SAFETY PRECAUTIONS AND PROCEDURES
This meter is in compliance with safety standards IEC/EN61557-1 and IEC/EN61010-1 related to electronic measuring instruments. For your own safety and to avoid damaging the instrument follow the procedures described in this instruction manual and read carefully all notes preceded by this symbol . When taking measurements:
- Avoid doing that in humid or wet places – make sure that humidity is within the limits indicated in § 6.2.1.
- Avoid doing that in rooms where explosive gas, combustible gas, steam or excessive dust is present.
- Keep you insulated from the object under test.
- Do not touch exposed metal parts such as test lead ends, sockets, fixing objects, circuits etc.
- Avoid doing that if you notice anomalous conditions such as breakages, deformations, fractures, leakages of battery liquid, blind display etc.
- Be particularly careful when measuring voltages exceeding 20V to avoid risk of electrical shocks.
The following symbols are used:
CAUTION – refer to the instruction manual – an improper use may damage the
instrument or its components.
- Double insulation
- AC Voltage
PRELIMINARY
- This instrument has been designed for use in environments of pollution degree 2.
- It can be used for testing the phase sequence on installations of overvoltage CAT IV 300V and CAT III 600V to the ground.
- When using the instrument always respect the usual safety regulations aimed at protecting you against the dangerous electric currents and protecting the instrument against incorrect operations.
- Only the leads supplied with the instrument guarantee compliance with the safety standards in force. They must be in good conditions and, if necessary, replaced with identical ones.
- This instrument is not suitable for measurements of non sine wave voltage.
- Do not test or connect to any circuit exceeding the specified overload protection or under environmental conditions exceeding the limits indicated in § 6.1.1 and § 6.2.1.
DURING USE
We recommend carefully reading the following recommendations and instructions:
CAUTION: An improper use may damage the instrument and/or its components or injure the operator.
When the instrument is connected to measuring circuits never touch any unused terminal.
NOMENCLATURE
INSTRUMENT DESCRIPTION
Fig. 1: Instrument description
CAPTION:
- Input terminals
- Display
PREPARATION FOR USE
INITIAL
This instrument was checked both mechanically and electrically prior to shipment. All possible cares and precautions were taken to let you receive the instrument in perfect conditions. Notwithstanding we suggest you to check it rapidly (eventual damages may have occurred during transport – if so please contact the local distributor from whom you bought the item). Make sure that all standard accessories mentioned in § 6.3.1 are included. Should you have to return back the instrument for any reason please follow the instructions mentioned in § 7.
SUPPLY VOLTAGE
The instrument is self powered by the mains.
STORAGE
After a period of storage under extreme environmental conditions exceeding the limits mentioned in § 6.2.1 let the instrument resume normal measuring conditions before using it.
OPERATING INSTRUCTIONS
CAUTION: Do not test or connect to any circuit exceeding the specified overload protection. Do not attempt to measure higher voltages to avoid electrical shocks or damages to the instrument.
- Connect the test cables by following their numbering.
- Apply the relevant alligator clips to the free ends of the cables.
- Connect the alligator clips to the electrical mains.
- The instrument shows:
- The connected phase cables, L1, L2, L3 referred to the relevant inputs (two cables have to be connected at least).
- The phase sequence: the letter “R” with a clockwise arrow indicates the correct phase sequence, the letter “L” with a counterclockwise arrow indicates the incorrect phase sequence
MAINTENANCE
GENERAL INFORMATION
This is a precision instrument. To guarantee its performances be sure to use it according to these instructions and keep it stored on suitable environmental conditions Do not expose it to high temperatures or humidity or direct sunlight.
CLEANING
To clean the instrument use a soft dry cloth. Never use a wet cloth, solvents or water.
END OF LIFE
CAUTION: this symbol indicates that equipment and its accessories shall be subject to a separate collection and correct disposal.
TECHNICAL SPECIFICATIONS
TECHNICAL FEATURES
Electrical specifications
- Input voltage range: 40V ÷ 690V AC
- Frequency voltage range: 15Hz ÷ 400Hz
- Absorbed current (by phase): 1mA
Reference guidelines
- Safety: IEC/EN61010-1
- EMC: IEC/EN61326-1
- Insulation: double insulation
- Pollution degree: 2
- Measurement category: CAT III 600V, CAT IV 300V to ground
- Max height of use: 2000m (6561ft)
Mechanical characteristics
- Dimensions (L x W x H): 130 x 69 x 22mm (5 x 3 x 1in)
- Weight: 130g (4ounces)
- Mechanical protection: IP40
Power supply
- From the mains.
Display
- Characteristics: Custom with phase sequence and detected phases indications.
ENVIRONMENT
Environmental conditions
- Working temperature: 0°C ÷ 40°C (32°F ÷ 104°F)
- Relative humidity: <80%RH
- Storage temperature: 0°C ÷ 40°C (32°F ÷ 104°F)
- Storage humidity: <80%RH
This instrument satisfies the requirements of Low Voltage Directive 2014/35/EU
(LVD) and of EMC Directive 2014/30/EU
This instrument satisfies the requirements of European Directive 2011/65/EU
(RoHS) and 2012/19/EU (WEEE)
ACCESSORIES
Standard accessories
- KIT82: set of 3 test cables + 3 alligator clips
- Carrying case
- User manual.
Optional accessories
- 404-IEC#: test lead (# = color)
- 5004-IEC#: alligator clip (# = color)
- 5001-#: test cable (# = color)
SERVICE
WARRANTY CONDITIONS
This instrument is guaranteed against material or production defects, in accordance with our general sales conditions. During the warranty period the manufacturer reserves the right to decide either to repair or replace the product. Should you need for any reason to return back the instrument for repair or replacement take prior agreements with the local distributor from whom you bought it. Do not forget to enclose a report describing the reasons for returning (detected fault). Use only original packaging. Any damage occurred in transit due to no original packaging will be charged anyhow to the customer. The manufacturer will not be responsible for any damage to persons or things.
The warranty doesn’t apply to:
- Accessories (not covered by warranty).
- Repairs made necessary by improper use (including adaptation to particular applications not provided in the instructions manual) or improper combination with incompatible accessories or equipment.
- Repairs made necessary by improper shipping material causing damages in transit.
- Repairs made necessary by previous attempts for repair carried out by unskilled or unauthorized personnel.
- Instruments for whatever reason modified by the customer himself without explicit authorization of our Technical Dept.
- Incorrect use do not compliance to instrument specifications or to user’s manual.
The contents of this manual may not be reproduced in any form whatsoever without the manufacturer’s authorization.
Our products are patented and our logotypes registered. We reserve the right to modify specifications and prices in view of technological improvements or developments which might be necessary.
AFTER-SALE SERVICE
Shouldn’t the instrument work properly, before contacting your distributor make sure that batteries are correctly installed and working, check the test leads and replace them if necessary. Make sure that your operating procedure corresponds to the one described in this manual. Should you need for any reason to return back the instrument for repair or replacement take prior agreements with the local distributor from whom you bought it. Do not forget to enclose a report describing the reasons for returning (detected fault). Use only original packaging. Any damage occurred in transit due to non original packaging will be charged anyhow to the customer. The manufacturer will not be responsible for any damage to persons or things.