Huazheng HZRC9000B High and Low Voltage Clamp Meter User Manual

June 12, 2024
Huazheng

**Huazheng HZRC9000B High and Low Voltage Clamp Meter User Manual

**

Warning

Thanks for your purchase of HZRC9000B H/L Voltage Clamp Meter of our company. In order to make better use of this product, please make sure to:

  • Read this manual in detail and the operator must totally understand this manual and be in proficient in operation of this meter before making test on spot.
  • Strictly comply with the security rules and notice items listed on this manual.
  • In any case, it should pay special attention to safety in use of this meter, particularly in measurementof circuitry with more than AC100V and above voltages.
  • If the voltage of tested circuitry has exceeded 600V, it must be used by connecting with aninsulationrod.
  • As it is very dangerous of high voltage transmission line, the operator must get strict trainingandtherelevant certification on high-pressure operation of the state before using this meter and makingafieldtest.
  • It is strictly forbidden to use this meter to test the wire without any insulate protectionhasvoltageexceed 35KV or convergence generatrix.
  • Please pay attention to marked words and symbols on panel or backboard of this meter.
  • Please do not put or store this meter in the place of high temperature, with moisture, withfrozendewor with direct daylight irradiation for a long time.
  • Please note the battery polarity when replacing battery, and remove the battery if you expect not touse this meter for a long time.
  • It must be operated by qualified staff that has the authorization on tearing down or repairingthismeter.
  • Please do not use it when there is any damage on the transducer clamp or other parts of thismeter.
  • To avoid the impact of transducer clamp, it needs to maintain this meter regularly. Donot usecorrosive or coarse materials to clean, but use soft cloth (such as glasses cloth), dipping cleananti-rustdesiccant lubricant (such as WD-40), and making a gentle wiping.
  • For the reason of this meter, in case that any danger may occur if continue to use it, stop using it immediately and seal it up for keeping at once, which shall be dealt with by qualified authorization agency.
  • The danger symbol “ “on the meter and the manual, the user must make safe operation according to the indication.
  • The extremely dangerous symbol “  ”, the user must make safe operation according to the indication.
  • It suggests that this meter shall be made insulation intensity test at least once annually. (AC100kV/rms  between insulation pole and clamp core.)
    As to the part with “ ”mark in this manual, it is only limited to HZCR9000Btype(wirelessTransmission data type).

Brief Introduction

HZRC9000B Series H/L Voltage Clamp Meter has broken through the traditional structure, which is specially well-designed for measuring high voltage current, adopting the latest CT technology and integrated mask digital technology, formed by composition of a special use clamp meter with a high- voltage insulation rod, as to HZCR9000B type — wireless transmission of test data, it is equipped with wireless receivers, which can receive measured data within 30 meters line. If not using aninsulationrod, it can be also used as a high precision low voltage clamp meter, or an alternating current meter, which can accurately measure 0.01mA of current or leakage current.

HZRC9000B Series H/L Voltage Clamp Meter has an innovative integrated design betweentransducer clamp and transducer domain, ensuring the high-precision, high-reliability, and high-stabilityon constant test perennially

HZRC9000B Series H/L Voltage Clamp Meter is connected with insulation rod, which canbeusedfor measuring high voltage current that is below 60KV, on-line current measurement, also having peakmaintenance, data preservation, data storage, wireless transmission and other functions, anditsspecial clamp meter can make it easier for clamping or evacuating the tested wire through pressing or pulling back the insulation rod, time-saving and fast, widely used in transformer substation, power plant, industrial and mining enterprises as well as the inspection station and electrician maintenancedepartments for electrical current detection and field electrical operations. It can also replacetheH/Lvoltage transforming ratio tester, that is, to detect the high and low current for primary circuit andsecondary circuit separately, and then calculate to conclude the change of high and lowpressure. Theinsulation rod is light and convenient, with the advantages of anti moisture, high temperatureresistance,anti-impact, bending resistance, high insulation, flexibility andother characteristics.

Electrical Symbols

| Extremely Dangerous! The operator must strictly abide by the safety rules. Otherwise, there is electric injury danger, causing personal damage or casualty accident.
---|---
| Dangerous! The operator must strictly abide by the safety rules. Otherwise, there is electric injury danger, causing personal damage or casualty accident.
| Warning! It must strictly abide by the safety rules. Otherwise, it may cause personal damage or casualty accident
| Alternating Current (AC)
| Direct Current (DC)

Series Model

Model| Range of
measurement| Accuracy| Jaw Specification| Description
---|---|---|---|---
HZRC 9000| 0.00mA-1200A| 0.01mA| q)48mm| base
HZRC9000B| 0.00mA-1200A| 0.01mA| q)48mm| wireless

Technical Specification

Function| High voltage AC current measurement, low voltage AC current, leakage current measurement, on-line AC current supervision.
---|---
Power Supply| DC6V Alkaline Dry Battery (1.5V MA X 4)|
Test Method| Clamp CT, Integral Method|
‘Transmission Method| B   Model:           Wireless     Transmission, the                    maximum    distancetransmission is about 30m.| for direct
Display Mode| 4 digital LCD display, backlight function, suitable for dark place.|
LCD Dimension| 47mmx28.5mm|
Meter Dimension| W/H/T: 76mmx255mmx 31mm|
Clamp Diameter| (p48mm|
Sampling Speed| About 2 times/second|
Range of measurement| 0.00mA-1200A ( 50/60Hz Auto Identification )|
Resolution| 0.01mA|
Shift| 0.0mA-1200A Automatic Shift|
Test Accuracy ( 23t±5″C .| 0.0mA-299mA:            ±1 %±3dgt|
Below 80%R H )| 0.30A-49.9A:        ±1.5%t5dgt
50.0A-199.9A:      t.2.0%5dgt
200A-600A:                       ±3%
5dgt
601A-1200A:                     ±4%*5dgt
Data Storage| 99 Groups, during storage, the symbol “MEW gives indication, “FULL’ mark will flash to indicate the memory has been full.
Circuit Voltage| Test for the circuit below 60KV (operated with insulation rod)
Peak Maintenance| Automatically maintain the height of the test value, usually in the test mode
press key. PEAK fights, that is, to keep open the PEAK function, then
press             key to cancel this function
Data Preservation| Under general test mode. press ‘HOLD’ button to preserve data. ‘HOLD’
symbol display. then press IHOLDI Key to cancel this function
Data Access| ‘MR’ symbol indicates. it can read the stored data by turning upwards and downwards.
Overflow Display| Exceed measurement range overflow function: “OL A’ symbol display
‘ No signal Indication| When the receiver has not received transmit signal. it will display “no­-“symbol
Auto Shut Down| About 15 minutes after booting, the meter will shut down automatically, in order to decrease the battery consumption.
Battery Voltage| When       the      battery      voltage      is      below 4.8V.        the      symbol      of      battery voltagel or will show to remind to replace battery.
Weight| Tester: About 335g (Including battery), total quality of meter: about 2.5Kg (including insulation rod and battery.)
Work Temperature and
Humidity| -10°C -40°C; Below 80%Rh
Storage Temperature and
Humidity| -10°C -60°C: Below 70%Rh
Insulated Rod Dimension| p32mm, 1m/Section (5 Sections )
Insulation Intension| AC 100KV/rms (Between insulation rod and clamp core)
Structure| Anti-Dripping Type II

Structure

  1. Double input toroid (including the boot area)
  2. HZCR9000 Tester
  3. LCD Display
  4. PEAK Test Indication
  5. Key
  6. Key
  7.  Key
  8. HZCR9000B Receiver
  9. Insulation Rod Connector
  10. POWER Indication
  11. HZCR9000B Testers
    Structure

LCD Display

  1. LCD Display Screen
    LCD Display

  2. AC symbol

  3. Low battery symbol

  4. Date storage symbol

  5. Date access symbol

  6. 2-digit storage data serial number

  7. Unit symbol

  8. Date locked symbol

  9. Decimal system radix point

  10. 4-Digit LCD digital display

  11. Explanation for Special Symbols

  12. Low battery symbol, when the voltage of battery is lower than 4.8V, this symbol display,please replace battery in time.

  13. “OL A” This symbol indicates that the current on test has exceeded the maximummeasurementlimit of the meter.

  14. “MEM” Memory mode, it will display during the data storage process.

  15. “Full” symbol, when the storage memory has been filled with 99 groups of data, it will display“FULL” symbol by flash, which means it cannot continue to store data.

  16. “MR” data access symbol, which is displayed during looking up data, meanwhile, it will displaytheserial number of data in storage.

  17. End” exit symbol, it will display during the exit.

  18. “dEL” data delete symbol, it will display when deleting data.

  19. “no- -” None received signal instructions, dynamic display, it may not in test mode, or adjust the location and distance from receive

  20. Display Demonstration

  21. The current on testis 0.002A (2mA)

  22. Locked display Data ——The data is automatic stored as group 3 ——The current on test is: 160.5A

  23. The current on test is: 571A ——Low battery symbol , please replac

  24. Look up data of group 3 in storage ——The current on test is: 160.5A

  25. FULL” flash display: Storage is full of 99 groups ——It can’t store more unless delete storage

  26. dEL” Indication of data delete

  27. “End” Indication of exit

  28. “no- -”Dynamic display: none received signal

Operation

Please check all parts of the meter carefully before usage, to see whether thereisany damage. And make sure no damage before usage.

According to manual instructions to install the batte

Tester Operation

Power On/Off

Press button to power on, the instrument will displays the LCD screen, enteringnormal
testing mode. If LCD display is relatively dark after power on, it is possible that battery voltageisabitlower. Please replace battery. 15 minutes after powering on the meter, if it remainsidle, anauto-power off procedure starts to preserve the battery life and LCD will continue flashuntil thecomplete switch off takes place after 30 seconds. In case of LCD continuous flash, press POWER button, then the meter will continue to work.

Under HOLD mode, press button for power off.

Under general test mode, press button to power off. Under PEAK testing mode press POWE button to power off. Under data reference mode, firstly press button for more than 3 seconds to exit from data reference mode, returning to normal test mode, then press button to power off. During the exit from data access, it will display “End” symbol.

General Test

High voltage, extremely dangerous! It must be operated by qualified staff that hasacquired authority. The operator must strictly abide by the safety rules. Otherwise,there is electric injury danger, causing personal damage or casualty accident.

Dangerous! It cannot be used to measure the circuit over 35KV voltage. Otherwise,there is electric injury danger, causing personal damage or equipment damage.

Dangerous! It cannot be used to measure the circuit over 1200A voltage. Other wise, there is electric injury danger, causing personal damage or equipment damage.

General Test: In the process of test, LCD will display the tested current value real time, and LCD data will vary with the current change. When the tester is removed away from the lead on test, it does not preserve the test result, LCD display will return to zero.

In normal testing mode, it is suitable for close distance measurement, convenient for circuit testby direct read of LCD data.

Before test, firstly to connect insulation rod, which must be connected inright position,and then to connect tester, avoiding the impact of meter to ground surface.

Make sure to use specially equipped insulation rod to connect with the meter.

After test, it should incline the insulation rod accordingly on drawing in. Firstly to tear down the tester and then the insulation rod, avoiding the impact of meter to ground surface.

After normal boot, place the lead in the middle of clamp transducer domain, as shown in b, with the meter transducer domain perpendicular to the lead, pushing the meter forwards to clamp the lead on test, showing the result on LCD display. If showing “OL A”, it means the lead current on test has exceeded the maximum volume on the level. Please select a higher gear level or ameter with greater measurement limit.

To pull backwards can make the meter remove from the lead on teat, as shown in Figure C , please try to keep the meter transducer domain perpendicular to the lead when moving away
Instruction
Instruction

Under HOLD mode, press HOLD   button to cancel HOLD function, and return to normal testingmode. Under data reference mode, press POWER button for more than 3 seconds to exit fromdatareference mode, returning to normal testing mode. Under PEAK testing mode, press POWER button to exit from PEAK testing mode, returningtonormal testing mode. After data deletion, it will return to normal testing mode automatically.

Attention! For the sake of safety, when test has been finished, please remove the meter away from the lead on test

PEAK Test

PEAK test: the maximum current test. The meter will make automatic comparisononthechanges in measured current, indicating the maximum value and maintain it, when themeterisremoved away from the lead on test, the  test result will be kept consistently, suitable for thecircuittest on those LCD data hard to be read directly.

Under the normal testing mode, press PEAK button PEAK indication light will be bright,,enterPEAK testing mode. That means the meter will display and automatically keep the maximumvalue in the test.

Under any other mode, it must be returned to normal testing mode, and then make PEAKtestingaccording to the above operation.

Press button to exit from PEAK testing mode, returning to normal testing mode, anditwill display “End” symbol during the exit.

Data Maintenance

Under normal testing mode, press button to keep LCD display, “ ” symbol displays.Press HOLD button again to release data lock, returning to normal testing mode, and“ ”symbol disappears.

Data Memory

Under normal testing mode, press to storage data, at the same time, Meter will automatically form serial numbers, and memory the current preserved data. During the storage, “MEM” symbol will show once by flash. This meter can memory 99 groups of data, in case of full storage, “FULL” symbol will display by flash continuously, and it cannot continue to memory until cleaning out the previous memory

Data Reference

Under normal testing mode, press + button to enter data referencemode,displaying “MR” symbol, meanwhile, it will automatically display data saved in the group01. Thenpress or button to read the stored data by turning upwards or downwards incycle. Itwill return to the group 1’s data automatically after reaching the last group’s data in storage. Press HOLD button to exit from data reference mode, returning to normal testing mode. During the exit, it will display “End” symbol.

Data Deletion

Under data reference mode, press + button to delete all the data in storage, andreturn to normal testing mode. During the deletion of data, it will display “dEL” symbol.

Data Transmission

B Type: has the function of wireless data transmission. When the Meter under testingmode, thetest result will be transferred to receiver by wireless transmission and the receiver will displaytestresult real time, being clear at a glance. Only under testing mode, the meter will transmit, If the receiver has not receivedemissionsignals, it will display “no – -” symbol dynamically. B Type: Transferred

HZCR9000B Type: Wireless transmission test data, a straight-line distance of about 30meters,can penetrate the floor to receive data.

Operation of Receiver

(Note: For HZCR9000B only)

Power On/Off

Press button to power on, the instrument will displays the LCD screen, enteringnormal testing mode. If LCD display is relatively dark after power on, it is possible that battery voltageisabitlower. Please replace battery. 15 minutes after powering on the meter, if it remainsidle, anauto-power off procedure starts to preserve the battery life and LCD will continue flashuntil thecomplete switch off takes place after 30 seconds. In case of LCD continuous flash, press button, then the meter will continue to work.

Under HOLD mode, press to power off.
Under data reference, first, press button( for 3 seconds ) to exit data referencemode,then come back to data receive mode, press button once again to power off. Duringexitfrom data reference, it will display the symbol of “End.

Data Reception
After normal power on, the receiver will under receiving mode. If there are emissiondata, thereceiver will display the test result real time. If it has not received any signal, the receiver will searchsignals constantly, and display “no- -”symbol dynamically.

Data Maintenance

Under Data Reception mod, press button, keep LCD display, “ ” symbol indication.

Press button once again to relieve data lock, return to data reception mode, “ ” symbol display.

Data Memory

Under Date Reception mode, press button to maintain data, meanwhile, thereceiver will automatically form serial numbers, and memory the current preserved data. During thestorage,“MEM” symbol will display once by flash. The receiver can memory 99 groups of data, incaseof full storage, “FULL” symbol will display by flash continuously, and it cannot continue to memoryuntil cleaning out the previous memory.

Data Reference

Under Data Reception mode, press + button to enter Data Referencemode,“MR” symbol display, meanwhile, it will automatically display data saved in the group 1. Then press HOLD button or button to read the stored data by turning upwards or downwards incycle. Itwill return to the group 1’s data automatically after reaching the last group’s data in storage. Press POWER button for more than 3 seconds to exit from data reference mode, returningtoreceiving data mode. During the exit, it will show “End” symbol.

Data Deletion

Under data reference mode, press + button to delete all the data in storage, andreturn to Data Reception mode. During the deletion of data, it will display “dEL” symbol.

Replacing Batteries

Warning! In case that the battery’s cover board is not well closed, it is forbidden to make test. Otherwise, it is dangerous.

Pay attention to the polarity of battery, in case of damage to the meter.

Do not mix in the use of new and old batteries

  1. When the battery voltage is below 4.8V, the meter will display “ ” symbol, indicating the batteries have no sufficient power content. Please replace batteries.
  2. Power off, to make sure the meter is under the state of power off. To loosen two screws of the battery cover board, open the cover board to replace brand-new qualified batteries on. It should pay special attention on the battery specification and polarity, cover the board well and fasten the two screws.
  3. Press POWER button to check whether the meter can be powered on normally. If not, please repeat the operation according the step 2
    Instruction

Accessories

Tester 1PCS
Receiver (HZRC9000B special ) 1PCS
Insulation Rod (1M/Section) 5 Sections
Meter Box 1PCS
Battery (Alkaline Dry Battery AAA) 4 PCS(* or 8 PCS)
User’s Manual/ Maintenance Card/ Conformity Certificate 1SET

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals