electric auxiliary heat connection (optional).
- W : Electric auxiliary heat signal,connect to the Electric auxiliary heat or the first Electric auxiliary heat.
- W1 : The first Electric auxiliary heat signal.
- W2 : The second Electric auxiliary heat signal.
- Y2 : The second cooling signal, only for 61K HP system.
- Y1 and Y2 of INDOOR UNIT : Only for 61K HP system.
WARNING
Low Voltage line must be connected inside the outdoor unit case through
control wiring channel on the right. High Voltage line must be connected
through power wiring channel on the left. Mixed channel may result in personal
injury.
- During installation or maintenance, the tie of rubber ring on the electric control box shall not be cut with scissors. It can be untied by pressing the loose buckle. The tightening belt can be reused.
- After installation or maintenance, the tightening belt shall be tightened, can not be loosened or discarded; the control box access panel must be installed and the screws must be tightened.
ELECTRICAL – HIGH VOLTAGE
High Voltage Power Supply
WARNING LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and trouble shooting of this product,
it may be necessary to work with live electrical components. Failure tofollow
all electrical safety precautions when exposed to live electrical components
could result in death or serious injury. The high voltage power supply must
agree with the equipment nameplate. Power wiring must comply with National,
State and LocalCodes. Follow instructions on unit wiring diagram located on
the inside of the access panel.
High Voltage Disconnect Switch
Install a separate disconnect switch at the outdoor unit. Field provided
flexible electrical conduit must be used for high voltage wiring. High
Voltage Ground
Ground the outdoor unit per National, State and LocalCode requirements.
START UP
System Start Up
- Ensure Sections 7, 8, 9, 10, 11, and 12 have been completed.
- Set System Thermostat to OFF.
- Turn on disconnect to apply power to the indoor and outdoor units.
- Wait one (1) hour before starting the unit if compressor crankcase heater is used and the outdoor ambient temperature is below 70 ºF.
- Set system thermostat to ON.
SYSTEM CHARGE ADJUSTMENT
Charging: Weigh-In Method
Weigh-In method can be used for the initial installation,or anytime a system
charge is being replaced. Weigh-In Method can also be used when power is not
available to the equipment site or operating conditions (indoor/outdoor
temperatures) are not in range to verify with the suction line pressure
charging method.
Table 14-1
NOTE
The factory charge in the outdoor unit is sufficient for 15 feet of standard
size interconnecting liquid line.
New Installations — Calculating additional charge for
lineset greater than 15 feet.
- Total Line Length (ft) = _____(a)
- Standard Lineset (ft) = _____(b)
- (a) minus (b) = _____(c)
- Refrigerant Multiplier = _____(d)
- Refrigerant Adder (cd) = _____(e)
If lineset is less than 15 feet, (e) = 0Sealed-System Repairs — Calculating total system charge.
- Total Line Length (ft) = _____(a)
- Standard Lineset (ft) = _____(b)
- (a) minus (b) = _____(c)
- Refrigerant Multiplier = _____(d)
- Refrigerant Adder (cd) = _____(e)
- Factory Charge (namplate) = _____(f)
- Total System Charge (e+f) = _____
If lineset is less than 15 feet, (e) = 0
NOTE
The only mode approved for validating system charge is while in Cooling Mode. Outdoor temper -ature must be between 55°F and 115°F with Indoor Temperature kept between 70°F and 80°F.
Suction Line Pressure Charging And Refrigerant Adjustment In Coiling (above 55°F outdoor temp.)
- Check the outdoor ambient temperatures. Suction line pressure (in cooling mode) is the only recommended method of charging above 55ºFoutdoor ambient temperatures. For outdoor ambient temperatures below 55ºF, use weigh-in charge method.
- NOTE: **** It is important to return in the spring or summerto accurately charge the system in the cooling mode when outdoor ambient temperature is above 55ºF.
- Ensure Sections 7, 8, 9, 10,11,12 and 13 have been completed.
- Stabilize the system by operating for a minimum of 20 minutes.
- NOTE: At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made.
- Measured Suction Line Pressure = ____PSIG
- Outdoor Ambient Temperature = ___ ºF
- Indoor Ambient Temperature = ___ ºF
- Calculate Liquid Line Pressure = ____PSIG
- Measured Suction Line Temperature = __ºF
Design superheat with TXV throttle
Use the final superheat value, refrigerant temperature and pressure from STEP
4, to determine the proper suction gauge pressure using
Table 14-1.
Example: Assume a 12º F final superheat value and suction temp of 58º F.
- Locate 12º F final Superheat in Table 14-1.
- Locate the Suction Temperarature (58º F) in the left column.
- The Suction Gage Pressure should be approximately 133 PSIG. (This is the shown as the intersection of the Final Superheat column and the Suction
- Temperature row. Design Superheat Value = ____ºF
- Superheat Correction = ____ ºF Final Superheat Value = ____ ºF
- Adjust refrigerant level to attain proper final superheat.
NOTE
Add refrigerant if the measured superheat is higher than the final superheat
value.
- Connect gages to refrigerant bottle and unit as illustrated (Fig. 14-5).
- Purge all hoses.
- Open bottle.
- Stop adding refrigerant when gas line pressure matches the Refrigerant Charging Chart.
NOTE
Recover refrigerant if the measured superheat is lower than the final
superheat value.
Stabilize the system. Wait 20 minutes for the system condition to stabilize between adjustments.
NOTE
When the gas line pressure match the chart, the system is properly charged.
- Remove gages.
- Replace service port caps to prevent leaks. Tightenfinger tight plus an additional 1/6 turn.
- Record system Information for reference Table 14-2.
- Record system pressures and temperatures after charging is complete.
Description | Value |
---|---|
Outdoor model number | |
Measured Outdoor Ambient | °F |
Measured Indoor Ambient | °F |
Liquid Gage Pressure | PSIG |
Suction Gage Pressure | PSIG |
Suction Line Temperature | °F |
Table 14-2
SYSTEM OPERATION AND TROUBLESHOOTING
Compressor Crankcase Heater (CCH)
The crankcase heating start must meet two conditions:
- A. Outdoor temperature< 37.4°F
- B. At power up or if the compressor has been off for more than 3 hours
The crankcase heating stop must meet the following condition: Outdoor temperature>44.6°F or compressor starts.
Reversing Valve
Reversing valve energizes at the heating conditions, and cuts off at the
cooling condition.
Protection Function
Reversing valve energizes at the heating conditions, and cuts off at the
cooling condition.
- T3 = Outdoor Coil Temperature
- T3>143.6°F, compressor stops working
- T3< 125.6°F, compressor restarts working
- T4 = Ambient Temperature
- T4 < 5°F, compressor can’t start
- T4 > 10.4°F, compressor restarts working
- If 32°F ≤ T4 ≤ 120°F, unit can operate in cooling
- If 5°F ≤ T4 ≤ 75°F, unit can operate in heating
NOTE
When T4< 5°F, the outdoor unit would provide a signal to drive up the heater
installed in the indoor unit.
- Discharge temperature protection
- Discharge temperature > 239°F, compressor stops working.
- Discharge temperature < 167°F, compressor restarts working.
- High pressure protection
- High pressure > 638 PSIG, compressor and outdoor fan motor stop working.
- High pressure < 464 PSIG, compressor and outdoor fan motor restart working (3 minutes delay necessary).
- Low pressure protection
- Low pressure < 21 PSIG, compressor and outdoor fan motor stop working.
- Low pressure > 44 PSIG, compressor and outdoor fan motor restart working (3 minutes delay necessary).
NOTE
In stand-by status, the compressor will not startin low pressure protection.
Within 30 minutes, if 4 protection cycles occur. The system will be locked. It
will be restore after power cycle.
Defrost Mode
Manual defrost mode When the switch SW3-1 is set to “ON”, the system turns to
the defrost mode. The defrost mode exits by the logic of shut-down conditions
of defrost mode.
NOTE
Once the manual defrost mode is finished, please turn the switch SW3-1 back to
“off ”.
- Start-up conditions of defrost mode When SW3-3 switch is set to “ON” (Fig. 2-4), the mode
will start up in any of the following conditions:
- Compressor operates and T3 < 32°F for a period of 30 minutes.
- T3 < 28.4°F and compressor operates for the first time after connected to the power source.
- When T3 < 28.4°F and the system is on standby for two hours continuously.
When SW3-3 switch is set to “OFF”(Fig. 14-6), the mode will start up in any of the following conditions:
- Compressor operates and T3 < 32 °F for a period of 60 minutes.
- T3 < 28.4 °F and compressor operates for the first time after connected to the power source.
- When T3 < 28.4 °F and the system is on standby for two hours.
- Shut-down conditions of defrost mode:
The mode will shut down in any of the following conditions:
- The defrosted time lasts 10 minute.
- T3 ≥ 64.4°F and T4 ≥ 28.4°F. Compressor stops operating.
- T3 ≥ 64.4°F lasts 60 seconds when T4 < 28.4°F.
Two-stage Compressor (61K HP only)
The 61K HP Systems feature a Two-stage scroll compressor which is controlled by Y1 and Y2.
- Y1: 24VAC thermostat input for first stage operation of the unit.
- Y2: 24VAC thermostat input/output for second stage operation of the unit.
If the control receives a call for second−stage compressor operation Y2 in heating or cooling mode and the first-stage compressor output is active, the second-stage compressor solenoid output will be energized by the unit control system operation function. The unit control de−energizes the second-stage compressor solenoid output immediately when the Y2 signal is removed or the first-stage compressor output is de−energized for any reason.
Temperature Sensor Resistance Table
Table 15-1
Electrical Data Table
Model | 18 | 24 | 30 | 36 | 42 | 48 | 60 | 61 |
---|---|---|---|---|---|---|---|---|
Minimum circuit ampacity (A) | 13 | 15.5 | 17.2 | 23 | 26.9 | 29.6 | 34.6 | 37.9 |
Maximum circuit protector (A) | 20 | 25 | 30 | 40 | 50 | 50 | 60 | 60 |
Troubleshooting Table
Fault Code Table
For 18K-60K HP System
For 61K HP System
WARRANTY
Assist owner with processing Warranty cards and/or online registration.
Maintenance
- Dirt should not be allowed to accumulate on the indoor or outdoor coils or other parts in the air circuit. Clean as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment or other suitable means.
- The outdoor fan motor is permanently lubricated and does not require periodic oiling.
- Refer to the furnace or air handler instructions for filter and blower motor maintenance.
- The indoor coil and drain pan should be inspected and cleaned regularly to assure proper drainage.
NOTE
It is unlawful to knowingly vent, release or discharge refrigerant into the
open air during repair, service, maintenance or the final disposal of this
unit. When the system is functioning properly and the owner has been fully
instructed, secure the owner’s approval.
Removing and Installing The Cover Plate
- Before removing the cover plate of the electronic control box, plese be noted the screws 1 – 7 must be removed first.
- When install back the cover plate of the electric control box, plese be noted the screws 1 and 3 must be installed at the last step to facilitate assembly and avoid damage the waterproof sponge .
Changing Motor
When motor requires changing, follow the steps below:
- STEP 1 – Go into electrical panel, disconnect motor power lines.
- Note: Disconnect main power to unit. Severe burns and electrical shock will occur if you do not disconnect main power.
- STEP 2 – Remove cover (be careful of motor wires).
- STEP 3 – Be sure to place fan cover unit on the ground (Fig.16-2).
- Note: Do not place or lean fan blades on ground or against surface.
- STEP 4 – Remove fan motor by removing 5/16″ nuts from cover.
- STEP 5 – Remove fan blade from motor by removing 1/2″ nut and place fan on the ground.
- STEP 6 – Reverse removal process to reinstall the fan and motor.
- Note: When connecting motor wires be sure to check motor direction.
NOTE
- Damage will occur to condenser unit if you remove 5/16″ nuts prior to cover removal.
WIRING DIAGRAMS
For 18K-60K HP System
For 61K HP System
MATCHING TABLE AND CHECKOUT PROCEDURES
Matching Table
Condensing Unit| Air Handler / A-Coil| Piston Size / TXV Valve Model| SEER2|
If Preinstalled Piston Replace Required
---|---|---|---|---
J4HP5018E1000AA
| J4AH4P18E1A00AA| 4AYTXVH3G2436A| 14.3| YES
J4AH5E24E1B00AA| 4AYTXVH3G2436A| 15.2| YES
J4HP5024E1000AA
| J4AH4P24E1B00AA| 0.058/(4AYTXVH3G2436A)| 14.3| NO
J4AH5E24E1B00AA| 4AYTXVH3G2436A| 15.2| YES
J4HP5030E1000AA
| J4AH4P36E1B00AA| 4AYTXVH3G2436A| 14.3| YES
J4AH5E36E1B00AA| 4AYTXVH3G2436A| 15.2| YES
J4HP5036E1000AA
| J4AH4P36E1B00AA| 4AYTXVH3G2436A| 14.3| YES
J4AH5E36E1B00AA| 4AYTXVH3G2436A| 15.2| YES
J4HP5042E1000AA
| J4AH4P48E1C00AA| 4AYTXVH3G4248A| 14.3| YES
J4AH5E60E1C00AA| 4AYTXVH3G4248A| 15.2| YES
| J4AH4P48E1C00AA| 4AYTXVH3G4248A| 13.8| YES
J4HP5048E1000AA| J4AH5E60E1C00AA| 4AYTXVH3G4248A| 15.2| YES
J4HP5060E1000AA| J4AH5E60E1C00AA| 4AYTXVH3G6000A| 14.3| YES
J4HP5061E1000AA| J4AH5E61E1C00AA| 4AYTXVH3G6000A| 15.2| YES
Operational and Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts of the Outdoor Unit. After installation has been completed, it is recommended that the entire system be checked against the following list:
- Be sure unit suspension (if used) is secure and that there are no tools or loose debris in or around or on top of the unit
- Properly insulate suction lines and fittings
- Properly secure and isolate all refrigerant lines
- Verify that all electrical connections are tight
- Check all duct outlets; they must be open and unrestricted
- Check drain lines and be sure all joints are tight
- Be sure that a return air filter is installed
- Operate complete system in each mode to verify proper performance. Verify operation of supplementary electric heater
CONTACT
- TwentyThreeC, LLC
- 800 Beaty Street,
- Davidson,NC, 28036
- For more information contact your local dealer (distributor)
- www.oxboxhvac.com.
- Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change the design and specification without notice.
- c . 2019 TwentyThreeC, LLC
Thank you very much for purchasing our product. Before using your unit, please read this manual carefully and keep it for future reference. The figure shown in this manual is for reference only and may be slightly different from the actual product.
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
WARNING
These instructions are intended as an aid to qualified licensed service
personnel for proper installation, adjustment and operation of this unit. Read
these instructions thoroughly before attempting installation, or operation.
Failure to follow these instructions may result in improper installation,
adjustment, service, or maintenance possibly resulting in fire, electrical
shock, property damage, personal injury, or death.
WARNING
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.This unit is
only used outdooR.
WARNING
This product can expose you to chemicals including lead, which are known to
the state of California to cause cancer and birth defects or other
reproductive harm. For more information go to
www.p65Warnings.ca.gov.
NOTE
The manufacturer recommends installing only approved matched indoor and
outdoor systems. All of the manufacturer’s split systems are AHRI rated .Some
of the benefits of installing approved matched indoor and outdoor split
systems aremaximum efficiency, optimum performance, and the best overall
system reliability.