FOSTER XR600H Xtra Cabinets Refrigerator Instruction Manual
- June 12, 2024
- FOSTER
Table of Contents
FOSTER XR600H Xtra Cabinets Refrigerator
IMPORTANT INSTRUCTIONS
These instructions should be retained and made readily accessible by personnel using the appliance. The instructions should be read thoroughly prior to appliance installation. The information contained in this manual is intended to use by trained, competent personnel only. Failing to follow the advice contained in this manual may result in damage to the appliance and personal injury to the operator.
All installations must conform to local and municipal regulations and directives. In case of doubt contact your Foster authorised distributor or the Foster Technical Department.
The information contained in this manual is current at the time of publication and is subject to change without notice.
CAREFUL – DANGER
Ignoring this sign and remarks may result in personal danger.
CAREFUL – DANGER
Ignoring this sign and remarks may result in damage to your appliance.
INFORMATION
Useful hints to make the best use of your appliance.
Climate Class
Climate class indicated on the serial plate shows the ambient temperature & humidity at which this appliance has been tested, for the purposes of establishing values in line with European standards.
Climate Class
|
Temperature
|
Relative humidity
---|---|---
4
|
30˚C
|
55%
5
|
40˚C
|
40%
General Safety
- Do not store explosive substances such as aerosol cans with a flammable propellant in this appliance.
- Keep all ventilation openings in the appliance or in the structure of a built in unit clear of any obstructions.
- Do not use electrical appliances inside the storage compartment.
- Do not use steam cleaners, pressure washers or other jets/sprays of water on or around the appliance.
- The appliance is air tight when the door is closed therefore under no circumstances should any living body be stored or ‘locked in’ the appliance.
- This appliance is heavy. When moving the appliance care should be taken and correct safe practices followed. The appliance should not be moved over uneven surfaces.
- The emitted sound level of this appliance is not greater than 70dB(A).
- To ensure stability the appliance should be located on a flat, level surface, correctly loaded.
- Do not use mechanical devices to accelerate the defrost process.
- Care should be taken not to damage the refrigeration circuit and/or system.
- If the supply cord is damaged, it must be replaced by the manufacturer, it’s service agent or similarly qualified persons in order to avoid hazards.
- Care should be taken to avoid prolonged contact with cold surfaces with unprotected body parts, correct PPE to be used at all time.
Disposal Requirements
This appliance contains components and materials which can be harmful to the environment if not disposed of correctly. Disposal of this appliance should be carried out by a suitably licensed waste contractor in accordance with national laws and regulations which may be in force at the time.
Electrical Safety
This equipment shall be connected to an electrical supply protected by a Residual Current Device (RCD). This may include a residual current circuit breaker (RCCB) type socket, or through a Residual Current Circuit Breaker with overload protection (RCBO) supplied circuit.
Should it be necessary to replace the fuse, the replacement fuse must be of the value stated on the serial label for the appliance.
Start-Up and Test Sequence
After unpacking, clean (cleaning directions supplied within this manual) and allow the appliance to stand for 60 minutes before turning on.
Ensure the appliance is situated on a firm, level surface, away from both hot and cold air sources, as this will affect its performance.
Place the appliance in a location so as not to exceed the maximum rated ambient temperature.
The appliance produces warm air when operating normally and requires adequate
ventilation. The dimensions indicated are a minimum.
Connect the appliance to a suitable power supply. Do not connect or disconnect the appliance with wet hands. The appliance will turn on automatically displaying the actual internal temperature of the appliance and ‘PF’. To cancel the alarm press button 1. If this does not happen and the display shows ‘ – ‘ press and hold button 1 for 3 seconds to turn on the appliance.
As the operating temperature has been pre-set no adjustments are required. Allow the appliance to reach its normal operating temperature before loading with product.
Operating Instructions
Display Icons and Buttons
Icon | Button |
---|---|
a | Compressor on / Alarm |
b | Evaporator fans on |
c | Defrost on |
d | 2nd operating function on |
e | °C / User menu active |
f | Keypad locked / Service function active |
g | Decimal point / Defrost active |
Note – Icons a, b, c, d are only visible after pressing either buttons 1, 2, 3 or 4.
The appliance is designed for the storage of product at the appropriate temperature. It is not designed to chill or freeze product from a higher temperature. Using the appliance in this manner may result in malfunction, damage and invalidate the warranty
Standby
Pressing button 1 for 3 seconds will turn the unit on or into standby. When in standby the display will only display ‘ – ‘. The remainder of the display will be blank. When operating normally, the display will show the internal temperature of the cabinet.
Set Point
To display the appliance Set Point, with the display showing the temperature, press button 2 for 3 seconds and the display will show ‘SP’. Then press button 1 once to display the current set point.
Adjust the set point using button 2 to increase and button 4 to decrease. Press button 1 to save the new value and the display will show ‘Loc’. If button 1 is not pressed the new value will not be stored. Exit by pressing button 3.
If the Set Point cannot be adjusted to the value required please contact your authorised Foster dealer for advice.
The display will resume normal operation after 30 seconds or if button 3 is pressed.
Keypad Security Settings
The keypad can be locked to prevent unauthorised adjustment of the appliance and it’s operating temperature.
When the keypad is locked no adjustments can be made using the keypad and icon ‘f’ will be displayed.
To lock or unlock the keypad press and release button 2 for 3 seconds and the display will show ‘SP’. Release the button and then press button 2 once and the display will show ‘Loc’. Press button 1 to display the current keypad lock status. Adjust using button 2 and button 4 to set the value to ‘Yes’ to lock the keypad and ‘no’ to unlock the keypad. Press button 1 to save the new value. If button 1 is not pressed the new value will not be stored. The display will resume normal operation after 30 seconds or if button 3 is pressed.
Defrost
The appliance has an automatic defrost function and will defrost periodically each day without any user intervention. This process is normal and does not affect product stored in the appliance. During defrost the appliance can be used as normal.
To start a defrost manually press and hold button 1 for 5 seconds. This will turn off the appliance. When this happens do not release the button and after 2 more seconds the display will indicate a defrost has commenced (dEF is briefly displayed) and the button can be released. The appliance set point temperature will be displayed during defrost and icon ‘g’ will flash to indicate a defrost is in progress.
The defrost will operate for it’s full duration, it is not possible to cancel a defrost when it has started.
Keypad Sounds
If the user does not require the keypad to indicate with a sound when a button is pressed this can be turned off. Press and hold button 2 for 3 seconds until the display shows ‘SP’. Press button 2 until the display shows ‘biP’. Press button 1 to display the current value. ‘Yes’ indicates keypad sounds are active and ‘no’ indicates keypad sounds are not active. Select the value required and press button 1 to save the new value. If button 1 is not pressed the new value will not be stored. Exit with button 3.
Shelves, Supports, Loading and Air Flow
The appliance is supplied with adjustable, removable trayslides and shelves.
Each shelf is capable of holding up to 40kg of product evenly distributed.
Do not block air vents with product. A minimum of 25mm should be maintained between the top of the product and the shelf above.
Do not place product directly on the base of the appliance.
Always ensure air can circulate around/through the stored product. It is important that for optimum energy and temperature performance that adequate airflow is maintained around the perimeter of the shelves, and around all stored products.
Door Lock
To lock the door insert the key and turn 90°, turn in the opposite direction to unlock.
Alarms Notification
If an alarm condition occurs the appliance will indicate this with an audible signal, by illuminating icon ‘a’ and displaying a fault code from the list in the ‘Troubleshooting’ section of this manual . The audible notification can be muted temporarily by pressing button 1. While the fault is still present icon ‘a’ will continue to be illuminated and the display will cycle between the fault code and the appliance temperature.
Service Function
Controller Menu’s
The controller contains 2 menu levels, user level and service level.
User Level Menu
To access user level settings, press button 2 for 3 seconds and the display will show ‘SP’. Use buttons 2 and 4 to move through the parameter required. Press button 1 to display the current value. If it is required to amend the value use buttons 2 and 4 followed by button 1 to save the new value. The display will resume normal operation after 30 seconds or if button 3 is pressed.
User Level Parameters
Mnemonic | Description |
---|---|
SP | Appliance operating set point |
biP | Enable the key audible feedback |
rFP | Return controller to factory default parameters. Note – If the |
controller has not been programmed by Foster this function will load a
standard high temperature cabinet parameter set.
dEF| Time to next defrost cycle
thi| Maximum temperature logged
tLo| Minimum temperature logged
tA| Actual air probe value
tE| Actual evaporator probe value (Not enabled on all models)
Loc| Keypad lock function
Service Level Menu
To access service level menu, press and hold buttons 2 and 4 for 5 seconds and the display will show ‘MdL’. Icon ‘f’ will flash to indicate that the service function is active. Use buttons 2 and 4 to display the parameter required. Press button 1 to display the current value. If it is required to amend the value use buttons 2 and 4 followed by button 1 to save the new value. If button 1 is not pressed the new value will not be saved. Exit using button 3 or wait 30 seconds
Service Level Parameters
MNEMONIC: | DESCRIPTION: |
---|---|
MDL | Temperature control mode. |
conventional hysteresis control
‘HEA’ – Heated cabinet control / conventional hysteresis switching mode.
SPL| Minimum limit for ‘Performance’ mode SetPoint setting.|
SPH| Maximum limit for ‘Performance’ mode SetPoint setting.|
SP| Performance mode Setpoint.| Temperature value to be maintained in
the product.
HY0| Thermostat OFF -> ON differential (in Cooling Mode – ‘MDL’ =
‘HYS’).| In Cooling Mode – ‘MDL’ = ‘HYS’.
HY1| Thermostat ON -> OFF differential.| In Heating Mode – ‘MDL’ =
‘HEA’.
CMD| Compressor start delay ‘run’ mode.| The time between mains power
being applied and the compressor starting when in ‘run’ mode (i.e. following a
mains power cut).
CRT| Compressor rest time.| Minimum time compressor is switched off
following cycle operation (i.e. pull down, hot gas defrost).
CT1| Compressor/Heater (R1) output on time.| Followed by ‘CT2’ when
probe Ta (T1) is faulty.
CT2| Compressor/Heater (R1) output off time| Followed by ‘CT1’ when
probe Ta (T1) is faulty.
DFM| Defrost start mode.| ‘NON’ – defrost function is disabled – no
defrosts will occur.
‘TIM’ – Time. Defrosting occurs on a time base determined by ‘DFT’,
accumulated only in run mode.
‘FRO’ – Frost Forming. The defrost time count is only increased when the
conditions occur for frost to form on the evaporator.
‘DoD’ – Defrost On Demand. When ‘T2’ = ‘Yes’, the ‘Te’ temperature is below
‘DSP’ for the time defined in ‘DST’, a defrost will be initiated.
‘TAD’ – Time And Demand defrosting. Defrosting occurs in accordance with
‘DFT’, but additionally, if the ‘Te’ temperature is below ‘DSP’ for the time
defined in ‘DST’ a defrost will be initiated.
DFT| Time interval between defrosts.| When this time has elapsed since
the previous defrost (in run mode), a new defrost cycle is initiated.
DSP| Defrost suction temperature.| The sustained (based on ‘DST’ Time)
temperature, below which ‘Te’ must remain in order to initiate a ‘DoD’ or TAD’
defrost.
DST| Defrost suction time.| The time period that the measured
temperature must be below ‘DSP’ in order to initiate a ‘DoD’ or TAD’ defrost.
DMI| Defrost minimum interval.| The minimum time period between two
‘DoD’ or ‘TAD’ defrost periods.
DLI| Defrost end temperature.|
DTO| Maximum defrost duration.|
DTY| Defrost type.| ‘OFF’ – Off cycle defrost (Compressor and Heater
OFF).
‘ELE’ – Electric defrost (Compressor OFF and Heater ON).
‘GAS ‘ – Hot gas defrost (Compressor and Heater ON).
DSY| Defrost start synchronization.| ‘OFF’ – none. The defrost will
occur without delay.
---|---|---
‘LO’ – defrost start will be postponed to compressor cut-out (SOD = max
delay).
‘HI’ – defrost start will be postponed to compressor cut-in (SOD = max delay).
SOD| Timeout period for defrost start.| Using cycle synchronization
(‘DSY’) to prevent no defrost through usage. When ‘SOD’
= ‘0’ defrost will start immediately.
DPD| Evaporator pump down.| At the beginning of defrost, defrost outputs
(determined by ‘DTY’) are ‘OFF’ for ‘DPD’ seconds.
DRN| Pause after defrost (evaporator drain down time).|
DDM| Defrost display mode.| ‘RT’ – the real / actual temperature.
‘LT’ – the last temperature displayed before defrost initiation.
‘SP’ – the setpoint value.
‘dEF’ – ‘dEF’.
DDY| Display delay.| The display shows the information selected with
parameter ‘DDM’ during defrost and for ‘DDY’ minutes after defrost
termination.
FID| Evaporator Fans in defrost.| YES – Fans active during defrost and
drain (‘DRN’) and recovery / NO – Fans off during defrost and drain (‘DRN’)
and recovery (fan start based on ‘FDD’ or ‘FTO’ – whichever first).
FDD| Evaporator fan re-start temperature after defrost.|
FTO| Maximum evaporator fan stop after defrost.|
FMS| Fan Minimum stop time.| When the evaporator fan(s) stop(s), it/they
remains off for at least ‘FMS’ seconds.
FSD| ‘Evaporator fan stop delay after door opens:| Time in seconds: ‘-1’
= fan(s) do not stop / ‘0’ = fan(s) stop instantaneously / ‘1’-‘900’ = fans
stop after prescribed time elapses.
FCM| Thermostatic control fan mode.| ‘NON’ – The fans remain ON all the
time (subject to door switch operation and defrosts).
‘TMP’ – Temperature-based control. The fans are ON when the compressor is ON.
When the compressor is turned OFF, the fans remain ON as long as the
temperature difference Te-Ta is greater than ‘FDT’.
‘TIM’ – Timed-based control. The fans are ON when the compressor is ON. When
the compressor is OFF, the fans switch ON and OFF according to parameters
‘FT1’, ‘FT2’ and ‘FT3’.
FDT| Evaporator fan compressor stop over-run.| Where Evaporator (Te)
-Air (Ta) temperature difference for the fans to turn OFF after the compressor
has stopped.
FDH| Temperature differential for fan re-start.| Example: ‘FDT’ = ‘-1’
and ‘FDH=3’. If compressor is stopped, the fans are OFF when Te> Ta ‘-1’
(‘FDT’), whereas the fans are ON when Te < Ta ‘-4’ (‘FDT’-‘FDH’).
FT1| Fan stop delay after compressor/ heater stop.|
FT2| Timed fan stop.| When ‘FT2’ = ‘0’ the fans remain on all the time.
FT3| Timed fan run.| When ‘FT3’ = ‘0’, and ‘FT2’ > ‘0’, the fans remain
OFF all the time.
ATM| Alarm threshold management.| ‘NON’ – all temperature alarms are
inhibited (the following parameter will be ‘ACC’).
‘ABS’ – the values programmed in ‘ALA’ and ‘AHA’ represent the real alarm
thresholds.
‘REL’ – the alarm threshold is obtained by the sum of setpoint, thermostat
differential and ‘ALR’ / ‘AHR’.
ALA| Low temperature alarm threshold.|
AHA| High temperature alarm threshold.|
ALR| Low temperature alarm differential.| With ‘ALR’ = ‘0’ the low
temperature alarm is excluded.
AHR| High temperature alarm differential.| With ‘AHR’ = ‘0’ the high
temperature alarm is excluded.
ATI| Probe used for temperature alarm detection.|
PAD| Delay before alarm temperature warning at power on.|
---|---|---
ATD| Delay before alarm temperature warning.|
ACC| Condenser periodic cleaning.| When the compressor operation time,
expressed in weeks, matches the ‘ACC’ value programmed, ‘CL’ flashes in the
display. With ‘ACC’ = ‘0’ the condenser cleaning warning is disabled.
IISM| Switchover method to second parameter set.| ‘NON’ – the 2nd
Temperature / Switched Output button primary function is inhibited (the
following parameter will be ‘DSM’).
‘2ND’ – when activated the controller will change to mainatin temperature /
defrost in accordance with parameters ‘IISL’, ‘IISH’, ‘IISP’, ‘IIHY’, ‘IIFC’,
and ‘IIDF’.
‘LCM’ – The Switch / 2nd temperature button [3] will operate as determined by
parameter ‘LCM’.
IISL| Minimum limit for ‘IISP’ setting.|
IISH| Maximum limit for ‘IISP’ setting.|
IISP| Temperature setpoint to be achieved in ‘Mode 2’.|
IIHY| Off / On thermostat differential in ‘Mode 2’.|
IIFC| Evaporator fan mode during ‘Mode 2’ thermostatic control.|
IIDF| Time interval between defrosts in ‘Mode 2’.|
DSM| Door switch mode.| ‘NON’ – when ‘DI1’/’T3A’ = ‘DOR’ there is no
response to a state change.
‘ALR’ – when ‘DI1’/’T3A’ = ‘DOR’ and the digital input is ON, an alarm is
generated after ‘DAD’ minutes.
‘STP’ – when ‘DI1’/’T3A’ = ‘DOR” and the digital input is ON, in addition to
the alarm, the fans are stopped according to ‘FSD’ and the compressor is
stopped after ‘CSD’ seconds.
DAD
Delay before door open alarm warning.
CSD| ‘Relay 1’ de-energise delay after door open.| ‘0’ … ‘900’ – time in
seconds (‘-1’ = ‘Relay’ does not de-energise / ‘0’ = instantaneous / ‘1’-‘900’
= de-energises after prescribed time elapses).
DOT| Door stop overide.| If the door switch remains open for longer than
‘DOT’ minutes, the operating functionaity returns to normal thermostatic
control, however the alarm will remain. When ‘DOT’ = ‘0’, this function is
disabled.
DI1| ‘DI1’ digital input.| ‘NON’ – Digital Input 1 not active.
‘DOR’ – door input.
‘ALR’ – when the input is activated (set by ‘D1A’) alarm ‘Alr’ alarm is
generated, the compressor is stopped and the defrosts are suspended.
‘2ND’ – when the input is ‘ON’ the controller will use ‘2ND’ temperature
parameters.
‘RDS’ – when the input is ‘ON’ a defrost is started (by ‘remote’ control).
D1A| ‘DI1’ activation.| ‘OPN’ – on open.
‘CLS’ – on close.
LCM| | ‘MAN’ – Output switched directly through 2nd / Switched operating
button [3] when ‘RL2’ or ‘RL3’ = ‘LGT’.
‘2ND’ – Output activated/deactivated in line with ‘2ND’ temperature state (on
when ‘2ND’ active, off when ‘2ND’ is de-activeate).
‘DI1’ – lights activated/deactivated following the ‘DI1’ state.
‘NI1’ – lights activated/deactivated not following the ‘DI1’ state (as ‘DI1’
but operating in reverse).
‘DI2’ – lights activated/deactivated following the ‘DI2’ state.
‘NI2’ – lights activated/deactivated not following the ‘DI2’ state (as ‘DI2’
but operating in reverse).
RL2| Relay 2 output operation.| ‘NON’ – Relay output disabled (always
Off/Open).
---|---|---
‘LGT’ – Output enabled for light control.
‘0-1’ – Relay contacts follow the on/standby state of controller.
‘R1’ – Relay output energised in synchronisation with Relay 1 (compressor /
heater) incorporating delay ‘2CD’.
‘R1F’ – Relay output energised in synchronisation with Relay 1 (compressor)
except during defrost periods.
‘-R1’ – Relay output energised in antiphase to Relay 1 (run mode only).
‘FAN’ – Output enabled for evaporator fan switching.
‘-FAN’ – Relay output energised in antiphase to FAN (run mode only).
‘DEF’ – Output enabled for defrost switching.
‘-DEF’ – Relay output energised in antiphase to DEF (run mode only).
‘PET’ – Relay output energised for time defined in parameter ‘PET’ before
Relay 1 (condensing system) energised.
‘ALO’ – Contacts open when an alarm condition occurs.
‘ALC’ – Contacts make when an alarm condition occurs.
‘ACP’ – Auto Cycle Pattern – during run mode automatically switches relay on (
‘ACN’) and off (‘ACF’) based on a regular time pattern independent of
refrigeration cycle.
RL3| Relay 3 output operation.| Same operations and selection as ‘RL2’.
ACN| ‘When ‘RLx’ = ‘ACP’, ‘ACN’ is the ‘ON’ time of the Auto Cycle
Pattern.|
ACF| ‘When ‘RL’ = ‘ACP’, ‘ACF’ is the ‘OFF’
time of the Auto Cycle Pattern.
|
PET| Pre-c Condensing system (RL1) energisation of relays 2 / 3 for re-
start pressure equalisation. With ‘PEt’ = ‘0’ RL1 is energised instantly (no
delay), with ‘PEt’ = ‘0’ … ‘900’ RL1 is energised after the set delay. Relay
set to ‘PEt’ is is de-energised with RL1.|
2CD| Auxiliary compressor start delay.| If ‘RL1’ or ‘RL2’ = ‘R1’ the
output is switched on with a delay of ‘2CD’ seconds after the main compressor
(‘RL1’) has energised. Relays will be de-energised at the same time.
SDT| Service Countdown Function.| If ‘Sdt’ = ‘0’ the countdown function
is disabled. If ‘Sdt’ = ‘1’ – ‘999’ the countdown will reduce from the
specified value.
SB| Stand-by button enabling.|
BOS| Button Operation Sounder| YES’ provides positive feedback (i.e.
‘beep’) every time a display button is pressed, ‘NO’ sounder is silencer
during display button operation.
RHC| Routine Health Check.| Time period between automatic initiation of
Footprint test following a defrost. Used as part of IoT maintenance regime –
timer resets on mains power removal (‘0’ – no health check … time to elapse).
OSA| Probe TAir (T1) offset.|
TE| Probe TEvaporator (T2) enabling.|
OS2| Probe TEvaporator (T2) offset.|
T3A| DI2 / TAuxiliary Probe Enabling and Operation.| ‘NON’ – DI2 /
Auxiliary probe not fitted.
---|---|---
‘DSP’ – Auxiliary Probe – general purpose temperature measurement (i.e. stored
product temperature).
‘CND’ – Condenser probe – if measure temperature exceeds value of ‘AHT’
controller will react as defined by ‘AHM’.
‘2EU’ – Evaporator second temperature probe.
‘DOR’ – Digital Input 2 used for door switch operation.
‘ALR’ – Digital Input 2, when the input is ‘ON’ a High Pressure (‘HP’) alarm
is generated (if ‘AHM’ = ‘STP’ the compressor is stopped and the defrosts are
suspended).
‘2ND’ – Digital Input 2, when the input is ‘ON’ the controller will use ‘2nd’
Mode parameters.
‘RDS’ – Digital Input 2, when the input is ‘ON’ a defrost is started (by
‘remote’ control).
OS3| Auxiliary Probe 3 offset.|
D2A| ‘DI3’ activation.| ‘OPN’ – on open.
‘CLS’ – on close.
AHM| Operation in alarm when ‘T3A’ = ‘CND’.| ‘NON’ – Audible and visual
alarm is inhibited.
‘ALR’ – when ‘T3A’ = ‘CND’ and temp. > ‘AHT’ condenser high temperature ‘HC’
alternates in the display and the alarm sounder is activated.
‘STP’ – in addition to the alarm signal, the compressor is stopped and
defrosts are suspended.
AHT| Condenser temperature alarm (referring to TAuxiliary probe).|
TLD| Delay for minimum temperature (‘TLO’) and maximum temperature
(‘THI’) logging.| With ‘TLD’ = ‘0’ the logging is disabled.
TDS| The temperature probe value to be displayed.| ‘TA’ – actual Tair
(T1) value.
TAS’ – actual Tair (T1) value slowed (rate of change toward setpoint = actual
value, away from setpoint = mathematical algorithm applied).
‘A-E’ – the AVG-weighted average between TAir (T1) and TEvaporator (T2)
probes.
‘T3’ – TAuxiliary (T3) probe value (when ‘T3A’ = ‘DSP’, ‘CND’ or ‘2EU’).
SIM| Display slowdown.| Active when ‘TDS’ = ‘TAS’, the SIM value is the
controlling arithmetical value.
AVG| The relative weight of T2 in respect of T1 (when ‘TDS’ = ‘A-E’).|
SCL| Readout scale.| ‘°C’ with non adjustable resolution in User
Function Menu
‘°C’ with adjustable resolution in User Function Menu
‘°F’ with non adjustable resolution in User Function Menu
‘°F’ with adjustable resolution in User Function Menu
PRT| Modbus communication type.| RTL or ASCII
ADR| FD1-19 address for PC communication.|
RFP| Return to Factory Parameters.| Allow options through ‘User Menu’ to
reset all controller parameters to factory production values (i.e. those
programmed via UPS).
Parameter Setting
| Mnemonic:| Default| Single Section High Temperature|
Single Section Low Temperature| Double Section High Temperature|
Double Section Low Temperature
---|---|---|---|---|---|---
1| MDL| HY| HY| HY| HY| HY
2| SPL| 1| 1| -21| 1| -21
3| SPH| 3| 3| -15| 3| -15
4| SP| 2| 2| -21| 2| -21
5| HY0| 3| 3| 3| 3| 3
6| HY1| 0| 0| 0| 0| 0
7| CMD| 30| 30| 30| 30| 30
8| CRT| 90| 90| 90| 90| 90
9| CT1| 4| 4| 4| 4| 4
10| CT2| 7| 7| 7| 7| 7
11| DFM| tiM| tiM| tiM| tiM| tiM
12| DFT| 6| 6| 6| 6| 6
13| DSP| -12| -12| -12| -12| -12
14| DST| 15| 15| 15| 15| 15
15| DMI| 2| 2| 2| 2| 2
16| DLI| 10| 10| 20| 10| 20
17| DTO| 20| 20| 20| 20| 20
18| DTY| oFF| oFF| GAS| oFF| GAS
19| DSY| oFF| oFF| oFF| oFF| oFF
20| SOD| 5| 5| 5| 5| 5
21| DPD| 0| 0| 0| 0| 0
22| DRN| 60| 60| 60| 60| 60
23| DDM| SP| SP| SP| SP| SP
24| DDY| 2| 2| 2| 2| 2
25| FID| YES| YES| no| YES| no
26| FDD| 0| 0| 0| 0| 0
27| FTO| 2| 2| 2| 2| 2
28| FMS| 0| 0| 0| 0| 0
29| FSD| 0| 0| 0| 0| 0
30| FCM| non| non| non| non| non
31| FDT| 0| 0| 0| 0| 0
32| FDH| 2| 2| 2| 2| 2
33| FT1| 0| 0| 0| 0| 0
34| FT2| 0| 0| 0| 0| 0
35| FT3| 0| 0| 0| 0| 0
36| ATM| rEL| rEL| rEL| rEL| rEL
37| ALA| -30| -30| -30| -30| -30
38| AHA| 80| 80| 80| 80| 80
39| ALR| -5| -5| -5| -5| -5
40| AHR| 8| 8| 8| 8| 8
41| ATI| t1| t1| t1| t1| t1
42| PAD| 60| 60| 60| 60| 60
43| ATD| 90| 90| 90| 90| 90
44| ACC| 0| 0| 0| 0| 0
45| IISM| non| non| non| non| non
46| IISL| -21| -21| -21| -21| -21
47| IISH| -15| -15| -15| -15| -15
48| IISP| -21| -21| -21| -21| -21
49| IIHY| 3| 3| 3| 3| 3
50| IIFC| non| non| non| non| non
51| IIDF| 6| 6| 6| 6| 6
52| DSM| StP| StP| StP| StP| StP
53| DAD| 2| 2| 2| 2| 2
54| CSD| 90| 90| 90| 90| 90
55| DOT| 0| 0| 0| 0| 0
56| DI1| dor| dor| dor| dor| dor
57| D1A| oPn| oPn| oPn| oPn| oPn
58| LCM| non| non| non| non| non
59| RL2| FAn| FAn| FAn| FAn| FAn
60| RL3| 0-1| 0-1| dEf| 0-1| dEf
61| ACN| 0| 0| 0| 0| 0
62| ACF| 0| 0| 0| 0| 0
63| PET| 0| 0| 0| 0| 0
64| 2CD| 0| 0| 0| 0| 0
65| SDT| 0| 0| 0| 0| 0
66| SB| YES| YES| YES| YES| YES
67| BOS| YES| YES| YES| YES| YES
68| RHC| 0| 0| 0| 0| 0
69| OSA| 0| 0| 0| 0| 0
70| TE| NO| NO| YES| NO| YES
71| OSE| 0| 0| 0| 0| 0
72| T3A| non| non| non| dor| dor
73| OS3| 0| 0| 0| 0| 0
74| D3A| oPn| oPn| opn| oPn| opn
75| AHM| non| non| non| non| non
76| AHT| 60| 60| 60| 60| 60
77| TLD| 30| 30| 30| 30| 30
78| TDS| TAS| TAS| TAS| TAS| TAS
79| SIM| 10| 10| 10| 10| 10
80| AVG| 50| 50| 50| 50| 50
81| SCL| oCn| oCn| oCn| oCn| oCn
82| PRT| rtU| rtU| rtU| rtU| rtU
83| ADR| 1| 1| 1| 1| 1
84| RFP| YES| YES| YES| YES| YES
Other Information
Alarms/Warnings:
During operation the current temperature inside the appliance will be displayed. At certain times this will change to indicate a particular appliance operation or fault. The indicators you may see are as follows:
The temperature alarms are either relative to the set point or an absolute value. This is controlled by the value of parameter ‘ATM’. Where the alarms are relative the low alarm is the set point minus parameter ‘ALR’ and the high alarm is the set point plus ‘AHR’. When the temperature has been outside this value for the value of ‘ATD’ the relevant indicator will be displayed.
hi – The internal temperature of the appliance is higher than it should be. Ensure that the door is closed and that the air flow inside is not obstructed by excesive or poor loading of product. The alarm will reset if the temperature falls to a normal level.
Lo – The internal temperature of the appliance is lower than it should be. Check to ensure that the appliance has not been loaded with product at a lower temperature than the normal appliance operating temperature.
dO – The appliance door is open. Close the door to cancel the alarm. Note – the door switch is a magnetic switch located in the bottom edge of the front cover. If the cover is hinged up or removed for access purposes, the door switch will not function and the door open alarm will be displayed.
tA – This indicates that the internal temperature probe has failed. During this time the appliance cannot maintain an accurate temperature and all product should be removed and the appliance switched off.
tE – This indicates that the evaporator probe has failed.
PF – The mains power has been removed from the appliance for a period of time and has now been restored. This may have resulted in a rise in appliance temperature. Caution should be taken when using products stored within to ascertain whether these products are suitable for use. Upon restoration of the power supply the appliance will resume normal operation and the PF can be cancelled by pressing button 1 once.
hc – The condenser temperature is higher than it should be. If the appliance is being subjected to particularly high ambient temperatures steps should be taken to reduce this.
Cnd – The condenser clean period has expired.
While in an alarm condition icon ‘a’ will also be illuminated. The audible alarm can be muted temporarily by pressing button 1.
(Some indications are only visible periodically during specific appliance operations such as defrost or when activated through use of the appliance).
Probe Information
The probe is a type 10k NTC. The probes are identical in characteristics with the T1 and T2 identification markings and different colours being for ease of identification and not for functional reasons. Please refer to the image below for probe identification.
Probe Identification
Probe Resistance’
NTC10K Temperature Resistance Table SN4K
TEMP. (°C) | R-low (kΩ) | R-mid (kΩ) | R-high (kΩ) |
---|---|---|---|
-30 | 109.522 | 113.347 | 117.294 |
-25 | 84.823 | 87.559 | 90.374 |
-20 | 66.27 | 68.237 | 70.255 |
-15 | 52.229 | 53.65 | 55.104 |
-10 | 41.477 | 42.506 | 43.557 |
-5 | 33.147 | 33.892 | 34.651 |
0 | 26.678 | 27.219 | 27.767 |
5 | 21.63 | 22.021 | 22.417 |
10 | 17.643 | 17.926 | 18.21 |
15 | 14.472 | 14.674 | 14.877 |
20 | 11.938 | 12.081 | 12.224 |
25 | 9.9 | 10 | 10.1 |
30 | 8.217 | 8.315 | 8.413 |
35 | 6.854 | 6.948 | 7.043 |
40 | 5.745 | 5.834 | 5.923 |
Refrigerant Charge
The refrigerant charge weight can be found on the serial label within the appliance. Where this is not available please refer to the table below. The information below is correct time of printing but is subject to change without prior notice.
XR600H | 117gms |
---|---|
XR600L | 120gms |
XR1300H | 150gms |
XR1300L | 150gms |
Door Switch
The appliance is fitted with a magnetic door switch located in the underside of the front cover. Where the door switch is open and following the time set in parameter ‘DAD’, the controller will indicate ‘do’ and an alarm will sound. At the point the door is opened the evaporator fan(s) will stop and following the time set in parameter ‘cSd’ relay 1 will open until such time as the door is closed.
Defrost Indication
During defrost icon ‘c’ will be illuminated. The controller display will be determined by the value set in parameter ‘ddM’.
To start a defrost manually press and hold button 1 for 5 seconds. This will turn off the appliance. Continue to hold down button 1 after the appliance has turned off. After a further 2 seconds the display will indicate a defrost has commenced (icon ‘c’ illuminated) and the button can be released. While the defrost function is operating icon ‘c’ will be illuminated and icon ‘g’ will flash.
Where parameter ‘tE’ is set to ‘YES’ the defrost will operate until the temperature set in parameter ‘dLi’ or the time set in parameter ‘dto’ is reached. Where parameter ‘tE’ is set to ‘no’ the defrost will operate until the time set in parameter ‘dto’ is reached. Upon completion of the defrost cycle the appliance will resume normal operation with the current temperature displayed.
The defrost will operate for it’s full duration, it is not possible to cancel a defrost when it has started.
Relay Test
The controller contains a relay test function to enable the service engineer to operate individual relays, or a combination of relays for diagnostic purposes.
To access the relay test:
Press and hold buttons 2 and 4 for 5 seconds untilt he display shows ‘rL1’. Note – after 3 seconds the display will show ‘MdL’, continue to hold the buttons while this is displayed.
The controller is now in relay test mode.
- Select the relay to test by using buttons 2 and 4. When relay 1 is selected the display will show ‘rL1’ and icon ‘a’ will flash. This is repeated for relays 2 and 3 with icons ‘b’ and ‘c’.
- To activate relay 1 press button 1. Icon ‘a’ will illuminate. To deactivate relay 1 press button 1 again and icon ‘a’ will flash.
- To activate the selected relay press button 1. To deactivate the selected relay press button 1 again.
- When a relay is active the relevant icon (a, b or c) will be illuminated.
Multiple relays can be activated simultaneously to enable diagnostics.
Relay function:
- Relay 1 – Icon ‘a’ – Compressor.
- Relay 2 – icon ‘b’ – function determined by parameter ‘rL2’. Evaporator Fan.
- Relay 3 – icon ‘c’ – function determined by parameter ‘rL3’. Where appliance has an active defrost rL3 to will be set to ‘dEF’.
To exit the relay test function press button 3 once.
If no buttons are pressed for 30 seconds the controller will exit the relay test function and return to normal operation.
Factory Reset
Where the controller was originally programmed by Foster and is dedicated to a specific appliance type it is possible to return the setting to they’re original programmed state. If the controller was not programmed by Foster this function will return the parameters to the values in the original factory settings.
To reset the parameters:
- Press and hold button 2 for 3 seconds until the display shows ‘SP’.
- Press button 4 twice to display ‘rFP’.
- Press button 1 once and ‘rFP’ will flash.
- Press and hold buttons 2 and 4 for 3 seconds until the display shows ‘End’ and the display returns to the displaying the current temperature.
The original parameters as described above have now been restored.
If at any point the sequence of button operations and display indications are not completed the controller will, after 30 seconds resume operation with no changes to the parameters having been made.
Maintenance
Cleaning
Condenser
Regular cleaning of the condenser (located behind the front cover) increases energy efficiency and prolongs the life of your appliance. Never use a wire brush, abrasive or corrosive materials to clean the condenser. This should be carried out periodically, by a competent engineer as outlined in the Regular Maintenance section of this manual.
Gasket
All door gaskets should be inspected on a regular basis and replaced as
necessary if damaged. To clean, wipe with a warm damp soapy cloth followed by
a clean damp cloth. Finally dry thoroughly.
Shelves and Tray slides
The shelves and tray slides in the appliance can be removed for cleaning. The shelves are dishwasher safe however the vertical supports and tray slides should be cleaned with warm soapy water then rinsed and dried.
Wiring Diagrams
XR600H
XR600L
XR1300H
XR1300L
Customer Support
By Appointment to Her Majesty Queen Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator, King’s Lynn
For more information:
+44 (0) 1553 698485
regional@foster-gamko.com
fosterrefrigerator.com
Document ID code : 00-570677v1
For service and spares:
For service +44 (0) 1553 780333
service@foster-gamko.com
For parts +44 (0) 1553 780300