Honeywell 2108N Searchpoint Optima Plus Infrared Gas Detector for Hydrocarbon Gases User Manual

June 4, 2024
Honeywell

2108N Searchpoint Optima Plus Infrared Gas Detector for Hydrocarbon Gases

Safety Manual Search point Optima Plus

1. Safety Parameters

The Searchpoint Optima Plus safety parameters listed below were provided by TÜV in report
968/EZ 559.04/18.

SFF

|

PFDavg

|

PFH

---|---|---

90%

|

2.6×10-4

|

5.8×10-8

SFF: Safe Failure Fraction. A percentage of safe failures as compared to all failures PFDavg: Average probability of failure to perform its design function on demand

PFH: Probability of a dangerous failure per hour

1.1 Proof Test Interval

The purpose of a proof test is to return the unit to “as new” in terms of its safety parameters. The proof test interval is 1 year.

According to IEC 61508, users are allowed to extend the proof test interval to meet their system needs.  Honeywell allows such an extension, as long as the user follows the proper calculation method for  calculating a proof test interval as defined in IEC 61508 for the desired SIL level. This proof test interval will  vary depending on system, hardware architecture and application.

Note: The proof test interval should not preclude more frequent maintenance of Search point Optima Plus in  accordance with the Operating Instructions if site conditions require it.

1.2 Special Notes

  1. The HART® Communications and the RS485 link must not be used for safety purposes.
  2. Under a certain extremely rare combination of fault conditions, there is a risk that Search point Optima Plus could output >100 mA. Should a customer be concerned about this, it is recommended that a suitable fuse is fitted in the 4-20 mA output line.
  3. Searchpoint Optima Plus must be protected from over voltage conditions (i.e. above the supply voltage specification).

2. Proof test using SHC1 Handheld Interrogator

13. Replace the Dust Barrier and Standard Weather Protection.
14. Press Escape then Enter to release the 4-20 mA output signal.
15. Press Escape to return to the main menu.
16. Select Diagnose then Soft Reset to clear any faults or warnings that may have been generated by
cleaning.
17. Press Escape to return to the main menu.
2.1.2 Inspection of a unit fitted with a Flow Housing
Searchpoint Optima Plus should be inspected and cleaned.

Caution: Gas readings may be generated during this procedure.

  1. Select Calibrate then Display to inhibit the 4-20 mA output signal.

  2. Inspect the Searchpoint Optima Plus unit, its junction box and cabling for any signs of physical damage.

  3. Disconnect any pipework attached to the flow housing.

  4. Using a ½ inch / 13 mm A/F open ended spanner, remove the two black nuts which retain the flow housing. Keep the O-ring seals which are below the retaining nuts.

  5. Slide the flow housing off the Searchpoint Optima Plus. This may require some force due to the friction of the O-ring.

  6. Clean any dust or contaminants from the optics using mild detergent and a soft cloth or cotton bud.
    Do not use solvents or abrasive cleaners.

  7. Press Escape then Enter to release the 4-20 mA output signal.

  8. Block the optical beam (for example using the cleaning cloth)

  9. Confirm that a fault is generated on the 4-20 mA output, either locally or at the controller.
    Note: The 4-20 mA output can be monitored either at the control room or locally with a multimeter. When connecting or disconnecting a multimeter, power off the Searchpoint Optima Plus, otherwise the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs it can be cleared by performing a Soft Reset.

  10. Remove the blockage from the beam

  11. Select Calibrate then Display to inhibit the 4-20 mA output signal.

  12. Ensure that the large sealing O-ring in the body of the flow housing, and the two small O-rings which go below the retaining nuts, are clean and in good condition. Replace if in doubt.

  13. Slide the flow housing over the end of the Searchpoint Optima Plus and push until the flow housing is firmly seated.

  14. Re-fit the O-rings and retaining nuts.

  15. Press Escape then Enter to release the 4-20 mA output signal.

  16. Press Escape to return to the main menu.

  17. Select Diagnose then Soft Reset to clear any faults or warnings that may have been generated by cleaning.

  18. Press Escape to return to the main menu.

2. Proof test using

SHC1 Handheld Interrogator

2.2 Re-zero Searchpoint Optima Plus

  1. Select Calibrate then CalSensor. (This will inhibit the 4-20 mA output signal).

  2. Ensure that there is zero gas present in the vicinity of the Searchpoint Optima Plus. If necessary, fit a Gassing Cover and apply zero gas.

  3. Press Enter.
    When the process is complete the display will state Zero Calibrated. It will then show options to continue to a span calibration, or to exit calibration.

  4. Press Escape to exit calibration.

  5. Press Enter to release the 4-20 mA output signal.

  6. Press Escape to return to the main menu.

Note: If the option to Calibrate Span is selected in error, press Escape.

2.3 Bump Test (Gas Challenge)

2.3.1 Bump Test (Gas Challenge) for a unit fitted with a Standard
Weather Protection

Searchpoint Optima Plus should be functionally checked using an appropriate test gas.
Caution: Gas readings will be generated during this procedure.
Note: The unit should be powered up for 1 hour before a gas test is done.

1. Fit a Gassing Cover to the Searchpoint Optima Plus, if not already in place.
2. Apply an appropriate test gas at a rate of 1 – 1.5 liters per minute for ~ 30 – 60 s.
3. Check that the Searchpoint Optima Plus responds to the test gas.
4. Remove the Gassing Cover and wait for the test gas to clear (~ 30 s). Ensure that the gas reading has returned to zero.

2.3.2 Bump Test (Gas Challenge) for a unit fitted with a Flow Housing

Searchpoint Optima Plus should be functionally checked using an appropriate test gas.
Caution: Gas readings will be generated during this procedure.
Note: The unit should be powered up for 1 hour before a gas test is done.

  1. Apply an appropriate test gas, using the same flow rate as the sampling system in which the Searchpoint Optima Plus is installed.
  2. Check that the Searchpoint Optima Plus responds to the test gas.
  3. Apply zero gas and wait for the gas reading to return to zero.

2. Proof test using

SHC1 Handheld Interrogator

2.4 Fix the 4-20 mA Output

The 4-20 mA output can be set to a fixed value, to prove correct operation of the 4-20 mA loop.
Note: The 4-20 mA output can be monitored either at the control room or locally with a multimeter. When connecting or disconnecting a multimeter, power off the Searchpoint Optima Plus, otherwise the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs it can be cleared by performing a Soft Reset.

  1. Select Calibrate then Force 4-20.
  2. Use ▲ and ▼ to set the mA value to 4 mA and press Enter.
  3. Check that Searchpoint Optima Plus outputs the set mA value.
  4. When the test is complete, press Enter.
  5. Repeat steps 2 – 4 for mA values of 12 mA and 20 mA.
  6. Press Enter to release the 4-20 mA output signal.
  7. Press Escape to return to the main menu.

3. Proof test using HART® Communications

Use these proof test instructions if the HART® Communications are
being used to communicate with Searchpoint Optima Plus.
Note: The instructions that follow assume that a suitable HART® host (handheld or PC) is connected to the Searchpoint Optima Plus and that the user is logged in with Level 1 access privileges. See the Searchpoint Optima Plus Operating Instructions, 2108M0550, for further information about the operation of the HART® Communications.

3.1 Inspection

3.1.1 Inspection of a unit fitted with a Standard Weather Protection

Searchpoint Optima Plus should be inspected and cleaned.
Caution: Gas readings may be generated during this procedure. Follow the steps to inhibit the
4-20 mA output. Ensure that the unit is not left in Inhibit mode.

1. Select Device Setup.
2. Select Test.
3. Select Inhibit.
4. Select Start Inhibit and press Enter.
5. The display shows a confirmation message. Press OK. The 4-20 mA output is now inhibited.
6. Inspect the Searchpoint Optima Plus unit, its junction box and cabling for any signs of physical damage.
7. Using a ½ inch / 13 mm A/F open ended spanner, unscrew the two retaining nuts and remove the Standard Weather Protection.
8. Inspect the Standard Weather Protection for damage or build up of debris / contaminants. If required,
clean or replace weather protection.
9. Inspect the Dust Barrier and clean or replace if required.
10. Remove the Dust Barrier and inspect the optics.
11. Clean any dust or contaminants from the optics using mild detergent and a soft cloth or cotton bud.
Do not use solvents or abrasive cleaners.
12. Select Inhibit.
13. Select End Inhibit and press Enter.
14. The display shows a confirmation message. Press OK to release the 4-20 mA output.
15. Block the optical beam (for example using the cleaning cloth)

3. Proof test using HART® Communications

16. Confirm that a fault is generated on the 4-20 mA output, either locally or at the controller.
Note: The 4-20 mA output can be monitored either at the control room or locally with a multimeter. When connecting or disconnecting a multimeter, power off the Searchpoint Optima Plus, otherwise the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs it can be cleared by performing a Device Reset.
17. Remove the blockage from the beam.
18. Select Inhibit.
19. Select Start Inhibit and press Enter.
20. The display shows a confirmation message. Press OK. The 4-20 mA output is now inhibited.
21. Replace the Dust Barrier and Standard Weather Protection.
22. Select Device Reset to clear any faults or warnings that may have been generated by cleaning.
23. Press OK to initiate a Device Reset.
24. The display shows a confirmation message. Press OK.
25. The display shows a note that the Searchpoint Optima Plus will return to normal operation, press OK.
26. Select Inhibit.
27. Select End Inhibit and press Enter.
28. The display shows a confirmation message. Press OK to release the 4-20 mA output.
29. Return to the Welcome screen.

3.1.2 Inspection of a unit fitted with a Flow Housing

Searchpoint Optima Plus should be inspected and cleaned.
Caution: Gas readings may be generated during this procedure. Follow the steps to inhibit the
4-20 mA output. Ensure that the unit is not left in Inhibit mode.
1. Select Device Setup.
2. Select Test.
3. Select Inhibit.
4. Select Start Inhibit and press Enter.
5. The display shows a confirmation message. Press OK. The 4-20 mA output is now inhibited.
6. Inspect the Searchpoint Optima Plus unit, its junction box and cabling for any signs of physical damage.
7. Disconnect any pipework attached to the flow housing.
8. Using a ½ inch / 13 mm A/F open ended spanner, remove the two black nuts which retain the flow housing. Keep the O-ring seals which are below the retaining nuts.
9. Slide the flow housing off the Searchpoint Optima Plus. This may require some force due to the friction of the O-ring.
10. Clean any dust or contaminants from the optics using mild detergent and a soft cloth or cotton bud.
Do not use solvents or abrasive cleaners.
11. Select Inhibit.
12. Select End Inhibit and press Enter.
13. The display shows a confirmation message. Press OK to release the 4-20 mA output.
14. Block the optical beam (for example using the cleaning cloth).

3. Proof test using HART® Communications

15. Confirm that a fault is generated on the 4-20 mA output, either locally or at the controller.
Note: The 4-20 mA output can be monitored either at the control room or locally with a multimeter. When connecting or disconnecting a multimeter, power off the Searchpoint Optima Plus, otherwise the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs it can be cleared by performing a Device Reset.
16. Remove the blockage from the beam.
17. Select Inhibit.
18. Select Start Inhibit and press Enter.
19. The display shows a confirmation message. Press OK. The 4-20 mA output is now inhibited.
20. Ensure that the large sealing O-ring in the body of the flow housing, and the two small O-rings which go below the retaining nuts, are clean and in good condition. Replace if in doubt.
21. Slide the flow housing over the end of the Searchpoint Optima Plus and push until the flow housing is firmly seated.
22. Re-fit the O-rings and retaining nuts.
23. Select Device Reset to clear any faults or warnings that may have been generated by cleaning.
24. Press OK to initiate a Device Reset.
25. The display shows a confirmation message. Press OK.
26. The display shows a note that the Searchpoint Optima Plus will return to normal operation, press OK.
27. Select Inhibit.
28. Select End Inhibit and press Enter.
29. The display shows a confirmation message. Press OK to release the 4-20 mA output.
30. Return to the Welcome screen.

3.2 Re-zero Searchpoint Optima Plus

Caution: During this procedure the 4-20 mA output will be inhibited automatically. If the procedure is aborted, ensure that the unit is not left in Inhibit mode.
Note: the calibration routine will timeout after 2 minutes of inactivity.
1. Select Device Setup.
2. Select Calibrate.
3. Select Gas Calibration.
4. The display shows a warning message, press OK.
5. Ensure that there is zero gas present in the vicinity of the Searchpoint Optima Plus. If necessary, fit a Gassing Cover and apply zero gas.

3. Proof test using HART® Communications

6. When the gas reading on the display is stable press OK to initiate the Zero Calibration and then wait for
approximately 15s. The 4-20 mA output will be inhibited automatically at this time.
7. The display shows a message that the Zero Calibration was successful and offers to exit without a Span
Calibration. Select Yes and press Enter.
8. The display shows a note that the Searchpoint Optima Plus will return to normal operation,
press OK.
9. Return to the Welcome screen.

3.3 Bump Test (Gas Challenge)

3.3.1 Bump Test (Gas Challenge) for a unit fitted with a Standard
Weather Protection

Searchpoint Optima Plus should be functionally checked using an appropriate test gas.
Caution: Gas readings will be generated during this procedure.
Note: Do not use the HART® Communications Bump Test routine as this will automatically inhibit the 4-20 mA signal.
Note: The unit should be powered up for 1 hour before a gas test is done.
1. Fit a Gassing Cover to the Searchpoint Optima Plus.
2. Apply an appropriate test gas at a rate of 1 – 1.5 litres per minute for ~ 30 – 60 s.
3. Check that the Searchpoint Optima Plus responds to the test gas. The live gas concentration is shown on the screen.
4. Remove the Gassing Cover and wait for the test gas to clear (~ 30 s). Ensure that the gas reading has returned to zero.

3.3.2 Bump Test (Gas Challenge) for a unit fitted with a Flow Housing

Searchpoint Optima Plus should be functionally checked using an appropriate test gas.
Caution: Gas readings will be generated during this procedure.
Note: Do not use the HART® Communications Bump Test routine as this will automatically inhibit the 4-20 mA signal.
Note: The unit should be powered up for 1 hour before a gas test is done.
1. Apply an appropriate test gas, using the same flow rate as the sampling system in which the Searchpoint Optima Plus is installed.
2. Check that the Searchpoint Optima Plus responds to the test gas.
3. Apply zero gas and wait for the gas reading to return to zero.

3.4 Fix the 4-20 mA Output

The 4-20 mA output can be set to a fixed value, to prove correct operation of the 4-20 mA loop.
Note: This function will timeout after 10 minutes of inactivity.
Note: The 4-20 mA output can be monitored either at the control room or locally with a multimeter. When connecting or disconnecting a multimeter, power off the Searchpoint Optima Plus, otherwise the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs, it can be cleared by performing a Device Reset.
1. Select Device Setup.
2. Select Test.
3. Select mA Loop Test.
4. The display shows a warning message, press OK.
5. Select 4 mA as the required analogue output level and press Enter.
6. Check that Searchpoint Optima Plus outputs the set mA value.
7. When ready, press OK.
8. Repeat steps 4 to 7 for mA values of 12 mA and 20 mA, then select End.
9. The display shows a note that the Searchpoint Optima Plus will return to normal operation, press OK.
10. The display shows a confirmation message, return to the Welcome screen.

4. Proof test for a Searchpoint Optima Plus

being used with an XNX Universal Transmitter

Use these proof test instructions if Searchpoint Optima Plus is being
used with an XNX Universal Transmitter.

Note: If Searchpoint Optima Plus is being used with the XNX Universal Transmitter, it must be tested as part of a system with XNX. Therefore in addition to the proof test detailed below, also complete the XNX proof test described in the XNX Safety Manual. See the XNX Quick Start Guide and the XNX Technical Manual for further information about the operation of the XNX Universal Transmitter.

4.1 Inspection

4.1.1 Inspection of a unit fitted with a Standard Weather Protection

Searchpoint Optima Plus should be inspected and cleaned.
Caution: Gas readings may be generated during this procedure.
1. Select Test Mode, then Inhibit and Set Inhibit On to inhibit the 4-20 mA output signal.
2. Inspect the Searchpoint Optima Plus unit, its junction box and cabling for any signs of physical damage.
3. Using a ½ inch / 13 mm A/F open ended spanner, unscrew the two retaining nuts and remove the Standard Weather Protection.
4. Inspect the Standard Weather Protection for damage or build up of debris / contaminants. If required, clean or replace weather protection.
5. Inspect the Dust Barrier and clean or replace if required.
6. Remove the Dust Barrier and inspect the optics.
7. Clean any dust or contaminants from the optics using mild detergent and a soft cloth or cotton bud.
Do not use solvents or abrasive cleaners.
8. Block the optical beam (for example using the cleaning cloth).

9. Confirm that a fault is generated by viewing the indication on the XNX display.
10. Remove the blockage from the beam.
11. Replace the Dust Barrier and Standard Weather Protection.
12. Select Set Inhibit Off to release the 4-20 mA output signal.
13. Return to the main menu.
14. Select Calibration Mode then Soft Reset to clear any faults or warnings that may have been generated by cleaning.

4. Proof test for a Searchpoint Optima Plus

being used with an XNX Universal Transmitter

4.1.2 Inspection of a unit fitted with a Flow Housing

Searchpoint Optima Plus should be inspected periodically and cleaned if necessary. The required frequency of inspection will depend on local site conditions and will need to be established through experience.
Caution: Gas readings may be generated during this procedure.
1. Select Test Mode, then Inhibit and Set Inhibit On to inhibit the 4-20 mA output signal.
2. Inspect the Searchpoint Optima Plus unit, its junction box and cabling for any signs of physical damage.
3. Disconnect any pipework attached to the flow housing.
4. Using a ½ inch / 13 mm A/F open ended spanner, remove the two black nuts which retain the flow housing. Keep the O-ring seals which are below the retaining nuts.
5. Slide the flow housing off the Searchpoint Optima Plus. This may require some force due to the friction of the O-ring.
6. Clean any dust or contaminants from the optics using mild detergent and a soft cloth or cotton bud.
Do not use solvents or abrasive cleaners.
7. Block the optical beam (for example using the cleaning cloth).

8. Confirm that a fault is generated by viewing the indication on the XNX display.
9. Remove the blockage from the beam.
10. Ensure that the large sealing O-ring in the body of the flow housing, and the two small O-rings which go below the retaining nuts, are clean and in good condition. Replace if in doubt.
11. Slide the flow housing over the end of the Searchpoint Optima Plus and push until the flow housing is firmly seated.
12. Re-fit the o-rings and retaining nuts.
13. Select Set Inhibit Off to release the 4-20 mA output signal.
14. Return to the main menu.
15. Select Calibration Mode then Soft Reset to clear any faults or warnings that may have been generated by cleaning.

4.2 XNX Universal Transmitter Proof Test

After completing the tests in 4.1, please refer to the XNX Universal Transmitter Safety Manual (part number 1998-0808) and complete the Proof Test detailed there.

Find out more at: www.sps.honeywell.com
Contact Honeywell Analytics:
Europe, Middle East, Africa
Life Safety Distribution GmbH
Tel: 00800 333 222 44 (Freephone no.)
Tel: +41 (0)44 943 4380 (Alternative no.)
Middle East Tel: +971 4 450 5800 (Fixed Gas Detection)
Middle East Tel: +971 4 450 5852 (Portable Gas Detection)
[email protected]
Americas
Honeywell Analytics Inc.
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
[email protected]
Asia Pacific
Honeywell Analytics Asia Pacific Co Ltd
Tel: +82 (0) 2 6909 0300
India Tel: +91 124 4752700
China Tel: +86 10 5885 8788-3000
[email protected]
Technical Services
EMEA: [email protected]
US: [email protected]
AP: [email protected]
www.sps.honeywell.com

Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation and you are strongly advised to obtain copies of the most recently issued regulations, standards and
guidelines. This publication is not intended to form the basis of a contract.

Honeywell
Issue 2_08/22
H_MAN0921_EMEAI
2108M0552
© 2022 Honeywell Analytics

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals