Amana CAUFA3626C6 CAUFA Uncased Aluminum Evaporator Coil
Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these sym-bols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER
SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR REPAIR
(HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE
THE EQUIPMENT. THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR
PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU
SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE
WHICH MAY RESULT. IN ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE
LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED
PERSONNEL SHOULD SERVICE THE EQUIPMENT. IMPROPER INSTALLATION, ADJUSTMENT,
SERVICING OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING
TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL
WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
Shipping Inspection
Upon receiving the product, inspect it for damage from shipment. Shipping damage, and subsequent investigation is the responsibility of the carrier. Verify the model number, specifications, and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for trans-portation damage or installation of incorrectly shipped units.
Handling
Use caution when transporting/carrying unit.. Do not carry unit with hooks
or sharp object. The preferred method of carrying the unit after arrival at
the job site is to carry by two-wheel hand truck from the back or sides or by
hand by carrying at the cabinet corners.
Codes & Regulations
This product is designed and manufactured to comply with national codes.
Installation in accordance with such codes and/or prevailing local
codes/regulations is the responsibility of the in-staller. The manufacturer
assumes no responsibility for equip-ment installed in violation of any codes
or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and di-posal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions please contact the local office of the EPA.
Replacement Parts
Inspect the unit to verify all required components are present and intact. Report any missing components immediately to the manufacturer or to the distributor. Make sure to include the full product model number and serial number when reporting and/or obtaining service parts. Replacement parts for this product are available through your contractor or local distributor. For the location of your nearest distributor consult the white business pages, the yellow page section of the local telephone book or contact:
HOMEOWNER SUPPORT
GOODMAN MANUFACTURING COMPANY, L.P.
19001 KERMIER ROAD
WALLER, TEXAS 77484
877– 254 – 4729
Pre-Installation Instructions
Preparation
Keep this document with the unit. Carefully read all instructions for the
installation prior to installing product. Make sure each step or procedure is
understood and any special considerations are taken into account before
starting installation. Assemble all tools, hardware and supplies needed to
complete the installation. Some items may need to be purchased locally. Make
sure everything needed to install the product is on hand before starting.
Clearances
Refrigerant lines must be routed depending on configuration of unit to
maintain the required 24” minimum clearance for service. Consult all
appropriate regulatory codes prior to determining final clearances. In
installations that may lead to physical damage (i.e. a garage) it is advised
to install a protec-tive barrier to prevent such damage. Always install units
such that a positive slope in condensate line (1/4″ per foot) is al-lowed.
Application Information
Coils are designed for indoor installation only and must be in-stalled
downstream (discharge air) of the furnace. The CAPF/CAPT product line may be
installed in upflow or downflow orientations.
Condensate Drain Piping
In all cooling applications where condensate overflow may cause damage, a
secondary drain pan must be provided by the installer and placed under the
entire unit with a separate drain line prop-erly sloped and terminated in an
area visible to the owner. This secondary drain pan can provide extra
protection to the area under the unit should the primary drain plug up and
overflow. As expressed in our product warranty, we will not be liable for any
damages, structural or otherwise due to the failure to follow this
installation requirement.
Condensate drain connections are located in the drain pan at the bottom of the
coil/enclosure assembly. Use the female (3/4” FPT) threaded fitting that
protrudes outside of the enclosure for external connections. The connectors
required are 3/4″ NPT male, either PVC or metal pipe, and must be hand
tightened to a torque of no more than 37 in-lbs. to prevent damage to the
drain pan con-nection.
An insertion depth between .36 to .49 inches (3-5 turns) should be expected at this torque.
- Ensure drain pan hole is NOT obstructed.
- To prevent potential sweating and dripping on finished space, it may be necessary to insulate the condensate drain line located inside the building. Use Armaflex® or similar material.
A Secondary Condensate Drain Connection, now called for by many building codes, has been provided. Pitch the drain line 1/4″ per foot to provide free drainage. Provide required support to drain line to prevent bowing. Install a condensate trap in the primary drain line to ensure proper drainage. If the secondary drain line is required, run the line separately from the primary drain and end it where condensate discharge can be easily seen.
CAUTION
IF SECONDARY DRAIN IS NOT INSTALLED, THE SECONDARY ACCESS MUST BE PLUGGED.
Refrigerant Lines
CAUTION
THE COIL IS SHIPPED UNDER PRESSURE WITH AN R-410A GAS MIXTURE. USE APPROPRIATE
SERVICE TOOLS AND FOLLOW THESE INSTRUCTIONS TO PREVENT INJURY.
WARNING
A QUENCHING CLOTH IS STRONGLY RECOMMENDED TO PREVENT SCORCHING OR MARRING OF
THE EQUIPMENT FINISH WHEN BRAZING CLOSE TO THE PAINTED SURFACES. USE BRAZING
ALLOY OF 5% MINIMUM SILVER CONTENT.
NOTE: Refrigerant tubing must be routed to allow adequate access for
servicing and maintenance of the unit.
Do not handle coil assembly with manifold or flowrator tubes. Doing so may
result in damage to the tubing joints. Always use clean gloves for handling
coil assemblies.
Tubing Size/Length
For the correct tubing size, follow the specification for the condenser/heat
pump. Give special consideration to minimizing the length of refrigerant
tubing when installing coils. Refer to Remote Cooling/Heat Pump Technical
Publication TP-107* Long Line Set Application R-410A for guidelines for line
lengths over 80’. Leave a minimum 3″ straight in line set from braze joints
before any bends.
Tubing Preparation
All cut ends are to be round, burr-free, and cleaned. Any other condition
increases the chance of a refrigerant leak. Use a pipe cutter to remove the
closed end of the spun closed suction line.
Brazing
Braze joints should be made only with the connections provided external to the
cabinet. Do not alter the cabinet nor braze inside the cabinet. To avoid
overheating after brazing, quench all brazed joints with water or a wet rag.
CAUTION
APPLYING TOO MUCH HEAT TO ANY TUBE CAN MELT THE TUBE. TORCH HEAT REQUIRED TO
BRAZE TUBES OF VARIOUS SIZES MUST BE PROPORTIONAL TO THE SIZE OF THE TUBE.
SERVICE PERSONNEL MUST USE THE APPROPRIATE HEAT LEVEL FOR THE SIZE OF THE TUBE
BEING BRAZED.
Special Instructions for Flowrator (Piston) Version
Coils in flowrator version are equipped with a check style flowrator for
refrigerant management. For most installations with matching applications, no
change to the flowrator piston is required. However, in mix-matched
applications, a piston change may be required. See the piston kit chart or
consult your local distributor for details regarding mix-matched pis-ton
sizing. If the mix-matched application requires a different piston size,
change the piston in the distributor on the indoor coil before installing the
coil and follow the procedure shown below.
Tubing Connections for Flowrator Model
-
Loosen the 13/16 nut 1 TURN ONLY to allow high-pressure tracer gas to escape. No gas indicates a possible leak.
-
After the gas has escaped, remove the nut and discard the plastic or brass cap.
-
Remove the check piston to verify it is correct and then re-place the piston. See piston kit chart in instructions.
-
Use a tube cutter to remove the spin closure on the suction line.
DO NOT USE A CUTTING METHOD THAT WOULD RESULT IN THE GENERATION OF COPPER SHAVINGS OR COPPER DUST. -
Slide the 13/16 nut into place on the tailpiece supplied in the literature bag or with the unit.
-
Insert liquid line into the supplied tailpiece.
-
Insert the suction line into the connection, slide the insulation and the rubber grommet at least 18″ away from the braze joint. Braze both liquid and suction line joints.
-
AFTER THE TAILPIECE HAS COOLED, confirm position of the white Teflon® seal and hand tighten the 13/16 nut.
CAUTION
EXCESSIVE TORQUE CAN CAUSE ORIFICES TO STICK. USE THE PROPER TORQUE SETTINGS WHEN TIGHTENING ORIFICES. -
Torque the 13/16” nut to 10-20 ft-lbs. or 1/6 turn past hand tight.
-
Replace suction line grommet and insulation.
Tubing Connections for TXV Version
TXV models come with factory-installed non-adjustable TXV with the bulb
permanently located on the suction tube.
- Remove coil access panel.
- Remove access valve fitting cap and depress the valve stem in access fitting to release pressure. No pressure indicates possible leak.
- Replace the refrigerant tubing panel.
- Remove the spin closure on both the liquid and suction tubes using a tubing cutter. DO NOT USE A CUTTING METHOD THAT WOULD RESULT IN THE GENERATION OF COPPER SHAVINGS OR COPPER DUST.
- Insert liquid line set into liquid tube expansion and slide grommet about 18″ away from braze joint.
- Insert suction line set into suction tube expansion and slide insulation and grommet about 18″ away from braze joint.
- Braze suction and liquid line joints.
Top flanges can be bent for ease in installation to the duct flanges.
Filler Plates
Filler plates are supplied on all 17.5, 21, & 24.5-inch chassis to be used for adapting the unit to a furnace one size smaller. If the plenum and furnace openings are the same size, the filler plates must be removed. See Figure 3.
Plastic Drain Pan Application
WARNING
DO NOT USE THE COIL PAN SHIPPED WITH THE UNIT ON OIL FURNACES OR ANY
APPLICATION WHERE THE TEMPERATURE OF THE DRAIN PAN MAY EXCEED 300°F. A HIGH-
TEMPERATURE DRAIN PAN SUCH AS KITS HTP-A, -B, -C AND -D FOR NORMAL CABINET
WIDTHS OF 14, 17.5, 21 AND 24.5 INCHES, RESPECTIVELY, SHOULD BE USED FOR
APPLICATIONS WHERE THE TEMPERATURE EXCEEDS 300°F AND BELOW 450°F. A FIELD
FABRICATED METAL DRAIN PAN CAN ALSO BE USED FOR APPLICATIONS WHERE TEMPERATURE
EXCEEDS 300°F.
FAILURE TO FOLLOW THIS WARNING MAY RESULT IN PROPERTY DAMAGE AND/OR PERSONAL
INJURY.
If the uncased coil is to be installed on top of a gas furnace, allow enough
space between the top to the furnace and the bottom of the plastic coil drain
pan to have a free flow of air.
A minimum of 2.0″ distance from the top of the furnace and the bottom of the
coil pan is required.
NOTE: The coil must be installed with the line set and drain open-ings to
the front of the furnace.
NOTE: Water coming from the secondary line means the coil primary drain
is plugged and needs immediate attention.
Install a trap in the drain line below the bottom of the drain pan (Figure 5).
If using a copper drain line, solder a short piece of pipe, minimum 6” length,
to the connector before installing a drain fitting.
DO NOT over torque the 3/4” copper connector to the plastic drain connection. Using a wet rag or heatsink material on the short piece to protect the plastic drain pan, complete the drain line installation. Use Figure 6 as a template for typical drain pipe routing. This figure shows how to avoid interference with vent piping.
Return Ductwork
DO NOT TERMINATE THE RETURN DUCTWORK IN AN AREA THAT CAN INTRODUCE TOXIC OR
OBJECTIONABLE FUMES/ODORS INTO THE DUCTWORK.
Aluminum Indoor Coil Cleaning (Qualified Servicer Only)
This unit is equipped with an aluminum tube evaporator coil. The safest way
to clean the evaporator coil is to simply flush the coil with water. This
cleaning practice remains as the recommended cleaning method for both copper
tube and aluminum tube residential evaporator coils.
It has been determined that many coil cleaners and drain pan tablets contain
corrosive chemicals that can be harmful to aluminum tube and fin evaporator
coils. Even a one-time application of these corrosive chemicals can cause
premature aluminum evaporator coil failure. Any cleaners that contain
corrosive chemicals including, but not limited to, chlorine and hydroxides,
should not be used.
An alternate cleaning method is to use one of the products listed in TP-109*
to clean the coils. The cleaners listed are the only agents deemed safe and
approved for use to clean round-tube aluminum coils. TP-109 is also available
on the website in Part-ner Link > Service Toolkit.
NOTE: Ensure coils are rinsed well after use of any chemical cleaners.