PHILIPS BRP130/131/132 LED Street Light Instructions

June 4, 2024
Philips

PHILIPS BRP130/131/132 LED Street Light

Mounting Instruction

Type| LEDs| Power/W| CCT/K| *Light Source Energy Efficiency Class| Maximum Number of Luminaire on MCB 16A Type B| Inrush Current| Voltage
---|---|---|---|---|---|---|---
BRP130 LED88/WW 70W 220-240V DM GM| 82| 70| 3000|

D

|

50

|

15A/1.5μs

|

220-240~

50/60Hz

BRP130 LED88/NW 70W 220-240V DM GM| 82| 70| 4000
BRP130 LED88/CW 70W 220-240V DM GM| 82| 70| 5700
BRP131 LED125/WW 100W 220-240V DM GM| 112| 100| 3000|

D

|

35

|

15A/1.5μs

BRP131 LED125/NW 100W 220-240V DM GM| 112| 100| 4000
BRP131 LED125/CW 100W 220-240V DM GM| 112| 100| 5700
BRP132 LED175/WW 140W 220-240V DM GM| 154| 140| 3000|

D

|

25

|

15A/1.5μs

BRP132 LED175/NW 140W 220-240V DM GM| 154| 140| 4000
BRP132 LED175/CW 140W 220-240V DM GM| 154| 140| 5700

This product contains a light source of energy efficiency class: see table

Type Weight(kg) L×W×H(mm) Wind force area(m²)
BRP130 2.6 382.5×248.4×85 0.08
BRP131 3.2 453.8×277.2×85 0.11
BRP132 4 508.2×325.5×85 0.14
  1. Connect the power cord

  2. Pole mounting

  3. Anti-drop stainless steel rope and locknut for the luminaire.
    Signify does not provide the anti-drop stainless steel rope and locknut.

  4. Surge production device (SPD) replacement.

Warning

  1. The luminaire shall be installed by a qualified electrican and wired in accordance with the latest IEEE electrical regulations or national requirements.
  2. Turn the power off before inspection, installation, or removal.
  3. If the external flexible cable or cord of this luminaire is damaged, it shall be exclusively replaced by the manufacturer or his service agent or a similarly qualified person in order to avoid a hazard.
  4. Use IP66 rated environmentally sealed power connector with a cable clamp to ensure IP66 ingress protection
  5. Ensure power supply cables (L-N / L-N-E) are connected correctly before switching on.
  6. The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similarly qualified person.

Maintenance

  1. Ensure the power supply is switched off before attempting any maintenance work.
  2. Periodic cleaning of the luminaire optical lens cover will ensure maximum optical efficiency.
  3. Luminaire optical lens cover shall be cleaned with clean water and non-abrasive soap, cleaner or detergent solution.

Caution
The Luminaire must be used within the applicable product specifications, installation instructions and environmental conditions for storage & operations according to application guidelines provided by Signify for the product Warranty to be valid.

Signify (China) Investment Co., Ltd. Building No. 9, Lane 888 Tianlin Road, Minhang District, Shanghai, China
Postalcode: 200233

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Philips User Manuals

Related Manuals