Hisense R32 Standard Air Conditioner Instruction Manual
- June 12, 2024
- Hisense
Table of Contents
R32 Standard Air Conditioner
Product Information
This product is an Air Conditioner designed to provide cooling
and heating functions. It comes with a remote controller for easy
operation. The air conditioner has various features such as auto
restart, back-light function (optional), and a timer function.
Contents
- Safety instructions
- Preparation before use
- Installation instructions
- Maintenance
- Troubleshooting
- Display introduction
- Remote controller operating instructions
Safety Precautions
-
Do not use the power supply circuit breaker or pull off the
plug to turn off the air conditioner during operation to avoid fire
hazards. -
Do not touch the operation buttons when your hands are wet to
prevent electrical shock. -
Do not put any objects on the outdoor unit to ensure proper
functioning. -
Grounding is essential for safety. Make sure to connect the
appliance to a properly grounded power supply. -
Use the correct power supply in accordance with the rating
plate requirements to prevent faults, hazards, or fire. -
Avoid prolonged exposure to cool air as it may be harmful to
your health. Ensure proper air circulation in the room. -
Do not insert any objects into the unit to prevent injury from
the rotating fan. -
Keep the power supply circuit breaker or plug clean to maintain
a secure connection. -
Do not attempt to repair the appliance by yourself to prevent
electric shock or further damage. Seek professional assistance if
needed. -
Ensure the appliance is grounded according to local codes or
ordinances by a licensed technician.
Precautions for using R32 refrigerant
Additional precautions may be required for using R32
refrigerant. Please refer to the specific guidelines and
instructions provided by the manufacturer for safe handling and
usage of R32 refrigerant.
Product Usage Instructions
Preparation before use
Before using the air conditioner, perform the following
steps:
-
Check and preset the remote control by following the
instructions provided for remote control presetting. -
If applicable, activate the back-light function of the remote
control by holding down any button. The back-light will
automatically shut off after 10 seconds. -
If desired, set the auto restart function on the air
conditioner.
Installation
Follow the installation instructions provided in the manual for
proper installation of the air conditioner. The instructions
include:
- Installation diagram
- Selecting the installation locations
- Indoor unit installation
- Connecting the cable
- Wiring diagram
- Outdoor unit installation
- Air purging
Maintenance
Regular maintenance is important to ensure the proper
functioning and longevity of the air conditioner. Refer to the
maintenance section in the manual for detailed instructions on how
to maintain the appliance.
Troubleshooting
If you encounter any issues with the air conditioner, refer to
the troubleshooting section in the manual for possible solutions.
Follow the instructions provided to resolve common problems.
Remote Controller Operating Instructions
Refer to the remote controller operating instructions section in
the manual for detailed instructions on how to use the remote
controller. It provides information on various functions such as
temperature control, mode selection, fan speed adjustment, timer
settings, and more.
Thank you very much for purchasing this Air Conditioner. Please read this use and installation instructions carefully before installing and using this appliance and keep this manual for future reference.
Contents
Safety instructions
1
Preparation before use
1
Safety Precautions
2
Installation instructions
6
Installation diagram
6
Select the installation locations
7
Indoor unit installation
7
Connecting of the cable
8
Wiring diagram
9
Outdoor unit installation
9
Air purging
9
Maintenance
10
Protection
10
Troubleshooting
11
Display introduction
11
Remote controller operating instructions.See”remote controller instructions”.
Safety instructions
1. To guarantee the unit work normally, please read the manual carefully
before installation, and try to install strictly according to this manual. 2.
Do not let air enter the refrigeration system or discharge refrigerant when
moving the air conditioner. 3. Properly ground the air conditioner into the
earth. 4. Check the connecting cables and pipes carefully, make sure they are
correct and firm before connecting the power of the air conditioner. 5. There
must be an air-break switch. 6. After installing, the consumer must operate
the air conditioner correctly according to this manual, keep a suitable
storage for maintenance and moving of the air conditioner in the future. 7.
Fuse of indoor unit:T3.15A 250VAC or T5A 250VAC. Please refer to the screen
printing on the circuit board for the actual parameters, which must be
consistent with the parameters on the screen printing. 8. For 5K~13K models,
fuse of outdoor unit:T15A 250VAC or T 20A 250VAC. Please refer to the screen
printing on the circuit board for the actual parameters, which must
beconsistent with the parameters on the screen printing 9. For 14K~18K models,
fuse of outdoor unit: T 20A 250VAC. 10. For 21K~36K models, fuse of outdoor
unit: T 30A 250VAC. 11. The installation instructions for appliances that are
intended to be permanently connected to fixed wiring, and have a leakage
current that may exceed 10 mA, shall state that the installation of a residual
current device (RCD) having a rated residual operating current not exceeding
30 mA is advisable 12. Warning: Risk of electric shock can cause injury or
death: Disconnect all remote electric power supplies before servicing. 13. The
maximum length of the connecting pipe between the indoor unit and outdoor unit
should be less than 5 meters. It will affect the efficiency of the air
conditioner if the distance longer than that length 14. This appliance is not
intended for use by person (including children) with reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the appliance by a
person responsible for their safety.Children should be supervised to ensure
that they do not play with the appliance.Cleaning and user maintenance shall
not be made by childrenwithout supervision 15. This appliance can be used by
children aged from 8 years and above and personswith reduced physical, sensory
or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way
and understand the hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall not be made by children without
supervision.
16. The batteries in remote controller must be recycled or disposed of
properly. Disposal of Scrap Batteries — Please discard the batteries as sorted
municipal waste at the accessible collection point. 17. If the appliance is
fixed wiring, the appliance must be fitted with means for disconnection from
the supply mains having a contact separation in all poles that provide full
disconnection under over voltage category III conditions, and these means must
be incorporated in the fixed wiring in accordance with the wiring rules. 18.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
19.The appliance shall be installed in accordance with national wiring
regulations. 20. Servicing shall only be performed as recommended by the
equipment manufacturer. Maintenance and repair requiring the assistance of
other skilled personnel shall be carried out under the supervision of the
person competent in the use of flammable refrigerants. 21. The appliance shall
not be installed in the laundry 22.Regarding to installation, please refer to
section “Installation instructions”. 23. Regarding to maintenance, please
refer to section “Maintenance”. 24. For models using R32 refrigerant, piping
connection should be conducted on outdoor side.
Preparation before use
Note
1. When charging refrigerant into the system, make sure to charge in liquid
state,if therefrigerant of the appliance is R32.Otherwise, chemical
composition of refrigerant (R32) inside the system may change and thus affect
performance of the air conditioner 2. According to the character of
refrigerant (R32,the value of GWP is 675), the pressure of the tube is very
high, so be sure to be careful when you install and repair the appliance. 3.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard. 4.
Installation of this product must be done by experienced service technicians
professional installers only in accordance with this manual. 5. The
temperature of refrigerant circuit will be high, please keep the
interconnection cable away from the copper tube.
Preset
Before using the air conditioner, be sure to check and preset the following.
1.Remote Control presetting Each time after the remote control is replaced
with new batteries or is energized, remote control auto presettingheat pump.If
the air conditioner you purchased is a Cooling Only one, heat pump remote
controller can also be used.
1
2. Back-light function of Remote Control(optional) Hold down any button on
remote control to activate the back light. It automatically shuts off 10
seconds later. Note: Back-light is an optional function. 3. Auto Restart
Presetting The air conditioner has an Auto-Restart function.
Safeguarding the environment
ON OFF
Do not use the power
supply circuit breaker or pull off the plug to turn it off during operation. This may cause a fire due to
Do not touch the operation buttons when your hands are wet.
spark, etc.
ON
OFF
Do not put any objects on the outdoor unit.
This appliance is made of recyclable or re-usable material. Scrapping must be
carried out in compliance with local waste disposal regulations. Before
scrapping it, make sure to cut off the mains cord so that the appliance cannot
be re-used. For more detailed information on handling and recycling this
product, contact your local authorities who deal with the separate collection
of rubbish or the shop where you bought the appliance. SCRAPPING OF APPLIANCE
This appliance is marked according to the European Directive 2012/19/EC, Waste
Electrical and Electronic Equipment (WEEE). This marking indicates that this
product should not be disposed with other household wastes throughout the EU.
To prevent possible harm to the environment or human health from uncontrolled
waste disposal,recycle it responsibly to promote the sustainable reuse of
material resources. To return your used device, please use the return and
collection systems or contact the retailer where the product was purchased.
They can take this product for environmental safe recycling.
Safety precautions
Symbols in this Use and Care Manual are
interpreted as shown below.
Be sure not to do.
Grounding is essential.
Pay attention to such a situation.
Warning: Incorrect handling could cause a serious hazard, such as death,
serious injury, etc.
Use correct power
supply inaccordance
with the rating plate
requirement. Otherwise, serious faults or hazard may occur or a fire maybe break out.
It is harmful to your health if the cool air reaches you for a long time. It is advisable to let the air flow be
Never insert a stick or similar obstacle to the unit. Since the fan rotates at high speed,
ON
deflected to all the this may cause an injury.
OFF
room.
Keep the power
supply circuit
breaker or plug from
dirt. Connect the
power supply cord to
Do not repair the
it firmly and correctly,
appliance by yourself.
lest an electric shock Prevent the air flow If this is done
or a fire break out from reachingthe gas incorrectly, it may cause
due to insufficient burners and stove. an electric shock, etc.
contact.
SMART
TEMP.
MODE
SUPER
TEMP.
FAN SPEED
FEEL
SLEEP
CLOCK
TIMER ON
TIMER OFF
QUIET
DIMMER
ECONOMY
It is the user’s responsibility to make the appliance be grounded according to local codes or ordinances by a licenced technician.
Turn off the
Do not knit, pull or
applianceby remote press the power supply
control firstly before cord, lest the power
cutting off power supply cord be broken.
supply if malfunction An electric shock or fire
occurs.
is probably caused by
a broken power supply
cord.
Safety precautions
Precautions for using R32 refrigerant
The basic installation work procedures are the same as the conventional
refrigerant(R22 or R410A). However, pay attention to the following points:
1.Transport of equipment containing flammable refrigerants
Compliance with the transport regulations 2.Marking of equipment using signs
Compliance with local regulations 3.Disposal of equipment using flammable
refrigerants
Compliance with national regulations 4.Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s
instructions. 5.Storage of packed (unsold) equipment Storage package
protection should be constructed such that mechanical damage to the equipment
inside the package will not cause a leak of the refrigerant charge. The
maximum number of pieces of equipment permitted to be stored together will be
determined by local regulations. 6.Information on servicing 6-1 Checks to the
area Prior to beginning work on systems containing flammable refrigerants,
safety checks are necessary to ensure that the risk of ignition is minimised.
For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system. 6-2 Work procedure Work
shall be undertaken under a controlled procedure so as to minimise the risk of
flammable gas or vapour being present while the work is being performed.
2
6-3 General work area All maintenance staff and others working in the local
area shall be instructed on the nature of work being carried out. Work in
confined spaces shall be avoided. The area around the workspace shall be
sectioned off. Ensure that the conditions within the area have been made safe
by control of flammable material.
6-4 Checking for presence of refrigerant The area shall be checked with an
appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak
detection equipment being used is suitable for use with flammable
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
6-5 Presence of fire extinguisher If any hot work is to be conducted on the
refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
6-6 No ignition sources No person carrying out work in relation to a
refrigeration system which involves exposing any pipe work that contains or
has contained flammable refrigerant shall use any sources of ignition in such
a manner that it may lead to the risk of fire or explosion All possible
ignition sources, including cigarette smoking, should be kept sufficiently far
away from the site of installation, repairing, removing and disposal, during
which flammable refrigerant can possibly be released to the surrounding space.
Prior to work taking place, the area around the equipment is to be surveyed to
make sure that there are no flammable hazards or ignition risks. “No Smoking”
signs shall be displayed.
6-7 Ventilated area Ensure that the area is in the open or that it is
adequately ventilated before breaking into the system or conducting any hot
work. A degree of ventilation shall continue during the period that the work
is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere
6-8 Checks to the refrigeration equipment Where electrical components are
being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer’s maintenance and service
guidelines shall be followed. If in doubt consult the manufacturer’s technical
department for assistance.
The following checks shall be applied to installations using flammable
refrigerants: The charge size is in accordance with the
room size within which the refrigerant containing parts are installed; The
ventilation machinery and outlets are
operating adequately and are not obstructed; If an indirect refrigerating
circuit is being
used, the secondary circuit shall be checked for the presence of refrigerant;
Marking to the equipment continues to be
visible and legible. Markings and signs that are illegible shall be corrected;
Refrigeration pipe or components are
installed in a position where they are unlikely to be exposed to any substance
which may corrode refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded or
are suitably protected against being so corroded. 6-9 Checks to electrical
devices Repair and maintenance to electrical components shall include initial
safety checks and component inspection procedures. If a fault exists that
could compromise safety, then no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with. If the fault cannot be
corrected immediately but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised. Initial safety checks shall include:
That capacitors are discharged: this shall be
done in a safe manner to avoid possibility of sparking; That there no live
electrical components and
wiring are exposed while charging, recovering or purging the system; That
there is continuity of earth bonding
7. Repairs to sealed components During repairs to sealed components, all
electrical supplies shall be disconnected from the equipment being worked upon
prior to any removal of sealed covers, etc. If it is absolutely necessary to
have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point
to warn of a potentially hazardous situation. Particular attention shall be
paid to the following to ensure that by working on electrical components, the
casing is not altered in such a way that the level of protection is affected.
3
This shall include damage to cables,
Leak detection fluids are suitable for use with
excessive number of connections, terminals
most refrigerants but the use of detergents
not made to original specification, damage to
containing chlorine shall be avoided as the
seals, incorrect fitting of glands, etc.
chlorine may react with the refrigerant and
Ensure that apparatus is mounted securely.
corrode the copper pipe-work.
Ensure that seals or sealing materials have not If a leak is suspected, all naked flames shall
degraded such that they no longer serve the
be removed/ extinguished.
purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications. NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them. 8.Repair to intrinsically safe components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the
If a leakage of refrigerant is found which
requires brazing, all of the refrigerant shall be recovered from the system,
or isolated (by means of shut off valves) in a part of the system remote from
the leak. Oxygen free nitrogen (OFN) shall then be
purged through the system both before and during the brazing process.
12.Removal and evacuation When breaking into the refrigerant circuit to make
repairs or for any other purpose conventional procedures shall be used.
However, it is important that best practice is followed since flammability is
a consideration. The following procedure shall be adhered to: Remove
refrigerant;
presence of a flammable atmosphere. The test Purge the circuit with inert gas;
apparatus shall be at the correct rating.
Evacuate;
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
9.Cabling Check that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans 10.Detection of flammable
refrigerants Under no circumstances shall potential sources of ignition be
used in the searching for or detection of refrigerant leaks. A halide torch
(or any other detector using a naked flame) shall not be used 11.Leak
detection methods The following leak detection methods are deemed acceptable
for systems containing flammable refrigerants: Electronic leak detectors
shall be used to
detect flammable refrigerants, but the sensitivity may not be adequate, or may
need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential
Purge again with inert gas;
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be “flushed” with OFN to render the unit safe. This process
may need to be repeated several times. Compressed air or oxygen shall not be
used for this task. Flushing shall be achieved by breaking the vacuum in the
system with OFN and continuing to fill until the working pressure is achieved,
then venting to atmosphere, and finally pulling down to a vacuum. This process
shall be repeated until no refrigerant is within the system. When the final
OFN charge is used, the system shall be vented down to atmospheric pressure to
enable work to take place. This operation is absolutely vital if brazing
operations on the pipe-work are to take place. Ensure that the outlet for the
vacuum pump is not close to any ignition sources and there is ventilation
available. 13.Charging procedures In addition to conventional charging
procedures, the following requirements shall
source of ignition and is suitable for the
be followed:
refrigerant used. Leak detection equipment shall be set at a
Ensure that contamination of different refrigerants does not occur when using
percentage of the LFL of the refrigerant and
charging equipment.
shall be calibrated to the refrigerant employed and the appropriate percentage
of gas (25 % maximum) is confirmed.
4
Hoses or lines shall be as short as possible to
minimise the amount of refrigerant contained in them.
Cylinders shall be kept upright.
15.Labelling
Ensure that the refrigeration system is earthed Equipment shall be labelled stating that it has
prior to charging the system with refrigerant.
been de-commissioned and emptied of
Label the system when charging is complete
(if not already). Extreme care shall be taken not to overfill the
refrigeration system. Prior to recharging the system it shall be pressure
tested with OFN. The system shall be leak tested on completion of charging but
prior to commissioning. A follow up leak test shall be carried out prior to
leaving the site. 14.Decommissioning Before carrying out this procedure, it is
essential that the technician is completely familiar with the equipment and
all its detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant
sample shall be taken in case analysis is required prior to re-use of
reclaimed refrigerant. It is essential that electrical power is available
before the task is commenced. a) Become familiar with the equipment and its
operation. b) Isolate system electrically. c) Before attempting the procedure
ensure
that: Mechanical handling equipment is available,
refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contain flammable refrigerant. 16.Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
if required, for handling refrigerant cylinders; In addition, a set of calibrated weighing scales
All personal protective equipment is available shall be available and in good working order.
and being used correctly; The recovery process is supervised at all
times by a competent person; Recovery equipment and cylinders conform to
the appropriate standards. d) Pump down refrigerant system, if possible. e) If
a vacuum is not possible, make a manifold
so that refrigerant can be removed from various parts of the system. f) Make
sure that cylinder is situated on the scales before recovery takes place. g)
Start the recovery machine and operate in accordance with manufacturer’s
instructions. h) Do not overfill cylinders. (No more than 80 % volume liquid
charge). I ) Do not exceed the maximum working pressure of the cylinder, even
temporarily. j ) When the cylinders have been filled correctly and the process
completed, make sure that the cylinders and the equipment are removed from
site promptly and all isolation valves on the equipment are
Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers.
closed off. k) Recovered refrigerant shall not be charged
into another refrigeration system unless it has been cleaned and checked.
5
Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely. When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the unit Do not place any other electrical products or household belongings under indoor unit or outdoor unit. Condensation dripping from the unit might get them wet, and may cause damage or malfunction of your property. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources(for example, open flames, an operating gas appliance or an operating electric heater). Do not pierce or burn. Be aware that refrigerants may not contain an odor. To keep ventilation openings clear of obstruction. The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. The appliance shall be stored in a room without continuously operating open flames (for example an operating gas appliance) and ignition sources (for example an operating electric heater). Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industryaccredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification. Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. Appliance shall be installed, operated and stored in a room with a floor arealarger than 10 m2. The installation of pipe-work shall be kept to a a room with a floor area largerthan 10 m2. The pipe-work shall be complianced with national gas regulations. The maximum refrigerant charge amount is 2.5 kg.The specific refrigerant charge is based on the nameplate of the outdoor unit
Mechanical connectors used indoors shall comply with ISO 14903. When
mechanical connectors are reused indoors, sealing parts shall be renewed. When
flared joints are reused indoors, the flare part shall be re-fabricated. The
installation of pipe-work shall be kept to a minimum. Mechanical connections
shall be accessible for maintenance purposes.
Explanation of symbols displayed on the indoor unit or outdoor unit.
This symbol shows that this appliance uses
WA R N I N G
[symbol ISO 7010-W021
a If
flammable refrigerant. the refrigerant is leaked
and
exposed
to
(2011-05)] an external ignition source, there is a risk
Caution, risk of fire
of fire
WA R N I N G
Waring;low burning velocity material
A2L symbol
This symbol shows that this appliance uses a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire
[symbol ISO This symbol shows that the operation 7000-0790 manual should be read carefully. CAUTION (2004-01)]
This symbol shows that a service [symbol ISO personnel should be handling this CAUTION 7000-1659 equipment with reference to the (2004-01)] installation manual.
CAUTION
[symbol ISO 1641-0790
This symbol shows that information is available such as the operating manual
or
(2004-01)] installation manual.
Installation instructions
Installation diagram
Distance from wall should be over 50mm
Distance from ceiling should be over 200 mm
Distance from the obstacle should be over 3000mm.
Distance from floor should be over 2500mm.
Distance from the wall should be over 50mm
Distance from the obstacle should be over 500mm.
Air intake distance from the wall should be over 250mm
Air intake distance from the wal should be over 250mml
shaoiruoldutbleet odvisetra5n0ce0mfrmom the wall
over 250mm
Above figure is only a simple presentation of the unit, it may not match the external appearance of the unit you purchased. Installation must be performed in accordance with the national wiring standards by authorized personnel only.
6
Select the installation locations
Indoor unit installation
Location for Installing Indoor Unit
1. Where there is no obstacle nearIndoor unit Pipe length
the air outlet andair can be easily blown to every corner.
is 15 meters Max.
2. Where piping and wall hole can
be easily arranged.
Height should be less than 5m
3. Keep the required space from the unit to the ceiling and wall according to the installation
diagram on previous page.
4. Where the air filter can be easily removed.
Outdoor unit
5. Keep the unit and remote controller 1m or more
apart from television, radio etc. 6. Keep as far as possible from fluorescent lamps. 7. Do not put anything near the air inlet to obstruct it from air absorption. 8. Install on a wall that is strong enough to bear the weight of the unit. 9. Install in a place that will not increase operation
noise and vibration. 10. Keep away from direct sunlight and heating sources. Do not place flammable materials or combustion apparatuses on top of the unit.
Location for Installing Outdoor Unit
1. Installing the Mounting Plate Decide an installing location for the mounting plate according to the indoor unit location and pipe direction. Keep the mounting plate horizontally with a horizontal ruler or level. Drill holes of 32mm in depth on the wall for fixing the plate. Insert the plastic plugs to the hole, fix the mounting plate with tapping screws. Inspect if the mounting plate is well fixed. Then drill a hole for pipe.
Tapping screw
Mounting plate
Note: The shape of your mounting plate may be different from the one above, but the installation method is similar. Note: As the above figure shown, the six holes matched with tapping screw on the mounting plate must be used to fix the mounting plate, the others are prepared.
Height should be less than 5m
Indoor Outdoor
1. Where it is convenient to install and well ventilated.
2. Avoid installing it where flammable gas Outdoor unit could leak.
3. Keep the required distance apart from the wall.
Pipe length is 15 meters Max.
The pipe length between indoor and
2. Drill a Hole for Pipe
Decide the position of hole for pipe according to the location of mounting
plate. Drill a hole on the wall about 50mm. The hole
Wall hole sleeve ( hard polythene tube
prepared by user)
5mm (tilt downward)
outdoor unit should be not more than
should tilt a littledownward toward outside.
5 meters in factory default status, but it can go up to maximum 15 meters with
Install a sleeve through the wall hole to keep the wall tidy and clean.
additional refrigerant charge.
3. Indoor Unit Pipe Installation
6. Keep the outdoor unit away
Put the pipes (liquid and gas pipe) and cables
from greasy dirt, vulcanization
through the wall hole from outside or put them
gas exit.
through from inside after indoor pipe and cables
7. Avoid installing it by the
Indoor unit
roadside where there is a risk
of muddy water.
8. A fixed base where it is not subject to increased
operation noise.
connection complete so as to connect to outdoor unit. Decide whether saw the unloading piece off in accordance with the pipe direction.(as shown below) Pipe direction
9. Where there is not any blockage of the air outlet.
Trough
10. Avoid installing under direct sunlight, in an aisle
Knock-down panel
4
or sideway, or near heat sources and ventilation fans.
1
3
Keep away from flammable materials, thick oil fog,
and wet or uneven places.
Model
Max. allowed pipe
Limit of pipe Limit of Elevation Required amount of
length without additional length (m) Difference H (m) additional refrigerant
refrigerant (m)
(g/m)
5K~18K
5
15
5
20
21K~25K
5
15
5
30
28K~36K
5
15
5
40
If the height or pipe length is out of the scope of the
table, please consult the dealer.
Cut off the Knock-down panel along the trough using needle
2
Note: When installing the pipe at the directions 1,2 or 4, saw
nose pliers or other suitable the corresponding unloading
tool.
piece off the indoor unit base.
After connecting pipe as required, install the drain
hose. Then connect the power cords. After
connecting, wrap the pipes, cords and drain hose
together with thermal insulation materials.
7
Pipe Joints Thermal Insulation: Wrap the pipes joints with thermal insulation materials and then wrap with a vinyl tape.
wrapped with vinyl type
Thermal insulation
Pipes Thermal Insulation:
a. Place the drain hose under the pipes. b. Insulation material uses polythene Thermal insulation tube Notfeo:aDmraionvheors6emismpreinpathreidckbnyeussse.r.(juPsotwaesrcLchaoerrgdmeaptiicp)e
Drain pipe should point downward
for easy drain flow. Do not arrange
the drain pipe twisted, sticking out
or wave around, do not immerse
Small
the end of it in water.
Drain hose
pipe
(prepared by user)
If an extension drain hose is connected to the drain
pipe, make sure to thermal insulated when passing
along the indoor unit.
When the pipes is directed to the right, pipes, power Cord and drain pipe should be thermal insulated and fixed onto the back of the unit with a pipe fixer.
Insert here
large pipe
drain small hose pipe
large pipe
drain small hose pipe
Base
Pipe fixer Base
Pipe fixer Base
Hook here
A. Insert the pipe fixer to the slot. B. Press to hook the pipe fixer onto the base.
Piping Connection:
a.Before unscrewing the big and the small sealing caps, press the small
sealing cap with the finger until the exhaust noise stops, and then loosen the
finger.
b.Connect indoor unit pipes with two wrenches. Pay special attention to the
allowed torque as shown below to prevent the pipes, connectorsand flare nuts
from being deformed and damaged.
c. Pre-tighten them with fingers at first, then use the wrenches.
For ON-OFF appliance
Model
5~12K,13~18K,21~24K
Pipe size Liquid Side (6mm or 1/4 inch)
Torque Nut width Min.thickness
15~20N·m 17mm
0.5mm
18K#,22,24K#,28,30,36K 5~10K,12K
Liquid Side (9.53mm or 3/8 inch) 30~35N·m 22mm Gas Side (9.53mm or 3/8 inch) 30~35N·m 22mm
0.6mm 0.6mm
12K#,14,15,18K 18K#,22,24,28,30,36K 36K#
Gas Side (12mm or 1/2 inch) Gas Side (16mm or 5/8 inch) Gas Side (19mm or 3/4 inch)
50~55N·m 60~65N·m 70~75N·m
24mm 27mm 32mm
0.6mm 0.6mm 1.0mm
Note: The unit of 12K#,18K#,24K#,36K# is bigger than the unit of 12K,18K,24K,36K.
4. Connecting of the Cable
Indoor Unit
Connect the power cord to the indoor unit by connecting the wires to the
terminals on the control board individuallyin accordance with the outdoor unit
connection.
Note: For some models, it is necessary to remove the cabinet to connect to the
indoor unit terminal.
Outdoor Unit
- Remove the access door from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as follows.
- Secure the power cord onto the control board w. ith cable clamp.
- Reinstall the access door to the original position with the screw.
- Use a recognized circuit breaker for 24K model between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
Front panel Terminal (inside)
Indoor unit
Cabinet Chassis
Access door Terminal(inside)
If you don’t hear the exhaust noise, please contact with the merchant.
Outdoor unit
The figures in this manual are based on the external
For Inverter appliance
Model
Pipe size
Torque Nut width Min.thickness
view of a standard model. Consequently, the shape may differ from that of the air conditioner you have
5k~12K,13k~18K,21~24K Liquid Side (6mm or 1/4 inch) 15~20N·m 17mm
0.5mm
selected.
18K#, 21K~36K 5K~13K 12K#, 13K~18K 18K#, 21K~36K 36K#
Liquid Side (9.53mm or 3/8 inch) 30~35N·m Gas Side (9.53mm or 3/8 inch) 30~35N·m Gas Side (12mm or 1/2 inch) 50~55N·m Gas Side (16mm or 5/8 inch) 60~65N·m Gas Side (19mm or 3/4 inch) 70~75N·m
22mm 22mm 24mm 27mm 32mm
0.6mm 0.6mm 0.6mm 0.6mm 1.0mm
Note: The unit of 12K#,18K# and 36K# is bigger than the unit of 12K,
Caution: 1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, refer to the circuit diagram posted on the inside of the access door. 2. Comfirm that the cable thickness is as specified in the power source specification.
18K and 36K.
3. Check the wires and make sure that they are all tightly
fastened after cable connection.
Note: Piping connection should be conducted on outdoor 4. Be sure to install an earth leakage circuit breaker in wet or
side !
8 moist areas.
Cable Specifications for Inverter appliance
Capacity (Btu/h) 5K~13K 5K~13K 14K~18K 14K~18K
21K~36K 21K~30K 21K~24K
Power cord
Type
Normal cross – sectional area
Power connecting cord
Type
Normal cross – sectional area
H07RN-F 0.75~1.5mm2X3 H05RN-F 0.75mm2X4
H07RN-F H05VV-F IS:694
0.75~1.5mm2X3 0.75~1.5mm2X3
0.75~1.5mm2X3
H07RN-F H07RN-F IS:9968
0.75~1.5mm2X5 0.75~1.5mm2X4
0.75~1.5mm2X4
H07RN-F 1.5mm2X3
H07RN-F 1.5mm2X3 H05VV-F 1.5/2.5mm2X3
H05RN-F
H07RN-F H07RN-F
0.75mm2X4
1.5mm2X5 1.5/2.5mm2X4
IS:694
1.5/2.5mm2X3
IS:9968
1.5/2.5mm2X4
H07RN-F 2.5mm2X3
H05RN-F 0.75mm2X4
H07RN-F H07RN-F H05VV-F
2.5mm2X3 2.5mm2X3 2.5mm2X3
H07RN-F H07RN-F H07RN-F
1.0mm2X4 2.5mm2X5 2.5mm2X4
IS:694
2.5mm2X3
IS:9968
2.5mm2X4
H05VV-F 1.5mm2X3
H07RN-F 1.5mm2X4
NOTE: 1.K* means the power supply of this model comes from indoor unit. 2.K*
indicates indoor power supply unit model with power line and
plug. 3.For 14K~18K* models under Tropical(T3) Climate condition, the
normal cross-sectionl area of Power cord and Power connecting cord is
2.5mm2×4. Attention:
The plug must be accessible even after the installation of the appliance in
case there is a need to disconnect it. If not possible, connect appliance to a
double-pole switching device with contact separation of at least 3 mm placed
in an accessible position even after installation.
Cable Specifications for ON-OFF appliance
Capacity (Btu/h)
5K~13K 14K~24K 18K~30K
18K~30K 24K~36K 24K~36K
Power cord
Type
Normal cross – sectional area
Power connecting cord
Type
Normal cross – sectional area
Power connecting cord1
Type
Normal cross – sectional area
Main power supply
H05VV-F
0.75~1.5mm2X3
H07RN-F H05RN-F
1.5mm2X3 0.75~1.0mm2X3
H05RN-F
0.75mm2X2 (Heat-pump)
To indoor
H05VV-F 1.5~2.5mm2X3 H07RN-F
1.5~2.5mm2X3
H05RN-F
0.75mm2X2 (Heat-pump)
To indoor
H05VV-F
H07RN-F H07RN-F H07RN-F
1.5~2.5mm2X3
2.5mm2X3 2.5~4.0mm2X3
1.5mm2X5
H07RN-F
H05RN-F H07RN-F H05RN-F H07RN-F
H05RN-F
1.5~2.5mm2X4 H05RN-F
1.0mm2X3 1.0mm2X4Cooling only
H05RN-F
0.75mm2X4 1.0mm2X4
H05RN-F
0.75mm2X4 H05RN-F
0.75mm2X2 (Heat-pump&Optional)
To indoor
0.75mm2X3 (Heat-pump)
To outdoor
0.75mm2X2 (Heat-pump&Optional)
To outdoor
0.75mm2X2 (Heat-pump)
To outdoor
NOTE:
The cord may be different from the list above. It may be used as the next
list. And it can be larger.0-6A, use 0.75mm 2or 18AWG. 0-10A, use 1mm2 or
16AWG. 0-16A, use 1.5mm 2 or 14AWG 0-20A, use 2.5mm2 or 14AWG. 0-25A, use
2.5mm 2or 12AWG. 0-32A, use 4mm 2
Wiring diagram
Outdoor unit installation
1. Install Drain Port and Drain Hose (for heat-pump
model only)
The condensate drains
Rubber pad (optional) Place under the leg pedestal
from the outdoor unit when
the unit operates in heating
mode. In order not to
disturb your neighbor and
Washer
protect the environment, install
Drain port Drain hose
a drain port and a drain hose to direct (prepared by user)
the condensate water. Just install the drain port and
rubber washer to the chassis of the outdoor unit,
then connect a drain hose to the port as the right
figure demonstrates.
2. Install and Fix Outdoor Unit Fix with bolts and nuts tightly on a flat and
strong floor. If installed on the wall or roof, make sure to fix the supporter
well to prevent it from shaking due to serious vibration or strong wind. 3.
Outdoor Unit Piping Connection
Remove the valve caps from the 2-way and 3-way valve. Connect the pipes to the
2-way and 3-way valves separately according to the required torque.
4. Outdoor Unit Cable Connection (see previous page)
Air purging
The air which contains moisture remaining in the refrigeration cycle may cause
a malfunction on the compressor. After connecting the indoor and outdoor
units, release air and moisture from the refrigerant cycle using a vacuum
pump, as shown below.
Note: To protect the environment, be sure not to discharge the refrigerant to
the air directly.
Warning: Before obtaining access to terminals, all supply circuits must be disconnected. Make sure that the color of the wires in the outdoor unit and terminal No. are the same as those of the indoor unit, the details please refer to the wiring diagram which is near the terminal inside the unit.
Vacuum pump
indoor unit
Refrigerant flow direction
2-way valve
3-way valve diagram
3-way valve
connect to indoor unit
(6) Open 1/4 turn
Service port
(7) Turn to fully open the valve
(7) Turn to fully open the valve valve cap
(1) Turn
(8) Tighten
open position spindle
(2) Turn (8) Tighten
Valve cap
(1) Turn (8) Tighten
Connect to outdoor unit
needle
Valve core
service port cap
9
How to Purge Air Tubes:
(1) Unscrew and remove caps from 2 and 3-way valves. (2) Unscrew and remove
cap from service valve. (3) Connect vacuum pump flexible hose to the service
valve. (4) Start vacuum pump for 10-15 minutes until reaching a vacuum of
100Pa absolutes. (5) With vacuum pump still running close the low .pressure
knob on vacuum pump manifold. Then stop the vacuum pump. (6) Open 2-way valve
,1/4 turn, then close it after 10 seconds. Check tightness of all joints using
liquid soap or an electronic leak detector (7) Turn 2 and 3-way valves stem to
fully open the valves. Disconnect the flexible vacuum pump hose. (8) Replace
and tighten all valve caps.
Maintenance
Front panel maintenance
Cut off the power supply
a
Turn off the appliance first before disconnecting from power supply.
Grasp position “a”
and pull outward to
remove the front panel.
a
Wipe with a soft and dry cloth.
Use soft moisture cloth to clean if the front panel is very dirty;
Never use volatile Use a dry and substance such as gasoline soft cloth to or
polishing powder to clean
clean it. the appliance.
Protection
Operating condition
Operating temperature for Inverter appliance
Temperature Cooling operation Heating operation Drying operation
Indoor max temperature min
32 21
27 7
32 18
Outdoor max temperature min
note note
24 -15
43 21
NOTE: Optimum performance will be achieved within these operating
temperature. If air conditioner is used outside of the above conditions, the
protective device may trip and stop the appliance. Normally,the outdoor max
temperature is 43,but some models will be achieved 46,48,or 50.For Tropical
(T3) Climate condition models, the outdoor max temperature is
55 . For some models, can keep cooling at -15 outdoor ambient via unique
design. Normally, optimum cooling
performance will be achieved above 21 . Please consult the merchant to get
more information. For some models, can keep heating at -15 outdoor
ambient , some models heat at -20 outdoor ambient, even heat at lower outdoor
ambient The temperature of some products is allowed beyond the range. In
specific situation, please consult the merchant. When relative humidity is
above 80%, if the air conditioner runs in COOLING or DRY mode with door or
window opened for a long time, dew may drip down from the outlet.
Operating temperature for ON-OFF appliance
The protective device maybe trip and stop the appliance in the cases listed
below
Never sprinkle water onto the indoor unit
Reinstall and shut the
front panel.
Reinstall and shut the front panel by
pressing position “b” downward.
b
b
Dangerous! Electric shock!
Air filter maintenance
Stop the appliance, cut off
Clean and reinstall the
the power supply and remove air filter.
the air filter.
If the dirt is conspicuous, wash it with a solution of
detergent in lukewarm
water.After cleaning,
dry well in shade.
1
23
1.Open the front panel. 2.Press the handle of the filter gently from the
front. 3.Grasp the handle and slide out the filter.
Close the front panel again It is necessary to clean the air filter
after using it for about 100 hours. Clean the air filter every two weeks if
the air conditioner operates in an extremely dusty environment.
Outdoor air temperature is over 24oC HEATING Outdoor air temperature is below
-7oC
Room temperature is over 27oC
note COOLING Room temperature is below 21oC
DRY Room temperature is below 18oC
NOTE: Normally,the outdoor max temperature is 43,but some models will be
achieved 46,48,or 50.For Tropical (T3) Climate condition models, the outdoor
max temperature is 55 . The temperature of some products is allowed beyond the
range. In specific situation, please consult the merchant. If the air
conditioner runs in COOLING or DRY mode withdoor or window opened for a long
time when relative humidity is above 80%,dew may drip down from the outlet.
Noise pollution
Install the air conditioner at a place that can bear its weight in order to
operate more quietly. Install the outdoor unit at a place where the air
discharged and the operation noise would not annoy your neighbors. Do not
place any obstacles in front of the air outlet of the outdoor unit lest it
increases the noise level.
10
Features of protector
1. The protective device will work at following cases. Restarting the unit at
once after operation stops or changing mode during operation, you need to wait
for 3 minutes. Connect to power supply and turn on the unit at once, it may
start 20 seconds later.
2. If all operation has stopped, press ON/OFF button again to restart, Timer
should be set again if it has been canceled.
Features of HEATING mode
Preheat
At the beginning of the HEATING operation, the airflow from the indoor unit is
discharged 2-5 minutes later.
Defrost
In HEATING operation the appliance will defrost (de-ice) automatically to
raise efficiency. This procedure usually lasts 2-10 minutes. During
defrosting, fans stop operation. After defrosting completes, it returns to
HEATING mode automatically. Note: Heating is NOT available for cooling only
air conditioner models.
Troubleshooting
The following cases may not always be a malfunction, please check it before asking for service.
Trouble
Does not run
No cooling or heating air
Analysis
1. If the protector trip or fuse is blown. 2. Please wait for 3 minutes and
start again, protector device may be preventing unit to work. 3. If batteries
in the remote controller exhausted. 4. If the plug is not properly plugged.
1. Is the air filter dirty 2. Are the intakes and outlets of the air
conditioner blocked 3. Is the temperature set properly
Ineffective control
Does not operate immediately
If strong interference(from excessive static electricity discharge, power
supply voltage abnormality)presents, operation will be abnormal. At this time,
disconnect from the power supply and connect back 2-3 seconds later.
Changing mode during operation, 3 minutes will delay.
Trouble
Analysis
A sound of flowing water Caused by the flow of refrigerant in the
air conditioner, not a trouble.
Defrosting sound in heating mode.
Cracking sound is heard The sound may be generated by the expansion or
contraction of the front
panel due to change of temperature.
Spray mist from the outlet Mist appears when the room air becomes very cold
because of cool air discharged from indoor unit during COOLING or DRY
operation mode.
The compressor indicator The unit is shifting from heating mode (red) lights
on constantly, to defrost.The indicator will lights off and indoor fan stops.
within ten minutes andreturns to
heating mode.
Display introduction
NO
Display
Introduction
1
2
3 4 5 6 7 8 9 10 11 12 13
14 AI
Example:
Temperature indicator Display set temperature. It shows FC after 200 hours of
usage as reminder to clean the filter.After filter cleaning press the filter
reset button located on the indoor unit behind the front panel in order to
reset the display.(optional)
Running indicator It lights up when the AC is running. It flashes during
defrosting.
Timer indicator
It lights up during set time.
Sleep indicator It lights up in sleep mode Compressor indicator It lights up
when the compressor is on
Mode indicator Heating displays orange,others display white
Fan speed indicator
Signal Receptor
Smart WIFI indicator It lights up during WIFI is on
NANOE indicator It lights up in NANOE mode. FAN ONLY mode indicator It lights
up in FAN ONLY mode
Airflow Follow You/Airflow Avoid You indicator Humidity indicator It lights up
in humidity mode. Artificial Intelligence Smart Running Indicator It lights up
in AI mode
1
2 3 45
8
8
1
don’t run
Peculiar odor
This odor may come from another source such as furniture, cigarette etc, which issucked in the unit and blows out with the air.
3
2
4
The symbols may be different from these models, but the functions are similar.
11
Emergency button A
A
Pressing this button can let the AC run or stop.
The symbol may be different from your model, but the button is similar.
12
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>