NUMERIC Valura 1-3 kVA Single Phase UPS Instruction Manual

June 12, 2024
NUMERIC

NUMERIC Valura 1-3 kVA Single Phase UPS

NUMERIC-Valura-1-3-kVA-Single-Phase-UPS-product

Product Information

The Valura UPS from Numeric is a true online double conversion UPS available in a range of 1-3kVA, with or without a transformer.
It is easy to install and provides a reliable power solution. The UPS models covered in this user manual are:

  1. Valura 1 kVA FM or Valura 1 kVA FMI
  2. Valura 2 kVA FM or Valura 2 kVA FMI
  3. Valura 3 kVA FM or Valura 3 kVA FMI

Important Safety Warning

Please comply strictly with all warnings and operating instructions in this manual. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.

Transportation

Please transport the UPS system only in the original package to protect against shock and impact.

Preparation

Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate to the environment. Do not install the UPS system near water or in moist environments. Do not install the UPS system near a heater or where it would be exposed to direct sunlight. Do not block ventilation holes in the UPS housing.

Installation

Please refer to the installation and setup section for detailed instructions on installing the UPS.

Operation

Please refer to the operation section for detailed instructions on operating the UPS.

Maintenance, Service, and Faults

Please refer to the maintenance, service, and faults section for information on maintaining and troubleshooting the UPS.

Installation and Setup

Rear Panel View

UPS without ISO transformer| 1 kVA FM UPS with ISO transformer| 2 kVA FM| 3 kVA FM| 1 kVA FMI| 2 kVA FMI| 3 kVA FMI
---|---|---|---|---|---|---
1. AC input
2. Input circuit breaker
3. USB communication port
4. RS-232 communication port
5. SNMP intelligent slot (option)
6. External battery connection
7. Output receptacles
8. Output terminal| Same as UPS without an ISO transformer| Same as UPS without an ISO transformer| Same as UPS without an ISO transformer| Same as UPS without an ISO transformer| Same as UPS without an ISO transformer| Same as UPS without an ISO transformer

Setup the UPS

Step 1: UPS input connection

Plug the UPS into a two-pole, three-wire, grounded receptacle only. Please use the below-recommended cable & breaker for input.

Model Wire size in sq. mm./No. of runs Recommended input breaker
1/3 2.5/3 10 A (C Curve)
2/3 4/3 20 A (C Curve)
3/3 32 A (C Curve)

Preface

Congratulations

  • We are delighted to welcome you to our family of customers. Thank you for choosing Numeric as your power backup solution provider; you now have access to our widest network of 254 service centres in the country. Since 1984, Numeric has been enabling its clients to optimize their business with top notch power solutions that promise seamless and clean power with controlled environmental footprints.
  • We look forward to your continued patronage in the years to come!
  • This manual provides general information regarding installation and operation of Valura.

Disclaimer

  • The contents of this manual are bound to change without prior notice.
  • We have exercised reasonable care to give you an error-free manual. Numeric disclaims liability for any inaccuracies or omissions that may have occurred. If you find information in this manual that is incorrect, misleading or incomplete, we would appreciate your comments and suggestions. Before you begin the installation of the UPS system, please read this manual thoroughly. The warranty of this product is null and void, if the product is abused/misused.

Introduction

  • Valura from Numeric is a true on-line double conversion UPS available from a range of 1-3kVA, with and without a transformer. Valura is easy to install and is a reliable power solution backed by the widest service support.
  • This user manual covers the UPS listed below:
  1. Valura 1 kVA FM or Valura 1 kVA FMI
  2. Valura 2 kVA FM or Valura 2 kVA FMI
  3. Valura 3 kVA FM or Valura 3 kVA FMI

Please verify the model of the UPS you have purchased before you begin your installation.

Important Safety Warning

  • Please comply strictly with all warnings and operating instructions in this manual. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.

Transportation

  • Please transport the UPS system only in the original package to protect against shock and impact.

Preparation

  • Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate to the environment.
  • Do not install the UPS system near water or in moist environments.
  • Do not install the UPS system near heater or where it would be exposed to direct sunlight.
  • Do not block ventilation holes in the UPS housing.

Installation

  • Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
  • Place cables in such a way that no one can step on or trip over them.
  • Do not connect domestic appliances such as hair dryers to UPS output sockets.
  • The UPS can be operated by any individual with no previous experience.
  • Connect the UPS system only to an earthed shock-proof outlet which must be easily accessible and close to the UPS system.
  • Please use only VDE-tested, CE-marked, ISI-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shock-proof outlet). Please use only VDE-tested, CE-marked, ISI-marked power cables to
  • connect the loads to the UPS system.
  • When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5 mA.
  • UPS is designed for linear load applications.

Operation

  • Do not disconnect the mains cable in the UPS system or the building wiring outlet (shock-proof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
  • The UPS system features its own current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
  • In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
  • Prevent fluids or other foreign objects from entering into the UPS system.

Maintenance, service and faults

  • The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
  • Caution – Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system still connected to the battery may be electrically live and dangerous.
  • Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors. Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
  • Caution – Risk of electric shock. If the battery circuit is not isolated from the input voltage, hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present. Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
  • remove wristwatches, rings and other metal objects
  • use only tools with insulated grips and handles.
  • When changing batteries, install the same number and same type of batteries.
  • Do not attempt to dispose off batteries by burning them. This could cause battery explosion.
  • Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic. Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
  • Do not dismantle the UPS system.
  • Connect UPS to short circuit protected building wiring.
  • The UPS system has internal fuses on both DC & AC inputs. Those devices do not protect the upstream cables connected to DC & AC inputs and upstream breakers or fuses shall be set up in accordance with AC & DC wires ratings to meet the local national electrical code standard.

Installation and Setup

Note: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
Rear panel view
UPS without ISO transformer

UPS with ISO transformerNUMERIC-Valura-1-3-kVA-Single-Phase-UPS-
fig-2

  1. AC input
  2. Input circuit breaker
  3. USB communication port
  4. RS-232 communication port
  5. SNMP intelligent slot (option)
  6. External battery connection
  7. Output receptacles
  8. Output terminal

Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Please use the below-recommended cable & breaker for input.

Model| Wire size in sq. mm./No. of runs| Recommended input breaker
---|---|---
1 kVA – FM/FMI| 1/3| 10 A (C Curve)
2 kVA – FM/FMI| 2.5/3| 20 A (C Curve)
3 kVA – FM/FMI| 4/3| 32 A (C Curve)

Step 2: UPS output connection

  • For socket-type outputs, simply connect the devices to the outlets.
  • For terminal-type input or outputs, please follow the steps below, for the wiring configuration:
  • a) Remove the small cover of the terminal block.
  • b) Use AWG14 or 2.1 mm2 power cords.
  • c) Upon completion of the wiring configuration, please check whether the wires are securely affixed.
  • d) Put the small cover back to the rear panel.
  • Step 3: Communication connection
  • To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through the PC. The UPS is equipped with an intelligent slot perfect for either SNMP or AS400 cards. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
  • Note: The USB port and RS-232 port can’t work at the same time.

Step 4: Turn on the UPS

  • Press the ON/Mute button on the front panel for two seconds to power on the UPS.
  • Note: The battery charges fully during the first five hours of normal operation.
  • Do not expect full battery run capability during this initial charge period.

Step 5: Install the software

  • For optimal computer system protection, install UPS monitoring software to fully configure
  • UPS shutdown. You may insert the provided CD into CD-ROM to install the monitoring software. If not, please follow the on-screen instructions to install the software. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.

Step 6: External battery connection

  • These UPS series do not include batteries. Batteries are connected in a separate cabinet with protection. Please connect external batteries as per the below chart.

Recommended External Breaker Rating

S. No. Rating of UPS Battery Breaker
1 1 kVA – FM/FMI 50 Adc (C Curve)
2 2 kVA – FM/FMI 50 Adc (C Curve)
3 3 kVA – FM/FMI 50 Adc (C Curve)

Operations

Button operation

Button Function

ON/Mute button

| Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.

Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system.

But it’s not applied to the situations when warnings or errors occur.

Up key: Press this button to display previous selection in UPS setting mode.

Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.

OFF/Enter button| Turn off the UPS: Press and hold this button for at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by

pressing this button.

Confirm selection key: Press this button to confirm selection in UPS setting mode.

Select button| Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default display when pausing for 10 seconds.

Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby or Bypass mode.

Down key: Press this button to display next selection in UPS setting mode.

ON/Mute + Select button| Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter to Bypass mode. This action will be ineffective when the input voltage is out of acceptable range.

LCD panelNUMERIC-Valura-1-3-kVA-Single-Phase-UPS-
fig-6 NUMERIC-Valura-1-3-kVA-Single-Phase-UPS-
fig-7

Audible alarm

Battery mode Sounds every 4 seconds
Low battery Sounds every second
Overload Sounds twice every second
Fault Sounds continuously
Bypass mode Sounds every 10 seconds

LCD display wordings index

UPS setting

  • There are three parameters to set up the UPS.
  • Parameter 1: It’s for program alternatives. Refer to the below table. Parameter 2 and Parameter 3 are the setting options or values for each program.

Interface Setting

01: Output voltage setting
| Parameter 3: Output voltage

For 200/208/220/230/240 Vac models,

you may choose the following output voltage:

200: Presents output voltage is 200 Vac 208: Presents output voltage is 208 Vac 220: Presents output voltage is 220 Vac

230: Presents output voltage is 230 Vac (Default)

240: Presents output voltage is 240 Vac

02: Frequency converter enable/disable
| Parameters 2 & 3: Enable or disable converter mode. You may choose the following two options: CF ENA: Converter mode enable

CF DIS: Converter mode disabled (Default)

03: Output frequency setting
| Parameters 2 & 3: Output frequency setting.

You may set the initial frequency on battery mode:

BAT 50: Presents output frequency is 50 Hz BAT 60: Presents output frequency is 60 Hz If converter mode is enabled, you may choose the following output frequency:

CF 50: Presents output frequency is 50 Hz

CF 60: Presents output frequency is 60 Hz

Interface                                                         Setting

04: ECO enable/disable
Parameter 3: Enable or disable the ECO function.

EnA You may choose the following two options: ENA: ECO mode enable

DIS: ECO mode disabled (Default)

05: ECO voltage range setting
| **Parameter 2 & 3: **Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key.

HLS: High Loss Voltage in ECO mode in

parameter 2. For 200/208/220/230/240 Vac models, the setting range inparameter 3 is from +7 V to

+24 V of the nominal voltage. (Default: +12 V) LLS: Low Loss Voltage in ECO mode in parameter 2. For 200/208/220/230/240 Vac models, the setting range in parameter 3 is from

-7 V to -24 V of the nominal voltage. (Default: -12 V)

06: Bypass enable/disable when UPS is off
| **Parameter 3:** Enable or disable Bypass function. You may choose the following two options:

ENA: Bypass enable

DIS: Bypass disable (Default)

Interface                                                         Setting

07: Bypass voltage range setting
| **Parameter 2 & 3: **Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key

or Up key.

HLS: Bypass high voltage point

For 200/208/220/230/240 Vac models: 230-264: Setting the high voltage point in parameter 3 from 230 Vac to 264 Vac.

(Default: 264 Vac)

LLS: Bypass low voltage point

For 200/208/220/230/240 Vac models: 170-220: Setting the low voltage point in parameter 3 from 170 Vac to 220 Vac.

(Default: 170 Vac)

08: Autonomy limitation setting
| **Parameter 3:** Set backup time on battery mode for general outlets.

0-999: Setting the backup time in minutes from 0-999 for general outlets on battery mode.

0: When setting as “0”, the backup time will be only 10 seconds.

999: When setting as “999”, the backup time setting will be disabled. (Default)

Interface                                                         Setting

9: Battery minimum cut-off voltage setting
| Parameter 3: Set the acceptable battery minimum cut-off voltage point by pressing the Down key or Up key.

167-190: Setting the minimum battery cut-off voltage point in parameter 3 from 167 to 190.

Unit: 0.01 V/CELL (Default: 175)

10: Charger boost voltage setting
| Parameter 3: Set up the charger boost voltage. 225-240: Setting the charger boost voltage point in parameter 3 from 225 to 240.

Unit: 0.01 V/CELL (Default: 236)

11: Charger float voltage setting
| Parameter 3: Set up the charger float voltage. 220-233: Setting the charger float voltage point in parameter 3 from 220 to 233.

Unit: 0.01 V/CELL (Default: 228)

00: Exit setting

Charging current setting

3 bat (36 V)/6 bat (72 V)/8 bat (96 V)| For 6 A Model| For 10 A Model
---|---|---
J1| 1 Adc| 1 Adc
J2| 2 Adc| 2 Adc
J3| 4 Adc| 5 Adc
J4 (Default)| 6 Adc| 10 Adc

Operating mode descriptionNUMERIC-Valura-1-3-kVA-Single-Phase-UPS-
fig-21

Fault reference codes

Fault event Fault code
Bus start fail 01
Bus over 02
Bus under 03
Bus unbalance 04
Inverter soft start fail 11
Inverter voltage high 12
Charger fail 45
Fault event Fault code
--- ---
Inverter voltage low 13
Inverter output short 14
Battery voltage too high 27
Battery voltage too low 28
Over temperature 41
Overload 43
 

Warning indicatorNUMERIC-Valura-1-3-kVA-Single-Phase-UPS-
fig-22

Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table below.NUMERIC-Valura-1-3-kVA-Single-Phase-UPS-
fig-23

Symptom Possible cause Remedy
Fault code is shown as 45 on LCD display and alarm is continuously sounding.
**** Charger is faulty. **** Contact your dealer.

**** Fault code is shown as 01, 02, 03,

04, 11, 12, 13 and 41 on LCD display and alarm is continuously sounding.

| A UPS internal fault has occurred. There are two possible results:

1.  The load is still supplied, but directly from AC power via Bypass.

2.  The load is no longer supplied by power.

| Contact your dealer
Battery backup time is shorter than nominal value| Batteries are not fully charged| Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Batteries defect| Contact your dealer to replace the battery.

  • If the problem persists, visit www.numericups.com to register your service request and contact our nearest after sales service department; or call Toll Free no. 1800 425 3266 with the below details:
  1. Model number, Serial number
  2. Date on which the problem occurred
  3. LCD/LED display status, Buzzer alarm status
  4. Utility power condition, load type and capacity, environment temperature, ventilation condition
  5. The information (battery capacity, quantity) of external battery pack if the UPS is with external battery
  6. Other information for complete description of the problem

Storage and Maintenance

Operation

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Be sure to deliver the used battery to a recycling facility or ship it to your dealer in the replacement battery packing material.

Storage

Before storing, charge the UPS for 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage temperature Recharge frequency Charging duration
-25°C to 40°C Every 3 months 1-2 hours
40°C to 45°C Every 2 months 1-2 hours

Disposal

Ref standard: ISO 14001:2004

  • After unpacking the UPS & Battery, the removed packaging materials like polythene paper, thermocole/polyethylene, carton box, nylon belt, nylon thread shall be collected and disposed through authorized recycler.
  • Batteries when found faulty/damaged must be handed over to identified authorized recycler or to Numeric, where it is disposed properly.
  • Battery contains harmful metals and chemicals such as nickel-cadmium, alkaline, mercury, nickel-metal hydride and lead acid, which contaminates if it is not disposed properly.
  • When batteries containing cadmium is used in fills, they will eventually dissolve and release the toxic substance than can seep into water supplies posing serious health hazards for the population/society. Hence, recycling of batteries will prevent pollution and also saves resource.

Specifications

UPS without ISO transformer

*Nominal power (kVA)| 1 kVA FM/FM C| 2 kVA 2 kVA**

72 V FM/FM C        96 V FM/FM C

| 3 kVA                      3 kVA

72 V FM/FM C        96 V FM/FM C

---|---|---|---
Active power**| 1000 VA/800 W| 2000 VA/1600 W| 3000 VA/2400 W
Input

Voltage range

| Low line transfer| 160/140/120/110 Vac ± 5%

(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)

Low line comeback| 175/155/135/125 Vac ± 5 %

(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)

High line transfer| 300 Vac ± 5%
High line comeback| 290 Vac ± 5%
Frequency range| 40 Hz ~ 70 Hz
Phase| Single phase with ground
Power factor| > 0.99 @ nominal input voltage
Output
Output voltage| 200/208/220/230/240 Vac
AC voltage regulation| ± 1%
Frequency range (Synchronized )| 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency range (Batt. Mode)| 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz

Overload

| 105%~110%: UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110%~130%: UPS shuts down after 1 min at battery mode or 2 min transfer to Bypass when the utility is normal 130%~150%: UPS shuts down after 3 secs at battery mode or 30 secs transfer to Bypass when the utility is normal
Current crest ratio| 3:1
Harmonic distortion| ____   3% THD (Linear load)

____  5% THD (Non-linear load)

Transfer time| AC mode to batt. mode| Zero
Inverter to Bypass| 4 ms (Typical)
Waveform (batt. mode)| Pure Sinewave
*Nominal power (kVA)| 1 kVA FM/FM C| 2 kVA**

72 V FM/FM C

| 2 kVA

96 V FM/FM C

| 3 kVA

72 V FM/FM C

| 3 kVA

96 V FM/FM C

---|---|---|---|---|---
Active power**| 1000 VA/800 W| 2000 VA/1600 W| 3000 VA/2400 W
External battery
Battery type| Depending on the capacity of external batteries
Battery numbers| 3| 6|  | 8| 6|  | 8
Maximum battery AH| 120| 120|  | 100| 120|  | 100
Current of external BAT pack| 30 Adc max| 30 Adc max|  | 30 Adc max| 45 Adc max|  | 32 Adc max
Charging current| 6 A model

(FM/FM C)

| 1/ 2 / 4 / 6 A (adjustable)
10 A model

(FM/FM C)

| 1/ 2 / 5 / 10 A (adjustable)
Charging voltage| 41.0 Vdc ± 1%| 82.1 Vdc ±1%|  | 109.5 Vdc ±1%| 82.1 Vdc ±1%|  | 109.5 Vdc ±1%
Physical
Dimension (D x W x H) mm| 282 x 145 x 225| 405 x 145 x 236
Net weight (kgs)| 4.9|  | 7.9|  |  | 8.3|
Environment
Operation humidity| 20-90% RH @ 0- 40°C (non-condensing)
Noise level| Less than 50 dBA @ 1 Meter (AVG)
Management
Smart RS-232 or USB| Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMP| Power management from SNMP manager and web browser

  • FM – Floor Mount; FMI – Floor Mount with isloation transformer; FM C/FMI C – Long backup charger.
  • Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to 208 Vac/200 Vac. Product specifications are subject to change without further notice.

UPS with ISO transformerNUMERIC-Valura-1-3-kVA-Single-Phase-UPS-
fig-24

*Nominal power (kVA)| 1 kVA FMI/FMI C| 2 kVA**

72 V FMI/FMI C

| 2 kVA

96 V FMI/FMI C

| 3 kVA

72 V FMI/FMI C

| 3 kVA

96 V FMI/FMI C

---|---|---|---|---|---
Active power**| 1000 VA/800 W| 2000 VA/1600 W| 3000 VA/2400 W
External battery
Battery type                                                 Depending on the capacity of external batteries
Battery numbers                         3                    6 8                       6                       8
Maximum battery AH                 120                 120 100                    120                    100
Current of external BAT pack 30 Adc max   30 Adc max       30 Adc max       45 Adc max       32 Adc max
Charging current| 6 A model 1/ 2 / 4 / 6 A (adjustable)

(FMI/FMI C)

10 A model                                                               1/ 2 / 5 / 10 A (adjustable)

(FMI/FMI C)

Charging voltage                          41.0 Vdc ± 1%    82.1 Vdc ±1% 109.5 Vdc ±1%        82.1 Vdc ±1%        109.5 Vdc ±1%
Physical
Dimension (D x W x H) mm| 426 x 190

x 336

| 426 x 190 x 346
Net weight (kgs)| 15.3| 21.6| 24.3
Environment
Operation humidity                                             20-90% RH @ 0- 40°C (non-condensing)
Noise level                                                             Less than 50 dBA @ 1 Meter (AVG)
Management
Smart RS-232 or USB                   Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMP                                   Power management from SNMP manager and web browser

  • FM – Floor Mount; FMI – Floor Mount with isloation transformer; FM C/FMI C – Long backup charger.
  • Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to 208 Vac/200 Vac. Product specifications are subject to change without further notice.

Head Office

  • 10th Floor, Prestige Center Court, Office Block, Vijaya Forum Mall, 183, N.S.K Salai, Vadapalani,
  • Chennai – 600 026.
  • Phone: +91 44 4656 5555

Guwahati

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NUMERIC User Manuals

Related Manuals