EATON PowerXL DG1 Variable Frequency Drive Instruction Manual
- June 12, 2024
- EATON
Table of Contents
PowerXL DG1 Variable Frequency Drive
Product Information
The PowerXL DG1/DH1 Series VFD is a variable frequency drive
manufactured by Eaton. It is designed to provide efficient and
reliable control of motor speed for various industrial
applications. The VFD offers advanced features and capabilities to
optimize motor performance, energy efficiency, and system
reliability.
Product Usage Instructions
-
Installation: Before commencing the
installation, refer to the safety instructions provided in the user
manual. Ensure that all necessary precautions are taken to prevent
accidents or damage during installation. -
Support Services: If you require any
assistance with the operation or maintenance of the PowerXL DG1/DH1
Series VFD, Eaton provides support services through various
channels. You can contact your local distributor for product
pricing, availability, ordering, and repairs. Additionally, Eaton
offers a support website (Eaton.com/drives) where you can find
product information and details about local distributors and sales
offices. -
EatonCare Customer Support Center: If you need
further assistance with placing orders, stock availability,
expediting orders, emergency shipments, product price information,
or returns (excluding warranty returns), you can reach out to the
EatonCare Support Center. They can also provide information about
local distributors or sales offices. Contact details for the
support center can be found in the user manual. -
Drives Technical Resource Center: For
customers in Europe, there is a dedicated technical resource center
available. You can contact them via phone, hotline, or email for
technical support and after-sales services. The contact details are
provided in the user manual.
For detailed technical data and specifications of the PowerXL
DG1/DH1 Series VFD, refer to Appendix A in the user manual.
PowerXL DG1/DH1 Series VFD
Installation manual (original instructions)
Effective July 2022 Supersedes January 2022
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information, recommendations, descriptions, and safety notations in this
document are based on manufacturer’s experience and judgment and may not cover
all contingencies. If further information is required, a sales representative
should be consulted. Sale of the product shown in this literature is subject
to the terms and conditions outlined in appropriate manufacturer selling
policies or other contractual agreement between manufacturer and the
purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED,
INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY,
OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE
PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF THE MANUFACTURER.
THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT
BETWEEN THE PARTIES.
In no event will the manufacturer be responsible to the purchaser or user in
contract, in tort (including negligence), strict liability, or otherwise for
any special, indirect, incidental, or consequential damage or loss whatsoever,
including but not limited to damage or loss of use of equipment, plant or
power system, cost of capital, loss of power, additional expenses in the use
of existing power facilities, or claims against the purchaser or user by its
customers resulting from the use of the information, recommendations, and
descriptions contained herein. The information contained in this manual is
subject to change without notice.
Cover Photo: Eaton PowerXL Series Drive
ii
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Support services
Support services
The goal of Eaton is to ensure your greatest possible satisfaction with the
operation of our products. We are dedicated to providing fast, friendly, and
accurate assistance. That is why we offer you so many ways to get the support
you need. Whether it is by phone, fax, or email, you can access Eaton’s
support information 24 hours a day, seven days a week.
Our wide range of services is listed below.
You should contact your local distributor for product pricing, availability,
ordering, expediting, and repairs.
Website
Use the Eaton Website to find product information. You can also find
information on local distributors or Eaton’s sales offices.
Website address
Eaton.com/drives
EatonCare Customer Support Center
Call the EatonCare Support Center if you need assistance with placing an
order, stock availability or proof of shipment, expediting an existing order,
emergency shipments, product price information, returns other than warranty
returns, and information on local distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 a.m.6:00 p.m. EST) After-Hours
Emergency: 800-543-7038 (6:00 p.m.8:00
a.m. EST)
Drives Technical Resource Center
Voice: 877-ETN-CARE (386-2273) option 2, option 6 (8:00 a.m.5:00 p.m. Central
Time U.S. [UTC 6]) email: TRCDrives@Eaton.com
For customers in Europe, contact
Phone: +49 (0) 228 6 02-3640 Hotline: +49 (0) 180 5 223822 email:
AfterSalesEGBonn@Eaton.com Eaton.com/moeller/aftersales
PowerXL DG1/DH1 Series VFD
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
iii
PowerXL DG1/DH1 Series VFD
Table of contents
SAFETY Before commencing the installation . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . ix Definitions and symbols . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .x Hazardous high voltage . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .x Warnings and cautions . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .x
CHAPTER 1–POWERXL SERIES OVERVIEW How to use this manual . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Receiving and inspection. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .1 Real time clock battery activation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .1 Rating label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Carton labels (U.S.
and Europe). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .2 Catalog number system . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Power ratings and
product selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .4 DG1 replacement parts . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 DH1 replacement
parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 11
CHAPTER 2–ENGINEERING CONSIDERATIONS Introduction . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . .15 Electrical power network. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .16 Input voltage and
frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .16 Input voltage balance . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Total
harmonic distortion (THD). . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .17 Reactive power compensation devices. . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
CHAPTER 3–PRODUCT OVERVIEW Component identification . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Selection
criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .20 Proper use . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . .20 Maintenance and inspection . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .21 Storage . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .21 Service and warranty. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
CHAPTER 4–SAFETY AND SWITCHING Fuses and cable cross-sections. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Cables and
fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .22 Residual-current device (RCD). . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Leakage current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .23 Input contactor . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .23 EMC Measures . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
CHAPTER 5–MOTOR AND APPLICATION Motor selection . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.25 Connecting motors in parallel . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .25 Parallel connection of several
motors to one frequency inverter . . . . . . . . . . . . . . . .26 Bypass
operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .28 Connecting EX motors . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
iv
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
PowerXL DG1/DH1 Series VFD
Table of contents, continued
CHAPTER 6–INSTALLATION REQUIREMENTS Electrical installation warnings and
cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Standard mounting instructions . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .29 Dimensions . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .31 Standard drive mounting . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .32 FR6 wiring . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .37 Power wiring selection . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 Cable selection:
Power and motor leads. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .38 Line (Mains) and motor cable installation . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .38 Connection tightening torque .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .39 Cable routing . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .40 Wiring the VFD . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .40 Rubber grommet installation instructions . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .41 Control board . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .47 Safe torque off (STO). . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Connection to power section . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .48 Three-phase input connection . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Terminal designations in the power section . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .48 Ground connection . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Product modified sticker . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .49 Checking the cable and motor
insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.49
CHAPTER 7–EMC INSTALLATION EMC measures in the control panel . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 Earthing . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .50 Screen earth kit . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Installation requirements . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .51 International EMC protection cable
requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Installation in corner-grounded network and IT system . . . . . . . . . . . .
. . . . . . . . . . .53
APPENDIX A–TECHNICAL DATA AND SPECIFICATIONS Technical data . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .55
APPENDIX B–INSTALLATION GUIDELINES Cable and fuse sizing . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Temperature deratings . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .63 Heat loss data . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .70 Brake resistor sizing . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .71 Efficiency ratings .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .72
APPENDIX C–DIMENSION DRAWINGS
APPENDIX D–SAFETY INSTRUCTIONS FOR UL AND CUL UL standards compliance . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .90 Field wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .93
APPENDIX E–STO FUNCTION Description of safety function . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Requirement for
installation, commission, maintenance . . . . . . . . . . . . . . . . . . . .
.102 Requirements of proof test . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .102
APPENDIX F–CERTIFICATION AND COMPLIANCE INFORMATION UL/cUL certificate of
compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .103 CE declaration of conformity. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .103 UKCA declaration of
conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .103 Eco-design information . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .103 Manufacturer and
importer information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .103
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
v
PowerXL DG1/DH1 Series VFD
List of figures
Figure 1. RTC battery connection . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .1 Figure 2. Rating label–DG1 . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 3. Rating label–DH1 . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .2 Figure 4. Carton label–DG1. . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 5. Carton label–DH1. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .2 Figure 6. Catalog numbering system . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 7. Drive system (PDS = power drive system) . . . . . . . . . . . . . .
. . . . . . . . . . .15 Figure 8. AC power networks with grounded neutral
point (TN-/TT networks) . . . . .16 Figure 9. Description of the PowerXL
Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Figure
10. Block diagram, elements of PowerXL frequency inverters . . . . . . . . . .
. .19 Figure 11. Selection criteria. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .20 Figure 12. Identification on
the FI circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . .
.22 Figure 13. EMC measures . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .24 Figure 14. Parallel connection. . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.26 Figure 15. Example of a motor ratings plate . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .26 Figure 16. Star and delta circuit types . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 Figure
17. V/Hz characteristic curve . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .27 Figure 18. Bypass motor control (example) . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Figure 19.
Mounting space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .30 Figure 20. Open Drives FR0FR6 . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Figure 21. FR6
wiring layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .37 Figure 22. Brake resistor wiring . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 Figure 23.
Input power and motor cable stripping lengths . . . . . . . . . . . . . . . .
. . . .39 Figure 24. Ground wiring . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .42 Figure 25. Terminal block
layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .45 Figure 26. Basic internal control wiring diagram . . . . . . . . .
. . . . . . . . . . . . . . . . . . .46 Figure 27. PowerXL variable frequency
drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47 Figure
28. Connection to power section . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .48 Figure 29. Grounding . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 Figure 30.
FR0 grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .49 Figure 31. Product modified sticker . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 Figure 34.
EMC-Compliant Setup–230 Vac, 460/480 Vac, 600 Vac . . . . . . . . . . . . .51
Figure 35. Cable description . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .52 Figure 36. Location of the EMC Screw in
Frame 0 . . . . . . . . . . . . . . . . . . . . . . . . . .53 Figure 37.
Locations of the EMC Screw in Frame 1 and Frame 3 . . . . . . . . . . . . . .
.53 Figure 38. Locations of EMC and MOV Screws for Frame 2 and Frame 4 . . . .
. . . .54 Figure 39. Locations of the EMC Screws in Frame 5 and Frame 6 . . .
. . . . . . . . . .54 Figure 40. FR0 dimension drawing . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .77 Figure 41. FR1 dimension
drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .78 Figure 42. FR1 dimension drawing flange mount . . . . . . . . . . . .
. . . . . . . . . . . . . . .79 Figure 43. FR2 dimension drawing . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 Figure 44. FR2
dimension drawing flange mount . . . . . . . . . . . . . . . . . . . . . . . .
. . .81 Figure 45. FR3 dimension drawing . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .82 Figure 46. FR3 dimension drawing
flange mount . . . . . . . . . . . . . . . . . . . . . . . . . . .83 Figure
47. FR4 dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .84 Figure 48. FR4 dimension drawing flange mount . . .
. . . . . . . . . . . . . . . . . . . . . . . .85 Figure 49. FR5 dimension
drawing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .86 Figure 50. FR5 dimension drawing flange mount . . . . . . . . . . . .
. . . . . . . . . . . . . . .87 Figure 51. FR6 dimensional drawing. . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88 Figure 52.
FR6 dimensional drawing flange mount . . . . . . . . . . . . . . . . . . . . .
. . . . .89 Figure 53. Functional block diagram . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .100 Figure 54. Reliability block
diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .100 Figure 55. STO terminal block in PowerXL control board . . . . . . . .
. . . . . . . . . . . . .102 Figure 56. Thermistor STO wiring diagram . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .102
vi
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
PowerXL DG1/DH1 Series VFD
List of tables
Table 1. Common abbreviations . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .1 Table 2. Open Type IP20 . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Table 3. Type 1/IP21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .4 Table 4. Type 12/IP54 . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .5 Table 5. Open Type IP20 . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .5 Table 6. Type 1/IP21 . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .6 Table 7. Type 12/IP54 . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Table 8.
Type 1/IP21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .7 Table 9. Type 12/IP54 . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.7 Table 10. Frame 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .8 Table 11. Frame 1 . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .8 Table 12. Frame 2 . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Table 13. Frame
3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .9 Table 14. Frame 4 . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Table 15. Frame 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .10 Table 16. Frame 6 . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 11 Table 17. Frame 0 . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Table 18. Frame 1 . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 11 Table 19. Frame 2 . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Table 20.
Frame 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .12 Table 21. Frame 4 . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.13 Table 22. Frame 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .13 Table 23. Frame 6 . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .14 Table 24. Drive system components . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .15 Table 25. Elements of PowerXL
frequency inverters . . . . . . . . . . . . . . . . . . . . . . . .19 Table
26. Maintenance measures and intervals . . . . . . . . . . . . . . . . . . . .
. . . . . . . .21 Table 27. Motor power cable EMC guidelines . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .24 Table 28. Assignment of frequency
inverters to example motor circuit . . . . . . . . . .27 Table 29. Bypass
motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .28 Table 30. Space requirements for mounting the PowerXL
Series VFD and airflow . . 30 Table 31. Mounting drive dimensions . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Table 32.
Tightening torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .39 Table 33. Spacing between parallel motor cables
. . . . . . . . . . . . . . . . . . . . . . . . . . .39 Table 34. Maximum
motor power cable length 230/480 V. . . . . . . . . . . . . . . . . . . . .39
Table 35. Maximum motor power cable lengths 575 V . . . . . . . . . . . . . .
. . . . . . . . .39 Table 36. Input power and motor cable stripping and wire
lengths . . . . . . . . . . . . .39 Table 37. DG1 I/O connection . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43 Table
38. DH1 I/O connection. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .44 Table 39. I/O specifications. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Table 40. 1st Environment 2nd environment EMC levels according to EN 61800-3
(2004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .52
Table 41. Motor power cable EMC guidelines . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .52 Table 42. Cable categories . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52 Table 43.
PowerXL Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .55 Table 44. North America cable and fuse sizes–208
Vac to 240 Vac ratings . . . . . . .58 Table 45. International cable and fuse
sizes–208 Vac to 240 Vac ratings . . . . . . . . .59 Table 46. North America
cable and fuse sizes–440 Vac to 500 Vac ratings . . . . . . .60 Table 47.
International cable and fuse sizes–380 Vac to 440 Vac ratings . . . . . . . .
.61 Table 48. North America cable and fuse sizes–525 Vac to 600 Vac ratings .
. . . . . .62 Table 48a. International cable and fuse sizes–525 Vac to 600 Vac
ratings . . . . . . . .62 Table 49. 230 V temperature deratings (VT) . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .64 Table 50. 230 V
temperature deratings (CT) . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .65 Table 51. 480 V temperature deratings (VT) . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .66
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
vii
PowerXL DG1/DH1 Series VFD
List of tables, continued
Table 52. 480 V temperature deratings (CT) . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .67 Table 53. 600 V temperature deratings (VT) . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .68 Table 54. 600 V
temperature deratings (CT) . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .69 Table 55. 230 V heat loss data . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .70 Table 56. 400 V heat loss
data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .70 Table 57. 600 V heat loss data . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .71 Table 58. 230 V idle heat
loss FR0~FR6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .71 Table 59. 480 V idle heat loss FR0~FR6. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .71 Table 60. 575 V idle heat loss FR1~FR6.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71 Table
61. Brake resistor sizing data . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .71 Table 62. 230 V FR0-Xhp efficiency rating . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72 Table 63. 230 V
FR1-4hp efficiency rating. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .72 Table 64. 230 V FR2-10hp efficiency rating. . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .72 Table 65. 230 V FR3-20hp
efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .72 Table 66. 230 V FR4-40hp efficiency rating . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .73 Table 67. 230 V FR5-75hp efficiency rating
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73 Table 68.
400 V FR0-Xhp efficiency rating . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .73 Table 69. 400 V FR1-7.5hp efficiency rating . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .73 Table 70. 400 V FR2-20hp
efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .74 Table 71. 400 V FR3-40hp efficiency rating. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .74 Table 72. 400 V FR4-75hp efficiency
rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74 Table
73. 400 V FR5-150hp efficiency rating. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .74 Table 74. 575 V FR1-7.5hp efficiency rating . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .75 Table 75. 575 V
FR2-20hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .75 Table 76. 575 V FR3-40hp efficiency rating. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .75 Table 77. 575 V FR4-75hp
efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .76 Table 78. 575 V FR5-150hp efficiency rating. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .76 Table 79. Protection ratings–480 V drive
series . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 Table 80.
Protection ratings–230 V drive series . . . . . . . . . . . . . . . . . . . .
. . . . . . . .92 Table 81. Protection ratings–575 V drive series . . . . . .
. . . . . . . . . . . . . . . . . . . . . .93 Table 82. Required line and
motor wire torque (480 V) . . . . . . . . . . . . . . . . . . . . . . .94
Table 83. Required line and motor wire torque (230 V) . . . . . . . . . . . .
. . . . . . . . . . .95 Table 84. Required line and motor wire torque (575 V)
. . . . . . . . . . . . . . . . . . . . . . .96 Table 85. Required grounding
wire torque (480 V) . . . . . . . . . . . . . . . . . . . . . . . . . .97
Table 86. Required grounding wire torque (230 V) . . . . . . . . . . . . . . .
. . . . . . . . . . .98 Table 87. Required grounding wire torque (575 V) . . .
. . . . . . . . . . . . . . . . . . . . . . . .99 Table 88. Safety-related
parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .100 Table 89. Power supply and input/output . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .100 Table 90. Environmental and EMC
conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
viii
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
PowerXL DG1/DH1 Series VFD
Safety
WARNING
DANGEROUS ELECTRICAL VOLTAGE!
Before commencing the installation
· Disconnect the power supply of the device
· Ensure that devices cannot be accidentally restarted
· Verify isolation from the supply
· Earth and short circuit the device
· Cover or enclose any adjacent live components
· Only suitably qualified personnel in accordance with EN 50110-1/-2 (VDE 0105
Part 100) may work on this device/system
· Before installation and before touching the device ensure that you are free
of electrostatic charge
· The functional earth (FE, PES) must be connected to the protective earth
(PE) or the potential equalization. The system installer is responsible for
implementing this connection
· Connecting cables and signal lines should be installed so that inductive or
capacitive interference does not impair the automation functions
· Install automation devices and related operating elements in such a way that
they are well protected against unintentional operation
· Suitable safety hardware and software measures should be implemented for the
I/O interface so that an open circuit on the signal side does not result in
undefined states in the automation devices
· Ensure a reliable electrical isolation of the extra-low voltage of the 24 V
supply. Only use power supply units complying with IEC 60364-4-41 (VDE 0100
Part 410) or HD384.4.41 S2
· Deviations of the input voltage from the rated value must not exceed the
tolerance limits given in the specifications, otherwise this may cause
malfunction and dangerous operation
· Emergency stop devices complying with IEC/EN 60204-1 must be effective in
all operating modes of the automation devices. Unlatching the emergency-stop
devices must not cause a restart
· Devices that are designed for mounting in housings or control cabinets must
only be operated and controlled after they have been installed and with the
housing closed. Desktop or portable units must only be operated and controlled
in enclosed housings
· Measures should be taken to ensure the proper restart of programs
interrupted after a voltage dip or failure. This should not cause dangerous
operating states even for a short time. If necessary, emergency-stop devices
should be implemented
· Wherever faults in the automation system may cause injury or material
damage, external measures must be implemented to ensure a safe operating state
in the event of a fault or malfunction (for example, by means of separate
limit switches, mechanical interlocks, and so on)
· Depending on their degree of protection, adjustable frequency drives may
contain live bright metal parts, moving or rotating components, or hot
surfaces during and immediately after operation
· Removal of the required covers, improper installation, or incorrect
operation of motor or adjustable frequency drive may cause the failure of the
device and may lead to serious injury or damage
· The applicable national accident prevention and safety regulations apply to
all work carried out on live adjustable frequency drives
· The electrical installation must be carried out in accordance with the
relevant regulations (for example, with regard to cable cross sections, fuses,
PE)
· Transport, installation, commissioning, and maintenance work must be carried
out only by qualified personnel (IEC 60364, HD 384 and national occupational
safety regulations)
· Installations containing adjustable frequency drives must be provided with
additional monitoring and protective devices in accordance with the applicable
safety regulations. Modifications to the adjustable frequency drives using the
operating software are permitted
· All covers and doors must be kept closed during operation
· To reduce hazards for people or equipment, the user must include in the
machine design measures that restrict the consequences of a malfunction or
failure of the drive (increased motor speed or sudden standstill of motor).
These measures include:
· Other independent devices for monitoring safety-related variables (speed,
travel, end positions, and so on)
· Electrical or non-electrical system-wide measures (electrical or mechanical
interlocks)
· Never touch live parts or cable connections of the adjustable frequency
drive after it has been disconnected from the power supply. Due to the charge
in the capacitors, these parts may still be live after disconnection. Fit
appropriate warning signs
Read this manual thoroughly and make sure you understand the procedures before
you attempt to install, set up, operate or carry out any maintenance work on
this PowerXL Adjustable Frequency Drive.
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
ix
PowerXL DG1/DH1 Series VFD
Definitions and symbols
WARNING
THIS SYMBOL INDICATES HIGH VOLTAGE. IT CALLS YOUR ATTENTION TO ITEMS OR
OPERATIONS THAT COULD BE DANGEROUS TO YOU AND OTHER PERSONS OPERATING THIS
EQUIPMENT. READ THE MESSAGE AND FOLLOW THE INSTRUCTIONS CAREFULLY.
THIS SYMBOL IS THE “SAFETY ALERT SYMBOL.” IT OCCURS WITH EITHER OF TWO SIGNAL
WORDS: CAUTION OR WARNING, AS DESCRIBED BELOW.
WARNING
INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, CAN RESULT
IN SERIOUS INJURY OR DEATH.
CAUTION
INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, CAN RESULT
IN MINOR TO MODERATE INJURY, OR SERIOUS DAMAGE TO THE PRODUCT. THE SITUATION
DESCRIBED IN THE CAUTION MAY, IF NOT AVOIDED, LEAD TO SERIOUS RESULTS.
IMPORTANT SAFETY MEASURES ARE DESCRIBED IN CAUTION (AS WELL AS WARNING).
Hazardous high voltage
WARNING
MOTOR CONTROL EQUIPMENT AND ELECTRONIC CONTROLLERS ARE CONNECTED TO HAZARDOUS
LINE VOLTAGES. WHEN SERVICING DRIVES AND ELECTRONIC CONTROLLERS, THERE MAY BE
EXPOSED COMPONENTS WITH HOUSINGS OR PROTRUSIONS AT OR ABOVE LINE POTENTIAL.
EXTREME CARE SHOULD BE TAKEN TO PROTECT AGAINST SHOCK. · STAND ON AN
INSULATING PAD AND MAKE IT A HABIT TO USE
ONLY ONE HAND WHEN CHECKING COMPONENTS · ALWAYS WORK WITH ANOTHER PERSON IN
CASE AN
EMERGENCY OCCURS · DISCONNECT POWER BEFORE CHECKING CONTROLLERS OR
PERFORMING MAINTENANCE · BE SURE EQUIPMENT IS PROPERLY EARTHED · WEAR SAFETY
GLASSES WHENEVER WORKING ON
ELECTRONIC CONTROLLERS OR ROTATING MACHINERY
WARNING
THE COMPONENTS IN THE DRIVE’S POWER SECTION REMAIN ENERGIZED AFTER THE SUPPLY
VOLTAGE HAS BEEN SWITCHED OFF. AFTER DISCONNECTING THE SUPPLY, WAIT AT LEAST
FIVE MINUTES BEFORE REMOVING THE COVER TO ALLOW THE INTERMEDIATE CIRCUIT
CAPACITORS TO DISCHARGE. PAY ATTENTION TO HAZARD WARNINGS!
DANGER 5 MIN
WARNING
ELECTRIC SHOCK HAZARD–RISK OF INJURIES! CARRY OUT WIRING WORK ONLY IF THE UNIT
IS DE-ENERGIZED.
WARNING
DO NOT PERFORM ANY MODIFICATIONS ON THE AC DRIVE WHEN IT IS CONNECTED TO
MAINS.
Warnings and cautions WARNING
BE SURE TO GROUND THE UNIT FOLLOWING THE INSTRUCTIONS IN THIS MANUAL.
UNGROUNDED UNITS MAY CAUSE ELECTRIC SHOCK AND/OR FIRE.
WARNING
THIS EQUIPMENT SHOULD ONLY BE INSTALLED, ADJUSTED, AND SERVICED BY QUALIFIED
ELECTRICAL MAINTENANCE PERSONNEL FAMILIAR WITH THE CONSTRUCTION AND OPERATION
OF THIS TYPE OF EQUIPMENT AND THE HAZARDS INVOLVED. FAILURE TO OBSERVE THIS
PRECAUTION COULD RESULT IN DEATH OR SEVERE INJURY.
WARNING
COMPONENTS WITHIN THE DRIVE ARE LIVE WHEN IT IS CONNECTED TO POWER. CONTACT
WITH THIS VOLTAGE IS EXTREMELY DANGEROUS AND MAY CAUSE DEATH OR SEVERE INJURY.
WARNING
LINE TERMINALS (L1, L2, L3), MOTOR TERMINALS (U, V, W) AND THE DC LINK/BRAKE
RESISTOR TERMINALS (DC, DC+/R+, R) ARE LIVE WHEN THE DRIVE IS CONNECTED TO
POWER, EVEN IF THE MOTOR IS NOT RUNNING. CONTACT WITH THIS VOLTAGE IS
EXTREMELY DANGEROUS AND MAY CAUSE DEATH OR SEVERE INJURY.
WARNING
EVEN THOUGH THE CONTROL I/O-TERMINALS ARE ISOLATED FROM LINE VOLTAGE, THE
RELAY OUTPUTS AND OTHER I/OTERMINALS MAY HAVE DANGEROUS VOLTAGE PRESENT EVEN
WHEN THE DRIVE IS DISCONNECTED FROM POWER. CONTACT WITH THIS VOLTAGE IS
EXTREMELY DANGEROUS AND MAY CAUSE DEATH OR SEVERE INJURY.
x
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
PowerXL DG1/DH1 Series VFD
WARNING
THIS EQUIPMENT HAS A LARGE CAPACITIVE LEAKAGE CURRENT DURING OPERATION, WHICH
CAN CAUSE ENCLOSURE PARTS TO BE ABOVE GROUND POTENTIAL. PROPER GROUNDING, AS
DESCRIBED IN THIS MANUAL, IS REQUIRED. FAILURE TO OBSERVE THIS PRECAUTION
COULD RESULT IN DEATH OR SEVERE INJURY.
WARNING
BEFORE APPLYING POWER TO THIS DRIVE, MAKE SURE THAT THE FRONT AND CABLE COVERS
ARE CLOSED AND FASTENED TO PREVENT EXPOSURE TO POTENTIAL ELECTRICAL FAULT
CONDITIONS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN DEATH OR SEVERE
INJURY.
WARNING
AN UPSTREAM DISCONNECT/PROTECTIVE DEVICE MUST BE PROVIDED AS REQUIRED BY THE
NATIONAL ELECTRIC CODET (NECT). FAILURE TO FOLLOW THIS PRECAUTION MAY RESULT
IN DEATH OR SEVERE INJURY.
WARNING
THIS DRIVE CAN CAUSE A DC CURRENT IN THE PROTECTIVE EARTHING CONDUCTOR. WHERE
A RESIDUAL CURRENT-OPERATED PROTECTIVE (RCD) OR MONITORING (RCM) DEVICE IS
USED FOR PROTECTION IN CASE OF DIRECT OR INDIRECT CONTACT, ONLY AN RCD OR RCM
OF TYPE B IS ALLOWED ON THE SUPPLY SIDE OF THIS PRODUCT.
WARNING
CARRY OUT WIRING WORK ONLY AFTER THE DRIVE HAS BEEN CORRECTLY MOUNTED AND
SECURED.
WARNING
BEFORE OPENING THE DRIVE COVERS: · DISCONNECT ALL POWER TO THE DRIVE,
INCLUDING EXTERNAL
CONTROL POWER THAT MAY BE PRESENT · WAIT A MINIMUM OF FIVE MINUTES AFTER ALL
THE LIGHTS
ON THE KEYPAD ARE OFF. THIS ALLOWS TIME FOR THE DC BUS CAPACITORS TO DISCHARGE
· A HAZARD VOLTAGE MAY STILL REMAIN IN THE DC BUS CAPACITORS EVEN IF THE POWER
HAS BEEN TURNED OFF. CONFIRM THAT THE CAPACITORS HAVE FULLY DISCHARGED BY
MEASURING THEIR VOLTAGE USING A MULTIMETER SET TO MEASURE THE DC VOLTAGE
FAILURE TO FOLLOW THESE PRECAUTIONS MAY CAUSE DEATH OR SEVERE INJURY.
WARNING
THE OPENING OF THE BRANCH-CIRCUIT PROTECTIVE DEVICE MAY BE AN INDICATION THAT
A FAULT CURRENT HAS BEEN INTERRUPTED. TO REDUCE THE RISK OF FIRE OR ELECTRIC
SHOCK, CURRENT-CARRYING PARTS AND OTHER COMPONENTS OF THE CONTROLLER SHOULD BE
EXAMINED AND REPLACED IF DAMAGED. IF BURNOUT OF THE CURRENT ELEMENT OF AN
OVERLOAD RELAY OCCURS, THE COMPLETE OVERLOAD RELAY MUST BE REPLACED.
WARNING
OPERATION OF THIS EQUIPMENT REQUIRES DETAILED INSTALLATION AND OPERATION
INSTRUCTIONS PROVIDED IN THE INSTALLATION/OPERATION MANUAL INTENDED FOR USE
WITH THIS PRODUCT. IT SHOULD BE RETAINED WITH THIS DEVICE AT ALL TIMES. A HARD
COPY OF THIS INFORMATION MAY BE ORDERED FROM LITERATURE FULFILLMENT.
WARNING
BEFORE SERVICING THE DRIVE: · DISCONNECT ALL POWER TO THE DRIVE, INCLUDING
EXTERNAL
CONTROL POWER THAT MAY BE PRESENT · PLACE A “DO NOT TURN ON” LABEL ON THE
DISCONNECT
DEVICE · LOCK THE DISCONNECT DEVICE IN THE OPEN POSITION FAILURE TO FOLLOW
THESE INSTRUCTIONS WILL RESULT IN DEATH OR SERIOUS INJURY.
WARNING
THE DRIVE OUTPUTS (U, V, W) MUST NOT BE CONNECTED TO THE INPUT VOLTAGE OR THE
UTILITY LINE POWER AS SEVERE DAMAGE TO THE DEVICE MAY OCCUR AND THERE MAY BE A
RISK OF FIRE.
WARNING
THE HEAT SINK AND/OR OUTER ENCLOSURE MAY REACH A HIGH TEMPERATURE. PAY
ATTENTION TO HAZARD WARNINGS!
HOT SURFACE–RISK OF BURN. DO NOT TOUCH!
WARNING
IN A DOMESTIC ENVIRONMENT, THIS PRODUCT MAY CAUSE RADIO INTERFERENCE, IN WHICH
CASE SUPPLEMENTARY MITIGATION MEASURES MAY BE REQUIRED.
CAUTION
ANY ELECTRICAL OR MECHANICAL MODIFICATION TO THIS DRIVE WITHOUT PRIOR WRITTEN
CONSENT OF MANUFACTURER WILL VOID ALL WARRANTIES AND MAY RESULT IN A SAFETY
HAZARD IN ADDITION AND VOIDING OF THE ULT LISTING.
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
xi
PowerXL DG1/DH1 Series VFD
CAUTION
INSTALL THIS DRIVE ON FLAME-RESISTANT MATERIAL SUCH AS A STEEL PLATE TO REDUCE
THE RISK OF FIRE
CAUTION
INSTALL THIS DRIVE ON A PERPENDICULAR SURFACE THAT IS ABLE TO SUPPORT THE
WEIGHT OF THE DRIVE AND IS NOT SUBJECT TO VIBRATION, TO LESSEN THE RISK OF THE
DRIVE FALLING AND BEING DAMAGED AND/OR CAUSING PERSONAL INJURY.
CAUTION
PREVENT FOREIGN MATERIAL SUCH AS WIRE CLIPPINGS OR METAL SHAVINGS FROM
ENTERING THE DRIVE ENCLOSURE, AS THIS MAY CAUSE ARCING DAMAGE AND FIRE.
CAUTION
INSTALL THIS DRIVE IN A WELL-VENTILATED ROOM THAT IS NOT SUBJECT TO
TEMPERATURE EXTREMES, HIGH HUMIDITY, OR CONDENSATION, AND AVOID LOCATIONS THAT
ARE DIRECTLY EXPOSED TO SUNLIGHT, OR HAVE HIGH CONCENTRATIONS OF DUST,
CORROSIVE GAS, EXPLOSIVE GAS, INFLAMMABLE GAS, GRINDING FLUID MIST, ETC.
IMPROPER INSTALLATION MAY RESULT IN A FIRE HAZARD.
CAUTION
WHEN SELECTING THE CABLE CROSS-SECTION, TAKE THE VOLTAGE DROP UNDER LOAD
CONDITIONS INTO ACCOUNT. THE CONSIDERATION OF OTHER STANDARDS IS THE
RESPONSIBILITY OF THE USER. THE USER IS RESPONSIBLE FOR COMPLIANCE WITH ALL
INTERNATIONAL AND NATIONAL ELECTRICAL STANDARDS IN FORCE CONCERNING PROTECTIVE
GROUNDING OF ALL EQUIPMENT.
CAUTION
THE SPECIFIED MINIMUM PE CONDUCTOR CROSS-SECTIONS IN THIS MANUAL MUST BE
MAINTAINED. TOUCH CURRENT IN THIS EQUIPMENT EXCEEDS 3.5 MA (AC). THE MINIMUM
SIZE OF THE PROTECTIVE EARTHING CONDUCTOR SHALL COMPLY WITH THE REQUIREMENTS
OF EN 61800-5-1 AND/ OR THE LOCAL SAFETY REGULATIONS.
CAUTION
TOUCH CURRENTS IN THIS FREQUENCY INVERTER ARE GREATER THAN 3.5 MA (AC).
ACCORDING TO PRODUCT STANDARD IEC/EN 61800-5-1, AN ADDITIONAL EQUIPMENT
GROUNDING CONDUCTOR OF THE SAME CROSS-SECTIONAL AREA AS THE ORIGINAL
PROTECTIVE EARTHING CONDUCTOR MUST BE CONNECTED, OR THE CROSS-SECTION OF THE
EQUIPMENT GROUNDING CONDUCTOR MUST BE AT LEAST 10 MM2 CU. DRIVE REQUIRES THAT
ONLY COPPER CONDUCTOR SHOULD BE USED.
CAUTION
DEBOUNCED INPUTS MAY NOT BE USED IN THE SAFETY CIRCUIT DIAGRAM. RESIDUAL
CURRENT CIRCUIT BREAKERS (RCD) ARE ONLY TO BE INSTALLED BETWEEN THE AC POWER
SUPPLY NETWORK AND THE DRIVE.
CAUTION
DEBOUNCED INPUTS MAY NOT BE USED IN THE SAFETY CIRCUIT DIAGRAM. IF YOU ARE
CONNECTING MULTIPLE MOTORS ON ONE DRIVE, YOU MUST DESIGN THE CONTACTORS FOR
THE INDIVIDUAL MOTORS ACCORDING TO UTILIZATION CATEGORY AC-3. SELECTING THE
MOTOR CONTACTOR IS DONE ACCORDING TO THE RATED OPERATIONAL CURRENT OF THE
MOTOR TO BE CONNECTED.
CAUTION
DEBOUNCED INPUTS MAY NOT BE USED IN THE SAFETY CIRCUIT DIAGRAM. A CHANGEOVER
BETWEEN THE DRIVE AND THE INPUT SUPPLY MUST TAKE PLACE IN A VOLTAGE-FREE
STATE.
CAUTION
DEBOUNCED INPUTS MAY NOT BE USED IN THE SAFETY CIRCUIT DIAGRAM. FIRE HAZARD!
ONLY USE CABLES, PROTECTIVE SWITCHES, AND CONTACTORS THAT FEATURE THE
INDICATED PERMISSIBLE NOMINAL CURRENT VALUE.
CAUTION
BEFORE CONNECTING THE DRIVE TO AC MAINS MAKE SURE THAT THE EMC PROTECTION
CLASS SETTINGS OF THE DRIVE ARE APPROPRIATELY MADE ACCORDING TO INSTRUCTIONS
IN THIS MANUAL.
CAUTION
BEFORE CONNECTING THE DRIVE TO AC MAINS MAKE SURE THAT THE EMC PROTECTION
CLASS SETTINGS OF THE DRIVE ARE APPROPRIATELY MADE ACCORDING TO INSTRUCTIONS
IN THIS MANUAL. · IF THE DRIVE IS TO BE USED IN A FLOATING DISTRIBUTION
NETWORK, REMOVE SCREWS AT MOV AND EMC. SEE “INSTALLATION IN CORNER-GROUNDED
NETWORK” ON PAGE 53 AND “INSTALLATION IN IT SYSTEM” ON PAGE 53 RESPECTIVELY ·
DISCONNECT THE INTERNAL EMC FILTER WHEN INSTALLING THE DRIVE ON AN IT SYSTEM
(AN UNGROUNDED POWER SYSTEM OR A HIGH-RESISTANCE-GROUNDED [OVER 30 OHM] POWER
SYSTEM), OTHERWISE THE SYSTEM WILL BE CONNECTED TO GROUND POTENTIAL THROUGH
THE EMC FILTER CAPACITORS. THIS MAY CAUSE DANGER, OR DAMAGE THE DRIVE ·
DISCONNECT THE INTERNAL EMC FILTER WHEN INSTALLING THE DRIVE ON A CORNER
GROUNDED TN SYSTEM, OTHERWISE THE DRIVE WILL BE DAMAGED
xii
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
PowerXL DG1/DH1 Series VFD
NOTICE
WHEN THE INTERNAL EMC FILTER IS DISCONNECTED, THE DRIVE MIGHT BE NOT EMC
COMPATIBLE. · DO NOT ATTEMPT TO INSTALL OR REMOVE THE MOV OR
EMC SCREWS WHILE POWER IS APPLIED TO THE DRIVE’S INPUT TERMINALS
Motor and equipment safety
CAUTION
DO NOT PERFORM ANY MEGGAR OR VOLTAGE WITHSTAND TESTS ON ANY PART OF THE DRIVE
OR ITS COMPONENTS. IMPROPER TESTING MAY RESULT IN DAMAGE.
CAUTION
PRIOR TO ANY TESTS OR MEASUREMENTS OF THE MOTOR OR THE MOTOR CABLE, DISCONNECT
THE MOTOR CABLE AT THE DRIVE OUTPUT TERMINALS (U, V, W) TO AVOID DAMAGING THE
DRIVE DURING MOTOR OR CABLE TESTING.
CAUTION
DO NOT TOUCH ANY COMPONENTS ON THE CIRCUIT BOARDS. STATIC VOLTAGE DISCHARGE
MAY DAMAGE THE COMPONENTS.
CAUTION
BEFORE STARTING THE MOTOR, CHECK THAT THE MOTOR IS MOUNTED PROPERLY AND
ALIGNED WITH THE DRIVEN EQUIPMENT. ENSURE THAT STARTING THE MOTOR WILL NOT
CAUSE PERSONAL INJURY OR DAMAGE EQUIPMENT CONNECTED TO THE MOTOR.
CAUTION
SET THE MAXIMUM MOTOR SPEED (FREQUENCY) IN THE DRIVE ACCORDING TO THE
REQUIREMENTS OF THE MOTOR AND THE EQUIPMENT CONNECTED TO IT. INCORRECT MAXIMUM
FREQUENCY SETTINGS CAN CAUSE MOTOR OR EQUIPMENT DAMAGE AND PERSONAL INJURY.
CAUTION
BEFORE REVERSING THE MOTOR ROTATION DIRECTION, ENSURE THAT THIS WILL NOT CAUSE
PERSONAL INJURY OR EQUIPMENT DAMAGE.
CAUTION
MAKE SURE THAT NO POWER CORRECTION CAPACITORS ARE CONNECTED TO THE DRIVE
OUTPUT OR THE MOTOR TERMINALS TO PREVENT DRIVE MALFUNCTION AND POTENTIAL
DAMAGE.
CAUTION
MAKE SURE THAT THE DRIVE OUTPUT TERMINALS (U, V, W) ARE NOT CONNECTED TO THE
UTILITY LINE POWER AS SEVERE DAMAGE TO THE DRIVE MAY OCCUR.
CAUTION
WHEN THE CONTROL TERMINALS OF TWO OR MORE DRIVE UNITS ARE CONNECTED IN
PARALLEL, THE AUXILIARY VOLTAGE FOR THESE CONTROL CONNECTIONS MUST BE TAKEN
FROM A SINGLE SOURCE WHICH CAN EITHER BE ONE OF THE UNITS OR AN EXTERNAL
SUPPLY.
CAUTION
THE DRIVE WILL START UP AUTOMATICALLY AFTER AN INPUT VOLTAGE INTERRUPTION IF
THE EXTERNAL RUN COMMAND IS ON.
CAUTION
DO NOT CONTROL THE MOTOR WITH THE DISCONNECTING DEVICE (DISCONNECTING MEANS);
INSTEAD, USE THE CONTROL PANEL START AND STOP KEYS AND, OR COMMANDS VIA THE
I/O BOARD OF THE DRIVE. THE MAXIMUM ALLOWED NUMBER OF CHARGING CYCLES OF THE
DC CAPACITORS (I.E. POWER-UPS BY APPLYING POWER) IS FIVE IN TEN MINUTES.
CAUTION
IMPROPER DRIVE OPERATION: · IF THE DRIVE IS NOT TURNED ON FOR A LONG PERIOD,
THE
PERFORMANCE OF ITS ELECTROLYTIC CAPACITORS WILL BE REDUCED · IF IT IS STOPPED
FOR A PROLONGED PERIOD, TURN THE DRIVE ON AT LEAST EVERY SIX MONTHS FOR AT
LEAST 5 HOURS TO RESTORE THE PERFORMANCE OF THE CAPACITORS, AND THEN CHECK ITS
OPERATION. IT IS RECOMMENDED THAT THE DRIVE IS NOT CONNECTED DIRECTLY TO THE
LINE VOLTAGE. THE VOLTAGE SHOULD BE INCREASED GRADUALLY USING AN ADJUSTABLE AC
SOURCE FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN INJURY AND/OR
EQUIPMENT DAMAGE.
For more technical information, contact the factory or your local sales
representative..
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
xiii
PowerXL DG1/DH1 Series VFD
Sécurité
AVERTISSEMENT
TENSION ÉLECTRIQUE DANGEREUSE !
Avant de commencer l’installation
· Débrancher l’alimentation de l’appareil
· S’assurer que les dispositifs ne peuvent pas être accidentellement
redémarrés
· Vérifier l’isolement de l’alimentation
· Mettre l’appareil à la terre et le protéger contre les courts-circuits
· Couvrir ou enfermer tout composant sous tension adjacent
· Seul le personnel qualifié conformément à la norme EN 50110-1/-2 (VDE 0105
Partie 100) peut travailler sur cet appareil/ce système
· Avant l’installation et avant de toucher l’appareil, s’assurer de ne porter
aucune charge électrostatique
· La terre fonctionnelle (FE, PSE) doit être raccordée à la terre de
protection (PE) ou la compensation de potentiel. L’installateur du système a
la responsabilité d’assurer cette connexion
· Les câbles de connexion et les lignes de signal doivent être installés de
façon à ce que les interférences capacitives ou inductives ne compromettent
pas les fonctions d’automatisation
· Installer les appareils d’automatisation et les éléments de fonctionnement
associés de manière à ce qu’ils soient bien protégés contre tout
fonctionnement accidentel
· Des dispositifs de sécurité matériels et logiciels appropriés doivent être
utilisés en rapport avec l’interface des E/S afin qu’un circuit ouvert sur le
côté signal ne résulte pas en états indéfinis dans les dispositifs
d’automatisation
· Assurer une isolation électrique fiable sur le côté tension extra basse de
l’alimentation 24 V. Utiliser uniquement des blocs d’alimentation conformes à
la norme CEI 60364-4-41 (VDE 0100, partie 410) ou HD384.4.41 S2
· Les écarts entre la tension d’entrée et la tension nominale ne doivent pas
dépasser les limites de tolérance indiquées dans les spécifications, au risque
de provoquer un mauvais fonctionnement et une utilisation dangereuse du
système
· Les dispositifs d’arrêt d’urgence conformes à la norme CEI/EN 60204-1
doivent être efficace dans tous les modes de fonctionnement des dispositifs
d’automatisation. Le déverrouillage des dispositifs d’arrêt d’urgence ne doit
pas entraîner un redémarrage
· Les dispositifs conçus pour un montage dans des boîtiers ou armoires de
commande ne doivent être utilisés et contrôlés qu’après avoir été installés et
avec le boîtier fermé. Les unités de bureau ou portatives ne doivent être
utilisées et contrôlées que dans leurs boîtiers fermés
· Des mesures doivent être prises pour assurer un bon redémarrage des
programmes interrompus après une chute ou une panne de tension. Ceci ne doit
pas causer des états de fonctionnement dangereux, même pour un court laps de
temps. Si nécessaire, des dispositifs d’arrêt d’urgence doivent être utilisés
· Quand des défaillances du système d’automatisation peuvent entraîner des
blessures ou des dommages matériels, des mesures externes doivent être
appliquées pour assurer un état de fonctionnement sans danger en cas de panne
ou de mauvais fonctionnement (par exemple au moyen de disjoncteurs séparés, de
verrouillages mécaniques, etc.)
· En fonction de leur degré de protection, les entraînements à fréquence
variable peuvent contenir des pièces métalliques sous tension, des composants
rotatifs ou en mouvement et des surfaces brûlantes, pendant le fonctionnement
et immédiatement après l’arrêt
· Le retrait des protections requises, une installation incorrecte ou un
mauvais fonctionnement du moteur ou de l’entraînement à fréquence variable
peuvent causer la défaillance de l’appareil et entraîner des blessures graves
et des dommages importants
· La réglementation nationale applicable en matière de sécurité et de
prévention des accidents s’applique à tous les travaux effectués sur les
entraînements à fréquence variable sous tension
· L’installation électrique doit être effectuée conformément aux
réglementations applicables (par exemple, en ce qui concerne les sections
transversales des câbles, les fusibles, la mise à la terre de protection)
· Le transport, l’installation, la mise en service et les travaux de
maintenance doivent être effectués uniquement par un personnel qualifié (IEC
60364, HD 384 et règles de sécurité du travail)
· Les installations contenant des entraînements à fréquence variable doivent
être équipées de dispositifs de surveillance et de protection, conformément
aux réglementations applicables en matière de sécurité. Les modifications des
entraînements à fréquence variable réalisées à l’aide du logiciel
d’exploitation sont autorisées
· Toutes les protections et les portes doivent être maintenues fermées pendant
le fonctionnement
xiv
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
PowerXL DG1/DH1 Series VFD
· Pour réduire les risques d’accidents et de dommages matériels, l’utilisateur
doit inclure dans la conception de la machine des mesures limitant les
conséquences de panne ou de mauvais fonctionnement de l’entraînement
(augmentation de la vitesse ou arrêt soudain du moteur). Ces mesures
comprennent:
· Autres dispositifs indépendants de surveillance des variables en rapport
avec la sécurité (vitesse, voyages, positions d’extrémité, etc.)
· Mesures électriques ou non électriques appliquées à l’ensemble du système
(verrouillages électriques ou mécaniques)
· Ne jamais toucher les pièces sous tension ni les connexions des câbles de
l’entraînement à fréquence variable après leur déconnexion de l’alimentation.
En raison de la charge dans les condensateurs, ces pièces peuvent être encore
sous tension après la déconnexion. Installer les panneaux d’avertissement
appropriés.
Lire ce manuel en entier et s’assurer de bien comprendre les procédures avant
de tenter d’installer, de configurer, d’utiliser et d’effectuer tout travail
d’entretien sur cet entraînement à fréquence variable PowerXL.
Définitions et symboles
AVERTISSEMENT
(CE SYMBOLE INDIQUE UNE HAUTE TENSION. IL ATTIRE L’ATTENTION SUR LES ÉLÉMENTS
OU LES OPÉRATIONS QUI POURRAIENT ÊTRE DANGEREUX POUR LES PERSONNES UTILISANT
CET ÉQUIPEMENT. LIRE ATTENTIVEMENT LE MESSAGE ET SUIVRE ATTENTIVEMENT LES
INSTRUCTIONS.
Haute tension dangereuse
AVERTISSEMENT
L’ÉQUIPEMENT DE CONTRÔLE DU MOTEUR ET LES CONTRÔLEURS ÉLECTRONIQUES SONT
BRANCHÉS SUR DES TENSIONS SECTEUR DANGEREUSES. LORS DE L’ENTRETIEN DES
ENTRAÎNEMENTS ET DES CONTRÔLEURS ÉLECTRONIQUES, IL PEUT Y AVOIR DES COMPOSANTS
EXPOSÉS AVEC DES BOÎTIERS OU DES PROTUBÉRANCES AU NIVEAU DU POTENTIEL DU
RÉSEAU OU AU-DESSUS. TOUTES LES PRÉCAUTIONS DOIVENT ÊTRE PRISES POUR SE
PROTÉGER CONTRE LES CHOCS ÉLECTRIQUES. · SE TENIR SUR UN TAPIS ISOLANT ET
PRENDRE
L’HABITUDE DE N’UTILISER QU’UNE SEULE MAIN POUR VÉRIFIER LES COMPOSANTS ·
TOUJOURS TRAVAILLER AVEC UNE AUTRE PERSONNE LORSQU’UNE SITUATION D’URGENCE SE
PRODUIT · DÉBRANCHER L’ALIMENTATION AVANT DE VÉRIFIER LES CONTRÔLEURS OU
D’EFFECTUER DES TRAVAUX D’ENTRETIEN · S’ASSURER QUE L’ÉQUIPEMENT EST
CORRECTEMENT RELIÉ À LA TERRE · PORTER DES LUNETTES DE SÉCURITÉ LORS DES
TRAVAUX SUR LES CONTRÔLEURS ÉLECTRONIQUES OU LES MACHINES ROTATIVES
AVERTISSEMENT
LES COMPOSANTS DE LA SECTION D’ALIMENTATION DE L’ENTRAÎNEMENT RESTENT SOUS
TENSION APRÈS LA COUPURE DE LA TENSION D’ALIMENTATION. APRÈS LA DÉCONNEXION DE
L’ALIMENTATION, ATTENDRE AU MOINS CINQ MINUTES AVANT DE RETIRER LE COUVERCLE
POUR PERMETTRE LA DÉCHARGE DES CONDENSATEURS DU CIRCUIT INTERMÉDIAIRE. PRÊTER
ATTENTION AUX AVERTISSEMENTS SIGNALANT DES DANGERS !
CE SYMBOLE EST LE « SYMBOLE D’ALERTE DE SÉCURITÉ ». IL ACCOMPAGNE LES DEUX
TERMES D’AVERTISSEMENT SUIVANTS : MISE EN GARDE OU AVERTISSEMENT, COMME DÉCRIT
CI-DESSOUS.
AVERTISSEMENT
INDIQUE UNE SITUATION POTENTIELLEMENT DANGEREUSE QUI, SI ELLE N’EST PAS
ÉVITÉE, PEUT ENTRAÎNER DES BLESSURES GRAVES OU LA MORT.
MISE EN GARDE
INDIQUE UNE SITUATION POTENTIELLEMENT DANGEREUSE QUI, SI ELLE N’EST PAS
ÉVITÉE, PEUT ENTRAÎNER DES BLESSURES LÉGÈRES À MODÉRÉES ET D’IMPORTANTS DÉGÂTS
MATÉRIELS. LA SITUATION DÉCRITE DANS LA MISE EN GARDE PEUT, SI ELLE N’EST PAS
ÉVITÉE, ENTRAÎNER DES CONSÉQUENCES GRAVES. DES MESURES DE SÉCURITÉ IMPORTANTES
SONT DÉCRITES DANS LES MISES EN GARDE (AINSI QUE DANS LES AVERTISSEMENTS).
DANGER 5 MIN
AVERTISSEMENT
RISQUE DE CHOC ÉLECTRIQUE – RISQUE DE BLESSURES ! EFFECTUER LE CÂBLAGE
UNIQUEMENT SI L’UNITÉ N’EST PLUS SOUS TENSION.
AVERTISSEMENT
NE PAS EFFECTUER DE MODIFICATIONS SUR L’ENTRAÎNEMENT CA LORSQU’IL EST CONNECTÉ
À L’ALIMENTATION SECTEUR.
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
xv
PowerXL DG1/DH1 Series VFD
Avertissements et mises en garde
AVERTISSEMENT
S’ASSURER DE METTRE L’APPAREIL À LA TERRE EN SUIVANT LES INSTRUCTIONS DE CE
MANUEL. LES UNITÉS NON MISES À LA TERRE PEUVENT CAUSER DES CHOCS ÉLECTRIQUES
ET DES INCENDIES.
AVERTISSEMENT
CET ÉQUIPEMENT NE DOIT ÊTRE INSTALLÉ, RÉGLÉ ET ENTRETENU QUE PAR UN PERSONNEL
D’ENTRETIEN ÉLECTRIQUE QUALIFIÉ CONNAISSANT LA CONSTRUCTION ET LE
FONCTIONNEMENT DE CE TYPE D’ÉQUIPEMENT, AINSI QUE LES RISQUES ENCOURUS. LE
NON-RESPECT DE CETTE PRÉCAUTION PEUT ENTRAÎNER LA MORT OU DES BLESSURES
GRAVES.
AVERTISSEMENT
LES COMPOSANTS À L’INTÉRIEUR DE L’ENTRAÎNEMENT SONT SOUS TENSION LORSQUE
L’ENTRAÎNEMENT EST BRANCHÉ À L’ALIMENTATION. LE CONTACT AVEC CETTE TENSION EST
EXTRÊMEMENT DANGEREUX ET PEUT CAUSER LA MORT OU DES BLESSURES GRAVES.
AVERTISSEMENT
LES BORNES DE PHASE (L1, L2, L3), LES BORNES DU MOTEUR (U, V, W) ET LES BORNES
DE RÉSISTANCE DE LIAISON CC/FREIN (DC-, DC+ /R+, R-) SONT SOUS TENSION LORSQUE
L’ENTRAÎNEMENT EST BRANCHÉ À L’ALIMENTATION, MÊME SI LE MOTEUR NE TOURNE PAS.
LE CONTACT AVEC CETTE TENSION EST EXTRÊMEMENT DANGEREUX ET PEUT CAUSER LA MORT
OU DES BLESSURES GRAVES.
AVERTISSEMENT
MÊME SI LES BORNES E/S DE COMMANDE SONT ISOLÉES DE LA TENSION SECTEUR, LES
SORTIES DE RELAIS ET LES AUTRES BORNES E/S PEUVENT PRÉSENTER UNE TENSION
DANGEREUSE MÊME LORSQUE L’ENTRAÎNEMENT EST DÉBRANCHÉ. LE CONTACT AVEC CETTE
TENSION EST EXTRÊMEMENT DANGEREUX ET PEUT CAUSER LA MORT OU DES BLESSURES
GRAVES.
AVERTISSEMENT
CET ÉQUIPEMENT A UN GRAND COURANT DE FUITE CAPACITIF PENDANT LE
FONCTIONNEMENT, CE QUI PEUT METTRE LES PIÈCES DU BOÎTIER À UN NIVEAU SUPÉRIEUR
AU POTENTIEL DE TERRE. UNE MISE À LA TERRE APPROPRIÉE, TELLE QUE DÉCRITE DANS
CE MANUEL, EST NÉCESSAIRE. LE NON-RESPECT DE CETTE PRÉCAUTION PEUT ENTRAÎNER
LA MORT OU DES BLESSURES GRAVES.
AVERTISSEMENT
AVANT DE METTRE L’ENTRAÎNEMENT SOUS TENSION, S’ASSURER QUE LES PROTECTIONS
AVANT ET DES CÂBLES SONT FERMÉES ET ATTACHÉES POUR EMPÊCHER L’EXPOSITION À
D’ÉVENTUELLES DÉFAILLANCES ÉLECTRIQUES. LE NON-RESPECT DE CETTE PRÉCAUTION
PEUT ENTRAÎNER LA MORT OU DES BLESSURES GRAVES.
AVERTISSEMENT
UN DISPOSITIF DE PROTECTION/DÉCONNEXION EN AMONT DOIT ÊTRE FOURNI, TEL QUE
REQUIS PAR LE CODE ÉLECTRIQUE NATIONAL (NECT). LE NON-RESPECT DE CETTE
PRÉCAUTION PEUT ENTRAÎNER LA MORT OU DES BLESSURES GRAVES.
AVERTISSEMENT
CET ENTRAÎNEMENT PEUT CAUSER UN COURANT CC DANS LE CONDUCTEUR DE MISE À LA
TERRE DE PROTECTION. LORSQU’UN DISPOSITIF DE PROTECTION OU DE SURVEILLANCE À
COURANT RÉSIDUEL EST UTILISÉ POUR LA PROTECTION EN CAS DE CONTACT DIRECT OU
INDIRECT, SEUL UN DISPOSITIF DE TYPE B EST AUTORISÉ SUR LE CÔTÉ ALIMENTATION
DE CE PRODUIT.
AVERTISSEMENT
NE TRAVAILLER SUR LE CÂBLAGE QU’APRÈS QUE L’ENTRAÎNEMENT A ÉTÉ CORRECTEMENT
MONTÉ ET ATTACHÉ.
AVERTISSEMENT
AVANT D’OUVRIR LES COUVERCLES DE L’ENTRAÎNEMENT : · DÉBRANCHER TOUTE
L’ALIMENTATION ALLANT À
L’ENTRAÎNEMENT, Y COMPRIS L’ALIMENTATION DE COMMANDE EXTERNE POUVANT ÊTRE
PRÉSENTE · ATTENDRE UN MINIMUM DE CINQ MINUTES APRÈS L’EXTINCTION DE TOUS LES
VOYANTS DU CLAVIER. CELA PERMET AUX CONDENSATEURS DE BUS CC DE SE DÉCHARGER ·
UNE TENSION DANGEREUSE PEUT RESTER DANS LES CONDENSATEURS DE BUS CC MÊME SI
L’ALIMENTATION A ÉTÉ COUPÉE. CONFIRMER QUE LES CONDENSATEURS SONT ENTIÈREMENT
DÉCHARGÉS EN MESURANT LA TENSION À L’AIDE D’UN MULTIMÈTRE RÉGLÉ POUR MESURER
LA TENSION CC LE NON-RESPECT DE CETTE PRÉCAUTION PEUT ENTRAÎNER LA MORT OU DES
BLESSURES GRAVES.
AVERTISSEMENT
L’OUVERTURE DU DISPOSITIF DE PROTECTION DU CIRCUIT DE DÉRIVATION PEUT INDIQUER
QUE LE COURANT DE DÉFAUT A ÉTÉ INTERROMPU. POUR RÉDUIRE LE RISQUE D’INCENDIE
OU DE CHOC ÉLECTRIQUE, LES PIÈCES PORTEUSES DE COURANT ET LES AUTRES
COMPOSANTS DU CONTRÔLEUR DOIVENT ÊTRE EXAMINÉS ET REMPLACÉS S’ILS SONT
ENDOMMAGÉS. SI L’ÉLÉMENT DE COURANT D’UN RELAIS DE SURCHARGE A GRILLÉ, LE
RELAIS DE SURCHARGE DOIT ÊTRE INTÉGRALEMENT REMPLACÉ.
AVERTISSEMENT
LE FONCTIONNEMENT DE CET ÉQUIPEMENT NÉCESSITE LE RESPECT DES INSTRUCTIONS
D’INSTALLATION ET DE FONCTIONNEMENT DÉTAILLÉES FOURNIES DANS LE MANUEL
D’INSTALLATION/DE FONCTIONNEMENT DESTINÉ À ÊTRE UTILISÉ AVEC CE PRODUIT. CE
SUPPORT DOIT ÊTRE CONSERVÉ AVEC CET APPAREIL À TOUT MOMENT.
xvi
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
PowerXL DG1/DH1 Series VFD
AVERTISSEMENT
AVANT DE PROCÉDER À L’ENTRETIEN DE L’ENTRAÎNEMENT : · DÉBRANCHER TOUTE
L’ALIMENTATION ALLANT À
L’ENTRAÎNEMENT, Y COMPRIS L’ALIMENTATION DE COMMANDE EXTERNE POUVANT ÊTRE
PRÉSENTE · PLACER UNE ÉTIQUETTE « NE PAS UTILISER » SUR LE DISPOSITIF DE
DÉCONNEXION · VERROUILLER LE DISPOSITIF DE DÉCONNEXION EN POSITION OUVERTE LE
NON-RESPECT DE CES INSTRUCTIONS PEUT ENTRAÎNER LA MORT OU DES BLESSURES
GRAVES.
AVERTISSEMENT
LES SORTIES DE L’ENTRAÎNEMENT (U, V, W) NE DOIVENT PAS ÊTRE CONNECTÉES À LA
TENSION D’ENTRÉE NI À L’ALIMENTATION SECTEUR, CAR CECI POURRAIT GRAVEMENT
ENDOMMAGER L’APPAREIL ET CAUSER UN INCENDIE.
AVERTISSEMENT
LE DISSIPATEUR DE CHALEUR ET/OU LE BOÎTIER EXTERNE PEUVENT ATTEINDRE UNE
TEMPÉRATURE ÉLEVÉE. PRÊTER ATTENTION AUX AVERTISSEMENTS SIGNALANT DES DANGERS
!
SURFACE BRÛLANTE – RISQUE DE BRÛLURE. NE PAS TOUCHER !!
MISE EN GARDE
TOUTE MODIFICATION ÉLECTRIQUE OU MÉCANIQUE DE CET ENTRAÎNEMENT SANS
CONSENTEMENT ÉCRIT PRÉALABLE ANNULE TOUTES LES GARANTIES, PEUT ENTRAÎNER UN
DANGER POUR LA SÉCURITÉ ET ANNULER L’HOMOLOGATION UL®.
MISE EN GARDE
INSTALLER CET ENTRAÎNEMENT SUR UNE MATIÈRE RÉSISTANTE AUX FLAMMES, TELLE
QU’UNE PLAQUE D’ACIER, POUR RÉDUIRE LES RISQUES D’INCENDIE.
MISE EN GARDE
INSTALLER CET ENTRAÎNEMENT SUR UNE SURFACE PERPENDICULAIRE CAPABLE DE
SUPPORTER LE POIDS DE L’ENTRAÎNEMENT ET NON SOUMISE À DES VIBRATIONS AFIN DE
DIMINUER LES RISQUES DE CHUTE ET DE DOMMAGE DE L’ENTRAÎNEMENT, AINSI QUE LES
RISQUES DE BLESSURES.
MISE EN GARDE
EMPÊCHER LA PÉNÉTRATION DE CORPS ÉTRANGERS, TELS QUE MORCEAUX DE FILS ET
COPEAUX MÉTALLIQUES, DANS LE BOÎTIER DE L’ENTRAÎNEMENT, CAR CECI POURRAIT
PROVOQUER LA FORMATION D’UN ARC ÉLECTRIQUE ET UN INCENDIE.
MISE EN GARDE
INSTALLER CET ENTRAÎNEMENT DANS UNE PIÈCE BIEN AÉRÉE NON SOUMISE À DES
TEMPÉRATURES EXTRÊMES, À UNE FORTE HUMIDITÉ OU À LA CONDENSATION. ÉVITER LES
ENDROITS DIRECTEMENT EXPOSÉS AU SOLEIL OU PRÉSENTANT DE FORTES CONCENTRATIONS
DE POUSSIÈRES, DES GAZ CORROSIFS, DES GAZ EXPLOSIFS, DES GAZ INFLAMMABLES, OU
DES VAPEURS DE LIQUIDE DE MEULAGE, ETC. UNE INSTALLATION INADÉQUATE PEUT
ENTRAÎNER UN RISQUE D’INCENDIE.
MISE EN GARDE
LORS DE LA SÉLECTION DE LA SECTION TRANSVERSALE DES CÂBLES, PRENDRE EN COMPTE
LA CHUTE DE TENSION DANS DES CONDITIONS DE CHARGE. LA PRISE EN COMPTE D’AUTRES
PARAMÈTRES RELÈVE DE LA RESPONSABILITÉ DE L’UTILISATEUR. IL RELÈVE DE LA
RESPONSABILITÉ DE L’UTILISATEUR DE RESPECTER TOUTES LES NORMES ÉLECTRIQUES
NATIONALES ET INTERNATIONALES EN VIGUEUR CONCERNANT LA MISE À LA TERRE DE
PROTECTION DE L’ENSEMBLE DE L’ÉQUIPEMENT.
MISE EN GARDE
LES SPÉCIFICATIONS MINIMUM RELATIVES AUX SECTIONS TRANSVERSALES DES
CONDUCTEURS DE TERRE DE PROTECTION INDIQUÉES DANS CE MANUEL DOIVENT ÊTRE
RESPECTÉES. LE COURANT DE FUITE DE CET ÉQUIPEMENT DÉPASSE 3,5 MA (CA). LA
TAILLE MINIMUM DU CONDUCTEUR DE LA MISE À LA TERRE DE PROTECTION DOIT ÊTRE
CONFORME AUX EXIGENCES DE LA NORME EN 61800-5-1 ET/OU AUX RÉGLEMENTATIONS DE
SÉCURITÉ LOCALES.
MISE EN GARDE
LES COURANTS DE FUITE DE CE CONVERTISSEUR DE FRÉQUENCE SONT SUPÉRIEURES À 3,5
MA (CA). CONFORMÉMENT À LA NORME CEI/EN 61800-5-1, UN CONDUCTEUR DE MISE À LA
TERRE DE L’ÉQUIPEMENT SUPPLÉMENTAIRE POSSÉDANT LA MÊME SUPERFICIE DE COUPE
TRANSVERSALE QUE LE CONDUCTEUR DE MISE À LA TERRE DE PROTECTION D’ORIGINE DOIT
ÊTRE BRANCHÉ, OU LA SECTION TRANSVERSALE DU CONDUCTEUR DE MISE À LA TERRE DE
L’ÉQUIPEMENT DOIT ÊTRE D’AU MOINS 10 MM2 CU. SEUL UN CONDUCTEUR EN CUIVRE DOIT
ÊTRE UTILISÉ AVEC CET ENTRAÎNEMENT.
MISE EN GARDE
LES ENTRÉES ANTI-REBOND NE SONT PAS PERMISES DANS LE SCHÉMA DU CIRCUIT DE
SÉCURITÉ. DES DISJONCTEURS DE COURANT RÉSIDUEL (RCD) NE PEUVENT ÊTRE INSTALLÉS
QU’ENTRE LE RÉSEAU DE COURANT ALTERNATIF ET L’ENTRAÎNEMENT.
MISE EN GARDE
LES ENTRÉES ANTI-REBOND NE SONT PAS PERMISES DANS LE SCHÉMA DU CIRCUIT DE
SÉCURITÉ. DES DISJONCTEURS DE COURANT RÉSIDUEL (RCD) NE PEUVENT ÊTRE INSTALLÉS
QU’ENTRE LE RÉSEAU DE COURANT ALTERNATIF ET L’ENTRAÎNEMENT.
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
xvii
PowerXL DG1/DH1 Series VFD
MISE EN GARDE
LES ENTRÉES ANTI-REBOND NE SONT PAS PERMISES DANS LE SCHÉMA DU CIRCUIT DE
SÉCURITÉ. SI PLUSIEURS MOTEURS SONT CONNECTÉS À UN ENTRAÎNEMENT, DES
CONTACTEURS DOIVENT ÊTRE CONÇUS POUR LES MOTEURS INDIVIDUELS CONFORMÉMENT À LA
CATÉGORIE D’UTILISATION AC-3. SÉLECTIONNER DU CONTACTEUR DU MOTEUR EN FONCTION
DU COURANT DE FONCTIONNEMENT NOMINAL DU MOTEUR À CONNECTER.
MISE EN GARDE
LES ENTRÉES ANTI-REBOND NE SONT PAS PERMISES DANS LE SCHÉMA DU CIRCUIT DE
SÉCURITÉ. UNE COMMUTATION ENTRE L’ENTRAÎNEMENT ET L’ALIMENTATION D’ENTRÉE DOIT
AVOIR LIEU DANS UN ÉTAT SANS TENSION.
MISE EN GARDE
LES ENTRÉES ANTI-REBOND NE SONT PAS PERMISES DANS LE SCHÉMA DU CIRCUIT DE
SÉCURITÉ. RISQUE D’INCENDIE ! UTILISER UNIQUEMENT DES CÂBLES, DES
INTERRUPTEURS DE PROTECTION ET DES CONTACTEURS INDIQUANT LE COURANT NOMINAL
PERMIS.
MISE EN GARDE
AVANT DE CONNECTER L’ENTRAÎNEMENT À L’ALIMENTATION SECTEUR CA, S’ASSURER QUE
LES RÉGLAGES DE LA CLASSE DE PROTECTION CEM SONT CORRECTEMENT EFFECTUÉS SELON
LES INSTRUCTIONS DE CE MANUEL. · SI L’ENTRAÎNEMENT DOIT ÊTRE UTILISÉ DANS UN
RÉSEAU DE
DISTRIBUTION FLOTTANT, RETIRER LES VIS AU NIVEAU DES VOM ET CEM. VOIR «
INSTALLATION DANS UN RÉSEAU À UNE PHASE CONNECTÉE À LA TERRE (CORNER-GROUNDED)
» À LA PAGE 53 ET « INSTALLATION DANS UN RÉSEAU IT » À LA PAGE 53
RESPECTIVEMENT · DÉBRANCHER LE FILTRE CEM INTERNE LORS DE L’INSTALLATION DE
L’ENTRAÎNEMENT SUR UN RÉSEAU IT (SYSTÈME D’ALIMENTATION NON MIS À LA TERRE OU
SYSTÈME D’ALIMENTATION ÉLECTRIQUE MIS À LA TERRE HAUTE RÉSISTANCE [PLUS DE 30
OHMS]) POUR NE PAS QUE LE SYSTÈME SOIT CONNECTÉ AU POTENTIEL DE TERRE VIA LES
CONDENSATEURS DU FILTRE CEM. CECI PEUT ÊTRE UNE CAUSE DE DANGERS OU ENDOMMAGER
L’ENTRAÎNEMENT · DÉBRANCHER LE FILTRE CEM INTERNE LORS DE L’INSTALLATION DE
L’ENTRAÎNEMENT SUR UN SYSTÈME TN À UNE PHASE CONNECTÉE À LA TERRE POUR NE PAS
ENDOMMAGER L’ENTRAÎNEMENT REMARQUE: LORSQUE LE FILTRE CEM INTERNE EST
DÉBRANCHÉ, L’ENTRAÎNEMENT PEUT NE PAS ÊTRE CONFORME AUX NORMES DE
COMPATIBILITÉ ÉLECTROMAGNÉTIQUE. · NE PAS TENTER D’INSTALLER OU DE RETIRER LES
VIS DES VOM ET CEM LORSQUE L’ALIMENTATION EST APPLIQUÉE AUX BORNES D’ENTRÉE DE
L’ENTRAÎNEMENT.
Sécurité du moteur et de l’équipement
MISE EN GARDE
N’EFFECTUER AUCUN TEST DE RÉSISTANCE DE TENSION OU AU MÉGOHMMÈTRE SUR TOUTE
PARTIE DE L’ENTRAÎNEMENT OU DE SES COMPOSANTS. UN TEST INADÉQUAT PEUT
ENTRAÎNER DES DOMMAGES.
MISE EN GARDE
AVANT TOUT TEST OU MESURE DU MOTEUR OU DU CÂBLE DU MOTEUR, DÉBRANCHER LE CÂBLE
DU MOTEUR AU NIVEAU DES BORNES DE SORTIE DE L’ENTRAÎNEMENT (U, V, W) POUR
ÉVITER D’ENDOMMAGER CE DERNIER LORS DES TESTS.
MISE EN GARDE
NE TOUCHER AUCUN COMPOSANT SUR LES CARTES DE CIRCUIT. LES DÉCHARGES
D’ÉLECTRICITÉ STATIQUE PEUVENT ENDOMMAGER LES COMPOSANTS.
MISE EN GARDE
AVANT DE METTRE LE MOTEUR EN MARCHE, VÉRIFIER QU’IL EST CORRECTEMENT MONTÉ ET
ALIGNÉ AVEC L’ÉQUIPEMENT ENTRAÎNÉ. S’ASSURER QUE LE DÉMARRAGE DU MOTEUR NE
RISQUE PAS DE PROVOQUER DES BLESSURES OU D’ENDOMMAGER L’ÉQUIPEMENT CONNECTÉ AU
MOTEUR.
MISE EN GARDE
RÉGLER LA VITESSE MAXIMALE DU MOTEUR (FRÉQUENCE) DANS L’ENTRAÎNEMENT
CONFORMÉMENT AUX EXIGENCES DU MOTEUR ET DE L’ÉQUIPEMENT QUI LUI EST CONNECTÉ.
DES RÉGLAGES DE FRÉQUENCE MAXIMUM INCORRECTS PEUVENT ENDOMMAGER LE MOTEUR OU
L’ÉQUIPEMENT ET CAUSER DES BLESSURES.
MISE EN GARDE
AVANT D’INVERSER LE SENS DE ROTATION DU MOTEUR, VEILLER À CE QUE CELA NE
RISQUE PAS DE PROVOQUER DES BLESSURES OU DES DOMMAGES MATÉRIELS.
MISE EN GARDE
S’ASSURER QU’AUCUN CONDENSATEUR DE CORRECTION DE PUISSANCE N’EST CONNECTÉ À LA
SORTIE DE L’ENTRAÎNEMENT OU AUX BORNES DU MOTEUR POUR ÉVITER UN MAUVAIS
FONCTIONNEMENT DE L’ENTRAÎNEMENT ET DES DOMMAGES POTENTIELS.
MISE EN GARDE
S’ASSURER QUE LES BORNES DE SORTIE DE L’ENTRAÎNEMENT (U, V, W) NE SONT PAS
CONNECTÉES À L’ALIMENTATION SECTEUR, CE QUI POURRAIT CAUSER DE GRAVES DOMMAGES
À L’ENTRAÎNEMENT.
xviii
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
MISE EN GARDE
LORSQUE LES BORNES DE COMMANDE DE DEUX OU PLUSIEURS UNITÉS D’ENTRAÎNEMENT SONT
RACCORDÉES EN PARALLÈLE, LA TENSION AUXILIAIRE DE CES CONNEXIONS DE COMMANDE
DOIT ÊTRE FOURNIE PAR UNE SOURCE UNIQUE, QUI PEUT ÊTRE SOIT L’UNE DES UNITÉS,
SOIT UNE ALIMENTATION EXTERNE.
MISE EN GARDE
L’ENTRAÎNEMENT DÉMARRE AUTOMATIQUEMENT APRÈS UNE INTERRUPTION DE LA TENSION
D’ENTRÉE SI LA COMMANDE DE DÉMARRAGE EXTERNE EST ACTIVE.
MISE EN GARDE
NE PAS COMMANDER LE MOTEUR AVEC LE DISPOSITIF DE DÉCONNEXION ; À LA PLACE,
UTILISER LES TOUCHES DE MARCHE ET D’ARRÊT DU TABLEAU DE CONTRÔLE OU LES
COMMANDES DU TABLEAU DES E/S DE L’ENTRAÎNEMENT. LE NOMBRE DE CYCLES DE CHARGE
MAXIMUM PERMIS DES CONDENSATEURS CC (C’EST-À-DIRE LES MISES SOUS TENSION PAR
APPLICATION DE PUISSANCE) EST DE CINQ EN DIX MINUTES.
MISE EN GARDE
FONCTIONNEMENT INCORRECT DE L’ENTRAÎNEMENT : · SI L’ENTRAÎNEMENT N’EST PAS MIS
EN MARCHE PENDANT
UNE LONGUE PÉRIODE, LA PERFORMANCE DE SES CONDENSATEURS ÉLECTROLYTIQUES SERA
RÉDUITE · S’IL EST ARRÊTÉ POUR UNE PÉRIODE PROLONGÉE, LE METTRE EN MARCHE AU
MOINS TOUS LES SIX MOIS PENDANT AU MOINS 5 HEURES POUR RESTAURER LA
PERFORMANCE DES CONDENSATEURS, PUIS VÉRIFIER SON FONCTIONNEMENT. IL EST
RECOMMANDÉ DE NE PAS BRANCHER L’ENTRAÎNEMENT DIRECTEMENT SUR LA TENSION
SECTEUR. LA TENSION DOIT ÊTRE AUGMENTÉE PROGRESSIVEMENT EN UTILISANT UNE
SOURCE CA RÉGLABLE LE NON-RESPECT DE CES INSTRUCTIONS PEUT ENTRAÎNER DES
BLESSURES OU DES DÉGÂTS MATÉRIELS.
Pour plus d’informations techniques, contacter l’usine ou le représentant
commercial local.
PowerXL DG1/DH1 Series VFD
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
xix
PowerXL DG1/DH1 Series VFD
xx
POWERXL DG1/DH1 SERIES VFD MN040002EN–June 2022 www.eaton.com
Chapter 1–PowerXL Series overview
Chapter 1–PowerXL Series overview
This chapter describes the purpose and contents of this manual, the receiving
inspection recommendations and the PowerXL Series Open Drive catalog numbering
system.
How to use this manual
The purpose of this manual is to provide you with information necessary to
install, set and customize parameters, start up, troubleshoot and maintain the
PowerXL Series Variable Frequency Drive (VFD). To provide for safe
installation and operation of the equipment, read the safety guidelines at the
beginning of this manual and follow the procedures outlined in the following
chapters before connecting power to the PowerXL Series VFD. Keep this
operating manual handy and distribute to all users, technicians and
maintenance personnel for reference.
Receiving and inspection
The PowerXL Series VFD has met a stringent series of factory quality
requirements before shipment. It is possible that packaging or equipment
damage may have occurred during shipment. After receiving your PowerXL Series
VFD, please check for the following:
Check to make sure that the package includes the Instruction Leaflet, Quick
Start Guide and accessory packet. The accessory packet includes:
· Rubber grommets
· Control cable grounding clamps
· Additional grounding screw
Inspect the unit to ensure it was not damaged during shipment.
Make sure that the part number indicated on the nameplate corresponds with the
catalog number on your order.
If shipping damage has occurred, please contact and file a claim with the
carrier involved immediately.
If the delivery does not correspond to your order, please contact your
representative.
Note: Do not destroy the packing. The template printed on the protective
cardboard can be used for marking the mounting points of the PowerXL VFD on
the wall or in a cabinet.
Real time clock battery activation
To activate the real time clock (RTC) functionality in the PowerXL Series VFD,
the RTC battery (already mounted in the drive) must be connected to the
control board.
Simply remove the primary drive cover, locate the RTC battery directly below
the keypad, and connect the white 2-wire connector to the receptacle on the
control board. Battery should be replaced after connected 3 or 4 years to keep
it working
Figure 1. RTC battery connection
Table 1. Common abbreviations
Abbreviation
CT
VT IH IL VFD
RTC
Definition
Constant torque with high overload rating (150%) Variable torque with low
overload rating (110%) High overload current (150%) Low overload current
(110%) Variable Frequency Drive Real Time Clock
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
1
Chapter 1–PowerXL Series overview
Rating label
Figure 2. Rating label–DG1
Contents: EAN number
Contents: NAED number
Powering BusinessWorldwide
Cat. No.: DG1-343D3FB-C54C
Style No.:9702-1104-XXP
Article No.:9702-1104-XXP
PowerXLTM DG1 VFD Factory ID: I
CT/VT
Input
Output
1.1KW/ U (V~) 380-440 3Ø 0~Vin 3Ø
1.5KW F (Hz) 50/60 Hz
0-400 Hz
I (A) 3.1/4
3.3/4.3
1.5HP/ U (V~) 440-500 3Ø 0~Vin 3Ø
2HP F (Hz) 50/60 Hz
0-400 Hz
I (A) 2.8/3.2
3/3.4
Enclosure Rating TYPE 1 / IP 21
IE Class IE2 90/100 loss 2.0% Details http://eaton.com/EcoDesign-VFD
User installation manual:MN040002EN Serial No.: XXXXXXXXXX
EAN: 4015081710782 NAED: 786685887760
Contents: EcoDesign website link
Contents: Serial No Style No, Cat. No, date
Carton labels (U.S. and Europe)
Figure 4. Carton label–DG1
Powering BusinessWorldwide
Cat. No.: DG1-343D3FB-C54C
Style No.:9702-1104-XXP
Article No.:9702-1104-XXP
PowerXLTM DG1 VFD Factory ID: I
CT/VT 1.1KW/ 1.5KW
1.5HP/ 2HP
U (V~) F (Hz) I (A) U (V~) F (Hz) I (A)
Input 380-440 3Ø 50/60 Hz 3.1/4 440-500 3Ø 50/60 Hz 2.8/3.2
Enclosure Rating IE Class IE2
TYPE 1 / IP 21
90/100 loss 2.0%
Details
http://eaton.com/EcoDesign-VFD
Output 0~Vin 3Ø 0-400 Hz 3.3/4.3 0~Vin 3Ø 0-400 Hz 3/3.4
Contents: EAN number
Contents: NAED number
User installation manual:MN040002EN Serial No.: XXXXXXXXXX
EAN: 4015081710782 NAED: 786685887760
Contents: EcoDesign website link
Contents: Serial No, Style No, Cat. No, date
Field installed conductors must be copper rated at 75°C
XXXXXX
www.eaton.com Made in China
Data code
Figure 3. Rating label–DH1
Contents: NAED number
Powering BusinessWorldwide
Cat. No.: DH1-343D3FN-C21C
Style No.:9712-1001-XX
Article No.:9712-1001-XX
PowerXLTM DH1 VFD Factory ID: I
VT
Input
Output
U (V~) 380-440 3Ø 0~Vin 3Ø
1.1KW F (Hz) 50/60 Hz
0-400 Hz
I (A) 3.1
3.3
U (V~) 440-500 3Ø 0~Vin 3Ø
1.5HP F (Hz) 50/60 Hz
0-400 Hz
I (A) 2.8
3
Enclosure Rating TYPE 1 / IP 21
IE Class IE2 90/100 loss 2.2% Details http://eaton.com/EcoDesign-VFD
User installation manual:MN040002EN Serial No.: XXXXXXXXXX
NAED: 786689047641
Contents: EcoDesign website link
Contents: Serial No, Style No, Cat. No, date
N.W.: XX.XX KG G.W.: XX.XX KG
XXXXXX
www.eaton.com Made in China
Data code
Figure 5. Carton label–DH1
Powering BusinessWorldwide
Cat. No.: DH1-343D3FN-C21C
Style No.:9712-1001-XX
Article No.:9712-1001-XX
PowerXLTM DH1 VFD Factory ID: I
VT
Input
U (V~)
380-440 3Ø
1.1KW
F (Hz)
50/60 Hz
I (A)
3.1
U (V~)
440-500 3Ø
1.5HP
F (Hz)
50/60 Hz
I (A)
2.8
Enclosure Rating
TYPE 1 / IP 21
IE Class IE2
90/100 loss 2.2%
Details
http://eaton.com/EcoDesign-VFD
Output 0~Vin 3Ø 0-400 Hz 3.3 0~Vin 3Ø 0-400 Hz 3
Contents: NAED number
User installation manual:MN040002EN Serial No.: XXXXXXXXXX
NAED: 786689047641
Contents: EcoDesign website link
Contents: Serial No Style No, Cat. No, date
Field installed conductors must be copper rated at 75°C
XXXXXX
www.eaton.com Made in China
Data code
N.W.: XX.XX KG G.W.: XX.XX KG
XXXXXX
www.eaton.com Made in China
Data code
2
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 1–PowerXL Series overview
Catalog number system
Catalog number system is for illustrative purposes only and not to be used to
create new catalog numbers.
Figure 6. Catalog numbering system
D G1 3 4 011 N N C 21 C
Basic naming D = Drive
Series G1 = General purpose H1 = HVAC
Phase reference 3 = 3~ INPUT/3~ OUTPUT
Input/output voltage rating 2 = 230 V (208240 V, 15%, +10%) 4 = 400 V
(380500 V, 15%, +10%) 5 = 600 V (525600 V, 15%, +10%)
DG1–Output current rating (CT)
208240 V
380500 V
525600 V
3D7 = 3.7 A, 0.55 kW, 0.75 hp 4D8 = 4.8 A, 0.75 kW, 1 hp 6D6 = 6.6 A, 1.1 kW, 1.5 hp 7D8 = 7.8 A, 1.5 kW, 2 hp 011 = 11 A, 2.2 kW, 3 hp 012 = 12.5 A, 3 kW, 5 hp (VT) 017 = 17.5 A, 3.7 kW, 5 hp 025 = 25 A, 5.5 kW, 7.5 hp 031 = 31 A, 7.5 kW, 10 hp 048 = 48 A, 11 kW, 15 hp 061 = 61 A, 15 kW, 20 hp 075 = 75 A, 18.5 kW, 25 hp 088 = 88 A, 22 kW, 30 hp 114 = 114 A, 30 kW, 40 hp 143 = 143 A, 37 kW, 50 hp 170 = 170 A, 45 kW, 60 hp 211 = 211 A, 55 kW, 75 hp 248 = 248 A, 75 kW, 100 hp
2D2 = 2.2 A, 0.75 kW, 1 hp 3D3 = 3.3 A, 1.1 kW, 1.5 hp 4D3 = 4.3 A, 1.5 kW, 2 hp 5D6 = 5.6 A, 2.2 kW, 3 hp 7D6 = 7.6 A, 3 kW, 5 hp 9D0 = 9 A, 4 kW, 7.5 hp (VT) 012 = 12 A, 5.5 kW, 7.5 hp 016 = 16 A, 7.5 kW, 10 hp 023 = 23 A, 11 kW, 15 hp 031 = 31 A, 15 kW, 20 hp 038 = 38 A, 18.5 kW, 25 hp 046 = 46 A, 22 kW, 30 hp 061 = 61 A, 30 kW, 40 hp 072 = 72 A, 37 kW, 50 hp 087 = 87 A, 45 kW, 60 hp 105 = 105 A, 55 kW, 75 hp 140 = 140 A, 75 kW, 100 hp 170 = 170 A, 90 kW, 125 hp 205 = 205 A, 110 kW, 150 hp 245 = 245 A, 132 kW, 200 hp
3D3 = 3.3 A, 1.5 kW, 2 hp 4D5 = 4.5 A, 2.2 kW, 3 hp 7D5 = 7.5 A, 3.7 kW, 5 hp 010 = 10 A, 5.5 kW, 7.5 hp 013 = 13.5 A, 7.5 kW, 10 hp 018 = 18 A, 11 kW, 15 hp 022 = 22 A, 15 kW, 20 hp 027 = 27 A, 18.5 kW, 25 hp 034 = 34 A, 22 kW, 30 hp 041 = 41 A, 30 kW, 40 hp 052 = 52 A, 37 kW, 50 hp 062 = 62 A, 45 kW, 60 hp 080 = 80 A, 55 kW, 75 hp 100 = 100 A, 75 kW, 100 hp 125 = 125 A, 90 kW, 125 hp 144 = 144 A, 110 kW, 150 hp 208 = 208 A, 132 kW, 200 hp
Internal brake chopper N = No brake chopper B = Brake chopper
Internal EMC filter D = DC choke only E = EMC filter only F = Internal EMC
filter and DC choke N = No EMC filter, no DC choke
208240 V
4D8 = 4.8 A, 1.0 hp, 0.75 kW 6D6 = 6.6 A, 1.5 hp, 1.1 kW 7D8 = 7.8 A, 2.0 hp,
1.5 kW 011 = 11 A, 3.0 hp, 2.2 kW 012 = 12.5 A, hp, 3.0 kW 017 = 17.5 A, 5.0
hp, 3.7 kW 025 = 25 A, 7.5 hp, 5.5 kW 031 = 31 A, 10 hp, 7.5 kW 048 = 48 A, 15
hp, 11 kW 061 = 61 A, 20 hp, 15 kW 075 = 75 A, 25 hp, 18.5 kW 088 = 88 A, 30
hp, 22 kW 114 = 114 A, 40 hp, 30 kW 143 = 143 A, 50 hp, 37 kW 170 = 170 A, 60
hp, 45 kW 211 = 211 A, 75 hp, 55 kW 261 = 261 A, 100 hp, 75 kW 312 = 312 A,
125 hp, 90 kW
DH1–Output current rating (VT)
380500 V
525600 V
3D3 = 3.3 A, 1.5 hp, 1.1 kW 4D3 = 4.3 A, 2.0 hp, 1.5 kW 5D6 = 5.6, 3.0 hp, 2.2 kW 7D6 = 7.6 A, 5.0 hp, 3 kW 9D0 = 9 A, 7.5 hp, 4 kW 012 = 12 A, 7.5 hp, 5.5 kW 016 = 16 A, 10 hp, 7.5 kW 023 = 23 A, 15 hp, 11 kW 031 = 31 A, 20 hp, 15 kW 038 = 38 A, 25 hp, 18.5 kW 046 = 46 A, 30 hp, 22 kW 061 = 61 A, 40 hp, 30 kW 072 = 72 A, 50 hp, 37 kW 087 = 87 A, 60 hp, 45 kW 105 = 105 A, 75 hp, 55 kW 140 = 140 A, 100 hp, 75 kW 170 = 170 A, 125 hp, 90 kW 205 = 205 A, 150 hp, 110 kW 261 = 261 A, 200 hp, 132 kW 310 = 310 A, 250 hp, 160 kW
4D5 = 4.5 A, 3 hp, 2.2 kW 7D5 = 7.5 A, 5.0 hp, 3.7 kW 010 = 10 A, 7.5 hp, 5.5 kW 013 = 13.5 A, 10 hp, 7.5 kW 018 = 18 A, 15 hp, 11 kW 022 = 22 A, 20 hp, 15 kW 027 = 27 A, 25 hp, 18.5 kW 034 = 34 A, 30 hp, 22 kW 041 = 41 A, 40 hp, 30 kW 052 = 52 A, 50 hp, 37 kW 062 = 62 A, 60 hp, 45 kW 080 = 80 A, 75 hp, 55 kW 100 = 100 A, 100 hp, 75 kW 125 = 125 A, 125 hp, 90 kW 144 = 144 A, 150 hp, 110 kW 208 = 208 A, 200 hp, 132 kW 250 = 250 A, 250 hp, 160 kW
IP00 FR7 and FR8 is not available for 230 V input product or with the PowerXL DH1 product.
Coating of boards C = Coated
Enclosure (IP rating) 00 = IP00/Open Type 20 = IP20/Open Type 21 = IP21/Type 1
54 = IP54/Type 12
Display option C = LCD (graphical) N = No display
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
3
Chapter 1–PowerXL Series overview
Power ratings and product selection
PowerXL Series drives–FR0, 208240 Volt
Table 2. Open Type IP20
Constant torque (CT)/high overload (IH)
Frame 230 V, 50 Hz 230 V, 60 Hz Current
size kW rating
hp
A
FR0 0.55
0.75
3.7
0.75
1
4.8
1.1
1.5
6.6
Variable torque (VT)/low overload (IL)
230 V, 50 Hz 230 V, 60 Hz Current
kW rating
hp
A
0.75
1
4.8
1.1
1.5
6.6
1.5
2
7.8
DG1 Catalog number
DG1-323D7EB-C20C DG1-324D8EB-C20C DG1-326D6EB-C20C
DH1 Catalog number
DH1-324D8EB-C20C DH1-326D6EB-C20C DH1-327D8EB-C20C
PowerXL Series drives–FR1FR6, 208240 Volt
Table 3. Type 1/IP21
Constant torque (CT)/high overload (IH)
Frame 230 V, 50 Hz 230 V, 60 Hz Current
size kW rating
hp
A
FR1 0.55
0.75
3.7
0.75
1
4.8
1.1
1.5
6.6
1.5
2
7.8
2.2
3
11
FR2 3
12.5
3.7
5
17.5
5.5
7.5
25
FR3 7.5
10
31
11
15
48
FR4 15
20
61
18.5
25
75
22
30
88
FR5 30
40
114
37
50
143
45
60
170
FR6 55
75
211
75
100
248
Variable torque (VT)/low overload (IL)
230 V, 50 Hz 230 V, 60 Hz Current
kW rating
hp
A
0.75
1
4.8
1.1
1.5
6.6
1.5
2
7.8
2.2
3
11
3
12.5
3.7
5
17.5
5.5
7.5
25
7.5
10
31
11
15
48
15
20
61
18.5
25
75
22
30
88
30
40
114
37
50
143
45
60
170
55
75
211
75
100
261
90
125
312
DG1 Catalog number
DG1-323D7FB-C21C DG1-324D8FB-C21C DG1-326D6FB-C21C DG1-327D8FB-C21C DG1
-32011FB-C21C DG1-32012FB-C21C DG1-32017FB-C21C DG1-32025FB-C21C DG1-32031FB-
C21C DG1-32048FB-C21C DG1-32061FN-C21C DG1-32075FN-C21C DG1-32088FN-C21C DG1
-32114FN-C21C DG1-32143FN-C21C DG1-32170FN-C21C DG1-32211FN-C21C DG1-32248FN-
C21C
DH1 Catalog number
DH1-324D8DN-C21C DH1-326D6DN-C21C DH1-327D8DN-C21C DH1-32011DN-C21C DH1
-32012DN-C21C DH1-32017DN-C21C DH1-32025DN-C21C DH1-32031DN-C21C DH1-32048DN-
C21C DH1-32061DN-C21C DH1-32075DN-C21C DH1-32088DN-C21C DH1-32114DN-C21C DH1
-32143DN-C21C DH1-32170DN-C21C DH1-32211DN-C21C DH1-32261DN-C21C DH1-32312DN-
C21C
4
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 1–PowerXL Series overview
Table 4. Type 12/IP54
Constant torque (CT)/high overload (IH)
Frame 230 V, 50 Hz 230 V, 60 Hz Current
size kW rating
hp
A
FR1 0.55
0.75
3.7
0.75
1
4.8
1.1
1.5
6.6
1.5
2
7.8
2.2
3
11
FR2 3
12.5
3.7
5
17.5
5.5
7.5
25
FR3 7.5
10
31
11
15
48
FR4 15
20
61
18.5
25
75
22
30
88
FR5 30
40
114
37
50
143
45
60
170
FR6 55
75
211
75
100
248
Variable torque (VT)/low overload (IL)
230 V, 50 Hz 230 V, 60 Hz Current
kW rating
hp
A
0.75
1
4.8
1.1
1.5
6.6
1.5
2
7.8
2.2
3
11
3
12.5
3.7
5
17.5
5.5
7.5
25
7.5
10
31
11
15
48
15
20
61
18.5
25
75
22
30
88
30
40
114
37
50
143
45
60
170
55
75
211
75
100
261
90
125
312
DG1 Catalog number
DG1-323D7FB-C54C DG1-324D8FB-C54C DG1-326D6FB-C54C DG1-327D8FB-C54C DG1
-32011FB-C54C DG1-32012FB-C54C DG1-32017FB-C54C DG1-32025FB-C54C DG1-32031FB-
C54C DG1-32048FB-C54C DG1-32061FN-C54C DG1-32075FN-C54C DG1-32088FN-C54C DG1
-32114FN-C54C DG1-32143FN-C54C DG1-32170FN-C54C DG1-32211FN-C54C DG1-32248FN-
C54C
DH1 Catalog number
DH1-324D8DN-C54C DH1-326D6DN-C54C DH1-327D8DN-C54C DH1-32011DN-C54C DH1
-32012DN-C54C DH1-32017DN-C54C DH1-32025DN-C54C DH1-32031DN-C54C DH1-32048DN-
C54C DH1-32061DN-C54C DH1-32075DN-C54C DH1-32088DN-C54C DH1-32114DN-C54C DH1
-32143DN-C54C DH1-32170DN-C54C DH1-32211DN-C54C DH1-32261DN-C54C DH1-32312DN-
C54C
PowerXL Series drives–FR0, 380500 Volt
Table 5. Open Type IP20
Frame size
FR0
380-440 Volts 50Hz kW rating
CT output CT kW VT kW current
0.75
1.1
2.2
1.1
1.5
3.3
1.5
2.2
4.3
2.2
3
5.6
VT output current
3.3 4.3 5.6 7.6
440500 Volt 60Hz HP rating
CT HP
VT HP
CT output VT output current current Catalog
1
1.5
2.1
3
DG1-342D2EB-C20C
1.5
2
3
3.4
DG1-343D3EB-C20C
2
3
3.4
4.8
DG1-344D3EB-C20C
3
5
4.8
7.6
DG1-345D6EB-C20C
Catalog
DH1-343D3EB-C20C DH1-344D3EB-C20C DH1-345D6EB-C20C DH1-347D6EB-C20C
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
5
Chapter 1–PowerXL Series overview
PowerXL Series drives–FR1FR6, 380500 Volt
Table 6. Type 1/IP21
Frame size
FR1
FR2 FR3 FR4 FR5 FR6
380-440 Volts 50Hz kW rating
CT output VT output CT kW VT kW current current
0.75
1.1
2.2
3.3
1.1
1.5
3.3
4.3
1.5
2.2
4.3
5.6
2.2
3
5.6
7.6
3
4
7.6
9
4
5.5
9
12
5.5
7.5
12
16
7.5
11
16
23
11
15
23
31
15
18.5
31
38
18.5
22
38
46
22
30
46
61
30
37
61
72
37
45
72
87
45
55
87
105
55
75
105
140
75
90
140
170
90
110
170
205
110
132
205
261
132
160
245
310
440500 Volt 60Hz HP rating
CT HP
VT HP
CT output current
1
1.5
2.1
1.5
2
3
2
3
3.4
3
5
4.8
5
–
7.6
–
7.5
–
7.5
10
11
10
15
14
15
20
21
20
25
27
25
30
34
30
40
40
40
50
52
50
60
65
60
75
77
75
100
96
100
125
124
125
150
156
150
200
180
200
250
240
VT output current
3 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156 180 240 302
Catalog
DG1-342D2FB–C21C DG1-343D3FB–C21C DG1-344D3FB-C21C DG1-345D6FB-C21C DG1
-347D6FB-C21C DG1-349D0FB-C21C DG1-34012FB-C21C DG1-34016FB-C21C DG1-34023FB-
C21C DG1-34031FB-C21C DG1-34038FB-C21C DG1-34046FB-C21C DG1-34061FB-C21C DG1
-34072FB-C21C DG1-34087FB-C21C DG1-34105FB-C21C DG1-34140FB-C21C DG1-34170FB-
C21C DG1-34205FB-C21C DG1-34245FB-C21C
Catalog
DH1-343D3DN–C21C DH1-344D3DN-C21C DH1-345D6DN-C21C DH1-347D6DN-C21C DH1
-349D0DN-C21C DH1-34012DN-C21C DH1-34016DN-C21C DH1-34023DN-C21C DH1-34031DN-
C21C DH1-34038DN-C21C DH1-34046DN-C21C DH1-34061DN-C21C DH1-34072DN-C21C DH1
-34087DN-C21C DH1-34105DN-C21C DH1-34140DN-C21C DH1-34170DN-C21C DH1-34205DN-
C21C DH1-34261FN-C21C DH1-34310FN-C21C
Table 7. Type 12/IP54
Frame size
FR1
FR2 FR3 FR4 FR5 FR6
380-440 Volts 50Hz kW rating
CT output CT kW VT kW current
0.75
1.1
2.2
1.1
1.5
3.3
1.5
2.2
4.3
2.2
3
5.6
3
4
7.6
4
5.5
9
5.5
7.5
12
7.5
11
16
11
15
23
15
18.5
31
18.5
22
38
22
30
46
30
37
61
37
45
72
45
55
87
55
75
105
75
90
140
90
110
170
110
132
205
132
160
245
VT output current
3.3 4.3 5.6 7.6 9 12 16 23 31 38 46 61 72 87 105 140 170 205 261 310
440500 Volt 60Hz HP rating
CT output VT output CT HP VT HP current current
1
1.5
2.1
3
1.5
2
3
3.4
2
3
3.4
4.8
3
5
4.8
7.6
5
–
7.6
–
–
7.5
–
11
7.5
10
11
14
10
15
14
21
15
20
21
27
20
25
27
34
25
30
34
40
30
40
40
52
40
50
52
65
50
60
65
77
60
75
77
96
75
100
96
124
100
125
124
156
125
150
156
180
150
200
180
240
200
250
240
302
Catalog
DG1-342D2FB-C54C DG1-343D3FB-C54C DG1-344D3FB-C54C DG1-345D6FB-C54C DG1
-347D6FB-C54C DG1-349D0FB-C54C DG1-34012FB-C54C DG1-34016FB-C54C DG1-34023FB-
C54C DG1-34031FB-C54C DG1-34038FB-C54C DG1-34046FB-C54C DG1-34061FB-C54C DG1
-34072FB-C54C DG1-34087FB-C54C DG1-34105FB-C54C DG1-34140FB-C54C DG1-34170FB-
C54C DG1-34205FB-C54C DG1-34245FB-C54C
Catalog
DH1-343D3DN–C54C DH1-344D3DN-C54C DH1-345D6DN-C54C DH1-347D6DN-C54C DH1
-349D0DN-C54C DH1-34012DN-C54C DH1-34016DN-C54C DH1-34023DN-C54C DH1-34031DN-
C54C DH1-34038DN-C54C DH1-34046DN-C54C DH1-34061DN-C54C DH1-34072DN-C54C DH1
-34087DN-C54C DH1-34105DN-C54C DH1-34140DN-C54C DH1-34170DN-C54C DH1-34205DN-
C54C DH1-34261FN-C54C DH1-34310FN-C54C
6
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 1–PowerXL Series overview
PowerXL Series drives–FR1FR6, 600 Volt
Table 8. Type 1/IP21
Constant torque (CT)/high overload (IH)
Frame 600 V, 50 Hz 600 V, 60 Hz Current
size kW rating
hp
A
FR1 1.5
2
3.3
2.2
3
4.5
3.7
5
7.5
FR2 5.5
7.5
10
7.5
10
13.5
11
15
18
FR3 15
20
22
18.5
25
27
22
30
34
FR4 30
40
41
37
50
52
45
60
62
FR5 55
75
80
75
100
100
90
125
125
FR6 110
150
144
132
200
208
Variable torque (VT)/low overload (IL)
600 V, 50 Hz 600 V, 60 Hz Current
kW rating
hp
A
2.2
3
4.5
3.7
5
7.5
5.5
7.5
10
7.5
10
13.5
11
15
18
15
20
22
18.5
25
27
22
30
34
30
40
41
37
50
52
45
60
62
55
75
80
75
100
100
90
125
125
110
150
144
132
200
208
160
250
250
DG1 Catalog number
DG1-353D3FB-C21C DG1-354D5FB-C21C DG1-357D5FB-C21C DG1-35010FB-C21C DG1
-35013FB-C21C DG1-35018FB-C21C DG1-35022FB-C21C DG1-35027FB-C21C DG1-35034FB-
C21C DG1-35041FN-C21C DG1-35052FN-C21C DG1-35062FN-C21C DG1-35080FN-C21C DG1
-35100FN-C21C DG1-35125FN-C21C DG1-35144FN-C21C DG1-35208FN-C21C
DH1 Catalog number
DH1-354D5DN-C21C DH1-357D5DN-C21C DH1-35010DN-C21C DH1-35013DN-C21C DH1
-35018DN-C21C DH1-35022DN-C21C DH1-35027DN-C21C DH1-35034DN-C21C DH1-35041DN-
C21C DH1-35052DN-C21C DH1-35062DN-C21C DH1-35080DN-C21C DH1-35100DN-C21C DH1
-35125DN-C21C DH1-35144DN-C21C DH1-35208DN-C21C DH1-35250DN-C21C
Table 9. Type 12/IP54
Constant torque (CT)/high overload (IH)
Frame 600 V, 50 Hz 600 V, 60 Hz Current
size kW rating
hp
A
FR1 1.5
2
3.3
2.2
3
4.5
3.7
5
7.5
FR2 5.5
7.5
10
7.5
10
13.5
11
15
18
FR3 15
20
22
18.5
25
27
22
30
34
FR4 30
40
41
37
50
52
45
60
62
FR5 55
75
80
75
100
100
90
125
125
FR6 110
150
144
132
200
208
Variable torque (VT)/low overload (IL)
600 V, 50 Hz 600 V, 60 Hz Current
kW rating
hp
A
2.2
3
4.5
3.7
5
7.5
5.5
7.5
10
7.5
10
13.5
11
15
18
15
20
22
18.5
25
27
22
30
34
30
40
41
37
50
52
45
60
62
55
75
80
75
100
100
90
125
125
110
150
144
132
200
208
160
250
250
DG1 Catalog number
DG1-353D3FB-C54C DG1-354D5FB-C54C DG1-357D5FB-C54C DG1-35010FB-C54C DG1
-35013FB-C54C DG1-35018FB-C54C DG1-35022FB-C54C DG1-35027FB-C54C DG1-35034FB-
C54C DG1-35041FN-C54C DG1-35052FN-C54C DG1-35062FN-C54C DG1-35080FN-C54C DG1
-35100FN-C54C DG1-35125FN-C54C DG1-35144FN-C54C DG1-35208FN-C54C
DH1 Catalog number
DH1-354D5DN-C54C DH1-357D5DN-C54C DH1-35010DN-C54C DH1-35013DN-C54C DH1
-35018DN-C54C DH1-35022DN-C54C DH1-35027DN-C54C DH1-35034DN-C54C DH1-35041DN-
C54C DH1-35052DN-C54C DH1-35062DN-C54C DH1-35080DN-C54C DH1-35100DN-C54C DH1
-35125DN-C54C DH1-35144DN-C54C DH1-35208DN-C54C DH1-35250DN-C54C
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
7
Chapter 1–PowerXL Series overview
DG1 replacement parts
Table 10. Frame 0
Description
Standard keypad Control module kit with keypad Control module kit without
keypad Software kit (software, cable, manual) Main power board Fan kit IGBT
module EMC kit
DG1 DG1 DG1 DG1 FR0 FR0 IGBT EMC
Catalog number
Catalog number
Catalog number
230 V
480 V
600 V
DXG-KEY-LCD
DXG-KEY-LCD
—
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
—
DXG-SPR-CTRLBOARD
DXG-SPR-CTRLBOARD
—
DXG-ACC-SOFTWARE
DXG-ACC-SOFTWARE
—
DXG-SPR-2FR0MPB-xxx DXG-SPR-4FR0MPB-xxx —
DXG-SPR-FR0FAN
DXG-SPR-FR0FAN
—
DXG-SPR-2FR0IGBT
DXG-SPR-4FR0IGBT
—
DXG-SPR-FR0EMCKIT
DXG-SPR-FR0EMCKIT
—
Table 11. Frame 1
Description
Standard keypad
DG1
Catalog number 230 V
DXG-KEY-LCD
Catalog number 480 V
DXG-KEY-LCD
Catalog number 600 V
DXG-KEY-LCD
Control module kit with keypad
DG1
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
Control module kit without keypad DG1
DXG-SPR-CTRLBOARD DXG-SPR-CTRLBOARD DXG-SPR-CTRLBOARD
Software kit (software, cable, manual) DG1 DXG-ACC-SOFTWARE
DXG-ACC-SOFTWARE
DXG-ACC-SOFTWARE
Type 1/IP21 standard cover
Type1/IP21
DXG-SPR-FR1CVR
DXG-SPR-FR1CVR
DXG-SPR-FR1CVR
EMI board
EMI
DXG-SPR-2FR1EB
DXG-SPR-4FR1EB
DXG-SPR-5FR1EB
Type 12/IP54 kit
Type12/IP54
DXG-ACC-2FR1N12KIT
DXG-ACC-4FR1N12KIT
DXG-ACC-4FR1N12KIT
Main power board Control board cover
FR1
DXG-SPR-2FR1MPB-XXX DXG-SPR-4FR1MPB-XXX DXG-SPR-5FR1MPB-XXX
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
Main fan kit Control fan
DXG-SPR-FR1FAN DXG-SPR-2FR1CF
DXG-SPR-FR1FAN DXG-SPR-4FR1CF
DXG-SPR-FR1FAN DXG-SPR-4FR1CF
Middle chassis cover
DXG-SPR-FR1MCC
DXG-SPR-FR1MCC
DXG-SPR-FR1MCC
Outer housing
DXG-SPR-FR1OH
DXG-SPR-FR1OH
DXG-SPR-5FR1OH
UL conduit plate
DXG-SPR-FR1CPUL
DXG-SPR-FR1CPUL
DXG-SPR-FR1CPUL
IEC conduit plate
DXG-SPR-FR1CPIEC
DXG-SPR-FR1CPIEC
DXG-SPR-FR1CPIEC
Type 12 grommet
DXG-SPR-FR1GRN12
DXG-SPR-FR1GRN12
DXG-SPR-FR1GRN12
Terminal block
DXG-SPR-2FR1TB
DXG-SPR-FR1TB
DXG-SPR-FR1TB
Table 12. Frame 2
Description
Standard Keypad
DG1
Catalog number 230 V
DXG-KEY-LCD
Catalog number 480 V
DXG-KEY-LCD
Catalog number 600 V
DXG-KEY-LCD
Control module kit with keypad
DG1
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
Control module kit without keypad DG1
DXG-SPR-CTRLBOARD
DXG-SPR-CTRLBOARD
DXG-SPR-CTRLBOARD
Software kit (software, cable, manual) DG1 DXG-ACC-SOFTWARE
DXG-ACC-SOFTWARE
DXG-ACC-SOFTWARE
Type 1/IP21 standard cover
Type1/IP21
DXG-SPR-FR2CVR
DXG-SPR-FR2CVR
DXG-SPR-FR2CVR
EMI board
EMI
DXG-SPR-2FR2EB
DXG-SPR-4FR2EB
DXG-SPR-5FR2EB
Type 12/IP54 kit
Type1/IP54
DXG-ACC-FR2N12KIT
DXG-ACC-FR2N12KIT
DXG-ACC-FR2N12KIT
Main power board Control board cover
FR2
DXG-SPR-2FR2MPB-XXX DXG-SPR-4FR2MPB-XXX DXG-SPR-5FR2MPB-XXX
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
Factory recommended spare parts. Output current rating code.
8
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 1–PowerXL Series overview
Table 12. Frame 2, continued
Description
Main fan kit Control fan Bus capacitor IGBT module Middle chassis cover Outer
housing UL conduit plate IEC conduit plate Type 12 grommet Terminal block
Catalog number 230 V
DXG-SPR-FR2FAN DXG-SPR-FR2CF DXG-SPR-2FR2BC DXG-SPR-FR2IGBT DXG-SPR-FR2MCC
DXG-SPR-FR2OH DXG-SPR-FR2CPUL DXG-SPR-FR2CPIEC DXG-SPR-FR2GRN12 DXG-SPR-FR2TB
Catalog number 480 V
DXG-SPR-FR2FAN DXG-SPR-FR2CF DXG-SPR-4FR24BC DXG-SPR-FR2IGBT DXG-SPR-FR2MCC
DXG-SPR-FR2OH DXG-SPR-FR2CPUL DXG-SPR-FR2CPIEC DXG-SPR-FR2GRN12 DXG-SPR-FR2TB
Catalog number 600 V
DXG-SPR-FR2FAN DXG-SPR-FR2CF DXG-SPR-5FR24BC DXG-SPR-5FR2IGBT DXG-SPR-FR2MCC
DXG-SPR-5FR2OH DXG-SPR-FR2CPUL DXG-SPR-FR2CPIEC DXG-SPR-FR2GRN12 DXG-SPR-FR2TB
Table 13. Frame 3
Description
Standard keypad
DG1
Catalog number 230 V
DXG-KEY-LCD
Catalog number 480 V
DXG-KEY-LCD
Catalog number 600 V
DXG-KEY-LCD
Control module kit with keypad
DG1
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
Control module kit without keypad DG1
DXG-SPR-CTRLBOARD DXG-SPR-CTRLBOARD DXG-SPR-CTRLBOARD
Software kit (software, cable, manual) DG1 DXG-ACC-SOFTWARE DXG-ACC-SOFTWARE DXG-ACC-SOFTWARE
Type 1/IP21 standard cover
Type1/IP21
DXG-SPR-FR3CVR
DXG-SPR-FR3CVR
DXG-SPR-FR3CVR
EMI board
EMI
DXG-SPR-2FR3EB
DXG-SPR-4FR3EB
DXG-SPR-5FR3EB
Drive board Main power board
FR3
DXG-SPR-2FR3DB-XXX DXG-SPR-4FR3DB-XXX DXG-SPR-5FR3DB-XXX
DXG-SPR-2FR3MPB
DXG-SPR-4FR3MPB
DXG-SPR-5FR3MPB
Control board cover
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
Main fan kit Main fan
DXG-SPR-FR3FANKIT DXG-SPR-FR3FAN
DXG-SPR-FR3FANKIT DXG-SPR-FR3FAN
DXG-SPR-FR3FANKIT DXG-SPR-FR3FAN
Control fan
DXG-SPR-FR34CF
DXG-SPR-FR34CF
DXG-SPR-FR34CF
Bus capacitor
DXG-SPR-FR3BC
DXG-SPR-FR3BC
DXG-SPR-5FR3BC
Output board
DXG-SPR-FR3OB
DXG-SPR-FR3OB
DXG-SPR-5FR3OB
Middle chassis cover
DXG-SPR-FR3MCC
DXG-SPR-FR3MCC
DXG-SPR-FR3MCC
Outer housing
DXG-SPR-FR3OH
DXG-SPR-FR3OH
DXG-SPR-FR3OH
UL conduit plate
DXG-SPR-FR3CPUL
DXG-SPR-FR3CPUL
DXG-SPR-FR3CPUL
IEC conduit plate
DXG-SPR-FR3CPIEC
DXG-SPR-FR3CPIEC
DXG-SPR-FR3CPIEC
Type 12 grommet
DXG-SPR-FR3GRN12
DXG-SPR-FR3GRN12
DXG-SPR-FR3GRN12
Terminal block
DXG-SPR-FR3TB
DXG-SPR-FR3TB
DXG-SPR-FR3TB
Table 14. Frame 4
Description
Standard keypad Control module kit with keypad Control module kit without
keypad Software kit (software, cable, manual) Type 1/IP21 standard cover EMI
board
DG1 DG1 DG1 DG1 Type1/IP21 EMI
Catalog number 230 V
DXG-KEY-LCD DXG-SPR-CTRLKIT DXG-SPR-CTRLBOARD DXG-ACC-SOFTWARE DXG-SPR-FR4CVR
DXG-SPR-4FR4EB
Catalog number 480 V
DXG-KEY-LCD DXG-SPR-CTRLKIT DXG-SPR-CTRLBOARD DXG-ACC-SOFTWARE DXG-SPR-FR4CVR
DXG-SPR-4FR4EB
Catalog number 600 V
DXG-KEY-LCD DXG-SPR-CTRLKIT DXG-SPR-CTRLBOARD DXG-ACC-SOFTWARE DXG-SPR-FR4CVR
DXG-SPR-5FR4EB
Factory recommended spare parts. Output current rating code.
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
9
Chapter 1–PowerXL Series overview
Table 14. Frame 4, continued
Description
Softstart board Main power board Control board cover Main fan kit Main fan
Control fan Bus capacitor IGBT module Rectifier module Brake chopper module
Middle chassis cover Outer housing UL conduit plate IEC conduit plate Type 12
grommet Terminal block
FR4
Catalog number
Catalog number
Catalog number
230 V
DXG-SPR-2FR4SB
480 V
DXG-SPR-4FR4SB
600 V
DXG-SPR-5FR4SB
DXG-SPR-2FR4MPB-XXX DXG-SPR-4FR4MPB-XXX DXG-SPR-5FR4MPB-XXX
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-FR4FANKIT
DXG-SPR-FR4FANKIT
DXG-SPR-FR4FANKIT
DXG-SPR-FR4FAN
DXG-SPR-FR4FAN
DXG-SPR-FR4FAN
DXG-SPR-FR34CF
DXG-SPR-FR34CF
DXG-SPR-FR34CF
DXG-SPR-2FR4BC
DXG-SPR-4FR24BC
DXG-SPR-5FR24BC
DXG-SPR-2FR4IGBT
DXG-SPR-4FR4IGBT
DXG-SPR-5FR4IGBT
DXG-SPR-2FR4RM
DXG-SPR-4FR4RM
DXG-SPR-5FR4RM
DXG-SPR-2FR4BCM
DXG-SPR-4FR4BCM
DXG-SPR-5FR4BCM
DXG-SPR-FR4MCC
DXG-SPR-FR4MCC
DXG-SPR-FR4MCC
DXG-SPR-FR4OH
DXG-SPR-FR4OH
DXG-SPR-5FR4OH
DXG-SPR-FR4CPUL
DXG-SPR-FR4CPUL
DXG-SPR-FR4CPUL
DXG-SPR-FR4CPIEC
DXG-SPR-FR4CPIEC
DXG-SPR-FR4CPIEC
DXG-SPR-FR4GRN12
DXG-SPR-FR4GRN12
DXG-SPR-FR4GRN12
DXG-SPR-FR4TB
DXG-SPR-FR4TB
DXG-SPR-FR4TB
Table 15. Frame 5
Description
Standard keypad
DG1
Catalog number 230 V
DXG-KEY-LCD
Catalog number 480 V
DXG-KEY-LCD
Catalog number 600 V
DXG-KEY-LCD
Control module kit with keypad DG1
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
Control module kit without keypad DG1
DXG-SPR-CTRLBOARD
DXG-SPR-CTRLBOARD
DXG-SPR-CTRLBOARD
Software kit (software, cable, manual)
Type 1/IP21 standard cover
DG1 DXG-ACC-SOFTWARE
Type1/IP21
DXG-SPR-FR5CVR
DXG-ACC-SOFTWARE DXG-SPR-FR5CVR
DXG-ACC-SOFTWARE DXG-SPR-FR5CVR
EMI-1 board
EMI-1
DXG-SPR-2FR5E1B
DXG-SPR-4FR5E1B
DXG-SPR-5FR5E1B
Main power board Control board cover
FR5
DXG-SPR-2FR5MPB-XXX DXG-SPR-4FR5MPB-XXX DXG-SPR-5FR5MPB-XXX
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
Main fan kit Main fan
DXG-SPR-FR5FANKIT DXG-SPR-FR5FAN
DXG-SPR-FR5FANKIT DXG-SPR-FR5FAN
DXG-SPR-FR5FANKIT DXG-SPR-FR5FAN
Control fan
DXG-SPR-FR5CF
DXG-SPR-FR5CF
DXG-SPR-FR5CF
Bus capacitor
DXG-SPR-FR5BC
DXG-SPR-FR5BC
DXG-SPR-5FR5BC
EMI-2 board
DXG-SPR-2FR5E2B
DXG-SPR-4FR5E2B
DXG-SPR-5FR5E2B
EMI-3 board
DXG-SPR-FR5E3B
DXG-SPR-FR5E3B
N/A
IGBT module
DXG-SPR-FR5IGBT
DXG-SPR-FR5IGBT
DXG-SPR-5FR5IGBT
Rectifier module
DXG-SPR-2FR5RM
DXG-SPR-4FR5RM
DXG-SPR-5FR5RM
Brake chopper module
DXG-SPR-2FR5BCM
DXG-SPR-4FR5BCM
DXG-SPR-5FR5BCM
Middle chassis cover
DXG-SPR-FR5MCC
DXG-SPR-FR5MCC
DXG-SPR-FR5MCC
Outer housing
DXG-SPR-FR5OH
DXG-SPR-FR5OH
DXG-SPR-FR5OH
UL conduit plate
DXG-SPR-FR5CPUL
DXG-SPR-FR5CPUL
DXG-SPR-FR5CPUL
IEC conduit plate
DXG-SPR-FR5IECCP
DXG-SPR-FR5IECCP
DXG-SPR-FR5IECCP
Type 12 grommet
DXG-SPR-FR5GRN12
DXG-SPR-FR5GRN12
DXG-SPR-FR5GRN12
Terminal block (1-pole)
DXG-SPR-FR5TB1P
DXG-SPR-FR5TB1P
DXG-SPR-FR5TB1P
Terminal block (3-pole)
DXG-SPR-FR5TB3P
DXG-SPR-FR5TB3P
DXG-SPR-FR5TB3P
Factory recommended spare parts. Output current rating code.
10
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 1–PowerXL Series overview
Table 16. Frame 6
Catalog number
Catalog number
Catalog number
Description
230 V
480 V
600 V
Standard keypad
DG1
DXG-KEY-LCD
DXG-KEY-LCD
DXG-KEY-LCD
Control module kit with keypad DG1
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
DXG-SPR-CTRLKIT
Control module kit without keypad DG1
DXG-SPR-CTRLBOARD
DXG-SPR-CTRLBOARD
DXG-SPR-CTRLBOARD
Software kit (software, cable, manual)
DG1 DXG-ACC-SOFTWARE
DXG-ACC-SOFTWARE
DXG-ACC-SOFTWARE
Main power board
FR6
DXG-SPR-2FR6MPB-XXX DXG-SPR-4FR6MPB-XXX DXG-SPR-5FR6MPB-XXX
Control board cover
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
Type 1/IP21 standard cover
DXG-SPR-FR6CVR
DXG-SPR-FR6CVR
DXG-SPR-FR6CVR
Main fan kit
DXG-SPR-FR6FANKIT
DXG-SPR-FR6FANKIT
DXG-SPR-FR6FANKIT
Control fan
DXG-SPR-FR6CF
DXG-SPR-FR6CF
DXG-SPR-FR6CF
Bus capacitor
DXG-SPR-FR6BC
DXG-SPR-FR6BC
DXG-SPR-5FR6BC
EMI board
DXG-SPR-FR6EB
DXG-SPR-FR6EB
DXG-SPR-FR6EB
Softstart board
DXG-SPR-2FR6SB
DXG-SPR-4FR6SB
DXG-SPR-5FR6SB
Rectifier snubber board
DXG-SPR-2FR6RSB
DXG-SPR-4FR6RSB
DXG-SPR-5FR6RSB
IGBT module with drive board
DXG-SPR-2FR6IGBT
DXG-SPR-4FR6IGBT
DXG-SPR-5FR6IGBT
Rectifier module
DXG-SPR-FR6RM
DXG-SPR-FR6RM
DXG-SPR-5FR6RM
Middle chassis cover
DXG-SPR-FR6MCC
DXG-SPR-FR6MCC
DXG-SPR-FR6MCC
Outer housing
DXG-SPR-FR6OH
DXG-SPR-FR6OH
DXG-SPR-FR6OH
UL conduit plate
DXG-SPR-FR6CPUL
DXG-SPR-FR6CPUL
DXG-SPR-FR6CPUL
IEC conduit plate
DXG-SPR-FR6CPIEC
DXG-SPR-FR6CPIEC
DXG-SPR-FR6CPIEC
Type 12 grommet
DXG-SPR-FR6GRN12
DXG-SPR-FR6GRN12
DXG-SPR-FR6GRN12
Terminal block (1-pole)
DXG-SPR-FR6TB1P
DXG-SPR-FR6TB1P
DXG-SPR-FR6TB1P
Terminal block (3-pole)
DXG-SPR-FR6TB3P
DXG-SPR-FR6TB3P
DXG-SPR-FR6TB3P
DH1 replacement parts
Table 17. Frame 0
Description
Standard keypad Main control board Control module kit with keypad Main fan kit
Main power board EMI kit for C2 Factory recommended spare parts. Output
current rating code.
Catalog number
Catalog number
Catalog number
230 V
480 V
575 V
DXH-KEY-LCD
DXH-KEY-LCD
—
DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD —
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
—
DXG-SPR-FR0FAN
DXG-SPR-FR0FAN
—
DXG-SPR-2FR0MPB-xxx DXG-SPR-4FR0MPB-xxx —
DXG-SPR-FR0EMCKIT
DXG-SPR-FR0EMCKIT
—
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
11
Chapter 1–PowerXL Series overview
Table 18. Frame 1
Description
Standard keypad Control module kit with keypad Main control board Standard
cover EMI board Type 12/IP54 kit Main power board Control board cover Main fan
kit Control fan Middle chassis cover Outer housing UL conduit plate IEC
conduit plate
Table 19. Frame 2
Description
Standard keypad Control module kit with keypad Main control board Standard
cover EMI board Type 12/IP54 kit Main power board Control board cover Main fan
kit Control fan Bus capacitor Middle chassis cover Outer housing UL conduit
plate IEC conduit plate
Table 20. Frame 3
Description
Standard keypad Control module kit with keypad Main control board Standard
cover EMI board Control board cover Main fan kit
Catalog number 230 V
DXH-KEY-LCD DXH-SPR-CTRLKIT DXH-SPR-CTRLBOARD DXH-SPR-FR1CVR DXG-SPR-2FR1EB
DXH-ACC-2FR1N12KIT DXH-SPR-2FR1MPB DXG-SPR-BCOVER DXG-SPR-FR1FAN
DXG-SPR-FR1MCC DXG-SPR-FR1OH DXG-SPR-FR1CPUL DXG-SPR-FR1CPIEC
Catalog number 480 V
DXH-KEY-LCD DXH-SPR-CTRLKIT DXH-SPR-CTRLBOARD DXH-SPR-FR1CVR DXG-SPR-4FR1EB
DXH-ACC-4FR1N12KIT DXH-SPR-4FR1MPB DXG-SPR-BCOVER DXG-SPR-FR1FAN DXG-SPR-
4FR1CF DXG-SPR-FR1MCC DXG-SPR-FR1OH DXG-SPR-FR1CPUL DXG-SPR-FR1CPIEC
Catalog number 575 V
DXH-KEY-LCD DXH-SPR-CTRLKIT DXH-SPR-CTRLBOARD DXH-SPR-FR1CVR DXG-SPR-5FR1EB
DXH-ACC-5FR1N12KIT DXG-SPR-5FR1MPB DXG-SPR-BCOVER DXG-SPR-FR1FAN DXG-SPR-
4FR1CF DXG-SPR-FR1MCC DXG-SPR-5FR1OH DXG-SPR-FR1CPUL DXG-SPR-FR1CPIEC
Catalog number
Catalog number
Catalog number
230 V
480 V
575 V
DXH-KEY-LCD
DXH-KEY-LCD
DXH-KEY-LCD
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD
DXH-SPR-FR2CVR
DXH-SPR-FR2CVR
DXH-SPR-FR2CVR
DXG-SPR-2FR2EB
DXG-SPR-4FR2EB
DXG-SPR-5FR2EB
DXH-ACC-FR2N12KIT DXH-ACC-FR2N12KIT DXH-ACC-FR2N12KIT
DXH-SPR-2FR2MPB DXH-SPR-4FR2MPB DXG-SPR-5FR2MPB
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-FR2FAN
DXG-SPR-FR2FAN
DXG-SPR-FR2FAN
DXG-SPR-FR2CF
DXG-SPR-FR2CF
DXG-SPR-FR2CF
DXG-SPR-4FR24BC
DXG-SPR-4FR24BC
DXG-SPR-5FR24BC
DXG-SPR-FR2MCC
DXG-SPR-FR2MCC
DXG-SPR-FR2MCC
DXG-SPR-FR2OH
DXG-SPR-FR2OH
DXG-SPR-5FR2OH
DXG-SPR-FR2CPUL DXG-SPR-FR2CPUL DXG-SPR-FR2CPUL
DXG-SPR-FR2CPIEC DXG-SPR-FR2CPIEC DXG-SPR-FR2CPIEC
Catalog number 230 V
DXH-KEY-LCD DXH-SPR-CTRLKIT DXH-SPR-CTRLBOARD DXH-SPR-FR3CVR DXG-SPR-2FR3EB
DXG-SPR-BCOVER DXG-SPR-FR3FANKIT
Catalog number 480 V
DXH-KEY-LCD DXH-SPR-CTRLKIT DXH-SPR-CTRLBOARD DXH-SPR-FR3CVR DXG-SPR-4FR3EB
DXG-SPR-BCOVER DXG-SPR-FR3FANKIT
Catalog number 575 V
DXH-KEY-LCD DXH-SPR-CTRLKIT DXH-SPR-CTRLBOARD DXH-SPR-FR3CVR DXG-SPR-5FR3EB
DXG-SPR-BCOVER DXG-SPR-FR3FANKIT
12
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Table 20. Frame 3, continued
Description
Main fan Control fan Bus capacitor Middle chassis cover Outer housing UL
conduit plate IEC conduit plate Drive board Output board
Table 21. Frame 4
Description
Standard keypad Control module kit with keypad Main control board Standard
cover EMI board Main power board Control board cover Main fan kit Main fan
Control fan Bus capacitor Middle chassis cover Outer housing UL conduit plate
IEC conduit plate Softstart board IGBT Module Rectifier module Brake chopper
module
Table 22. Frame 5
Description
Standard keypad Control module kit with keypad Main control board Standard
cover EMI-1 board EMI-2 board EMI-3 board Main power board Control board cover
Chapter 1–PowerXL Series overview
Catalog number 230 V
DXG-SPR-FR3FAN DXG-SPR-FR34CF DXG-SPR-FR3BC DXG-SPR-FR3MCC DXG-SPR-FR3OH DXG-
SPR-FR3CPUL DXG-SPR-FR3CPIEC DXH-SPR-2FR3DB DXG-SPR-FR3OB
Catalog number 480 V
DXG-SPR-FR3FAN DXG-SPR-FR34CF DXG-SPR-FR3BC DXG-SPR-FR3MCC DXG-SPR-FR3OH DXG-
SPR-FR3CPUL DXG-SPR-FR3CPIEC DXH-SPR-4FR3DB DXG-SPR-FR3OB
Catalog number 575 V
DXG-SPR-FR3FAN DXG-SPR-FR34CF DXG-SPR-5FR3BC DXG-SPR-FR3MCC DXG-SPR-FR3OH DXG-
SPR-FR3CPUL DXG-SPR-FR3CPIEC DXG-SPR-5FR3DB DXG-SPR-5FR3OB
Catalog number
Catalog number
Catalog number
230 V
480 V
575 V
DXH-KEY-LCD
DXH-KEY-LCD
DXH-KEY-LCD
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD
DXH-SPR-FR4CVR
DXH-SPR-FR4CVR
DXH-SPR-FR4CVR
DXG-SPR-2FR4EB
DXG-SPR-4FR4EB
DXG-SPR-5FR4EB
DXH-SPR-2FR4MPB DXH-SPR-4FR4MPB DXG-SPR-5FR4MPB
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-FR4FANKIT DXG-SPR-FR4FANKIT DXG-SPR-FR4FANKIT
DXG-SPR-FR4FAN
DXG-SPR-FR4FAN
DXG-SPR-FR4FAN
DXG-SPR-FR34CF
DXG-SPR-FR34CF
DXG-SPR-FR34CF
DXG-SPR-4FR24BC
DXG-SPR-4FR24BC
DXG-SPR-5FR24BC
DXG-SPR-FR4MCC
DXG-SPR-FR4MCC
DXG-SPR-FR4MCC
DXG-SPR-FR4OH
DXG-SPR-FR4OH
DXG-SPR-5FR4OH
DXG-SPR-FR4CPUL DXG-SPR-FR4CPUL DXG-SPR-FR4CPUL
DXG-SPR-FR4CPIEC DXG-SPR-FR4CPIEC DXG-SPR-FR4CPIEC
DXH-SPR-2FR4SB
DXH-SPR-4FR4SB
DXG-SPR-5FR4SB
DXG-SPR-2FR4IGBT DXG-SPR-4FR4IGBT DXG-SPR-5FR4IGBT
DXG-SPR-2FR4RM
DXG-SPR-4FR4RM
DXG-SPR-5FR4RM
DXG-SPR-2FR4BCM DXG-SPR-4FR4BCM DXG-SPR-5FR4BCM
Catalog number
Catalog number
Catalog number
230 V
480 V
575 V
DXH-KEY-LCD
DXH-KEY-LCD
DXH-KEY-LCD
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD
DXH-SPR-FR5CVR
DXH-SPR-FR5CVR
DXH-SPR-FR5CVR
DXG-SPR-2FR5E1B
DXG-SPR-4FR5E1B
DXG-SPR-5FR5E1B
DXG-SPR-2FR5E2B
DXG-SPR-4FR5E2B
DXG-SPR-5FR5E2B
DXG-SPR-FR5E3B
DXG-SPR-FR5E3B
DXH-SPR-2FR5MPB DXH-SPR-4FR5MPB DXG-SPR-5FR5MPB
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
13
Chapter 1–PowerXL Series overview
Table 22. Frame 5, continued
Description
Main fan kit Main fan Control fan Bus capacitor Middle chassis cover Outer
housing UL conduit plate IEC conduit plate IGBT Module Rectifier module Brake
chopper module DC terminal kit
Table 23. Frame 6
Description
Standard keypad Control module kit with keypad Main control board Standard
cover EMI board Main power board Control board cover Main fan kit Main fan
Control fan Bus capacitor Middle chassis cover Outer housing UL conduit plate
IEC conduit plate IGBT Module Brake chopper module Rectifier module Type 12
grommet kit Softstart board Rectifier snubber board Terminal block kit
(1-pole) Terminal block kit (3-pole)
Catalog number 230 V
DXG-SPR-FR5FANKIT DXG-SPR-FR5FAN DXG-SPR-FR5CF DXG-SPR-FR5BC DXG-SPR-FR5MCC
DXG-SPR-FR5OH DXG-SPR-FR5CPUL DXG-SPR-FR5IECCP DXG-SPR-2FR5IGBT DXG-SPR-FR5RM
DXG-SPR-2FR5BCM DXG-SPR-FR5DCKIT
Catalog number 480 V
DXG-SPR-FR5FANKIT DXG-SPR-FR5FAN DXG-SPR-FR5CF DXG-SPR-FR5BC DXG-SPR-FR5MCC
DXG-SPR-FR5OH DXG-SPR-FR5CPUL DXG-SPR-FR5IECCP DXG-SPR-4FR5IGBT DXG-SPR-FR5RM
DXG-SPR-4FR5BCM DXG-SPR-FR5DCKIT
Catalog number 575 V
DXG-SPR-FR5FANKIT DXG-SPR-FR5FAN DXG-SPR-FR5CF DXG-SPR-5FR5BC DXG-SPR-FR5MCC
DXG-SPR-FR5OH DXG-SPR-FR5CPUL DXG-SPR-FR5IECCP DXG-SPR-5FR5IGBT DXG-SPR-5FR5RM
DXG-SPR-5FR5BCM DXG-SPR-FR5DCKIT
Catalog number
Catalog number
Catalog number
230 V
480 V
575 V
DXH-KEY-LCD
DXH-KEY-LCD
DXH-KEY-LCD
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLKIT
DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD DXH-SPR-CTRLBOARD
DXH-SPR-FR6CVR
DXH-SPR-FR6CVR
DXH-SPR-FR6CVR
DXG-SPR-FR6EB
DXG-SPR-FR6EB
DXG-SPR-FR6EB
DXG-SPR-2FR6MPB DXG-SPR-4FR6MPB DXG-SPR-5FR6MPB
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-BCOVER
DXG-SPR-FR6FANKIT DXG-SPR-FR6FANKIT DXG-SPR-FR6FANKIT
DXG-SPR-FR6FAN
DXG-SPR-FR6FAN
DXG-SPR-FR6FAN
DXG-SPR-FR6CF
DXG-SPR-FR6CF
DXG-SPR-FR6CF
DXG-SPR-FR6BC
DXG-SPR-FR6BC
DXG-SPR-5FR6BC
DXG-SPR-FR6MCC
DXG-SPR-FR6MCC
DXG-SPR-FR6MCC
DXG-SPR-FR6OH
DXG-SPR-FR6OH
DXG-SPR-FR6OH
DXG-SPR-FR6CPUL DXG-SPR-FR6CPUL DXG-SPR-FR6CPUL
DXG-SPR-FR6CPIEC DXG-SPR-FR6CPIEC DXG-SPR-FR6CPIEC
DXG-SPR-2FR6IGBT DXG-SPR-4FR6IGBT DXG-SPR-5FR6IGBT
DXG-SPR-2FR6BCM DXG-SPR-4FR6BCM DXG-SPR-5FR6BCM
DXG-SPR-FR6RM
DXG-SPR-FR6RM
DXG-SPR-5FR6RM
DXG-SPR-FR6GRN12 DXG-SPR-FR6GRN12 DXG-SPR-FR6GRN12
DXG-SPR-2FR6SB
DXG-SPR-4FR6SB
DXG-SPR-5FR6SB
DXG-SPR-2FR6RSB DXG-SPR-4FR6RSB DXG-SPR-5FR6RSB
DXG-SPR-FR6TB1P DXG-SPR-FR6TB1P DXG-SPR-FR6TB1P
DXG-SPR-FR6TB3P DXG-SPR-FR6TB3P DXG-SPR-FR6TB3P
14
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 2–Engineering considerations
Chapter 2–Engineering considerations
Introduction
This chapter describes the most important features in the energy circuit of a
drive system that you should take into consideration in your project planning.
Figure 7. Drive system (PDS = power drive system) L1 L2 L3 PE
RCD
Table 24. Drive system components
Item no. Description
1
Power grid configuration, input voltage, input frequency,
interactions with PF correction systems
2
Breakers, fuses, cable cross-sections
3
Protection of persons and animals with residual-current protective
devices
4
Input contactor, disconnector
5
Frequency inverter: mounting, installation; power connection; EMC
measures; circuit examples
6
Output contactor, disconnector
7
Output reactor, dV/dT filter, sine-wave filter
8
Motor protection; thermistor (can be connected to drive directly)
9
Cable lengths, motor cables, shielding (EMC)
10
Motor and application, parallel operation of multiple motors on a
VFD, bypass circuit, DC braking
PE L1 L2 L3
CPU
78
PE U V W
PES M
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
15
Chapter 2–Engineering considerations
Electrical power network
Input connection and configuration
The PowerXL Series frequency inverters can be connected and operated with all
control-point grounded AC power networks (see IEC 60364 for more information).
Figure 8. AC power networks with grounded neutral point (TN-/TT networks)
TN-S
TN-C
L1
L1
L2
L2
L3
L3
N
PEN
PE
TN-C-S
L1 L2 L3 N PE
TT
L1 L2 L3 N
The frequency inverter can be applied to all types of power networks above. If
multiple frequency inverters with single-phase supplies are to be connected, a
symmetrical distribution to the three external conductors shall be taken into
account. In addition, the total current of all single-phase consumers is not
to cause an overload of the neutral conductor (N-conductor).
The connection and operation of frequency inverters to asymmetrically grounded
TN networks (phase-grounded delta network “Grounded Delta”, USA) or neutral
point ungrounded or high-resistance grounded (>30 ohms) IT networks is only
conditionally permissible. In these networks above-mentioned, the internal
interference suppression filter of frequency inverter must be disconnected
(unscrew the screw marked `EMC’, see “Installation in IT System” on Page 53).
Then the required filtering for EMC (electromagnetic compatibility) is no
longer present (degrade to Class T).
Measures for EMC are mandatory in a drive system in order to meet the legal
requirements for EMC and low voltage regulations.
Good grounding measures are a prerequisite for the effective insert of further
measures such as shielding of filters. Without respective grounding measures,
further steps are superfluous.
Input voltage and frequency
The standardized input voltages (IEC 60038, VDE017-1) for energy suppliers
(EVU) guarantee the following conditions at the transition points:
· Deviation from the rated value of voltage: Max. ±10%
· Deviation in voltage phase balance: Max. ±3%
· Deviation from rated value of the frequency: Max. ±4%
The board tolerance band of the PowerXL Series frequency inverter considers
the rated value for European as (EU: ULN = 230 V/400 V, 50 Hz), American as
(USA: ULN = 240 V/480 V, 60 Hz) and Canada as (CAN: ULN = 600 V, 60 Hz)
standard voltages:
· 230 V, 50 Hz (EU) and 240 V, 60 Hz (USA) at DG1/DH1-32
· 400 V, 50 Hz (EU) and 480 V, 60 Hz (USA) at DG1/DH1-34
· 600 V, 60 Hz (CAN) at DG1/DH1-35
For the bottom voltage value, the permitted voltage drop of 4% in the consumer
circuits is also taken into account, therefore a total of ULN 14%.
· 230 V device class (DG1/DH1-32): 208 V 15% to 240 V +10% (177 V 0% to 264
V +0%)
· 400 V device class (DG1/DH1-34): 380 V 15% to 500 V +10% (323 V 0% to 550
V +0%)
· 600 V device class (DG1/DH1-35): 525 V 15% to 600 V +10% (446 V 0% to 660
V +0%)
The permitted frequency range is 50/60 Hz (45 Hz 0% to 66 Hz +0%).
Input voltage balance
Due to the uneven loading on the conductor, and with the direct connection of
greater power ratings, deviations from the ideal voltage form and asymmetrical
voltages can be caused in three-phase AC power networks. These asymmetric
divergences in the input voltage can lead to different loading of the diodes
in input rectifiers with three-phase supplied frequency inverters, and as a
result, an advance failure of this diode.
In the project planning for the connection of three-phase supplied frequency
inverters, consider only AC power networks that handle permitted asymmetric
divergences in the input voltage +3%.
If this condition is not fulfilled, or symmetry at the connection location is
uncertain, the use of an assigned AC choke is recommended.
16
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 2–Engineering considerations
Total harmonic distortion (THD)
Non-linear consumers (loads) in an AC supply system produce harmonic voltages
that again result in harmonic currents. These harmonic currents at the
inductive and capacitive reactances of a mains supply system produce
additional voltage drops with different values that are then overlaid on the
sinusoidal mains voltage and result in distortions. In supply systems, this
form of “noise” can give rise to problems in an installation if the sum of the
harmonics exceeds certain limit values.
Non-linear consumers (harmonics producers) include for example:
· Induction and arc furnaces, welding devices
· Current converters, rectifiers and inverters, soft starters, variable
frequency drives
· Switched-mode power supply units (computers, monitors, lighting),
uninterrupted power supply (UPS)
The THD value (THD = Total Harmonic Distortion) is defined in standard IEC/EN
61800-3 as the ratio of the rms value of all harmonic components to the rms
value of the fundamental frequency. It is given in percent of the total value.
Reactive power compensation devices
Special compensation measures on the power supply side is not required for
PowerXL Series drives, which take on very little reactive power of the
fundamental harmonics from the AC power supply network (cosØ ~0.98).
In the AC power networks with non-choked reactive current compensation
devices, current deviations can enable parallel resonance and undefinable
circumstances.
In the project planning for the connection of frequency inverters to AC power
networks with undefined circumstances, please consider using AC chokes.
The THD value of the harmonic distortion is stated in relation to the rms
value of the total signal as a percentage. On a variable frequency drive, the
total harmonic distortion is around 2836%.
To assist in the calculation of system harmonics, a Harmonic Estimation
Calculator Tool is available at Eaton.com/drives.
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
17
Chapter 3–Product overview
Chapter 3–Product overview
Component identification
Figure 9. Description of the PowerXL Series
Features
The PowerXL frequency inverter converts the voltage and frequency of an
existing AC network into a DC voltage. This DC voltage is used to generate a
three-phase AC voltage with adjustable frequency and assigned amplitude values
for the variable speed control of three-phase asynchronous motors.
18
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Figure 10. Block diagram, elements of PowerXL frequency inverters
Chapter 3–Product overview
Table 25. Elements of PowerXL frequency inverters
Item no.
1
2 3 4 5 6
7 8
9
Description
Supply L1, L2 L D_1-32: 230 V
3, PE, class,
input supply three-phase
vinopltuatgceoUnnLNec=tUioen
at (3
50/60 Hz: AC 230 V/24
0
V)
D_1-34: 400 V class, three-phase input connection (3 AC 400 V/480 V)
D_1-35: 600 V class, three-phase input connection (3 AC 600 V)
Internal interference suppression filter, category C2 to IEC/EN 61800-3 EMC- connection of internal interference suppression filter to PE
Rectifier bridge, converts the AC voltage of the electrical network into DC voltage
DC link with charging resistor, capacitor and switching mode power supply unit
(SMPS = Switching Mode Power Supply): DC link voltage UDC with three-phase
input connection (3 AC): UDC = 1.41 x ULN
Inverter. The IGBT based inverter converts the DC voltage of the DC link (UDC)
into a three-phase AC voltage (U2) with variable amplitude and frequency (f2).
Sinusoidal pulse width modulation (PWM) with V/f control can be switched to
speed control with slip compensation
Motor connection U/T1, V/T2, W/T3 with output voltage U2 (0100% Ue) and output frequency f2 (0400 Hz) output current (I2): D_1-32: 3.7 A to 248 A D_1-34: 2.2 A to 245 A D_1-35: 3.3 A to 208 A 100% at an ambient temperature of 122 °F (50 °C) with an overload capacity of 150% for 60 s every 600 s and a starting current of 200% for 2 s every 20 s
Keypad with control buttons, graphic display, control voltage, control signal terminals, micro-switches, and interface for the PC interface module (option)
Three-phase asynchronous motor, variable speed control of three-phase asynchronous motor for assigned motor shaft power values (P2): D_1-32: 0.55 kW to 75 kW (230 V, 50 Hz) or 0.75 hp to 100 hp (240 V, 60 Hz) D_1-34: 0.75 kW to 132 kW (400 V, 50 Hz) or 1 hp to 200 hp (460 V, 60 Hz) D_1-35: 1.5 kW to 132 kW (600 V, 50 Hz) or 2 hp to 200 hp (600 V, 60 Hz)
DC link–chokes, to minimize current harmonics
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
19
Chapter 3–Product overview
Selection criteria
The frequency inverter [3] is selected according to the supply voltage ULN of
the input supply [1] and the rated current of the assigned motor [2]. The
circuit type (/) of the motor must be selected according to the supply voltage
[1]. The rated output current I of the
e
frequency inverter must be greater than/equal to the rated motor current.
Figure 11. Selection criteria
When selecting the drive, the following criteria must be known: · Type of
motor (three-phase asynchronous motor) · Input voltage = rated operating
voltage of the motor
(for example, 3 AC ~400 V) · Rated motor current (guide value, dependent on
the
circuit type and the supply voltage) · Load torque (quadratic, constant) ·
Starting torque · Ambient temperature (rated value 122 °F [50 °C]) When
connecting multiple motors in parallel to the output of a frequency inverter,
the motor currents are added geometrically–separated by effective and idle
current components. When you select a frequency inverter, make sure that it
can supply the total resulting current. If necessary, for dampening and
compensating the deviating current values, motor reactors or sinusoidal
filters must be connected between the frequency inverter and the motor. The
parallel connection of multiple motors in the output of the frequency inverter
is only permitted with V/Hz characteristic curve control.
If you connect a motor to an operational frequency inverter, the motor draws a
multiple of its rated operational current. When you select a frequency
inverter, make sure that the starting current plus the sum of the currents of
the running motors will not exceed the rated output current of the frequency
inverter.
Switching in the output of the frequency inverter is only permitted with V/Hz
characteristic curve control.
Proper use
The PowerXL frequency inverters are electrical apparatus for controlling
variable speed drives with three-phase motors. They are designed for
installation in machines or for use in combination with other components
within a machine or system.
After installation in a machine, the frequency inverters must not be taken
into operation until the associated machine has been confirmed to comply with
the safety requirements of Machinery Directive (MD) 2006/42/EC (meets the
requirements of EN 60204-1). The user of the equipment is responsible for
ensuring that the machine use complies with the relevant EU Directives.
The CE markings on the PowerXL frequency inverters confirm that, when used in
a typical drive configuration, the apparatus complies with the relevant EU
Directives listed in Appendix F.
The UKCA markings on the PowerXL frequency inverters confirm that, when used
in a typical drive configuration, the apparatus complies with the relevant UK
Regulations listed in Appendix F.
In the described system configurations, PowerXL frequency inverters are
suitable for use in public and non-public networks.
A connection to IT networks (networks without reference to earth potential) is
permissible only to a limited extent, because the device’s built-in filter
capacitors connect the network with the earth potential (enclosure). On earth
free networks, this can lead to dangerous situations or damage to the device
(isolation monitoring required).
To the output of the frequency inverter (terminals U, V, W) you must not:
· Connect a voltage or capacitive loads (for example, phase compensation
capacitors)
· Connect multiple frequency inverters in parallel
· Make a direct connection to the input (bypass)
Observe the technical data and connection requirements. For additional
information, refer to the equipment nameplate or label at the frequency
inverter, and the documentation.
Any other usage constitutes improper use.
20
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 3–Product overview
Maintenance and inspection
PowerXL frequency inverters are maintenance free. However, external influences
may affect the function and the lifespan of the PowerXL frequency inverter. We
therefore recommend that the devices are checked regularly and the following
maintenance measures are carried out at the specified intervals.
If the PowerXL frequency inverter is damaged by external influences, contact
Technical Service.
Table 26. Maintenance measures and intervals
Maintenance measure
Clean cooling vents (cooling slits) Check the fan function
Filter in the switching cabinet doors (see manufacturer specifications) Check
the tightening torques of the terminals (control signal terminals, power
terminals) Check connection terminals and all metallic surfaces for corrosion
Maintenance interval
If required 624 months (depending on the environment) 624 months (depending
on the environment) Regularly
624 months (depending on the environment)
Storage
If the frequency inverter is stored before use, suitable ambient conditions
must be ensured at the site of storage:
· Storage temperature: 40 °F to 158 °F (40 °C to 70 °C)
· Relative average air humidity: <95%, noncondensing (EN 50178)
· To prevent damage to the DC link capacitors, storage times longer than 12
months are not recommended
Charging the internal DC link capacitors
After extended storage times or extended downtimes during which no power is
supplied (>12 months), the capacitors in the internal DC link must be
recharged in a controlled manner in order to prevent damage. To do this, the
PowerXL variable frequency drive must be supplied with power, with a
controlled DC power supply unit, via two mains DC bus connection terminals.
Please consult the factory for detailed instructions.
Service and warranty
In the unlikely event that you have a problem with your PowerXL frequency
inverter, please contact your local sales office.
When you call, have the following information ready:
· The exact frequency inverter part no. (see nameplate)
· The date of purchase
· A detailed description of the problem that has occurred with the frequency
inverter
If some of the information printed on the nameplate is not legible, please
state only the information that is clearly legible. This information can also
be found on the cover of the control terminals.
Information concerning the guarantee can be found in the General Terms and
Conditions of Sale.
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
21
Chapter 4–Safety and switching
Chapter 4–Safety and switching
Note: All following information is strongly recommended but is not necessary
if sufficient system design and validation has been completed.
Fuses and cable cross-sections
The fuses and wire cross-sections allocated for power-side connections depend
on the rated input current and output current of the frequency inverter
(without AC choke).
CAUTION
WHEN SELECTING THE CABLE CROSS-SECTION, TAKE THE VOLTAGE DROP UNDER LOAD
CONDITIONS INTO ACCOUNT. THE CONSIDERATION OF OTHER STANDARDS (FOR EXAMPLE,
VDE 0113 OR VDE 0289) IS THE RESPONSIBILITY OF THE USER. THE NATIONAL AND
REGIONAL STANDARDS (FOR EXAMPLE VDE 0113, EN 60204) MUST BE OBSERVED AND THE
NECESSARY APPROVALS (FOR EXAMPLE UL) AT THE SITE OF INSTALLATION MUST BE
FULFILLED. WHEN THE DEVICE IS OPERATED IN A UL-APPROVED SYSTEM, USE ONLY UL-
APPROVED FUSES, FUSE BASES, AND CABLES. SEE APPENDIX DSAFETY INSTRUCTIONS FOR
UL AND CUL FOR DETAILS.
CAUTION
THE SPECIFIED MINIMUM PE CONDUCTOR CROSS-SECTIONS IN THIS MANUAL MUST BE
MAINTAINED. THE MINIMUM SIZE OF THE PROTECTIVE EARTHING CONDUCTOR MUST COMPLY
WITH THE REQUIREMENTS OF EN 61800-5-1 AND/OR THE LOCAL SAFETY REGULATIONS.
TOUCH CURRENTS IN THIS FREQUENCY INVERTER ARE GREATER THAN 3.5 MA (AC).
ACCORDING TO PRODUCT STANDARD IEC/EN 61800-5-1, AN ADDITIONAL EQUIPMENT
GROUNDING CONDUCTOR OF THE SAME CROSS-SECTIONAL AREA AS THE ORIGINAL
PROTECTIVE EARTHING CONDUCTOR MUST BE CONNECTED, OR THE CROSS-SECTION OF THE
EQUIPMENT GROUNDING CONDUCTOR MUST BE AT LEAST 10 MM2 CU. CHOOSE THE CROSS-
SECTION OF THE PE CONDUCTOR IN THE MOTOR LINES AT LEAST AS LARGE AS THE CROSS-
SECTION OF THE PHASE LINES (U, V, W).
Cables and fuses
The cross-sections of the cables and line protection fuses used must
correspond with local standards.
For an installation in accordance with UL guidelines:
· Use UL listed Class RK5, J, T or equivalent fuses for the branch circuit
protection
· Use 75 °C or higher copper wire only
· Use UL listed conduit fittings with the same type rating (Type 1/Type 12) as
the enclosure
See Appendix DSafety Instructions for UL and cUL for details.
Use power cables with insulation according to the specified input voltages for
the permanent installation. A shielded cable is not required on the input
side.
A completely (360°) shielded low impedance cable is required on the motor
side. The length of the motor cable depends on the RFI class and must not
exceed approximately 300 ft (100 m) without additional filtering.
Residual-current device (RCD)
RCD (Residual Current Device): Residual current device, residual current
circuit breaker (FI circuit breaker).
Residual current circuit breakers protect persons and animals from the
existence (not the origination) of impermissibly high contact voltages. They
prevent dangerous, and in some cases deadly injuries caused by electrical
accidents, and also serve as fire prevention.
CAUTION
THIS DRIVE CAN CAUSE A DC CURRENT IN THE PROTECTIVE EARTHING CONDUCTOR. WHERE
A RESIDUAL CURRENT-OPERATED PROTECTIVE (RCD) OR MONITORING (RCM) DEVICE IS
USED FOR PROTECTION IN CASE OF DIRECT OR INDIRECT CONTACT, ONLY AN RCD OR RCM
OF TYPE B IS ALLOWED ON THE SUPPLY SIDE OF THIS PRODUCT.
Figure 12. Identification on the FI circuit breakers
AC/DC sensitive (R CD, type B)
Frequency inverters work internally with rectified AC currents. If an error occurs, the DC currents can block a type A RCD circuit breaker from triggering and therefore disable the protective functionality.
22
POWERXL DG1/DH1 SERIES VFD MN040002EN–July 2022 www.eaton.com
Chapter 4–Safety and switching
CAUTION
DEBOUNCED INPUTS MAY NOT BE USED IN THE SAFETY CIRCUIT DIAGRAM. RESIDUAL
CURRENT CIRCUIT BREAKERS (RCD) ARE ONLY TO BE INSTALLED BETWEEN THE AC POWER
SUPPLY NETWORK AND THE FREQUENCY INVERTER. SAFETY-RELEVANT LEAKAGE CURRENTS
CAN OCCUR WHILE HANDLING AND WHEN OPERATING THE FREQUENCY INVERTER, IF THE
FREQUENCY INVERTER IS NOT GROUNDED (BECAUSE OF A FAULT). LEAKAGE CURRENTS TO
GROUND ARE MAINLY CAUSED BY FOREIGN CAPACITIES WITH FREQUENCY INVERTERS,
BETWEEN THE MOTOR PHASES AND THE SHIELDING OF THE MOTOR CABLE AND VIA THE
Y-CAPACITORS OF THE RFI FILTER. THE SIZE OF THE LEAKAGE CURRENT IS MAINLY
DEPENDENT UPON THE: · LENGTH OF THE MOTOR CABLE · SHIELDING OF THE MOTOR CABLE
· HEIGHT OF THE SWITCHING FREQUENCY OF THE INVERTER · DESIGN OF THE RFI FILTER
· GROUNDING MEASURES AT THE SITE OF THE MOTOR THE LEAKAGE CURRENT TO GROUND IS
GREATER THAN 3.5 MA WITH A FREQUENCY INVERTER. ACCORDING TO PRODUCT STANDARD
IEC/EN 61800-5-1, AN ADDITIONAL EQUIPMENT GROUNDING (PE) CONDUCTOR OF THE SAME
CROSS-SECTIONAL AREA AS THE ORIGINAL PROTECTIVE EARTHING CONDUCTOR SHOULD BE
CONNECTED, OR THE CROSS-SECTION OF THE EQUIPMENT GROUNDING CONDUCTOR SHOULD BE
AT LEAST 10 MM2 CU. RESIDUAL CURRENT CIRCUIT BREAKERS MUST BE SUITABLE FOR: ·
THE PROTECTION OF INSTALLATIONS WITH DC CURRENT
COMPONENT IN CASE OF FAULT SCENARIO (RCD TYPE B) · HIGH LEAKAGE CURRENTS ·
BRIEF DISCHARGES OF PULSE CURRENT SPIKES
Leakage current
CAUTION
AS SHOWN IN TABLE 16, THE FOLLOWING LEAKAGE CURRENTS WERE DETECTED. THESE
VALUES WERE OBTAINED UNDER NORMAL OPERATING CONDITIONS WITH NO OUTSIDE
INFLUENCES. ACTUAL VALUES WILL DIFFER DEPENDING ON
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>