NUMERIC 1-3KVA Single Phase Pure Sine Wave Industrial Transformer Installation Guide

June 12, 2024
NUMERIC

NUMERIC 1-3KVA Single Phase Pure Sine Wave Industrial Transformer

Product Information

Product Name Onfiniti 1-3 kVA
Manufacturer Numeric UPS
Website www.numericups.com

Product Usage Instructions

Important Safety Warning
Please read the following instructions carefully before installing the unit and strictly comply with all the warnings and operating instructions herein. Save this manual for future reference and do not operate this unit before reading through all safety information and operating instructions carefully.

Installation and Setup

Note: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.

Rear panel view – UPS without ISO transformer
Rear panel view – UPS with ISO transformer

Operations
Refer to the user manual for detailed button operation, LCD panel usage, audible alarm indications, LCD display wordings index,UPS setting, charging current setting, operating mode description,fault reference codes, and warning indicator information.

Troubleshooting
Refer to the user manual for troubleshooting guidelines.

Storage and Maintenance
Refer to the user manual for information on operation, storage,and disposal of the product.

Specifications
Refer to the user manual for detailed specifications of the product.

PREFACE

Congratulations.

  • We are delighted to welcome you to our family of customers. Thank you for choosing Numeric as your power backup solution provider, you now have access to our widest network of 254 service centers in the country.
  • Since 1984, Numeric has been enabling its clients to optimize their business with top notch power solutions that promise seamless and clean power with controlled environmental footprints.
  • We look forward to your continued patronage in the years to come!
  • This manual provides general information regarding installation and operation of Onfiniti.

Disclaimer

  • The contents of this manual are bound to change without prior notice.
  • We have exercised reasonable care to give you an error-free manual. Numeric disclaims liability for any inaccuracies or omissions that may have occurred. If you find information in this manual that is incorrect, misleading or incomplete, we would appreciate your comments and suggestions.
  • Before you begin the installation of the UPS system, please read this manual thoroughly.
  • The warranty of this product is null and void, if the product is abused/misused.

INTRODUCTION

Today’s business continuity demands a cost-effective power protection solution, for ensuring Power Continuity and Power Quality with optimal Total Cost of Ownership (TCO). The Onfiniti range of UPS is a true online double conversion topology UPS, designed with IGBT-based rectifier and inverter to suit customer requirements.
Onfiniti provides maximum protection and power quality for entry level servers, workstations, communication equipment, ATMs, etc.

IMPORTANT SAFETY WARNING

Please read the following instructions carefully before installing the unit and strictly comply with all the warnings and operating instructions herein. Save this manual for future reference and do not operate this unit before reading through all safety information and operating instructions carefully.

Transportation

  • Please transport the UPS system in the original package only to protect against shock and impact.

Preparation

  • Condensation may occur if the UPS system is moved directly from a cold to warm environment.
    The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimatize to the environment.

  • Do not install the UPS system near water or in moist environments.

  • Do not install the UPS system where it would be exposed to direct sunlight or near a heater.

  • Do not block ventilation holes in the UPS housing.

Installation

  • Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
  • Do not place cables in such a way that one can step on or trip over them.
  • Do not connect domestic appliances such as hair dryers to UPS output sockets.
  • The UPS can be operated by any individual with no previous experience.
  • Connect the UPS system to an earthed shock-proof outlet which must be easily accessible and close to the UPS system.
  • Use only VDE-tested, CE-marked, ISI-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shock-proof outlet).
  • Use only VDE-tested, CE-marked, ISI-marked power cables to connect the loads to the UPS system.
  • When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5 mA.
  • UPS is designed for linear load, worst case inductive resistive load.

Operation

  • Do not disconnect the mains cable on the UPS system or the building wiring outlet (shock-proof socket outlet) during operations since this would cancel the protective earthing of the UPS system and all connected loads.
  • The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
  • In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
  • Prevent fluids or other foreign objects from entering the UPS system.

Maintenance, service and faults

  • The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.

  • Caution – Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery.
    They might be electrically live and dangerous.

  • Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exist in the terminals of high-capability capacitor such as BUS capacitors.

  • Only people adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept away from the batteries.

  • Caution – Risk of electric shock. The battery circuit is not isolated from the input voltage.
    Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present.

  • Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:

  • Remove wristwatches, rings and other metal object

  • Use only tools with insulated grips and handles

  • When changing batteries, install the same number and same type of batteries.

  • Do not attempt to dispose of batteries by burning them. This could cause the batteries to explode.

  • Do not open or destroy batteries. Escaping electrolytes can be toxic and cause injury to the skin and eyes.

  • Replace the fuse with the same type and amperage in order to avoid fire hazards.

  • Do not dismantle the UPS system.

  • Connect UPS to short-circuit-protected building wiring.

  • The UPS system has internal fuses on both DC & AC inputs. Those devices do not protect the upstream cables connected to DC & AC inputs and upstream breakers or fuses shall be set up in accordance with AC & DC wires ratings to meet the local national electrical code standard.

INSTALLATION AND SETUP

Note: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.
Please keep the original package in a safe place for future use.

Rear panel view
UPS without ISO transformer

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-1

UPS with ISO transformer

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-2

  1. AC input
  2. Input circuit breaker
  3. USB communication port
  4. RS-232 communication port
  5. SNMP intelligent slot (optional)
  6. External battery connection
  7. Output receptacles
  8. Output terminal
Setting up the UPS

Step 1: UPS input connection
Plug the UPS into a 2-pole, 3-wire, grounded receptacle only. Please use recommended cable and breaker for input.

Mode| Wire size in sq. mm./No. of runs| Recommended input breaker
---|---|---
1 kVA – FM/FMI| 2.5/3| 16 A AC (C Curve)
2 kVA – FM/FMI| 6.0/3| 32 A AC (C Curve)
3 kVA – FM/FMI| 10.0/3| 40 A AC (C Curve)

Step 2: UPS output connection

  • For socket-type outputs, simply connect the devices to the outlets.
  • For terminal-type input or outputs, please follow the steps below, for the wiring configuration:
    • Remove the small cover of the terminal block.
    • Use AWG14 or 2.1 mm2 power cords.
    • Upon completion of the wiring configuration, please check whether the wires are securely affixed.
    • Put the small cover back to the rear panel.

Communication port:

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-3

Step 3: Communication connection
To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of then communication cable to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through a PC.
The UPS is equipped with intelligent slot for either SNMP or AS400 card. Installing either SNMP or AS400 card in the UPS, will provide advanced communication and monitoring options.

Note: USB port and RS-232 port can’t work at the same time.

Step 4: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.

Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.

Step 5: Install software
You may insert the CD provided into the CD-ROM to install the monitoring software.
If not, please follow the on screen instructions to install the software. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray near the clock.

Step 6: External battery connection
This UPS series is not including batteries. Batteries are connected in a separate cabinet with protection.
Please connect external batteries as below chart.

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-4

Recommended External Breaker Rating

S. No. Rating of UPS Battery Breaker
1 1 kVA – FM/FMI 50 A DC (C Curve)
2 2 kVA – FM/FMI 50 A DC (C Curve)
3 3 kVA – FM/FMI 50 A DC (C Curve)

OPERATIONS

Button operation

Button Function





ON/Mute button

| •     Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.

•     Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. But it is not applied to situations when warnings or errors occur.

•     Up key: Press this button to display previous selection in UPS setting mode.

Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or Converter mode.




OFF/Enter button

| •     Turn off the UPS: Press and hold this button at least 2 seconds to turn off UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass setting is enabled by pressing this button.

•     Confirm selection key: Press this button to confirm selection in UPS setting mode.





Select button

| •     Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default display when pausing

for 10 seconds.

•     Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or Bypass mode.

•     Down key: Press this button to display next selection in UPS setting mode


ON/Mute + Select button

| •     Switch to Bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter to Bypass mode. This action will be ineffective when the input voltage is out of acceptable range.

LCD panel

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-5

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-6 NUMERIC-1-3KVA-
Single-Phase-Pure-Sine-Wave-Industrial-Transformer-7

Audible alarm

Battery mode Sounds every 4 seconds
Low battery Sounds every second
Overload Sounds twice every second
Fault Sounds continuously
Bypass mode Sounds every 10 seconds

LCD display wordings index

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-8

UPS setting

There are three parameters to set up the UPS.

  • Parameter 1: For program alternatives. Refer to table.
  • Parameter 2 and Parameter 3 are setting options or values for each program.

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-10 NUMERIC-1
-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-11 NUMERIC-1
-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-12 NUMERIC-1
-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-13

Charging current setting

  3 Batt. CHG (36 V) 6 Batt. (72 V)/8 Batt (96 V)CHG
J1 1 A 1 A
J2 2 A 2 A
J3 4 A 4 A
J4 (Default) 8 A 6 A

Operating mode description

NUMERIC NUMERIC-1-3KVA-
Single-Phase-Pure-Sine-Wave-Industrial-Transformer-15

Fault reference codes

Fault event| Fault code| Icon| Fault event| Fault code| Icon
---|---|---|---|---|---
BUS start fail| 01| x| Inverter voltage low| 13| x
BUS over| 02| x| Inverter output short| 14| SHORT
BUS under| 03| x| Battery voltage too high| 27| x
BUS unbalance| 04| x| Battery voltage too low| 28| x
Inverter soft start fail| 11| x| Temperature overload| 41| x
Inverter voltage high| 12| x| Overload| 43| OVER LOAD
Charger fail| 45| x|  |  |

Warning indicator

NUMERIC-1-3KVA-Single-Phase-Pure-Sine-Wave-Industrial-
Transformer-16

TROUBLESHOOTING

If the UPS system does not operate correctly, please solve the problem by using the table.

Symptom Possible cause Remedy

No indication and alarm even though the mains is normal.

| The AC input power is not connected well.| Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.| Plug AC input power cord to AC input correctly.
The icons  and  flashing on LCD display and alarm is sounding every second.| The external or internal battery is incorrectly connected.| Check if all batteries are connected well.
Fault code is shown as 27 and the icon BATT,FAULT is lighting on LCD display and alarm is sounding continuously.| Battery voltage is too high or the charger is faulty.| Contact your dealer.
Fault code is shown as 28 and the icon BATT,FAULT is lighting on LCD display and alarm is continuously sounding.| Battery voltage is too low or the charger is faulty.| Contact your dealer.
The icons and OVER LOAD is flashing on LCD display and alarm is sounding twice every second.| UPS is overloaded.| Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass.| Remove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains.| Remove excess loads from UPS output first. Then shut down the UPS and restart it.
Fault code is shown as 43, the icon OVER LOAD is lighting on LCD display and alarm is sounding continuously.| The UPS shutdown automatically because of overload at the UPS output.| Remove excess loads from UPS output and restart it.
Fault code is shown as 14 and the icon SHORT is lighting on LCD display and alarm is sounding continuously.| The UPS shutdown automatically because short circuit occurs on the UPS output.| Check output wiring and if connected devices are in short circuit status.
Fault code shown as 45 on LCD display and alarm sounds continuously.| ****

Charger is faulty.

| ****

Contact your dealer

---|---|---



Fault code is shown as 01, 02, 03,

04, 11, 12, 13 and 41 on LCD display and alarm is sounding continuously.

| A UPS internal fault has occurred. There are two possible results:

1.  The load is still supplied, but directly from AC power via Bypass.

2.  The load is no longer supplied by power.

| ****



Contact your dealer



Battery backup time is shorter than nominal value

| Batteries are not fully charged| Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Battery faulty| Contact your dealer to replace the battery.

If the problem persists contact our nearest after sales service department by visiting www.numericups.com or call Toll Free no: 18004253266 with the following information.:

  1. Model number, Serial number
  2. Date on which the problem occurred
  3. LCD/LED display status, Buzzer alarm status
  4. Utility power condition, load type and capacity, environment temperature, ventilation condition
  5. The information (battery capacity, quantity) of external battery pack if the UPS is with external battery
  6. Other information for complete description of the problem

STORAGE AND MAINTENANCE

Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case,please contact your dealer.
Be sure to deliver the used battery to a recycling facility or ship it to your dealer in the replacement battery packing material.

Storage
Before storing, charge the UPS for 5 hours. Store the UPS covered and upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:

Storage temperature Recharge frequency Charging duration
-25°C to 40°C Every 3 months 1-2 hours
40°C to 45°C Every 2 months 1-2 hours

Disposal
Ref. standard: ISO 14001:2015

  • After unpacking the UPS and Battery, the removed packaging materials like polythene paper, thermocole/polyethylene, carton box, Nylon belt, nylon thread shall be collected and disposed through authorized recycler.
  • Batteries when found faulty/damaged must be handed over to identified authorized recycler or to NUMERIC, where it is disposed properly.
  • Battery contains harmful metals and chemicals such as nickel-cadmium, alkaline, mercury, nickel-metal hydride and lead acid, which contaminates if it is not disposed properly.
  • When batteries containing cadmium is used in fills, they will eventually dissolve and release the toxic substance than can seep into water supplies posing serious health hazards for the population/society. Hence, recycling of batteries will prevent pollution and also saves resource.

SPECIFICATIONS

UPS without ISO transformer

MODEL| 1 kVA              2 kVA                 2 kVA 3 kVA                 3 kVA

FM               72 FM                96 FM                72 FM 96 FM

---|---
**CAPACITY*| 1000 VA/800 W              2000 VA/1600 W 3000 VA/2400 W
INPUT**



Voltage

| Low line transfer| 160 VAC/140 VAC/120 VAC/110 VAC ± 5%

(based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)

Low line comeback| 185 VAC/165 VAC/145 VAC/135 VAC ± 5 %

(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)

High line transfer| 300 Vac ± 5%
High line comeback| 290 Vac ± 5%
Frequency range| 40 Hz ~ 70 Hz
Phase| Single phase with ground
Power factor| ≥ 0.99 @ nominal input voltage
OUTPUT
Output voltage| 200/208/220/230/240 Vac
AC voltage regulation| ± 1%
Frequency Range

(Synchronized Range )

| 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)| 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz


Overload

| 105%~110%: UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110%~130%: UPS shuts down after 1 min at battery mode or transfer to Bypass when the utility is normal

> 130%: UPS shuts down after 3 secs at battery mode

or transfer to Bypass when the utility is normal

Current crest ratio| 3:1
Harmonic distortion| ≤ 3% THD (Linear load)

≤ 5% THD (Non-linear load)

Transfer time| AC mode to Batt. mode| Zero
Inverter to Bypass| 4 ms (Typical)
Waveform (Batt. mode)| Pure Sinewave
EXTERNAL BATTERY

Battery type| Depending on the capacity of external batteries
Battery numbers| 3| 6| 8| 6| 8
Maximum battery AH| 150| 200| 200| 200| 200
Current of external Batt. pack| 30 A max| 30 A max| 30 A max| 45 A max| 32 A max
Charging current| 1.0A/2.0A/

4.0A/8.0A

| 1.0A/2.0A/4.0A/6.0 A|
Charging voltage| 41.0 Vdc ± 1% 82.1 Vdc ±1%| 109.5 Vdc ±1%| 82.1 Vdc ±1%| 109.5 Vdc ±1%
PHYSICAL
Dimension (D x W x H) mm| 405x145x235| 435 x 190 x 335
Net weight (kgs)| 6.2| 11.5|  | 12.0
ENVIRONMENT
Operation humidity| 20-90% RH @ 0- 40°C (non-condensing)
Noise level| Less than 50 dBA @ 1 Meter (AVG)
MANAGEMENT
Smart RS-232 or USB| Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMP| Power management from SNMP manager and web browser

Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 208 VAC/200 VAC. Product specifications are subject to change without further notice.

UPS with ISO transformer

MODEL| 1 kVA              2 kVA                 2 kVA 3 kVA                 3 kVA

FMI              7 2FMI              96V FMI              72 FMI 96 FMI

---|---
**CAPACITY*| 1000 VA/800 W              2000 VA/1600 W 3000 VA/2400 W
INPUT**



Voltage

| Low line transfer| 160 VAC/140 VAC/120 VAC/110 VAC ± 5%

(based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)

Low line comeback| 185 VAC/165 VAC/145 VAC/135 VAC ± 5 %

(based on load percentage 100% – 80%/80% – 70%/70 – 60%/60% – 0)

High line transfer| 300 Vac ± 5%
High line comeback| 290 Vac ± 5%
Frequency range| 40 Hz ~ 70 Hz
Phase| Single phase with ground
Power factor| ≥ 0.99 @ nominal input voltage
OUTPUT
Output voltage| 200/208/220/230/240 Vac
AC voltage regulation| ± 1%
Frequency Range

(Synchronized Range )

| 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)| 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz


Overload

| 105%~110%: UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110%~130%: UPS shuts down after 1 min at battery mode or transfer to Bypass when the utility is normal

> 130%: UPS shuts down after 3 secs at battery mode or transfer to Bypass when the utility is normal

Current crest ratio| 3:1
Harmonic distortion| ≤ 3% THD (Linear load)

≤ 5% THD (Non-linear load)

Transfer time| AC mode to batt. mode| Zero
Inverter to Bypass| 4 ms (Typical)
Waveform (Batt. mode)| Pure Sinewave
EXTERNAL BATTERY

Battery type| Depending on the capacity of external batteries
Battery numbers| 3| 6| 8| 6|  | 8
Maximum battery AH| 150| 200| 200| 200|  | 200
Current of external Batt. pack| 30 A max| 30 A max| 30 A max| 45 A max|  | 32 A max
Charging current| 1.0A/2.0A/

4.0A/8.0A

| 1.0A/2.0A/4.0A/6.0 A|  |
Charging voltage| 41.0 Vdc ± 1% 82.1 Vdc ±1%| 109.5 Vdc ±1% 82.1 Vdc ±1%|  | 109.5 Vdc ±1%
PHYSICAL
Dimension (D x W x H) mm| 465x190x465| 435 x 190 x 595
Net weight (kgs)| 21.3| 35.5|  | 43.0|
ENVIRONMENT
Operation humidity| 20-90% RH @ 0- 40°C (non-condensing)
Noise level| Less than 50 dBA @ 1 Meter (AVG)
MANAGEMENT
Smart RS-232 or USB| Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMP| Power management from SNMP manager and web browser

Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 208 VAC/200 VAC. Product specifications are subject to change without further notice.

Head Office
10th Floor, Prestige Center Court,
Office Block, Vijaya Forum Mall,
183, N.S.K. Salai, Vadapalani,
Chennai – 600 026.
Phone: +91 44 4656 5555

10th Floor, Prestige Center Court, Office Block,
Vijaya Forum Mall, 183, N.S.K. Salai, Vadapalani,
Chennai – 600 026, India. | Phone: +91 44 4656 5555
Sales – enquiry.numeric˝numericups.com
Service – support.numeric˝numericups.com
TOLL FREE No.: 1800 425 3266
www.numericups.com
*NUMERIC reserves at any time the right to modify the contents of this booklet and to communicate, in any form and modality, the changes brought to the same.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals