MEAN WELL DUPS20 DIN Rail Type Uninterruptible DC-UPS Module Owner’s Manual
- June 12, 2024
- MEAN WELL
Table of Contents
MEAN WELL DUPS20 DIN Rail Type Uninterruptible DC-UPS Module
Product Information
- Product Name: 24V/20A DIN Rail Type Uninterruptible DC-UPS Module
- Model: DUPS20
- User’s Manual: UL62368-1 TPTC004
- Features:
- Uninterruptible DC-UPS controller
- Parallel connection to DC BUS
- Suitable for 24V system, up to 20A
- 2A Battery charging current
- Complete diagnostic and monitoring for DC BUS OK, battery discharge, battery fail
- LED indicator for signal status
- Protections: Battery reverse polarity protection & Short circuit(By internal detection) / Battery discharge / Over discharge current
- Cooling by free air convection
- Width only by 40mm
- 3 years warranty
- Applications:
- Industrial control system
- Semiconductor fabrication equipment (Power supply + DC-UPS Module + Batteries + Load)
- Factory automation
- Electro-mechanical apparatus
- GTIN CODE: MW Search: https://www.meanwell.com/serviceGTIN.aspx
Product Usage Instructions
To use the 24V/20A DIN Rail Type Uninterruptible DC-UPS Module (DUPS20), follow these instructions:
- Make sure the input voltage for the DC UPS is within the range of 24V to 29Vdc.
- Connect the DC UPS module to the appropriate industrial control system or semiconductor fabrication equipment using parallel connection to the DC BUS.
- Choose a suitable lead-acid battery with capacities ranging from 4AH to 135AH.
- Connect the battery to the DC UPS module, ensuring correct polarity.
- If batteries are not connected, it is recommended to use an external fuse for short circuit protection.
- The DC UPS module supports a discharge current range of 0 to 20A. Ensure that the load does not exceed this range.
- To charge the battery, connect a power supply with a charging current of 2A to the DC UPS module.
- Monitor the LED indicator for signal status, which will indicate the battery’s OK status or any warnings related to battery over-discharge or breakage.
- The DC UPS module provides complete diagnostic and monitoring for DC BUS OK, battery discharge, and battery fail. Refer to the user manual for details on interpreting these diagnostics.
- The module is cooled by free air convection, so ensure proper ventilation for optimal performance.
Features
- Uninterruptible DC-UPS controller
- Parallel connection to DC BUS (Power supply + DC-UPS Module + Batteries + Load)
- Suitable for 24V system, up to 20A
- 2A Battery charging current
- Allows 4AH~135AH lead-acid various battery capacities
- Complete diagnostic and monitoring for DC BUS OK, battery discharge, battery fail
- LED indicator for signal status
- Protections: Battery reverse polarity protection & Short circuit(By internal detection) / Battery discharge / Over discharge current
- Cooling by free air convection
- Width only by 40mm
- 3 vears warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
The DUPS20 is a 20A DIN rail type DC-UPS module, and it is paired with a power supply and an external battery to achieve the backup function. When the AC mains fails or is interrupted, the load will be immediately connected to the battery pack to avoid interruption and to ensure the continuous operation of the entire system (the operating time depends on the capacity of the battery pack). The main features of DUPS20 include: fast installation, small size (only 40mm wide)suitability for 24 V battery packs and various capacities of 4AH~135AH, 2A battery charging current, low voltage disconnect for battery protection and more. The product is suitable for use in data centers, security systems, emergency lighting, wireless communication UPS, central monitoring systems, etc.
Model Encoding
SPECIFICATION
MODEL | DUPS20 |
---|---|
DC UPS INPUT | NORMAL INPUT VOLTAGE |
INPUT VOLTAGE RANGE | 24 ~ 29Vdc |
RATED CURRENT | 20A |
DC UPS OUTPUT | VOLTAGE RANGE |
DISCHARGE CURRENT RANGE | 0 ~ 20A |
CHARGING CURRENT | 2A |
BATTERY | NORMAL BATTERY VOLTAGE |
24Vdc)
BATTERY TYPE| Lead-acid battery
EXTERNAL BATTERY CAPACITIES| 4AH ~ 135AH
PROTECTION| BATTERY POLARITY| Protected by internal detection, No
Damage, recovers automatically after fault conduction is removed
SHORT CIRCUIT| This protection only works when batteries are not
connected, No Damage. External fuse is recommended when batteries are
connected.
OVER DISCHARGE CURRENT| 21~23A,After 3 sec., unit will cut-off battery
discharging by relay
BATTERY DEEP DISCHARGE| Cut-off battery discharging by relay
FUNCTION| RELAY CONTACT RATINGS (max.)| 30VDC/1A resistive load
DC BUS OK| Relay contact: Short when DC voltage between 21~29V(±2%),
relay contacts
LED(Green): DC BUS OK : light ; DC BUS fail : dark
BATTERY FAIL Note.2| Short when battery voltage falls below 22V(±2%)
or battery failure is observed through the battery test function, relay
contacts
LED(Red): Battery over-discharge warning or battery broken : light ; Battery
OK : dark
BATTERY DISCHARGE| Relay contact: Short when battery in discharge
condition, relay contacts
LED(Yellow): light : Battery discharging ; dark : Battery is not discharging
or discharging current < 1.0A
ENVIRONMENT| COOLING| Free air convection
WORKING TEMP. Note.3| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 5 ~ 95% RH non-condensing
STORAGE TEMP.| -40 ~ +85℃
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE Note.4| 2000 meters/OVC II
SAFETY & EMC **(Note.5)| SAFETY STANDARDS| UL62368-1, EAC TP TC
004 approved
WITHSTAND VOLTAGE| IP/OP – Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ;
Relay – Chassis : 0.5KVac
ISOLATION RESISTANCE| IP/OP – Chassis, IP/OP- Relay, Relay –
Chassis:>100M Ohms / 500Vdc / 25℃/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| —–| —–
Radiated| BS EN/EN55032(CISPR32)| Class B
Voltage Flicker| —–| —–
Harmonic Current| —–| —–
EMC IMMUNITY| BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level / Note**
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact; criteria B
Level 2, 4KV air ; Level 1, 2KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 0.5KV(DC input ports)
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
OTHERS
| MTBF| 1252.0K hrs min. Telcordia SR-332 (Bellcore) ;
482.1K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 40125.2113.5mm (WHD)
PACKING| 0.31Kg; 20pcs/7.2Kg/1.16CUFT
NOTE
| 1. All parameters NOT specially mentioned are measured at normal input(24V) , rated load and 25℃ of ambient temperature.
2. Every 30 seconds, unit will test the battery.If the testing result is faulty, unit will turn on “Battery Fail” relay contact and “Red LED” indicator.
3. Derating may be needed over high ambient temperature. Please check the derating curve for more details.
4. The ambient temperature derating of 3.5℃I1000m with fanless models and of 5℃I1000m with fan models for operating altitude higher than 2000m(6500ft).
5. The unit is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360*720mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests,please refer to “EMI testing of component power supplies.”(as available on http://www.meanwell.com)
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Mechanical Specification
Block Diagram
Derating Curve
Buffering Time
Discharge Current | Buffering Time(Reference) |
---|---|
7.5AH | 12AH |
2.5A | 6500s |
5A | 3000s |
10A | 1200s |
20A | 400s |
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
Suggested Application
- Back up connection for AC interruption.
- Combine redundancy module (DRDN20) to back up AC interruption or failure of PSU.
Installation Manual
Please refer to: http://www.meanwell.com/manual.html
User’s Manual
Documents / Resources
| MEAN
WELL DUPS20 DIN Rail Type Uninterruptible DC-UPS
Module
[pdf] Owner's Manual
DUPS20 DIN Rail Type Uninterruptible DC-UPS Module, DUPS20, DIN Rail Type
Uninterruptible DC-UPS Module, Type Uninterruptible DC-UPS Module,
Uninterruptible DC-UPS Module, DC-UPS Module, Module
---|---
Read User Manual Online (PDF format)