Product Information
- Product Name: Motion Detector 353-852011
- Model Number: 5413736374249
- Dimensions: 70.7 mm (a), 45 – 65 mm (b)
- Power: 230 V/DALI
- Installation: Surface Mounting
Product Usage Instructions
- Ensure that the power supply is turned off (230 V/DALI power – OFF).
- Secure the product with a miniature circuit breaker (MCB) of max. 16 A in the electrical cabinet. The MCB rating should comply with national installation rules.
- Wiring Connections:
- Connect DA-, DA+, L, and N to the corresponding terminals in DALI zone 1.
- Connect DA, L, and N to the corresponding terminals in DALI zone 2.
- Connect DA, L, and N to the corresponding terminals in DALI zone 3.
- Connect T1 and T2 to the respective terminals.
- If using a BMS system, connect the BMS terminals as specified.
- Mount the motion detector on the surface using suitable screws or mounting brackets.
- If replacing a grommet, ensure that the new grommet is halogen-free.
- For advanced settings, refer to the BMS software instructions and configure the memory bank addresses accordingly.
- To dismantle the product, turn off the power supply (230 V/DALI power – OFF) and follow the disassembly instructions.
- For additional information and troubleshooting, refer to the user manual.
Installation
230 V/DALI power – OFF
If a grommet needs to be replaced, please make sure the new grommet is halogen-free.
Dismantling
App settings
Settings by BMS software
Table memory bank 2
Address| Description| Default value| Memory type
0x00| Address and last accessible memory location| 0x03| ROM
0x01| Indicator byte (manufacture definable)| 0x00| any
0x02| Memory bank lock byte (<>0x55 = Read Only else Read/ Write)| 0xFF| RAM
0x03| PIR sensitivity segment A (MR, LR and HC detectors) 4 = MAX 3 = HIGH 2 =
LOW 1 = MIN 0 = OFF| 0x03| NVM
0x04| PIR sensitivity segment B (LR and HC detectors)
4 = MAX 3 = HIGH 2 = LOW 1 = MIN 0 = OFF
| 0x03| NVM
0x05| PIR sensitivity segment C (LR and HC detectors)
4 = MAX 3 = HIGH 2 = LOW 1 = MIN 0 = OFF
| 0x03| NVM
0x06| LUX range
0 = NORMAL 0 – 1023 lux, 10-bit
1 = HIGH 0 – 10360 lux, 14 bit
| 0x00| NVM
0x07| Bluetooth® communication 0 = enabled, 1 = disabled| 0x00| NVM
LED behaviour
Green LED continuous on| | Connection OK|
---|---|---|---
Green LED flashing| | Warming up*| Wait
Red LED continuous on| ****| Error| More info – >
Blue LED flashing| ****| Walk test active
When Bluetooth® communication is disabled, the green LED does not flash while warming up.
Specifications
- Article number 353-852011
- Configuration DALI-2 secondary/BMS
- Input voltage via the DALI bus
- Maximum current consumption 28.1 mA
- Nominal current consumption (12 V, 25°C) Bluetooth® enabled 8.1 mA
- Nominal current consumption (12 V, 25°C) Bluetooth® disabled 5.0 mA
- Maximum startup time DALI < 1200 ms
- Maximum PIR detection startup time 70 s
- Detection angle 360 °
- Detection range (PIR) ø 53 m from a height of 12 m
- Light intensity range 0 – 10360 lux (see DALI BMS settings)
- Ambient temperature -25 – +40 °C
- Mounting method surface mounting
- Mounting height 4 – 12 m
- Colour white (RAL 9010)
- Dimensions visible (HxWxD) 100 x 100 x 70.7 mm
- Dimensions (HxWxD) 100 x 100 x 70.7 mm
- Wire capacity 1.5/2.5 mm²
- Maximum range Bluetooth® (free field, depending on the device) 50 m
- Operating frequency 2.4 GHz
- Maximum radio frequency power -2 dBm
- Protection degree IP54
- Impact resistance IK04
- Modification of settings app (iOS/Android) and 2-way Bluetooth® communication / BMS software
- Halogen-free yes
- Marking CE
Detection area
Troubleshooting
Motion detector M46HC, DALI-2, secondary and BMS, high ceiling, 18-53 m, 360°,for surface mounting
Wiring
Secondary
This product must be secured with a miniature circuit breaker (MCB) of max. 16 A in the electrical cabinet. The MCB rating is limited by national installation rules.
BMS
Dimensions
Support & contact
+32 3 778 90 80 support@niko.eu
Niko prepares its manuals with the greatest care and strives to make them as complete,correct and up to date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>