Carrier XCT-7 Variable Refrigerant Flow Controls Owner’s Manual
- June 13, 2024
- Carrier
Table of Contents
XCT-7 Variable Refrigerant Flow Controls
Owner’s Manual MODEL NAME:
KNX Gateway
Installation and Owner’s Manual
40VCBK17FQEE
1-T-40VCQUE-231020-EN-0
KNX gateway —40VCBK17FQEE 40VCBK27FQEE 40VCBK37FQEE
40VCBK17/27/37FQEE allows a complete and natural integration of air
conditioners with KNX control systems.
Compatible with all models of XCT7 line of air conditioners. Each SD outdoor
unit, 40VCCR17FQEE required.
Main features:
Compatible with all models of XCT7 line of air conditioners.
- Reduced dimensions. Installation even inside the A.C. indoor unit.
- Quick and non-visible installation.
- External power not required.
- Direct connection to the KNX EIB bus.
- Direct connection to the AC indoor unit.
- Fully KNX interoperable, configuration from ETS.
- Multiple objects for control (of different types: bit, byte, characters…).
- Control of the AC unit based in the ambient temperature read by the own AC unit, or in the ambient temperature read by any KNX thermostat.
- Total Control and Monitoring of the AC unit from KNX, including monitoring of AC unit’s state of internal variables, running hours counter (for filter maintenance control), and error indication and error code.
- AC unit can be controlled simultaneously by the IR remote control of the AC unit and by KNX.
- Max. 8/16/64 indoor units can be connected in one system
Technical Specifications
Connection
Connection of the interface to the AC indoor unit:
Disconnect mains power from the AC unit. Open the front cover of the indoor
unit in order to have access to the internal control board. In the control
board locate the socket connector marked as ABG1.
Using a 3-wire cable, connect the ABG1 connector from the 40VCBK17/27/37FQEEto
the A B G1 connector of the AC unit’s control board.
Fix the 40VCBK17/27/37FQEEinside or outside the AC indoor unit depending on
your needs – remember that 40VCBK17/27/37FQEEmust be also connected to the KNX
bus. Close the AC indoor unit’s front cover again.
Connection of the interface to the KNX bus:
Disconnect power of the KNX bus. Connect the interface to the KNX TP-1 (EIB)
bus using the KNX standard connector (red/grey) of the interface, respect
polarity. Reconnect power of the KNX bus.
Connections diagram:
Each Communication Adaptor connects to a single Outdoor Unit.
The 40VCBK17/27/37FQEE can be connected to more than one Communication Adaptor
simultaneously.
NOTE: More than one Communication Adaptor can be present in the installation.
Please make sure that the address of the Communication Adaptor is correctly
set in the ETS. Check section 4.6 for more information.
Configuration and setup
This is a fully compatible KNX device which must be configured and setup using
standard KNX tool ETS.
ETS project for this device can be downloaded from:
https://www.intesisbox.com/en/carrier-knx-ac-ha-acknx-8_16_64/gateway/ Please
consult the README.txt file, located inside the downloaded zip file, to find
instructions on how to install the database.
ETS Parameters
When imported to the ETS software for the first time, the gateway shows the
following default parameter configuration:
1.1.1 Interface (multiple indoor units) > General configurationWith this configuration it’s possible to send On/Off (Control
On/Off), change the AC Mode (Control Mode), the Fan Speed (Control Fan
Speed) and also the Setpoint Temperature (Control Setpoint Temperature). The
Status objects, for the mentioned Control objects, are also available to use
if needed. Objects Status AC Ambient Reference Temperature and Status
Error/Alarm are shown too. 4.1 General
configuration
Inside this parameter’s dialog it is possible to activate or change the
parameters shown in the Figure 4.1.
4.1.1 Download latest database entry for this product and its User Manual
from:
The first field shows the URL where to download the database and the user
manual for the product. 4.1.2 Intesis Product
This parameter is used to check, before sending the programing, the maximum
number of AC units your device supports. Select the
version of the gateway that you have:
- 40VCBK17FQEE, if you only want to control up to 8 AC unit.
- 40VCBK27FQEE, if you only want to control up to 16 AC units.
- 40VCBK37FQEE, if you only want to control up to 64 AC units
4.1.3 Number of Indoor Units in ETS
This parameter is used to hide/show communication object according to the
number of AC units you need to configure. Value ranges go from 1 to 64.
In case you introduce a number higher
than the maximum number of units allowed by your license, you will get a
warning message. This is just for information and will not block the
configuration process. Configurations with more indoor units configured than
the ones allowed by the license will not be downloaded correctly. 4.1.4 First Status Updated to KNX
This parameter defines how fast the status is updated to KNX. Depending on the
value selected, more or less priority will be assigned to this action. As
there are so many parameters available, it is important to consider carefully
how to set this parameter.
- If set to “ASAP”, all status communication objects will send its value (if needed).
- If set to “Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (ASAP).
- If set to “Super Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (Slow).
4.1.5 Enable object “Error Code [2byte]”
This parameter shows/hides the Status Error Code communication object which
shows the indoor unit errors, if occurred, in numeric format.o If set to “Disabled” the object will not be shown.
o If set to “Enabled” the Status Error Code [2byte signed value] object will
appear.
This object can be read and also sends the indoor unit error, if occurred, in
numeric format. If a “0” value is shown that means no error.
4.1.6 Enable object “Error Text Code [14byte]”
This parameter shows/hides the Status Error Text Code communication object
which shows the indoor unit errors, if occurred, in text format.o If set to “Disabled” the object will not be shown.
o If set to “Enabled” the Status Error Text Code object will appear.
This object can be read and also sends the indoor unit error, if occurred, in
text format. The errors shown have the same format as in the remote controller
and in the error list from the indoor unit manufacturer. If the object’s value
is empty, that means there is no error.
4.2 Global mode configuration
1.1.1 Interface (multiple indoor units)> Global Mode ConfigurationAll the parameters in this section are related with the
different mode properties and communication objectsThe byte-type communication object for Mode works with the
DTP20.105. Auto mode will be enabled with a “0” value, Heat mode with a “1”
value, Cool mode with a “3” value, Fan mode with a “9” value and Dry mode with
a “14” value.
4.2.1 Enable use of “Operating Mode” objects
This parameter shows/hides the Control and Status Mode Operating Mode
communication objects.4.2.2 Enable use of Mode
Heat/Cool objects
This parameter shows/hides the Control and Status Mode Cool/Heat
communication objects.o If set to “Disabled” the
objects will not be shown.
o If set to “Enabled” the Control and Status Mode Cool/Heat objects will
appear.
• When a “1” value is sent to the Control communication object, Heat mode
will be enabled in the indoor unit, and the Status object will return this
value.
• When a “0” value is sent to the Control communication object, Cool mode
will be enabled in the indoor unit, and the Status object will return this
value.
4.2.3 Enable use of + / – object for Mode
This parameter shows/hides the Control Mode +/- communication object which
let’s you change the indoor unit mode by using two different datapoint
types.o If set to “Disabled” the object will
not be shown.
o If set to “Enabled” the Control_ Mode +/- object and a new parameter will
appear.
. DPT type for +/- Mode Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008]
and 1- Decrease / 1-Increase [DPT1.007] for the Control Mode +/- object.
The sequence followed when using this object is shown below: Keep in mind that depending on the indoor unit you have and the
available features, Auto mode and Dry mode may not be present.
4.2.4 Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type Control Mode objects.o If set to “no” the objects will not be shown.
o If set to “yes” the Control Mode objects for Auto, Heat, Cool, Fan and Dry
will appear. To activate a mode by using these objects a “1” value has to be
sent.
4.2.5 Enable use of bit-type Mode objects (for status)
This parameter shows/hides the bit-type Status Mode objects.o If set to “no” the objects will not be shown.
o If set to “yes” the Status Mode objects for Auto, Heat, Cool, Fan and Dry
will appear. When enabled, a mode will return a “1” through its bit-type
object.
4.2.6 Enable use of Text object for Mode
This parameter shows/hides the Status Mode Text communication object.
o If set to “no” the object will not
be shown.
o If set to “yes” the Status Mode Text object will appear. Also, in the
parameters, will be shown five text fields, one for each mode, that will let
modify the text string displayed by the Status Mode Text when changing mode.
4.3 Global Fan Speed Configuration
dialog All the parameters in this section are
related with the Fan Speed properties and communication objects.
4.3.1 DPT object type for fan speed
With this parameter is possible to change de DPT for the Control Fan Speed
and Status_ Fan Speed byte-type communication objects. Datapoints Scaling
(DPT_5.001) and Enumerated (DPT5.010) can be selected.
o When “Enumerated [DPT 5.010]” is selected, Control Fan Speed and Status
Fan Speed communication objects for this DPT will appear. Also, depending on
the number of fan speeds selected, these objects will be different. The first fan speed will be selected if a “1” is sent to the
Control object. The second one will be selected sending a “2”, and the last
one sending a “3”.
The Status object will always return the value for the fan speed selected.
Important: If a “0” value is sent to the Control object, the minimum fan
speed will be selected. If a value bigger than “3” is sent to the Control
object, then the maximum fan speed will be selected.
o When “Scaling [DPT 5.001]” is selected, Control Fan Speed and Status Fan
Speed communication objects for this DPT will appear. Also, depending on the
number of fan speeds selected, these objects will be different. When a value between 0% and 49% is sent to the Control object
the first fan speed will be selected.
When a value between 50% and 83% is sent to the Control object, the second
speed will be selected.
When a value between 84% and 100% is sent to the Control object, the third
speed will be selected.
The Status object will return a 33% when the first speed is selected, a 67%
for the second one and a 100% for the third one. 4.3.2 Enable use of “Fan Speed Man/Auto” objects (for Control
and Status)
This parameter shows/hides the Control Fan Speed Man/Auto and Status Fan
Speed Man/Auto communication object which lets you set the Fan Speed into
Manual or Auto mode. 4.3.3 Enable use of +/-
object for Fan Speed
This parameter shows/hides the Control Fan Speed +/- communication object
which lets you increase/decrease the indoor unit fan speed by using two
different datapoint types. ![Carrier XCT-7 Variable Refrigerant Flow Controls
-
figure 26](https://manuals.plus/wp-content/uploads/2023/08/Carrier-XCT-7 -Variable-Refrigerant-Flow-Controls-figure-26.jpg) If set to “no” the object will not be shown.
-
If set to “yes” the Control_ Fan Speed +/- object and a new parameter will appear.
-
Fan speed +/- operation
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT1.007] for the Control Fan Speed +/- object. -
Sequence for +/- object
This parameter lets choose between the different modes available: -
S1>S2>….>SN
Select this option if you don’t have Auto mode and you don’t want roll-over to be enabled. -
S1>S2>….>SN>S1>…
Select this option if you don’t have Auto mode and you want roll-over to be enabled. -
Auto>S1>S2>….>SN
Select this option if you have Auto mode and you don’t want roll-over to be enabled. -
Auto>S1>S2>….>SN>Auto>S1>…
Select this option if you have Auto mode and you want roll-over to be enabled.
-
4.3.4 Enable use of bit-type Fan Speed objects (for Control)
This parameter shows/hides the bit-type Control Fan Speed objects.o If set to “no” the objects will not be shown.
o If set to “yes” the Control Fan Speed objects for Speed 1, Speed 2 and
Speed 3 (if available) will appear. To activate a Fan Speed by using these
objects a “1” value has to be sent.
4.3.5 Enable use of bit-type Fan Speed objects (for Status)
This parameter shows/hides the bit-type Status Fan Speed objects. o If set to “no” the objects will not be shown.
o If set to “yes” the Status Fan Speed objects for Speed 1, Speed 2 and Speed
3 (if available) will appear. When a Fan Speed is enabled, a “1” value is
returned through its bit- type object.
4.3.6 Enable use of Text object for Fan Speed
This parameter shows/hides the Status Fan Speed Text communication object.
o If set to “no” the object will not
be shown.
o If set to “yes” the Status Fan Speed Text object will appear. Also, in the
parameters, will be shown two (or three, depending on the number of fan speeds
selected) text fields, one for each Fan Speed, that will let modify the text
string displayed by the Status Fan Speed Text when changing a fan
speed. 4.4 Global temperature
configuration All the parameters in this section are
related with the Temperature properties and communication objects.
4.4.1 Enable use of +/- obj for Setpoint
This parameter shows/hides the Control Setpoint Temp +/- communication object
which lets you change the indoor unit setpoint temperature by using two
different datapoint types.o If set to “no” the object
will not be shown.
o If set to “yes” the Control_ Setpoint Temp +/- object and a new parameter
will appear.. DPT type for +/- Setp Temp object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008]
and 1- Decrease / 1-Increase [DPT1.007] for the Control Setpoint Temp +/-
object. 4.4.2 Ambient Ref. Temp. is provided
from KNX
This parameter shows/hides the Control Ambient Temperature communication
object which lets you use an ambient temperature reference provided by a KNX
device. o If set to “no” the object will not
be shown.
o If set to “yes” the Control Ambient Temperature object will appear. Meant
to be enabled when you want the temperature provided by a KNX sensor to be the
reference ambient temperature for the air conditioner. Then, the following
formula applies for the calculation of real Control_ Setpoint Temperature sent
ot the AC unit:
“AC Setp. Temp” = “Ambient ref. Temp” – (“KNX Amb. Temp.” – “KNX Setp Temp.”)
- AC Setp. Temp: AC indoor unit setpoint temperature
- Ambient Ref. Temp: AC indoor unit return temperature
- KNX Amb. Temp.: Ambient temperature provided from KNX
- KNX Setp. Temp: Setpoint temperature provided from KNX
As an example, consider the following situation:
User wants: 19ºC (“KNX Setp. Temp.”)
User sensor (a KNX sensor) reads: 21ºC (“KNX Amb Temp.”) Ambient temp. read by
system is: 24ºC (“Ambient Ref. Temp”)
In this example, the final setpoint temperature that 40VCBK17/27/37FQEEwill
send out to the indoor unit (shown in “Setp. Temp.”) will become 24ºC – (21ºC
– 19ºC)
= 22ºC. This is the setpoint that will actually be requested to unit.
This formula will be applied as soon as the Control Setpoint Temperature and
Control Ambient Temperature objects are written at least once from the KNX
installation. After that, they are kept always consistent.
Note that this formula will always drive the AC indoor unit demand in the
right direction, regardless of the operation mode (Heat, Cool or Auto).
4.5 Control Mode configuration All the parameters in
this section are related with the Mode properties and communication objects.
4.5.1 Enable use of Control Mode objects (for Control and Status)
This parameter shows/hides the Control Control Mode and Status Control Mode
communication objects which lets you change the indoor unit control: No
Central, LIFO (Last Input First Output), Central Controller and Lock Central
Controller.
- If set to “no” the objects will not be shown.
- If set to “yes” the Control and Status Control Mode objects for No Central, LIFO (Last Input First Output), Central Controller, Lock Central Controller will appear.
4.5.1 Initial state of Control Mode
This parameter sets the initial value for the Control Mode: No Central, LIFO
(Last Input First Output), Central Controller, Lock Central Controller or Do
not initialize.
- If set to “Apply same initial state to all Indoor Units”, the parameter option selected will apply to all indoor units.
- If set to “Initial state for each Indoor Unit might differ”, you will be able to set this parameter for each Indoor Unit individually.
4.6 Addressing of Indoor Units In this section you will be able to set the AC addressing for each AC unit present in the installation.
- Modbus GW address of ACxx refers to the addres of the Communication Addapters.
- IDU index (in Modbus GW) of ACxx refers to the AC system address of the Indoor Unit.
4.7 License Use this section to introduce the migration code in case you need to update your box from another version different from the factory default one.
Error Codes
Error Code in KNX Object| Error in Remote Controller| Category|
Error Name
---|---|---|---
1| 1| Indoor Unit| Indoor ambient temp.sensor TA (Tas) failure
2| 2| Indoor gas pipe temp. sensor TC1 failure
3| 3| Indoor liquid pipe temp. sensor TC2 failure
4| 4| Dual heat source sensor TW failure
5| 5| Indoor EEPROM failure
6| 6| Communication between indoor and outdoor failure
7| 7| Communication between indoor and wired controller failure
8| 8| Indoor float switch failure
9| 9| Indoor address repeated failure
10| 10| Reserved
11| 11| Reserved
12| 12| No 50 Hz zero passage signal
13| 13| Coil sensor TC3 failure
14| 14| DC motor failure
15| 15| Indoor ambient temp.sensor TA (Taf) failure
16| 16| –
17| 17| Outoor Unit| –
18| 18| –
19| 19| –
20| 20| Defrosting temp. sensor Tdef1 failure Defrosting temp. sensor Tdef2
failure
21| 21| Ambient temp. sensor Ta failure
22
| ****
22
| ****
Suction temp. sensor Ts1 failure Suction temp. sensor Ts2 failure Suction temp. sensor Tsacc failure Suction temp. sensor Tsuc failure
23| 23| Outdoor Unit| Discharging temp. sensor Tdi failure
Discharging temp. sensor Td1 failure Discharging temp. sensor Td2 failure
---|---|---|---
24| 24| Oil temp. sensor Toilp failure Oil temp. sensor Toil failure
25| 25| Inlet temp. of heat exchanger Toci1 failure Inlet temp. of heat
exchanger Toci2 failure indoor communication failure
Reduce the number of indoor units failure Increase the number of indoor units
failure
26| 26
27| 27| Oil temp. too high protection (Toil) Oil temp. too high protection
(Toi2)
28| 28| High pressure sensor Pd1 failure High pressure sensor Pd2 failure
29| 29| Low pressure sensor Ps failure
30| **** 30| High pressure switch HPSi failure High pressure switch HPS1
failure High pressure switch HPS2 failure
31| 31| Liquid pipe pressure Pl failure
32| 32| Outlet temp. of subcooler Tsco failure
Liquid pipe SC temp. of subcooler Tliqsc failure
33| 33| EEPROM (AT24C04) failure
34| 34| Discharging temp. too high protection (Tdi) Discharging
temp. too high protection (Td1) Discharging temp. too high protection (Td2)
35| 35| 4-way valve reversing failure 4-way valve reversing failure
36| 36| Oil temp. too low protection (Toil) Oil temp. too low protection
(Toi2)
Lack of phase of 3N power supply or wrong phase sequence
37| 37
38| 38| High pressure sensor Pd too low protection
39| 39| Low pressure sensor Ps too low protection Compression ratio too high
protection Compression 1 ratio too low protection Compression 2 ratio too low
protection
40| 40| High pressure sensor Pd1 too high protection High pressure sensor Pd2
too high protection
41| 41| Water temp. Twi too low protection Water temp. Twi too high protection
42| 42| Frost protection of water system
Water system out of water freeze protection
Water flow of Water system is too small to protect
43| 43| Discharging temp. sensor Tdi too low protection
Discharging temp. sensor Td1 too low protection Discharging temp. sensor Td2
too low protection
44| 44| Low pressure sensor PS too high protection
45| 45| Communication among outdoors failure
46| 46| Communication with inverter board 1 failure Communication with
inverter board 2failure
47| 47| –
48| 48| Unloading valve SV1 failure
49| 49| –
50| 50| Outdoor Unit|
---|---|---|---
51| 51| –
52| 52| –
53| 53| Current detector CT1 failure
54| 54| Communication with Thermal storage module failure
55| 55| Thermal storage module LEV failure
56| 56| Thermal storage module too hot failure
57| 57| Communication between Thermal storage module and host computer
58| 58| Thermal storage module Tc1 temp. sensor failure
59| 59| Thermal storage module Tc2 temp. sensor failure
60| 60| Reserved
61| 61| Reserved
62| 62| Reserved
63| 63| Thermal storage module DIP setting failure
64| 64| CT1 over current CT2 over current
65| 65| –
66| 66| –
67| 67| Communication with motor driving board failure
68| 68| –
69| 69| –
70| 70| –
71| 71| Left DC motor blocked Right DC motor blocked
72| 72| Left DC motor reversed Right DC motor reversed
73| 73| Left DC motor current too high Right DC motor current too high
74| 74| –
75| 75| No pressure drop between high pressure and low one Pressure too low
between high pressure and low one
76| 76| Incorrect outdoor address or capacity setting
77| 77| Oil equalization protection among outdoors
78| 78| Lack of refrigerant in cooling Lack of refrigerant in heating
79| 79| Incorrect wiring
80| 80| Indoor and outdoor do not match
81| 81| Model temp. too high protection
82| 82| Compressor current protection
83| 83| Wrong model selection
84| 84| –
85| 85| –
86| 86| –
87| 87| –
88| 88| –
89| 89| –
90| 90| –
91| 91| –
92| 92| –
93| 93| –
94| 94| –
95| 95| –
96| 96| –
97| 97| Outdoor Unit| –
---|---|---|---
98| 98| –
99| 99| Program self-test failure
100| 100| DC motor driving board IPM alarm
101| 101| DC motor driving board detecting out of control
102| 102| DC motor driving board EEPROM faulty
103| 103| DC motor driving board over current or current detector damaged
104| 104| Voltage too low protection of DC motor driving board
105| 105| Voltage too high protection of DC motor driving board
106| 106| DC motor driving board blocked
107| 107| Protection of motor rate over Limitation
108| 108| –
109| 109| –
110| 110| model 1 Over current model 2 Over current
111| 111| Compressor 1 out of control Compressor 2 out of control
112| 112| Radiator of model 1 temp. too high Radiator of model 2 temp. too
high
113| 113| model 1 overload
model 2 overload
114| 114| Voltage too low of model 1 Voltage too low of model 2
115| 115| Voltage too high of model 1 Voltage too high of model 2
116| 116| Communication abnormal with model 1 Communication abnormal with
model 2
117| 117| Model 1 Over current (software) Model 1 Over current (software)
118| 118| Model 1 startup failure Model 2 startup failure
119| 119| Current Detecting Circuit Abnormal of transducer 1 Current Detecting
Circuit Abnormal of transducer 2
120| 120| Power supply of transducer 1 abnormal Power supply of transducer 2
abnormal
121| 121| Power supply of inverter board 1 is abnormal Power supply of
inverter board 2 is abnormal
122| 122| Radiator temp. sensor of transducer 1 abnormal Radiator temp. sensor
of transducer 2 abnormal
123| 123| –
124| 124| –
125| 125| Compressor 1 frequency not match Compressor 2 frequency not match
126| 126| –
127| 127| MCU reset abnormal
128| 128| MCU Program needs to be upgraded
0| N/A| KNX interface| No error
65535 (-1)| N/A| KNX interface| Indoor Units not ready for communication
65436 (-100)| N/A| KNX interface| License Error / indoor unit not supported by
current license
65336 (-200)| N/A| KNX interface| Overconsumption error in EXY bus
In case you detect an error code not listed, contact your nearest technical
support service for more information on the error meaning.
Appendix A – Communication Objects Table
SECTION| OBJECT NUMBER| NAME| LENGTH| DATAPOINT TYPE| FLAGS|
---|---|---|---|---|---|---
DPT_NAME| DPTID| R| W| T| U| FUNCTION
On/Off| 1| Control On/Off| 1 bit| DPTSwitch| 1.001| | W| T| | 0 – Off; 1-On
Mode| 2| Control Operating Mode| 1 byte| DPTHVACMode| 20.102| | W| T| | 0 –
Auto; 1 – Com;
2 – Stan; 3 – Eco; 4
– Pro
3| **** Control Mode| 1 byte| DPT_ HVACControl| 20.105| |
W| T| | 0 – Auto; 1 – Heat;
3 – Cool; 9 – Fan;
14 – Dry
4| Control_ Mode Cool/Heat| 1 bit| DPT_Cool/Heat| 1.1| |
W| T| | 0 – Cool; 1 – Heat
5| Control_ Mode Auto| 1 byte| DPTScaling| 5.001| | W| T| | 1 – Auto
6| Control Mode Heat| 1 byte| DPTScaling| 5.001| | W| T| | 1 – Heat
7| Control Mode Cool| 1 bit| DPTBool| 1.002| | W| T| | 1 – Cool
8| Control Mode Fan| 1 bit| DPTBool| 1.002| | W| T| | 1 – Dry
9| Control Mode Dry| 1 bit| DPT_Bool| 1.002| | W| T| | 1 – Fan
10| Control_ Mode +/-| 1 bit| DPTStep| 1.007| |
W| | | **** 0 – Decrease; 1 – Increase
Control Mode +/-| 1 bit| DPTUpDown| 1.008| | W| | | 0 – Up; 1 – Down
Fan Speed| 11| Control Fan Speed / 3 Speeds| 1 byte| DPTScaling| 5.001| | W|
T| | 0%-49% – Speed 1;
50%-83% – Speed
2;84%-100%
Speed 3
**** Control Fan Speed / 3 Speeds| 1 byte| DPTEnumerated|
5.01| | W| T| | 1 – Speed 1;
2 – Speed 2;
3 Speed 3
12| Control Fan Speed Man/Auto| 1 bit| DPTBool|
1.002| | W| T| | 0 – Manual; 1 – Auto
**** 13| Control Fan Speed 1| 1 bit| DPTBool| 1.002| |
W| T| | 1 – Fan Speed 1
**** 14| Control Fan Speed 2| 1 bit| DPTBool| 1.002| |
W| T| | 1 – Fan Speed 2
**** 15| Control Fan Speed 3| 1 bit| DPTBool| 1.002| |
W| T| | 1 – Fan Speed 3
Fan Speed| 16| **** Control Fan Speed +/-| 1 bit| DPTStep|
1.007| | W| T| | 0 – Decrease; 1 – Increase
---|---|---|---|---|---|---|---|---|---|---
Control Fan Speed +/-| 1 bit| DPTUpDown| 1.008| | W|
T| | 0 – Up; 1 – Down
Temperature| **17**| Control Setpoint Temperature| 2 byte|
DPT_ValueTemp| 9.001| | W| T| | 17ºC to 30ºC
18| Control Setpoint Temp +/- Control_ Setpoint
Temp +/-| 1 bit
1 bit| DPT_Step
DPTUpDown| ** 1.007
1.008| | W
W| | | 0 – Decrease; 1 – Increase
0 – Up; 1 – Down
19**| Control Ambient Temperature| 2 byte| DPT_ValueTemp| 9.001| | W| T|
| ºC value in EIS5 format
Control Mode| 20| Control Control Mode No Central| 1 bit| DPTBool|
1.002| | W| T| | 1 – No Central Controller
21| Control Control Mode LIFO| 1 bit| DPTBool| 1.002| | W| T| | 1 –
Last Input First Output (LIFO)
22| Control Control Mode Central| 1 bit| DPTBool| 1.002| | W| T| | 1 –
Central Controller
23| Control Control Mode Lock| 1 bit| DPTBool| 1.002| | W| T| | 1 –
Lock Central Controller
On/Off| 24| Status On/Off| 1 bit| DPTSwitch| 1.001| R| | T| | 0 – Off;
1-On
Mode| 25| Status Operating Mode| 1 byte| DPTHVACMode| 20.102| R| | T|
| 0 – Auto; 1 – Com;
2 – Stan; 3 – Eco; 4
– Pro
26| Status Mode| 1 byte| DPT nHVACContrMode| 20.105| R| | T| | 0 –
Auto; 1 – Heat;
3 – Cool; 9
– Fan; 14 – Dry
27| Status Mode Cool/Heat| 1 bit| DPTHeat/Cool| ** 1.1| R| | T| | 0
– Cool; 1 – Heat
28**| Status Mode Auto| 1 bit| DPTBool| 1.002| R| | T| | 1 – Auto
29| Status Mode Heat| 1 bit| DPTBool| 1.002| R| | T| | 1 – Hea
30| Status Mode Cool| 1 bit| DPTBool| 1.002| R| | T| | 1 – Cool
31| Status Mode Fan| 1 bit| DPTBool| 1.002| R| | T| | 1 – Fan
32| Status Mode Dry| 1 bit| DPTBool| 1.002| R| | T| | 1 – Dry
33| Status Mode Text| 14 byte| DPT_ String_88591| 16.001| R| | T| |
ASCII String
Fan Speed| 34| Status Fan Speed / 3 Speeds| 1 byte| DPTScaling| 5.001| R| |
T| | **** 33% – Speed 1;
67% – Speed 2;
100% – Speed 3
---|---|---|---|---|---|---|---|---|---|---
Status Fan Speed / 3 Speeds| 1 byte| DPTEnumerated| 5.01| **** R| | T| | 1
– Speed 1;
2 -Speed 2;
3- Speed 3
35| Status Fan Speed Man/Auto| 1 bit| DPTBool| 1.002|
R| | T| | 0 – Manual;
1 – Auto
36| Status Fan Speed 1| 1 bit| DPTBool| 1.002| R| | T| | 1 – Speed 1
37| Status Fan Speed 2| 1 bit| DPTBool| 1.002| R| | T| | 1 – Speed 2
38| Status Fan Speed 3| 1 bit| DPTBool| 1.002| R| | T| | 1 – Speed 3
39| Status Fan Speed Text| 14 byte| DPT_ String_88591| 16.001| R| | T| |
ASCII String
Temperature| 40| Status AC Setpoint Temp| 2 byte| DPT_ValueTemp|
9.001| R| | T| | 16ºC to 32ºC
41| Status AC Ambient Ref Temp| 2 byte| DPT_ValueTemp| 9.001| R| | T| | ºC
value in EIS5 format
Error| 42| Status Error/ Alarm| 1 bit| DTPAlarm| 1.005| R| | T| | 0 – No
Alarm; 1 – Alarm
43| Status Error Code| 2 byte| Enumerated| R| | T| | 0 – No Error; Any other
see user’s manual
44| Status Error Text code| 14 byte| DPT String_88591| 16.001| R| | T| | 2
char Error; Empty – none
Control Mode| 45| Control Control Mode No Central| 1 bit| DPTBool|
1.002| | W| T| | 1 – No Central Controller
46| Control Control Mode LIFO| 1 bit| DPTBool| 1.002| | W| T| | 1 – Last
Input First Output (LIFO)
47| Control Control Mode Central| 1 bit| DPT_Bool| 1.002| | W| T| | 1 –
Central Controller
48| Control_ Control Mode Lock| 1 bit| DPT_Bool| 1.002| | W| T| | 1 – Lock
Central Controller
NOTE: This addressing corresponds to the first AC indoor unit of the
configuration. Communication objects for the rest of AC units are
consecutively listed .
Manufacturer reserves the right to discontinue, or change at any time,
specifications or designs without notice and without incurring obligations.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>