Carrier TV-UC253-V TruVu Advanced Application Controller Owner’s Manual

June 13, 2024
Carrier

Carrier TV-UC253-V TruVu Advanced Application Controller Owner’s Manual
Carrier TV-UC253-V TruVu Advanced Application
Controller

Application Features

  • Versatile controller suitable for a variety of applications, including: small AHUs, fan coils, exhaust fans

  • Standard library of control programs available for most unitary equipment and zone applications
    Supports Snap graphical programming software

  • Supports Carrier communicating sensors, which are available in a variety of zone and equipment sensing combinations

  • Supports Carrier Truven touchscreen interfaces for managing and troubleshooting the connected equipment easily and for occupant engagement

  • Supports live, visual displays of control logic, which uses real time operational data and aids in optimizing and troubleshooting system operations

Hardware Features

  • Hardware Features
  • Dual 10/100 MPs, BACnet IP and IP addressing
  • Supports home run, daisy chain and ring IP network topologies
  • Capacitor-backed real-time clock keeps time in the event of power failure or network interruption for at least three days
  • Integral airflow sensor
  • USB port for local device updates, hard-wired, and wireless service connections
  • DIN rail or screw mounting

System Features

  • Connects seamlessly to the i-Vu building automation system

Specifications

BACnet performance
Conforms to the BACnet Advanced Application Controller (B-AAC) and BACnet Broadcast Management Device (B-BBMD) standard device profiles, as defined in BACnet 135-2001 2012 Annex L Protocol Rev 14

Power
24Vac +/- 15% , 50 – 60Hz, 55VA | 24Vdc +/- 10%, 20W. (80VA / 35W if additional Act Net devices are connected)

Communication

  • BAS Primary: Dual 10/100 BaseT Ethernet ports with built-in fail safe, supporting direct connection or daisy chain
  • port: topology natively using BACnet/IP (non-routing)
  • Rnet port: 12Vdc @ 260mA Supports the following: Up to 5 ZS sensors (freely mix ZS zone, ZS duct, ZS immersion and ZS outdoor sensors), Equipment Touch, or True Vu ET Displays (external power required)
  • Act Net port: Supports up to 5 Act Net communicating devices such as the i-Vu Smart Valves and Smart Damper Kit
  • USB Service port: For Truven ET Display support |configuration | wireless service access | firmware updates and controller recovery via USB drive
  • USB Expansion port: For support of comma expansion devices (future

Inputs

  • Universal: 5 Universal Inputs electronically configurable to any of the following types: Dry | Pulse Counting |Thermistor | 0-10 Vdc
  • Auxiliary Power: 24Vdc @ 100mA total current capacity

Integral Airflow Sensor
Precision differential pressure sensor 0–2 in. H2O, sensitive down to ±0.001 in. H2O. Barbed tapered airflow connections accept 3/16 in. (4.75 mm) I.D. tubing. Allows for readings across the 0–2in. H2O range, accurate to ±5% of full flow at 2 in. H2O

Outputs

  • Universal output : 1 Output selectable to 0–10 Vdc (20 mA max), 12 Vdc 80 Hz PWM, or (Dry Contact) Rated @24VAC 1 Amp
  • Analog Output: 2 Analog Outputs 10Vdc @ 20mA max (D/A Resolution 12 bits)
  • Digital output: 2 Digital outputs (Dry Contact) Rated @24Vac/Vdc 1 Amp. Configured normally open

Memory
4 GBs eMMC Flash memory and 256 MB DDR3 DRAM. User data is archived to non- volatile flash memory when parameters are changed, every 90 seconds

Real Time Clock
Real-time clock keeps track of time in the event of a power failure for at least 3 days

Compliance

  • United States: FCC compliant to Title CFR47, Part 15, Subpart B, Class A; UL Listed, File E143900; CCN PAZX, UL 916, Energy Management Equipment;
  • ANZ: RCM Mark AS/NZS 61000-6-3;
  • Canada: UL Listed File E143900, CCN PAZX7, CAN/CSA C22.2 No. 205 Signal Equip., Industry Canada Compliant ICES-003,
  • Class A; CE Mark Compliant with 2014/30/EU, and RoHS
  • Compliant: 2015/863/EU; UKCA Mark compliant with Electromagnetic Compatibility Regulations 2016 – Gov.UK and RoHS for Electrical and Electronic Equipment 2012.

Plastic Rating
Fire-retardant plastic ABS, UL94-5VA

Environmental

  • Operating Range: -22 to 158°F (-30 to 70°C), 10-95% RH, non-condensing
  • Storage: -40 to 158°F (-40 to 70°C), 10-95% RH, non-condensing

Physical

Minimum panel depth: 2.75 in. (7 cm)

Dimensions

Overall

  • A: 7.785 in. (19.77 cm)

  • B: 4.89 in. (12.43 cm)

  • Depth: 2.00 in. (5.09 cm)

  • Weight: 1.6 lb. (0.82 kg)
    Screw Mounting

  • C: 6.45 in (16.38 cm) (fully extended)

  • D: 4.5 in. (11.43 cm)

DIN rail or Screw mounting
Dimensions

©Carrier 2021. All Rights Reserved. Cat. No. 11-808-864-01 Rev. 12/22 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs, without notice and without incurring obligations. Trademarks are properties of their respective companies and are hereby acknowledged.

For more information, contact
your local Carrier Controls Expert.
Controls Expert Locator:
www.carrier.com/controls-experts

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals