TRANE SO-SVN006A Danfoss Dual Transducer Installation Guide

June 13, 2024
Trane

Installation Instructions
Danfoss Dual Transducer
Waterbox Mounting

SO-SVN006A Danfoss Dual Transducer

This document applies to service offering applications only.
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Introduction

Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
    ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.

  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.

  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.

  • All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • Non-Trane personnel should always follow local regulations.

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

Document updated to reflect Service Offering number.

General Information

Mounting of Flow Measurement Assembly
This guidance is for mounting transducers on a wide variety of water boxes including marine type, non-marine type, for both 150 and 300 PSI applications in both fabricated steel and castiron construction.
Waterbox Types
Figure 1. Fabricated non-marine – 3/4-inch NPTI port (requires 3/4-inch NPTI to 1/2-inch NPTI bushing) Figure 2. Fabricated marine – 3/4-inch NPTI port (requires 3/4-inch NPTI to 1/2-inch NPTI bushing) Figure 3. Cast – 1/2-inch NPTI port (threads directly into port)

Parts List

Qty Part Number Description
4 BUS00006 ¾-in. NPTI to ½-in. NPTI reducer bushing
4 BUS00589 Reducer Pipe; Hex Bushing, 0.75 NPTE x 0.25 NPTI
4 WEL00859 Bulb Assembly, 1/2-14-in. NPT, 4.62-in. Overall
4 PLU00001 Plug; Pipe, 1/4-in. NPT
4 NIP00095 Nipple; 0.25 NPS x 1.50
4 VAL11188 Valve; Angle; 0.25 NPTF x 0.25 ACC x 0.25 NPTF
4 NIP00428 Nipple; 0.25 NPS x 0.88 304 SSTL
4 SRA00199 Strainer; Y-Type, 1/4-in. FPT – Cleanable
4 ADP01517 Brass angle fitting
4 TDR00735 Transducer: pressure; 475 PSIA, female flare
4 CAB01147 Harness; Branching, Male to 2 Female 39.37

Installation

Preparation of Wells
Install the provided well using bushings as needed. Waterbox Valve Mounting

  1. Mount transducers on the entering and leaving side water box locations with:
    • the strainer horizontal
    • the strainer cleanout port pointing down
    • the transducer facing upwards

  2. After system is filled, loosen the transducer in its threaded fitting.

  3. Crack the isolation valve until water starts dripping from threads.

  4. Close the valve and re-tighten the transducer.

  5. Reopen the valve for use.

  6. Connect pressure to unit control buss after bleeding and bind to AdaptiView or Symbio controller.
    • For horizontal well mounting place ¾-in. to ¼-in. bushing and ¼-in. plug in end of well. • For vertical well mounting place ¾-in. to ¼-in. bushing in end of well and ¼-in. plug on the side of well.

Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

SO-SVN006A-EN 31 Aug 2023
Supersedes PART-SVN254A-EN (Mar 2022)
©2023 Trane
August 2023
SO-SVN006A-EN

Documents / Resources

| TRANE SO-SVN006A Danfoss Dual Transducer [pdf] Installation Guide
SO-SVN006A-EN, SO-SVN006-EN, SO-SVN006A Danfoss Dual Transducer, Danfoss Dual Transducer, Dual Transducer, Transducer
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals