Ultravation ADV1224 HVAC Air and Surface Sanitizer Installation Guide

June 12, 2024
Ultravation

Ultravation ADV1224 HVAC Air and Surface Sanitizer

Product Information

  • Product Name: HVAC Air and Surface Sanitizer
  • Model Numbers: ADV1224, ADV1224-T3, ADV1724, ADV1724-T3
  • Power Consumption: 24 VAC .75 A (18 watt) for ADV1224, ADV1224-T3; 24 VAC 1.04 A (25 Watt) for ADV1724, ADV1724-T3
  • Maintenance: Replacement UVC Module
  • Available UVC Module Part Numbers:
    • UVC-MOD-12: 12 inch length UVC-Advantage power supply with 9,000-hour runtime UVC lamp. 1-year warranty.
    • UVC-MOD-12-T3: 12 inch length UVC-Advantage power supply with 18,000-hour runtime UVC lamp. 2-year warranty.
    • UVC-MOD-17: 17 inch length UVC-Advantage power supply with 9,000-hour runtime UVC lamp. 1-year warranty.
    • UVC-MOD-17-T3: 17 inch length UVC-Advantage power supply with 18,000-hour runtime UVC lamp. 2-year warranty.
  • Warranty: 1-year warranty for UVC-MOD-12 and UVC-MOD-17 models, and 2-year warranty for UVC-MOD-12-T3 and UVC-MOD-17-T3 models.
  • Package Contents: Not specified

Product Usage Instructions

  1. Disconnect power before proceeding with the installation.
  2. Choose the proper location for installation based on the provided diagram. In southern climates or areas with high humidity, additional systems may be required for certain components.
  3. Decide on the mounting option: external or internal.
    • For external mounting (most common for metal plenums):
    1. Drill a 1-inch hole for external mount applications.
    2. Install the Sanitizer using the supplied plate and gasket.
    • For internal mounting:
    1. Install the Sanitizer using the supplied plate and magnet for magnet mount option.
  4. Install a dedicated 40 VA 24 VAC transformer per applicable local and state regulations.
  5. Ensure that all wiring inside the air handler in direct line of sight of the UV lamp is shielded with aluminum foil tape or equivalent non-combustible material.
  6. Select a mounting location that prevents ultraviolet light exposure to synthetic or other plastic components with unknown resistance to ultraviolet light.
  7. After installation, check for any openings that would give direct line-of-sight to the UV light and make sure they are blocked.
  8. Follow proper disposal guidelines in accordance with local and state environmental laws for fluorescent lamps containing mercury in case of accidental breakage or replacement of the ultraviolet lamp.
  9. Always protect your eyes from ultraviolet light. Never look at UV lamps in operation. Unplug or disconnect power before re-lamping or servicing.

Please note that this product is intended to be sold and installed by professional HVAC contractors only. Improper installation may result in damage to the UV system and/or HVAC equipment. It is not intended for sale on the internet or in retail stores.

Remember, never look at an ultraviolet lamp in operation as cellular damage occurs within a fraction of a second.

Package Contents

  • 1 Integrated UVC Lamp-Module either 12 inch or 17 inch lamp length.
  • 1 round lamp mounting gasket.
  • 1 6 ft length 24vac. power cord.
  • 1 Mounting plate suitable for duct board and metal plenums.
  • 7 self tapping /4HEX#10X3/4”screws.
  • 3 #10-32×1/4” #2 phillips head screws for magnet mounting
  • 1 Light Shield (optional).
  • 1 magnet for optional internal mounting.
  • 1 Replacement lamp log sheet.
  • 1 UVC warning label.
  • 1 UV Viewport label with clear lens.
  • 1 cotton glove.
  • 1 alcohol prep pad.
  • 2 wire nuts

Safety Precautions

Attention
This product is sold only through and must be installed by professional HVAC contractors. Improper installation can result in damage to the UV system and/ or HVAC equipment. Human exposure to UV light damages eyes and skin. This product is not intended for sale on the internet or in retail stores.

WARNING
UV Hazard. Always protect eyes from ultraviolet light. NEVER look at UV lamps in operation. Unplug or disconnect power before re-lamping or servicing.
WARNING: Severe eye damage or temporary blindness may occur.
WARNING
DO NOT operate outside of air handler. Mount product in preferred location first. No openings should be allowed which would give direct line-of-sight to the UV light. In the event of accidental breakage or replacement of the ultraviolet lamp, please ensure that the lamp is disposed of in accordance with local and state environmental laws regarding fluorescent lamps containing mercury.
Notice
All wiring inside of the air handler in direct line of site of the UV lamp must be shielded with aluminum foil tape or equivalent non-combustible material.When installing this unit, select a mounting location that prevents ultraviolet light exposure to synthetic or other plastic components with unknown resistance to ultraviolet light. Ultraviolet light may cause color shift or structural degradation of plastic internal components.

Installation procedure

Disconnect power.
Locate the proper location for installation (see diagram) in southern climates or areas with high humidity, additional systems could be required for items such as HVAC blower motors or for systems that have coils shaped like a W.

Flexible mounting options work in all types of configurations. Choose between external (most common for metal plenums) or internal mounting of the system. Typical installation is after any other filtration device and before the duct work branches off .

  1. Drill a 1” hole for external mount applications
  2. Install the Sanitizer using the supplied plate and gasket or magnet
  3. Install a dedicated 40 VA 24 VAC transformer per applicable local and state electrical codes, not included. Or use optional 120v wall plug accessory sold separately (Part number 94-135)
  4. The UVC-Advantage is designed to operate constantly, it is not recommended to switch off and on with the fan motor.
  5. Connect the power cord using the supplied wire nuts to the transformer.
  6. Plug the connector into the UVC Advantage.
  7. Affix all warning and lamp replacement labels as well as the UVC viewport in a clear and logical location for quick inspection of the UVC system.
  8. Replace any service panels, reconnect system power.
  9. Ensure the system is operating by noting the blue glow within the viewport.

Remember
Never look at an ultraviolet lamp in operation. cellular damage occurs within a fraction of a second.

  • 120v wall plug-in accessory sold separately p/n: 94-135
  • light shields block unwanted UVC exposure, sold separately. p/n: 94-090-(12” or 17”)

Visit: Ultravation.com for more information.

Maintenance

Typical maintenance of the UVC-Advantage system is replacement of the UVC Lamp-Module every one or two years. Systems equipped with the Ultravation T3 lamp technology require replacement every 18,000hrs of operation or 2 years. All other products require lamp- Module changes every 9,000 hours or 1 year. UV lamps undergo a photochemical process during operation. This slowly reduces the amount of UV light generated to disinfect against airborne pathogens. The blue glow given off from a UVC lamp is a by-product and not an indicator of UVC energy performance. Contact your HVAC contractor or contact Ultravation customer service to locate a contractor near you for replacement parts or service.

Replacement UVC Module Part Numbers

  • UVC-MOD-12
    12 inch. Length UVC-Advantage power supply with 9,000-hour runtime UVC lamp.
    1-year warranty.

  • UVC-MOD-12-T3
    12 inch. Length UVC-Advantage power supply with 18,000-hour runtime UVC lamp.
    2-year warranty.

  • UVC-MOD-17
    17 inch. Length UVC-Advantage power supply with 9,000-hour runtime UVC lamp.
    1-year warranty.

  • UVC-MOD-17-T3
    17 inch. Length UVC-Advantage power supply with 18,000-hour runtime UVC lamp.
    2-year warranty.

Warranty

The Ultravation® UVC-Advantage series has a one year warranty from date of installation, with the exception of the UVC-Advantage T3 series, which is warranted for a period of two years after date of installation. This warranty does not include damage to the unit from accident, misuse or improper installation. If this product should become defective, Ultravation will elect to replace the product free of charge. Ultravation will return replaced warranted products pre-paid to the customer, provided that the product was delivered pre-paid. Ultravation shall have no responsibilities for charges incurred by the customer for installation or removal of warranted items. Liability is limited only to the replacement of this product. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state. All returns must be accompanied by a return authorization number, which may be obtained by contacting Ultravation,Inc.

For Models

  • ADV1224, ADV1224-T3,
  • Power Consumption:
  • 24 VAC .75 A (18 watt)
  • ADV1724, ADV1724-T3,
  • Power Consumption:
  • 24 VAC 1.04 A (25 Watt)

Ultravation, Inc.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals