Amana M9S80 Gas Furnace Instruction Manual Product Information
- May 15, 2024
- Amana
Table of Contents
M9S80 Gas Furnace
Product Information
Specifications
Model: IOG-2030A
Trademark: Maytag Corporation
Date: 08/2021
Safety Considerations
Adhere to the following warnings and cautions when installing,
adjusting, altering, servicing, or operating the furnace. To ensure
proper installation and operation, thoroughly read this manual for
specifics pertaining to the installation and application of this
product.
Product Usage Instructions
Installation
1. Prior to installation, thoroughly familiarize yourself with
the Instruction Manual and pay special attention to all safety
warnings.
2. Install the furnace to operate within the intended
temperature-rise range and ensure the duct system has external
static pressure within the allowable range specified on the furnace
rating plate.
3. When installing a gas-fired furnace in a residential garage,
follow the LOCATION REQUIREMENTS AND CONSIDERATIONS section of the
manual.
Maintenance
1. Regularly inspect and maintain the furnace as per the
instructions provided in the manual.
2. If in doubt, always refer to the manual for proper
installation, adjustment, alteration, service, or maintenance
procedures.
FAQ
Q: Can I use this furnace as a construction site heater?
A: This furnace may be used as a construction site heater only
if certain conditions are met, as listed in the PRODUCT APPLICATION
section of the manual.
Q: How should I check for gas leaks?
A: Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for leak
detection to check all connections.
Q: What should I do if I encounter a direct conflict between
existing practices and the manual?
A: In case of a direct conflict between existing practices and
the manual, the precautions listed in the manual take
precedence.
Installation Instructions for M9S80 & C9S80* Gas Furnace CATEGORY I
CATÉGORIE I
These furnaces comply with requirements embodied in the American National
Standard / National Standard of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central
Furnaces.
Installer: Affix all manuals adjacent to the unit.
TABLE OF CONTENTS
Safety Considerations …………………………………………… 2 Product Application
………………………………………………. 4 Location Requirements & Considerations………………. 5
Combustion & Ventilation Air Requirements ………….. 8 Masonry Chimneys
……………………………………………….. 10 Electrical Connections ……………………………………….. 10 Gas Supply
and Piping…………………………………………… 11 Circulating Air……………………………………………………… 14
Electrical…………………………………………………………….. 16 Airflow Tables……………………………………………………… 21
Status Codes………………………………………………………… 29 Troubleshooting Codes………………………………………..
31 Wiring Diagram …………………………………………………….. 33 Maintenance
…………………………………………………………. 34 Media Air Filter or Electronic Air
Cleaner Removal ……………………………………………… 34 Before Leaving an Installation
…………………………….. 35 Repair and Replacement Parts …………………………….. 35
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
As a professional installer you have an obligation to know the product better
than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this
Instruction Manual. Pay special attention to all safety warnings. Often during
installation or repair it is possible to place yourself in a position which is
more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know
it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense…a matter of thinking before acting. Most
dealers have a list of specific good safety practices…follow them.
The precautions listed in this Installation Manual are intended as
supplemental to existing practices. However, if there is a direct conflict
between existing practices and the content of this manual, the precautions
listed herein take precedence.
*NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.
WARNING
Only personnel that have been trained to install, adjust, service or
repair(hereinafter, “service”) the equipment specified in this manual should
service the equipment. The manufacturer will not be responsible for any injury
or property damage arising from improper service or service procedures. If you
service this unit, you assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require one or more
licenses to service the equipment specified in this manual, only licensed
personnel should service the equipment. Improper installation, adjustment,
servicing or repair of the equipment specified in this manual, or attempting
to install, adjust, service or repair the equipment specified in this manual
without proper training may result in product damage, property damage,
personal injury or death.
80% HEX
DO NOT LIFT PRODUCT USING HEAT EXCHANGER
IOG-2030A 08/2021
19001 Kermier Rd., Waller, TX 77484 www.goodmanmfg.com · www.amana-hac.com ©
2021 Goodman Manufacturing Company, L.P.
is a registered trademark of Maytag Corporation or its related companies and
is used under license.
All rights reserved.
Safety Considerations
Adhere to the following warnings and cautions when installing,adjusting,
altering, servicing, or operating the furnace. To ensure proper installation
and operation, thoroughly read this manual for specifics pertaining to the
installation and application of this product.
WARNING FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury,
death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap
solution made specifically for the detection of leaks to check all
connections. A fire or explosion may result causing property damage, personal
injury or loss of life.
AVERTISSEMENT
RISQUE D’INCENDIE OU D’EXPLOSION
Always install a furnace to operate within the furnace’s intended temperature-
rise range with a duct system which has external static pressure within the
allowable range, as specified on the furnace rating plate and OPERATIONAL
CHECKS section of these instructions.
When furnace duct(s) supply air outside the space containing the furnace, a
return air duct must terminate in the same space as the supply duct and be
sealed to the furnace casing. A gas-fired furnace for installation in a
residential garage must be installed as specified in the LOCATION REQUIREMENTS
AND CONSIDERATIONS section of this manual.
This furnace may be used as a construction site heater only if certain
conditions are met. These conditions are listed in the PRODUCT APPLICATION
section of this manual.
WARNING
To prevent personal injury or death due to improper installation, adjustment,
alteration, service, or maintenance, refer to this manual. For additional
assistance or information, consult a qualified installer, servicer agency or
the gas supplier.
Si les consignes de sécurité ne sont pas suivies à la lettre, cela peut
entraîner la mort, de graves blessures ou des dommages matériels.
Ne jamais vérifier la présence de fuites de gaz au moyen d’une flamme nue.
Vérifier tous les raccords en utilisant une solution savonneuse commerciale
conçue spécialement pour la détection de fuites. Un incendie ou une explosion
risque de se produire, ce qui peut entraîner la mort, des blessures ou des
dommages matériels.
This furnace is manufactured for use with natural gas. It may be field
converted to operate on L.P. gas by using the appropriate L.P. conversion kit
listed in the PROPANE GAS/ HIGH ALTITUDE INSTALLATIONS section of this manual
Install this furnace only in a location and position as specified in LOCATION
REQUIREMENTS & CONSIDERATIONS section and INSTALLATION POSITIONS section of
this manual.
Provide adequate combustion and ventilation air to the furnace as specified in
COMBUSTION & VENTILATION AIR REQUIREMENTS section of this manual.
WARNING
If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors
and liquid in the vicinity of this or any other appliance. What to do if you
smell gas:
· Do not try to light any appliance. · Do not touch any electrical switch; do
not use any
phone in your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions. If you can not reach your gas
supplier, call the fire department. Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
WARNING
This product contains or produces a chemical or chemicals which may cause
serious illness or death and which are known to the State of California to
cause cancer, birth defects or other reproductive harms.
Combustion products must be discharged to the outdoors. Connect this furnace to an approved vent system only, as specified in Category 1 Venting section of this manual.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in GAS SUPPLY AND PIPING section of this manual.
2
Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
RISQUE D’EMPOISONNEMENT AU MONOXYDE DE CARBONE
CO can cause serious illness including permanent brain
damage or death.
B10259-216
Las emisiones de monóxido de carbono pueden circular a través del aparato cuando se opera en cualquier modo.
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
B10259-216
Cee venlaon est nécessaire pour éviter le danger d’intoxicaon au CO pouvant
survenir si un appareil produisant du monoxyde de carbone connue de fonconner
au sein de la zone confinée.
Le monoxyde de carbone peut causer des maladies graves telles que des dommages
permanents au cerveau et meme la mort. B10259-216
WARNING
Heating unit should not be utilized without reasonable routine, inspection,
maintenance and supervision. If the building in which any such device is
routinely inspected, maintained and monitored. In the event that the building
may be exposed to freezing temperatures and will be vacant, all water-bearing
pipes should be drained. The building should be properly winterized and the
water source closed. In the event that the building may be exposed to freezing
temperatures and will be vacant, any hydronic coil units should be drained as
well and, in such case, alternative heat sources should be utilized.
WARNING
To prevent possible property damage, personal injury or death due to
electrical shock, the furnace must be located to protect the electrical
components from water.
WARNING
Should overheating occur or the gas supply fail to shut off, turn off the
manual gas shutoff valve external to the furnace before turning off the
electrical supply.
WARNING
Possible property damage, personal injury or death due to fire, explosion,
smoke, soot, condensation, electrical shock, or carbon monoxide may result
from improper installation, repair operation, or maintenance of this product.
WARNING
To prevent personal injury or death due to improper installation, adjustment,
alteration, service or maintenance, refer to this manual. For additional
assistance or information, consult a qualified installer, servicer agency or
the gas supplier.
WARNING
To prevent personal injury or death due to asphyxiation, this furnace must be
Category I vented. Do not vent using Category III Venting. Provisions must be
made for venting combustion products outdoors through a proper venting system.
This length of flue pipe could be a limiting factor in locating the furnace.
Additional Safety Considerations · This furnace is approved for Category I
Venting only. · Provisions must be made for venting combustion products
outdoors through a proper venting system. The length of flue pipe could be a
limiting factor in locating the furnace.
Shipping Inspection All units are securely packed in shipping containers
tested according to International Safe Transit Association specifications. The
carton must be checked upon arrival for external damage. If damage is found, a
request for inspection by carrier’s agent must be made in writing immediately.
The furnace must be carefully inspected on arrival for damage and bolts or
screws which may have come loose in transit. In the event of damage the
consignee should:
1. Make a notation on delivery receipt of any visible damage to shipment or
container.
2. Notify carrier promptly and request an inspection.
3
3. With concealed damage, carrier must be notified as soon as possible –
preferably within five days.
4. File the claim with the following support documents within a nine month
statute of limitations. · Original or certified copy of the Bill of Lading, or
indemnity bond. · Original paid freight bill or indemnity in lieu thereof. ·
Original or certified copy of the invoice, showing trade and other discounts
or reductions.
· Copy of the inspection report issued by carrier’s representative at the time
damage is reported to carrier.
The carrier is responsible for making prompt inspection of damage and for a
thorough investigation of each claim. The distributor or manufacturer will not
accept claims from dealers for transportation damage.
WARNING
To prevent property damage, personal injury, or death due to fire, do not
install this furnace in a mobile home, trailer, or recreational vehicle.
Product Application
This furnace is primarily designed for residential home-heating applications.
It is NOT designed or certified for use in mobile homes, trailers or
recreational vehicles. Neither is it designed or certified for outdoor
applications. The furnace must be installed indoors (i.e., attic space, crawl
space, or garage area provided the garage area is enclosed with an operating
door).
Keep this literature in a safe place for future reference.
Electrostatic Discharge (ESD) Precautions
NOTE: Discharge body’s static electricity before touching unit. An
electrostatic discharge can adversely affect electrical components.
Use the following precautions during furnace installation and servicing to
protect the integrated control module from damage. By putting the furnace, the
control, and the person at the same electrostatic potential, these steps will
help avoid exposing the integrated control module to electrostatic discharge.
This procedure is applicable to both installed and non-installed (ungrounded)
furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control
module or any wire connected to the control prior to discharging your body’s
electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnaces near the
control. Any tools held in a person’s hand during grounding will be
discharged.
3. Service integrated control module or connecting wiring following the
discharge process in step 2. Use caution not to recharge your body with static
electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded
objects, etc.). If you come in contact with an ungrounded object, repeat step
2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its
container. Follow steps 1 through 3 if installing the control on a furnace.
Return any old or new controls to their containers before touching any
ungrounded object.
To The Installer
Before installing this unit, please read this manual thoroughly to familiarize
yourself with specific items which must be adhered to, including but not
limited to: unit maximum external static pressure, gas pressures, BTU input
rating, proper electrical connections, circulating air temperature rise,
minimum or maximum CFM, and motor speed connections, and venting. These
furnaces are designed for Category I venting only.
This furnace can be used in the following non-industrial commercial
applications:
Schools, Office Buildings, Churches, Retail Stores, Nursing Homes,
Hotels/Motels, Common or Office Areas
In such applications, the furnace must be installed with the following
stipulations:
· It must be installed per the installation instructions provided and per
local and national codes.
· It must be installed indoors in a building constructed on site.
· It must be part of a ducted system and not used in a free air delivery
application.
· It must not be used as a “make-up” air unit. · All other warranty exclusions
and restrictions apply.
This furnace may be used as a construction site heater ONLY if all of the
following conditions are met:
· The vent system is permanently installed per these installation
instructions.
· A room thermostat is used to control the furnace. Fixed jumpers that provide
continuous heating CANNOT be used and can cause long term equipment damage.
Bi-metal thermostats, or any thermostat affected by vibration must not be used
during construction.
· Return air ducts are provided and sealed to the furnace. · A return air
temperature range between 60ºF (16ºC) and
80ºF (27ºC) is maintained. · Air filters are installed in the system and
replaced daily
during construction and upon completion of construction. · The input rate and
temperature rise are set per the
furnace rating plate. · 100% outside air must be used for combustion during
construction. Temporary ducting may be used to supply outside air to the
furnace for combustion do not connect this duct directly to the furnace.
Size this duct according to NFPA 54/ANSI Z223.1 section for Combustion and
Ventilation Air.
4
· The furnace heat exchanger, components, duct system, air filters and
evaporator coils are thoroughly cleaned following final construction clean up
by a qualified
person.
· All furnace operating conditions (including ignition, input rate,
temperature rise and venting) are verified by a qualified person according to
these installation instructions.
· Furnace doors must be in place on the furnace while the furnace is operating
in any mode.
· Damage or repairs due to failure to comply with these requirements are not
covered under the warranty.
In the USA, this furnace MUST be installed in accordance with the latest
edition of the ANSI Z223.1 booklet entitled “National Fuel Gas Code” (NFPA
54), and the requirements or codes of the local utility or other authority
having jurisdiction. Additional helpful publications available from the NFPA
are, NFPA 90A – Installation of Air Conditioning and Ventilating System and
NFPA 90B – Warm Air Heating and Air Conditioning System.
All venting shall be in accordance with the National Fuel Gas Code, ANSI
Z223.1, or applicable local building and/or air conditioning codes.
NOTE: The Commonwealth of Massachusetts requires that the following additional
requirements must also be met:
· Gas furnaces must be installed by a licensed plumber or gas fitter.
· A T-handle gas cock must be used. · If the unit is to be installed in an
attic, the passageway to
and the service area around the unit must have flooring.
WARNING
To prevent property damage, personal injury, or death due to fire, do not
install this furnace in a mobile home, trailer, or recreational vehicle.
To ensure proper furnace operation, install, operate and maintain the furnace
in accordance with these installation and operation instructions, all local
building codes and ordinances. In their absence, follow the latest edition of
the National Fuel Gas Code (NFPA 54/ANSI Z223.1) and/or local plumbing or
waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can be obtained
from any of the following:
American National Standards Institute 25 West 43rd Street, 4th Floor New York,
NY 10036
National Fire Protection Association 1 Batterymarch Park
Quincy, MA 02169-7471
CSA International 8501 East Pleasant Valley Independence, OH 44131
The rated heating capacity of the furnace should be greater than or equal to
the total heat loss of the area to be heated. The total heat loss should be
calculated by an approved method or in accordance with “ASHRAE Guide” or
“Manual J-Load Calculations” published by the Air Conditioning Contractors of
America.
NOTE: Furnaces with NOx screens meet the California NOx emission standards and
California seasonal efficiency standards. ANNUAL inspections of the furnace
and its vent system is strongly recommended.
Location Requirements and Considerations
Your unit model type determines which installation procedures must be used.
For M9S80 models, you must follow instructions for Horizontal Left,
Horizontal Right or Upflow installations only. These furnaces are not approved
for Downflow installations.
C9S80 models may be installed in the Downflow position as well as Horizontal Left & Horizontal Right positions.
WARNING
To prevent possible equipment damage, property damage, personal injury, or
death, the following bullet points must be observed when installing this unit.
Follow the instructions listed below when selecting a furnace location. Refer
also to the guidelines provided in the Combustion and Ventilation Air
Requirements.
· Centrally locate the furnace with respect to the proposed or existing air
distribution system.
· Ensure the temperature of the return air entering the furnace is between
55°F and 100°F when the furnace is heating.
· Provisions must be made for venting combustion products outdoors through a
proper venting system. The length of flue pipe could be a limiting factor in
locating the furnace.
· Ensure adequate combustion air is available for the furnace. Improper or
insufficient combustion air can expose building occupants to gas combustion
products that could include carbon monoxide. Refer to Combustion and
Ventilation Air Requirements section.
· The furnace must be level. If the furnace is to be set on a floor that may
become wet or damp at times, the furnace should be supported above the floor
on a concrete base sized approximately 1-½” larger than the base of the
furnace.
· Ensure upflow or horizontal furnaces are not installed directly on
carpeting, or any other combustible material. The only combustible material
allowed is wood.
5
· Exposure to contaminated combustion air will result in safety and
performance-related problems. Do not install the furnace where the combustion
air is exposed to the following substances: chlorinated waxes or cleaners
chlorine-based swimming pool chemicals water softening chemicals deicing salts
or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions
(such as perchloroethylene) printing inks paint removers varnishes
hydrochloric acid cements and glues antistatic fabric softeners for clothes
dryers and masonry acid washing materials
· If the furnace is used in connection with a cooling unit, install the
furnace upstream or in parallel with the cooling unit coil. Premature heat
exchanger failure will result if the cooling unit coil is placed ahead of the
furnace.
· For vertical applications, the minimum cooling coil width shall not be less
than furnace width minus 1″. Additionally, a coil installed above an upflow
furnace or under a counterflow furnace may be the same width as the furnace or
may be one size larger than the furnace. Example: a “C” width coil may be
installed with a “B” width furnace.
· For upflow applications, the front of the coil and furnace must face the
same direction.
· If the furnace is installed in a residential garage, position the furnace so
that the burners and ignition source are located not less than 18 inches (457
mm) above the floor. Protect the furnace from physical damage by vehicles.
· If the furnace is installed horizontally, the furnace access doors must be
vertical so that the burners fire horizontally into the heat exchanger. Do not
install the unit with the access doors on the “up/top” or “down/bottom” side
of the furnace.
· Do not connect this furnace to a chimney flue that serves a separate
appliance designed to burn solid fuel.
· Counterflow installation over a noncombustible floor. Before setting the
furnace over the plenum opening, ensure the surface around the opening is
smooth and level. A tight seal should be made between the furnace base and
floor by using a silicon rubber caulking compound or cement grout.
· Counterflow installation over a combustible floor. If installation over a
combustible floor becomes necessary, use an accessory subbase (see
Specification Sheet applicable to your model for details). A special accessory
subbase must be used for upright counterflow unit installations over any
combustible material including wood. Follow the instructions with the subbase
for proper installations.
· Do not install the furnace directly on carpeting, tile, or other combustible
material other than wood flooring. (NOTE: The subbase will not be required if
an air conditioning coil is installed between the supply air
opening on the furnace and the floor. The air conditioning coil must be
downstream from the heat exchanger of
the furnace.
Vent Pipe Clearance to Combustibles6″ using Single Wall Connector or 1″ using B-1 vent.
Top – 1″
Back – 0″
Side Clearance – 1″
Front Clearance – 3″
Figure 1
· Adequate combustion/ventilation air must be supplied to the closet.
· Furnace must be completely sealed to floor or base. Combustion/ventilation
air supply pipes must terminate 12″ from top of closet and 12″ from floor of
closet. DO NOT remove solid base plate for side return.
· Return air ducts must be completely sealed to the furnace and terminate
outside the enclosure surfaces.
Clearances and Accessibility
Unobstructed front clearance of 24″ for servicing is recommended.
VENT B1-VENT SINGLE
1″
6″
SIDES 1″
FRONT 3″
BACK 0″
TOP (PLENUM)
1″
Top clearance for horizontal configuration – 1″
Installation Positions
M9S80 model furnaces may be installed vertically (upflow) or horizontally with left or right side down. C9S80 model furnaces may be installed vertically (downflow) or horizontally with left or right side down. Do not install this furnace on its back. For vertically installed upflow furnaces, return air ductwork may be attached to the side panel(s) and/or basepan. For horizontally installed upflow furnaces, return air ductwork must be attached to the basepan. For counterflow furnaces, return ductwork must be attached to the blower compartment end of the furnace.
6
NOTE: Ductwork must never be attached to the back of the furnace. Horizontal
Installation Line contact to framing is permitted when installed in the
horizontal configuration. Line contact is defined as the portion of the
cabinet that is formed by the intersection of the top and side. ACCESSIBILITY
CLEARANCE, WHERE GREATER, SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE PROTECTION
CLEARANCE. A gas-fired furnace for installation in a residential garage must
be installed so that the ignition source and burners are located not less than
eighteen inches (18″) above the floor and is protected or located to prevent
physical damage by vehicles. A gas furnace must not be installed directly on
carpeting, tile, or other combustible materials other than wood flooring.
Furnace Suspension If suspending the furnace from rafters or joist, use 3/8″
threaded rod and 2″x2″x3/8″ angle iron as shown below. The length of rod will
depend on the application and the clearances necessary.
Suspended Furnace Figure 2
Existing Furnace Removal
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below
for each appliance connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death. The following steps shall
be followed for each appliance connected to the venting system being placed
into operation, while all other appliances connected to the venting system are
not in operation: 1) Seal any unused openings in the venting system. 2)
Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the
Natural Gas and Propane Installation Code, CSA B149.1 and these instructions.
Determine that there is no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe condition. 3) As far as
practical, close all building doors and windows and all doors between the
space in which the appliance(s) connected to the venting system are located
and other spaces of the building. 4) Close fireplace dampers. 5) Turn on
clothes dryers and any appliance not connected to the venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they are
operating at maximum speed. Do not operate a summer exhaust fan. 6) Follow the
lighting instructions. Place the appliance being inspected into operation.
Adjust the thermostat so appliance is operating continuously. 7) Test for
spillage from draft hood equipped appliances at the draft hood relief opening
after 5 minutes of main burner operation. Use the flame of a match or candle.
8) If improper venting is observed during any of the above tests, the venting
system must be corrected in accordance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or Natural Gas and Propane Installation Code, CSA B149.1.
9) After it has been determined that each appliance connected to the venting
system properly vents when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired burning appliance to
their previous conditions of use.
7
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE Si les étapes décrites ci-dessous
ne sont pas suivies pour chacun des appareils raccordés au système de
ventilation au moment de sa mise en marche, cela peut entraîner une
intoxication au monoxyde de carbone ou la mort. Les étapes suivantes doivent
être suivies pour chacun des appareils raccordés au système de ventilation au
moment de sa mise en marche, alors que tous les autres appareils raccordés au
système de ventilation ne sont pas en marche: 1) Sceller toutes les ouvertures
inutilisées du système
de ventilation. 2) Inspecter le système de ventilation afin de vérifier si la
taille et l’inclinaison par rapport à l’horizontale sont conformes aux
exigences du National Fuel Gas Code, ANSI Z223.1/NFPA 54 ou du Code
d’installation du gaz naturel et du propane, CSA B149.1 et à ces instructions.
Vérifier qu’il n’y a pas d’obstruction ou de restriction, de fuite, de
corrosion et d’autres problèmes qui pourraient entraîner une situation
dangereuse. 3) Si possible, fermer toutes les portes et fenêtres du bâtiment
ainsi que toutes les portes séparant l’endroit où se trouvent les appareils
raccordés au système de ventilation et les autres zones du bâtiment. 4) Fermer
le registre des foyers. 5) Mettre les sécheuses en marche ainsi que tous les
autres appareils qui ne sont pas raccordés au système de ventilation. Mettre
en marche tous les ventilateurs de tirage, comme celui des hottes de cuisine
et des salles de bains, et les régler à la puissance maximale. Ne pas mettre
en marche les ventilateurs d’été. 6) Suivre les instructions d’allumage.
Mettre en marche l’appareil soumis à l’inspection. Régler le thermostat de
manière à ce que l’appareil fonctionne en continu. 7) Vérifier la présence de
fuite au niveau de l’ouverture du coupe-tirage des appareils qui en sont dotés
après 5 minutes de fonctionnement du brûleur principal. Utiliser la flamme
d’une allumette ou d’une bougie. 8) Si un problème de ventilation est observé
pendant l’un des essais décrits ci-dessus, des correctifs doivent être
apportés au système de ventilation conformément au National Fuel Gas Code,
ANSI Z223.1/NFPA 54 et (ou) au Code d’installation du gaz naturel et du
propane, CSA B149.1. 9) Une fois qu’il a été déterminé que chaque appareil
raccordé au système de ventilation fonctionne correctement au moyen des essais
décrits ci-dessus, les portes, les fenêtres, les ventilateurs, les registres
de foyer et tous les autres appareils de combustion alimentés au gaz doivent
être remis dans leur état initial.
Corrections must be in accordance with the latest edition of the National Fuel
Gas Code NFPA 54/ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
If resizing is required on any portion of the venting system, use the
appropriate table in the latest edition of the National Fuel Gas Code ANSI
Z223.1.
Thermostat Location In an area having good air circulation, locate the
thermostat about five feet high on a vibration-free inside wall. Do not
install the thermostat where it may be influenced by any of the following:
· Drafts, or dead spots behind doors, in corners, or under cabinets.
· Hot or cold air from registers. · Radiant heat from the sun. · Light
fixtures or other appliances. · Radiant heat from a fireplace. · Concealed hot
or cold water pipes, or chimneys. · Unconditioned areas behind the thermostat,
such as
an outside wall.
Consult the instructions packaged with the thermostat for mounting
instructions and further precautions.
Combustion and Ventilation Air Requirements
WARNING
To avoid property damage, personal injury or death, sufficient fresh air for
proper combustion and ventilation of flue gas must be supplied. Most homes
require outside air be supplied into the furnace area.
Improved construction and additional insulation in buildings have reduced heat
loss by reducing air infiltration and escape around doors and windows. These
changes have helped in reducing heating/cooling costs but have created a
problem supplying combustion and ventilation air for gas fired and other fuel
burning appliances. Appliances that pull air out of the house (clothes dryers,
exhaust fans, fireplaces, etc.) increase the problem by starving appliances
for air.
House depressurization can cause back drafting or improper combustion of gas-
fired appliances, thereby exposing building occupants to gas combustion
products that could include carbon monoxide.
If this furnace is to be installed in the same space with other gas
appliances, such as a water heater, ensure there is an adequate supply of
combustion and ventilation air for all appliances. Refer to the latest edition
of the National Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/CSA B149 Installation
Codes or applicable provisions of the local building codes for determining the
combustion air requirements for the appliances.
This furnace must use indoor air for combustion. It cannot be installed as a
direct vent (i.e., sealed combustion) furnace.
8
Most homes will require outside air be supplied to the furnace area by means
of ventilation grilles or ducts connecting directly to the outdoors or spaces
open to the outdoors such as attics or crawl spaces.
Category I Venting (Vertical Venting)
WARNING
To prevent possible personal injury or death due to asphyxiation, this furnace
must be Category I vented. Do not vent using Category III venting.
Category I Venting is venting at a non-positive pressure. A furnace vented as
Category I is considered a fan-assisted appliance and the vent system does not
have to be “gas tight”. NOTE: Gas furnaces with induced draft blowers draw
products of combustion through a heat exchanger allowing, in some instances,
common venting with natural draft appliances (i.e. water heaters). All
installations must be vented in accordance with National Fuel Gas Code NFPA
54/ANSI Z223.1 – latest edition.
NOTE: The vertical height of the Category I venting system must be at least as
great as the horizontal length of the venting system.
WARNING
To prevent possible personal injury or death due to asphyxiation, common
venting with other manufacturer’s induced draft appliances is not allowed.
The minimum vent diameter for the Category I venting sys-
tem is as shown:
MINIMUM VENT
MODEL UPFLOW COUNTERFLOW
060
4 inch
4 inch
080
4 inch
4 inch
100
5 inch
4 inch
Under some conditions, larger vents than those shown above may be required or allowed. When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
transition bottom kit (part # 4053501S) is needed for proper alignment of the
inducer outlet and the vent exit hole in the side of the cabinet. The inducer
may NOT be rotated on *C9S80 model furnaces regardless of installation
position.
THIS PRODUCT IS NOT DESIGNED FOR COUNTERCLOCKWISE INDUCED DRAFT BLOWER
ROTATION.
Vent the furnace in accordance with the National Fuel Gas Code NFPA 54/ANSI
Z223.1 – latest edition.
Venting
THIS FURNACE IS NOT DESIGN CERTIFIED TO BE HORIZONTALLY VENTED.
To rotate the induced draft blower clockwise, you will need to purchase one
(4053501S) chimney transition bottom kit.
1. Disconnect electrical power from the furnace. 2. Disconnect the induced
draft blower power leads, flue
pipe, and pressure switch tubing. 3. Remove the round cutout from the right
side of the
wrapper. 4. Remove and save the four screws that fasten the
induced draft blower to the flue collector box. 5. Remove and save the three
screws that hold the
chimney assembly to the induced draft blower. 6. Remove and save the four
screws that fasten the
chimney top to the chimney bottom. 7. Remove the chimney transition bottom
from the
transition bottom kit. 8. Install the chimney top with the four screws
retained from
step 6 onto the new chimney transition bottom from the transition bottom kit.
9. Install chimney assembly with the three screws retained from step 5 onto
the induced draft blower. 10. Reinstall the induced draft blower rotating it
90 degrees clockwise from the original upflow configuration using the four
screws retained in step 3. Ensure the gasket located between the induced draft
blower and the collector box is rotated accordingly. 11. Reconnect the induced
draft blower power leads. NOTE: If the wires are not long enough, pull extra
wire from the wire bundle in the blower compartment. 12. Reconnect the flue
pipe, and the pressure switch tubing. Ensure that all wires and the pressure
switch tubing is at least one inch from the flue pipe, or any other hot
surface. 13. Restore power to furnace.
Furnaces are shipped with the induced draft blower dis-
charging from the top of the furnace. (“Top” is as viewed for
an upflow installation.) The induced draft blower on M9S80 models can be
rotated 90 degrees for Category I venting. For furnaces installed vertically
or horizontally, a four-inch single wall pipe can be used to extend the
induced draft
blower outlet ½” beyond the furnace cabinet. On M9S80 furnaces installed
upflow or horizontally with left side down, the draft inducer may be rotated
to discharge from the right
side of the cabinet. When rotating the inducer a chimney
Counterflow units are shipped with the induced draft blower discharging from
the top of the furnace. (“Top” as viewed for a counterflow installation.)
Vent the furnace in accordance with the National Fuel Gas Code NFPA54/ANSI
Z223.1 – latest edition.
WARNING
Never allow the products of combustion, including carbon monoxide, to enter
the return ductwork or circulation air supply.
9
Masonry Chimneys
WARNING
Possibility of property damage, personal injury or death damaging condensation
can occur inside masonry chimneys when a single fan-assisted Category I
appliance (80% AFUE furnace) is vented without adequate dilution air. Do not
connect an 80% furnace to a masonry chimney unless the furnace is common
vented with a draft hood equipped appliance or the chimney is lined with a
metal liner or Type B metal vent. All installations using masonry chimneys
must be sized in accordance with appropriate venting tables. If an 80%
furnaces common vented with a draft hood equipped appliance, the potential for
condensation damage may still exist with extremely cold conditions, long vent
connectors, exterior chimneys, or any combination of these conditions. The
risk of condensation damages is best avoided by using masonry chimney as a
pathway for properly sized metal liner or Type B metal vent.
Masonry Chimney Terminations A masonry chimney used as a vent for gas fired
equipment must extend at least three feet above the highest point where it
passes through the roof. It must extend at least two feet higher than any
portion of a building within a horizontal distance of 10 feet. In addition,
the chimney must terminate at least three feet above any forced air inlet
located within 10 feet. The chimney must extend at least five above the
highest connected equipment draft hood outlet or flue collar.
Electrical Connections
WARNING
HIGH VOLTAGE!
To avoid the risk of electrical shock, wiring to the unit must be polarized
and grounded.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper operation after
servicing.
WARNING
Wiring Harness
The wiring harness is an integral part of this furnace. Field alteration to
comply with electrical codes should not be required. Wires are color coded for
identification purposes. Refer to the wiring diagram for wire routings. If any
of the original wire as supplied with the furnace must be replaced, it must be
replaced with wiring material having a temperature rating of at least 105°C.
Any replacement wiring must be a copper conductor.
115 Volt Line Connections
Before proceeding with electrical connections, ensure that the supply voltage,
frequency, and phase correspond to that specified on the unit rating plate.
Power supply to the furnace must be NEC Class 1, and must comply with all
applicable codes. The furnace must be electrically grounded in accordance with
local codes or, in their absence, with the latest edition of The National
Electric Code, ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1.
Use a separate fused branch electrical circuit containing properly sized wire,
and fuse or circuit breaker. The fuse or circuit breaker must be sized in
accordance with the maximum overcurrent protection specified on the unit
rating plate. An electrical disconnect must be provided at the furnace
location.
Connect hot, neutral, and ground wires as shown in the wiring diagram located
on the unit’s blower door. Metal conduit is not considered a substitute for an
actual ground wire to the unit.
Line polarity must be observed when making field connections. Line voltage
connections can be made through either the right or left side panel. The
furnace is shipped configured for a right side electrical connection with the
junction box located inside the burner compartment (blower compartment for
downflows). To make electrical connections through the opposite side of the
furnace, the junction box must be relocated to the other side of the burner
(or blower) compartment prior to making electrical connections. To relocate
the junction box, follow the steps shown below.
NOTE: Wire routing must not to interfere with circulator blower operation,
filter removal, or routine maintenance.
HIGH VOLTAGE!
To avoid risk of injury, electrical shock or death, the furnace must be
electrically grounded in accordance with local codes or in their absence, with
the latest edition of the National Electric Code.
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a precaution when
removing hole plugs.
Junction Box Relocation
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a precaution when
removing hole plugs.
WARNING
To prevent personal injury or death due to electric shock, disconnect
electrical power before installing or servicing this unit.
10
1. Remove both doors from the furnace. 2. Remove and save the screws holding
the junction box
to the right side of the furnace. 3. Attach the junction box to the left side
of the furnace,
using the screws removed in step 2. 4. Check the location of the wiring.
Confirm that it will not be
damaged by heat from the burners or by the rotation of the fan. Also confirm
that wiring location will not interfere with filter removal or other
maintenance.
IMPORTANT NOTE: To avoid possible equipment malfunction, route the low voltage
wires to avoid interference with filter removal or other maintenance.
WARNING
HIGH VOLTAGE!
To avoid risk of injury, electrical shock or death, the furnace must be
electrically grounded in accordance with local codes or in their absence, with
the latest edition of the National Electric Code.
To ensure proper unit grounding, the ground wire should run from the furnace
ground screw located inside the furnace junction box all the way back to the
electrical panel. NOTE: Do not use gas piping as an electrical ground. To
confirm proper unit grounding, turn off the electrical power and perform the
following check.
1. Measure resistance between the neutral (white) connection and one of the
burners.
2. Resistance should measure 10 ohms or less.
INLET GAS SUPPLY PRESSURE Natural Gas Minimum: 4.5″ w.c. Maximum: 10.0″ w.c.
Propane Gas Minimum: 11.0″ w.c. Maximum: 13.0″ w.c.
NOTE: Adjusting the minimum supply pressure below the limits in the above
table could lead to unreliable ignition. Gas input to the burners must not
exceed the rated input shown on the rating plate. Overfiring of the furnace
can result in premature heat exchanger failure. Gas pressures in excess of 13
inches water column can also cause permanent damage to the gas valve.
At all altitudes, the manifold pressure must be within 0.3 inches w.c. of that
listed in the Specification Sheet applicable to your model for the fuel used.
At all altitudes and with either fuel, the air temperature rise must be within
the range listed on the furnace nameplate. Should this appliance be converted
to LP, refer to the instructions included in the factory authorized LP
conversion kit.
High Altitude Derate
When this furnace is installed at high altitude, the appropriate High Altitude
orifice kit must be applied. This is required due to the natural reduction in
the density of both the gas fuel and combustion air as altitude increases. The
kit will provide the proper design certified input rate within the specified
altitude range. High altitude kits are purchased according to the installation
altitude and usage of either natural or propane gas. Consult the furnace
Specification Sheet for appropriate kits.
This furnace is equipped with a blower door interlock switch which interrupts
unit voltage when the blower door is opened for servicing. Do not defeat this
switch.
Gas Supply and Piping
The furnace rating plate includes the approved furnace gas input rating and
gas types. The furnace must be equipped to operate on the type of gas applied.
This includes any conversion kits required for alternate fuels and/or high
altitude.
CAUTION
To prevent unreliable operation or equipment damage, the inlet gas supply
pressure must be as specified on the unit rating plate with all other
household gas fired appliances operating.
Inlet gas supply pressures must be maintained within the ranges specified in
the following table. The supply pressure must be constant and available with
all other household gas fired appliances operating. The minimum gas supply
pressure must be maintained to prevent unreliable ignition. The maximum must
not be exceeded to prevent unit overfiring.
NOTE: Do not remove the gas valve inlet plug before the gas line is installed.
Replace if water or debris has been introduced.
Do not derate the furnace by adjusting the manifold pressure to a lower
pressure than specified on the furnace rating plate. The combination of the
lower air density and a lower manifold pressure will prohibit the burner
orifice from drawing the proper amount of air into the burner. This may cause
incomplete combustion, flashback, and possible yellow tipping.
In some areas the gas supplier may artificially derate the gas in an effort to
compensate for the effects of altitude. If the gas is artificially derated,
the appropriate orifice size must be determined based upon the BTU/ft3 content
of the derated gas and the altitude. Refer to the National Fuel Gas Code, NFPA
54/ANSI Z223.1, and information provided by the gas supplier to determine the
proper orifice size.
A different pressure switch may be required at high altitude regardless of the
BTU/ft3 content of the fuel used. Consult the furnace Specification Sheet for
pressure switch.
WARNING
Possible property damage, personal injury or death may occur if the correct
conversion kits are not installed. The appropriate kits must be applied to
ensure safe and proper furnace operation. All conversions must be performed by
a qualified installer or service agency.
11
Consult the furnace Specification Sheet for appropriate manufacturer’s kits
for propane gas and/or high altitude installations. The indicated kits must be
used to insure safe and proper furnace operation. All conversions must be
performed by a qualified installer, or service agency.
Propane Gas Conversion
WARNING
Possible property damage, personal injury or death may occur if the correct
conversion kits are not installed. The appropriate kits must be applied to
ensure safe and proper furnace operation. All conversions must be performed by
a qualified installer or service agency.
This unit is configured for natural gas. The appropriate manufacturer’s
propane gas conversion kit must be applied for propane gas installations.
the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
Length of
Nominal Black Pipe Size
Pipe in Feet
1/2″
3/4″
1″
1 1/4″
10
132
278
520
1050
20
92
190
350
730
30
73
152
285
590
40
63
130
245
500
50
56
115
215
440
60
50
105
195
400
70
46
96
180
370
80
43
90
170
350
90
40
84
160
320
100
38
79
150
305
(Pressure 0.5 psig or less and pressure drop of 0.3″ W.C.; Based on
0.60 Specific Gravity Gas)
CFH = BTUH Furnace Input Heating Value of Gas (BTU/Cubic Foot)
1 1/2″ 1600 1100 980 760 670 610 560 530 490 460
Gas Altitude Kit
Natural
None
Orifice
Manifold Pressure
High Stage
Low Stage
Pressure Switch Change
45 3.5″ w.c. 1.9″ w.c. None
To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the installer may also need to supply a transition piece from ½” pipe to a larger pipe size.
0-7000
Propane
LPM-07* 1 1.25mm 10.0″ w.c. 6.0″ w.c.
None
1 LPM-07* supports both Honeywell and White-Rodgers 1-stage valves NOTE: In Canada, gas furnaces are only certified to 4500 feet.
If converting to LP gas, it is recommended that an LPLP0* kit also be
installed. The use of this kit will prevent the furnace from firing when the
LP gas supply pressure is too low to support proper combustion.
Gas Valve This unit is equipped with a 24 volt gas valve controlled during
furnace operation by the integrated control module. As shipped, the valve is
configured for natural gas. The valve is field convertible for use with
propane gas by replacing the regulator spring with a propane gas spring from
an appropriate manufacturer’s propane gas conversion kit. Taps for measuring
the gas supply pressure and manifold pressure are provided on the valve.
The gas valve has a manual ON/OFF control located on the valve itself. This
control may be set only to the “ON” or “OFF” position. Refer to the lighting
instructions label or Startup Procedure & Adjustment for use of this control
during start up and shut down periods.
Gas Piping Connections When sizing gas lines, be sure to include all
appliances which will operate simultaneously.
The gas piping supplying the furnace must be properly sized based on the gas
flow required, specific gravity of the gas, and length of the run. The gas
line installation must comply with local codes, or in their absence, with the
latest edition of
The following stipulations apply when connecting gas piping. · Gas piping must be supported external to the furnace cabinet so that the weight of the gas line does not distort the burner rack, manifold or gas valve. · Use black iron or steel pipe and fittings for the building piping. · Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used. · Use ground joint unions. · Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long. · Use two pipe wrenches when making connection to the gas valve to keep it from turning. The orientation of the gas valve on the manifold must be maintained as shipped from the factory. · Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is installed, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace. · Tighten all joints securely. · Connect the furnace to the building piping by one of the following methods: Rigid metallic pipe and fittings. Semi-rigid metallic tubing and metallic fittings. Aluminum alloy tubing must not be used in exterior locations. Use listed gas appliance connectors in accordance with their instructions. Connectors must be fully in the same room as the furnace. Protect connectors and semi-rigid tubing against physical and thermal damage when installed. Ensure aluminum-alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to re-
12
peated wetting by liquids such as water (except rain water), detergents, or sewage.
Gas Piping Checks
Before placing unit in operation, leak test the unit and gas connections.
Gas line entrance
Right side gas entrance (alternate)
WARNING
To avoid the possibility of explosion or fire, never use a match or open flame
to test leaks.
Check for leaks using an approved chloride-free soap and water solution, an
electronic combustible gas detector, or other approved testing methods.
WARNING
General Furnace Layout Figure 3
Upflow Installations
When the gas piping enters through the side of the furnace, the installer must
supply the following fittings (starting from the gas valve):
· Close nipple. · 90 degree elbow. · Straight pipe to reach the exterior of
the furnace. A ground joint union, drip leg, and manual shutoff valve must
also be supplied by the installer. In some cases, the installer may also need
to supply a transition piece from ½” to another pipe size.
When the gas piping enters through the left side of the furnace, the installer
must supply the following fittings (starting from the gas valve):
· 90 degree elbow. · Straight pipe to reach the exterior of the furnace. · A
ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the installer may also
need to supply a transition piece from ½ inch to another pipe size.
Counterflow Installations
When the gas piping enters through the left side of the furnace, the installer
must supply a straight pipe and a 90 degree elbow to reach the exterior of the
furnace.
A ground joint union, drip leg and manual shutoff valve must also be supplied
by the installer. In most cases, the installer may also need to supply a
transition piece from ½” to another pipe size. When the gas piping enters
through the right side of the furnace, the installer must supply the following
fittings (starting at the gas valve):
· Close Nipple · 90 Degree Elbow · Straight Pipe to Reach Exterior of Furnace.
To prevent property damage or personal injury due to fire, the following
instructions must be performed regarding gas connections, pressure testing,
location of shutoff valve and installation of gas piping.
NOTE: Never exceed specified pressures for testing. Higher pressure may cause
gas valve failure.
Disconnect this unit and shutoff valve from the gas supply piping system
before pressure testing the supply piping system with pressures in excess of ½
psig (3.48 kPa).
This unit must be isolated from the gas supply system by closing its manual
shutoff valve before pressure testing of gas supply piping system with test
pressures equal to or less than ½ psig (3.48 kPa). Propane Gas Tanks and
Piping
A gas detecting warning system is the only reliable way to detect a propane
gas leak. Rust can reduce the level of odorant in propane gas. Do not rely on
your sense of smell. Contact a local propane gas supplier about installing a
gas detecting warning system. If the presence of gas is suspected, follow the
instructions on Page 3 of this manual.
All propane gas equipment must conform to the safety standards of the National
Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 10 inch WC at the
furnace manifold with all gas appliances in operation. Maintaining proper gas
pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liquid, and “wetted
surface” area of the container or containers.
2. Proper pressure regulation (Two-stage regulation is recommended for both
cost and efficiency).
3. Pressure drop in lines between regulators, and between second stage
regulator and the appliance. Pipe size will depend on length of pipe run and
total load of all appliances.
13
Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas suppliers.
Circulating Air
WARNING
Use a pipe thread compound that is approved for natural gas and LP Gas.
Refer to the following illustration for typical propane gas installations and
piping.
First Stage Regulator
5 to 15 PSIG (20 PSIG Max.)
Continuous 11″ W.C.
200 PSIG Maximum
Second Stage Regulator
Never allow the products of combustion, including carbon monoxide, to enter
the return duct work or circulation air supply.
Duct systems and register sizes must be properly designed for the CFM and
external static pressure rating of the furnace. Ductwork should be designed in
accordance with the recommended methods of “Air Conditioning Contractors of
America” Manual D.
A duct system must be installed in accordance with Standards of the National
Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air
Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
Propane Gas Installation (Typ.) Figure 4
Propane Gas Piping Charts
Sizing Between First and Second Stage Regulator* Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Length,
Feet
3/8″
Tubing Size, O.D. Type L
1/2″
5/8″
3/4″
Nominal Pipe Size Schedule 40
7/8″
1/2″
3/4″
10
730
1,700 3,200 5,300 8,300 3,200 7,500
20
500
1,100 2,200 3,700 5,800 2,200 4,200
30
400
920
2,000 2,900 4,700 1,800 4,000
40
370
850
1,700 2,700 4,100 1,600 3,700
50
330
770
1,500 2,400 3,700 1,500 3,400
60
300
700
1,300 2,200 3,300 1,300 3,100
80
260
610
1,200 1,900 2,900 1,200 2,600
100
220
540
1,000 1,700 2,600 1,000 2,300
125
200
490
900
1,400 2,300
900
2,100
150
190
430
830
1,300 2,100
830
1,900
175
170
400
780
1,200 1,900
770
1,700
200
160
380
730
1,100 1,800
720
1,500
Sizing Between Second Stage and Appliance Regulator* Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or Tubing
Tubing Size, O.D. Type L
Nominal Pipe Size Schedule 40
Length,
Feet
3/8″ 1/2″ 5/8″ 3/4″ 7/8″ 1-1/8″ 1/2″ 3/4″ 1″ 1-1/4″
10
39 92 199 329 501 935 275 567 1,071 2,205
20
26 62 131 216 346 630 189 393 732 1,496
30
21 50 107 181 277 500 152 315 590 1,212
40
19 41 90 145 233 427 129 267 504 1,039
50
18 37 79 131 198 376 114 237 448 910
60
16 35 72 121 187 340 103 217 409 834
80
13 29 62 104 155 289 89 185 346 724
100
11 26 55 90 138 255 78 162 307 630
125
10 24 48 81 122 224 69 146 275 567
150
9
21 43 72 109 202 63 132 252 511
200
8
19 39 66 100 187 54 112 209 439
250
8
17 36 60 93 172 48 100 185 390
1-1/2″
3,307 2,299 1,858 1,559 1,417 1,275 1,066 976 866 787 665 590
A closed return duct system must be used, with the return duct connected to
the furnace. NOTE: Ductwork must never be attached to the back of the furnace.
For installations requiring more than 1800 CFM, use a bottom return or two
sided return. Supply and return connections to the furnace may be made with
flexible joints to reduce noise transmission. To prevent the blower from
interfering with combustion air or draft when a central return is used, a
connecting duct must be installed between the unit and the utility room wall.
A room, closet, or alcove must not be used as a return air chamber. When the
furnace is used in connection with a cooling unit, the furnace should be
installed in parallel with or on the upstream side of the cooling unit to
avoid condensation in the heating element. With a parallel flow arrangement,
the dampers or other means used to control the flow of air must be adequate to
prevent chilled air from entering the furnace and, if manually operated, must
be equipped with means to prevent operation of either unit unless the damper
is in the full heat or cool position.
When the furnace is installed without a cooling coil, it is recommended that a
removable access panel be provided in the outlet air duct. This opening shall
be accessible when the furnace is installed and shall be of such a size that
the heat exchanger can be viewed for visual light inspection or such that a
sampling probe can be inserted into the air stream. The access panel must be
made to prevent air leaks when the furnace is in operation.
When furnace duct(s) supply air outside the space containing the furnace, a
return air duct must terminate in the same space as the supply duct and be
sealed to the furnace casing.
When the furnace is heating, the temperature of the return air entering the
furnace must be between 55°F and 100°F.
Checking Duct Static
Refer to your furnace rating plate for the maximum ESP (external duct static)
rating.
14
Total external static refers to static pressure created by all components
external to the furnace cabinet. Cooling coils, filters, ducts, grilles,
registers must all be considered when reading your total external static
pressure. The supply duct pressure must be read between the furnace and the
cooling coil. This reading is usually taken by removing the “A” shaped block
off plate from the end on the coil; drilling a test hole in it and
reinstalling the block off plate. Take a duct static reading at the test hole.
Tape up the test hole after your test is complete. The negative pressure must
be read between the filter and the furnace blower.
Too much external static pressure will result in insufficient air that can
cause excessive temperature rise. This can cause limit switch tripping and
heat exchanger failure.
To determine total external duct static pressure, proceed as follows:
4. With clean filters in the furnace, use a manometer to measure the static
pressure of the return duct at the inlet of the furnace. (Negative Pressure)
5. Measure the static pressure of the supply duct. (Positive Pressure)
6. The difference between the two numbers is .4″ w.c.
Example: static reading from return duct = -.1″ w.c.
Filters – Read This Section Before Installing The Return Air Ductwork
Filters must be used with this furnace. Discuss filter maintenance with the
building owner. Filters do not ship with this furnace, but must be provided by
the installer. Filters must comply with UL900 or CAN/ULCS111 standards. Damage
or repairs due to the installation of the furnace without filters is not
covered under the warranty.
Upright Installations
Depending on the installation and/or customer preference, differing filter
arrangements can be applied. Filters can be installed in the central return
register or a side panel external filter rack kit (upflows), or the ductwork
above a downflow furnace. As an alternative, a media air filter or electronic
air cleaner can be used as the primary filter. Horizontal Installations
Filters must be installed in either the central return register or in the
return air duct work.
Circulation Air Filters
static reading from supply duct = .3″ w.c.
total external static pressure on this system = .4″ w.c.
NOTE: Both readings may be taken simultaneously and read directly on the
manometer if so desired. If an air
conditioner coil or Electronic Air Cleaner is used in conjunction with the
furnace, the readings must also include
these components, as shown in the following drawing.
7. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum listed on the furnace rating plate, check for closed dampers, registers, undersized or poorly laid out duct work.
Figure 6
Figure 7
Digital Manometer
Checking Static Pressure Figure 5
Figure 8
15
Figure 9
Thermostat Wiring Diagrams
W R G C Y ROOM THERMOSTAT
W R G C INTEGRATED FURNACE
Y2 Y/Y1
CONTROL MODULE
Figure 10
CY
REMOTE COOLING UNIT (SINGLE STAGE)
One of the most common causes of a problem in a forced
air heating system is a blocked or dirty filter. Circulating air filters must
be inspected monthly for dirt accumulation and replaced if necessary. Failure
to maintain clean filters can cause premature heat exchanger failure.
Thermostat – Single-Stage Heating with Single-Stage Cooling Figure 11
W R G C Y1 Y2 ROOM THERMOSTAT
A new home may require more frequent replacement until all construction dust and dirt is removed.
INTEGRATED FURNACE
W
R
G
C Y2 Y/Y1
CONTROL MODULE
Upflow Models
Minimum Recommended Filter Size
0403A
1 – 16 X 25 Side or 1 – 14 X 24 Bottom Return
0603A
1 – 16 X 25 Side or 14 X 24 Bottom Return
0603B
1 – 16 X 25 Side or Bottom Return
0604B
1 – 16 X 25 Side or Bottom Return
0803B
1 – 16 X 25 Side or Bottom Return
0804B
1 – 16 X 25 Side or Bottom Return
0804C
1 – 16 X 25 Side or Bottom Return
0805C
1 – 16 X 25 Side or Bottom Return¹
1005C
2 – 16 X 25 Side or 1 – 20 X 25 Bottom Return¹
1205D
2 – 16 X 25 Side or 1 – 24 X 24 Bottom Return¹
Downflow Models
0403A
2 – 10 X 20 or 1 – 14 X 25 Top Return
0603A
2 – 10 X 20 or 1 – 14 X 25 Top Return
0804B
2 – 14 X 20 or 1 – 16 X 25 Top Return
0805C 1005C
2 – 14 X 20 or 1 – 20 X 25 Top Return 2 – 14 X 20 or 1 – 20 X 25 Top Return
Larger filters may be used, filters may also be centrally located
¹ = Use 2 – 16 X 25 filters and two side returns or 20 X 25 filter on
bottom return if furnace is connected to a cooling unit over 4 tons
nominal capacity
A combination of one side & bottom may be used instead of both sides
Electrical
REMOTE COOLING UNIT
C Y1 Y2 (TWO STAGE)
Thermostat – Single-Stage Heating with Two-Stage Cooling Figure 12
Fossil Fuel Applications This furnace can be used in conjunction with a heat
pump in a fossil fuel application. A fossil fuel application refers to a
combined gas furnace and heat pump installation which uses an outdoor
temperature sensor to determine the most cost efficient means of heating (heat
pump or gas furnace).
A heat pump thermostat is required to properly use a single-stage furnace in
conjunction with a heat pump. Refer to the fossil fuel kit installation
instructions for additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit installation
instructions. All furnace connections must be made to the furnace two-stage
integrated control module and the “FURNACE” terminal strip on the fossil fuel
control board.
24 Volt Thermostat Wiring
Twinning
Important Note: Wiring routing must not interfere with circulator blower
operation, filter removal or routine maintenance. Low voltage connections can
be made through either the
right or left side panel. Thermostat wiring entrance holes
are located in the blower compartment. The following figure shows connections
for a “heat/cool system”.
Two furnaces of the same model may be twinned. The integrated control board has a 3/16″ terminal labeled “TWIN” located beside the low voltage thermostat connection strip. Twinning allows simultaneous operation of two furnaces and forces the indoor blower motors of each furnace to operate synchronously into a common duct system. Using the twinning function will require only field installed wiring with no
This furnace is equipped with a 40 VA transformer to facili- external kits or parts. The staging and speed tap options tate use with most cooling equipment. Consult the wiring di- must be set the same on both furnaces.
agram, located on the blower compartment door, for further
details of 115 Volt and 24 Volt wiring.
NOTE: Each furnace must be connected to it’s own 115 VAC
power supply. The L1 connection to each furnace must be in
phase (connected to circuit breakers on the same 115 VAC
service panel phase leg). To verify that the furnaces are in
phase, check from L1 to L1 on each furnace with a voltme-
ter. If the furnaces are in phase, the voltage between both
furnaces will be ZERO.
16
FURNACE 2
W R G C Y/Y1 Y2 TWIN
FURNACE 1
W R G C Y/Y1 Y2 TWIN
115 VAC HUM
115 VAC EAC
ROOM THERMOSTAT W R G C Y/Y1 Y2
COND UNIT CONTACTOR
COND UNIT CONTACTOR
Figure 13
115 Volt Line Connection of Accessories (Humidifier and Electronic Air
Cleaner)
The furnace integrated control module is equipped with line voltage accessory
terminals for controlling power to an optional field-supplied humidifier
and/or electronic air cleaner.
The accessory load specifications are noted in the chart:
Humidifier
1.0 Amp maximum at 120 VAC
Electronic Air Cleaner 1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any accessories. Follow the
humidifier or air cleaner manufacturers’ instructions for locating, mounting,
grounding, and controlling
these accessories. Accessory wiring connections are to be
made through the 1/4″ quick connect terminals provided on
the furnace integrated control module. The humidifier and electronic air
cleaner hot terminals are identified as HUM H and EAC H. The humidifier and
electronic air cleaner neutral terminals are identified as NEUTRAL. All field
wiring must conform to applicable codes. Connections should be made as shown.
W R G C Y
Accessories – Accessories Wiring Figure 14
Low Voltage Humidifier The furnace integrated control module is equipped with
a low voltage terminal for providing power to an optional field-supplied 24
volt humidifier. The 24V HUM terminal is energized any time the draft inducer
is powered. See connection diagram below.
NOTE: This is a 24 volt circuit only, the common connection must be on C
terminal of the low voltage terminal strip (where thermostat wires are
connected). Wiring for this circuit must NOT be connected to the line N
location where line voltage neutral wires are connected.
If it is necessary for the installer to supply additional line voltage wiring
to the inside of the furnace, the wiring must conform to all local codes, and
have a minimum temperature rating of 105°C. All line voltage wire splices must
be made inside the furnace junction box.
The integrated control module humidifier terminal (HUM H) is energized with
115 volts whenever the induced draft blower is energized. The integrated
control module electronic air cleaner terminal (EAC H) is energized with 115
volts whenever the circulator blower is energized. This terminal can also be
used to provide 115 volt power to a humidifier transformer. The remaining
primary transformer wire would be connected to the Line N on the control
board.
W R G C Y
24V HUM Terminal is energized when pressure switch is closed
24 VOLT HUM. & HUMIDISTAT
WARNING
HIGH VOLTAGE!
To avoid personal injury or death due to electrical shock, disconnect
electrical power before servicing or changing any electrical wiring.
17
24 Volt Humidifier Connection Figure 15
Furnace Startup
1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace. 3. Set the room thermostat
to the lowest possible setting. 4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which automatically
lights the burner. Do not try to light the burner by hand.
5. Move the furnace gas valve manual control to the OFF position.
6. Wait five minutes then smell for gas. Be sure check near the floor as some
types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow the safety
instructions in the Safety Considerations on page 2 of this manual. If you do
not smell gas after five minutes, move the furnace gas valve manual control to
the ON position.
8. Replace the burner compartment door. 9. Open the manual gas shutoff valve
external to the
furnace. 10. Turn on the electrical power to the furnace. 11. Adjust the
thermostat to a setting above room
temperature. 12. After the burners are lit, set the thermostat to desired
temperature.
Gas Heat Sequence of Operation
Call for Heat · On a call for heat, the thermostat contacts close & the
control board receives 24 VAC on the W terminal. · The control board
microcomputer runs its self-check routine. · The control verifies the limit
switch is closed (24 VAC on Pin 8 of the 12 Pin connector). · The control
verifies that pressure switch circuit is open (0 VAC on Pin 5). · The control
module performs a gas valve circuitry check to verify gas valve relay state
and presence of voltage at the valve. · The system will energize the Induced
draft blower. · The pre-purge period begins once the pressure switch is
detected closed (24 VAC on Pin 5). · After the completion of pre-purge, the
control will energize the igniter. · After completion of the ignitor warm-up
period: · The gas valve is energized. · The ignitor is de-energized as soon as
flame is sensed. · After 30 seconds the indoor blower is energized on heating
speed. · When the thermostat is satisfied: · The gas valve is de-energized. ·
The inducer remains energized for the post purge period (15 seconds). · The
indoor blower runs for the selected off delay period (90 seconds by default,
adjustable from 30 180 seconds).
Heating Mode Speed Selection
To change the main blower speed in HEATING mode, follow the following steps:
- Press left or right button till LED displays “gA1 “(for single
stage HEATING). Press center button and LED will display the selected speed number as Fxx (xx: Blower speed number). 2. The control shall rotate available speed number every time Left/Right switches are pressed. Table below shows the available speeds for Low & High heat mode. 3. When the center switch is pressed, the current displayed speed shall be selected, and control shall apply the newly selected speed in next heating call.
NOTE: Always refer to the Heating Chart to choose from available heating speeds
THERMOSTAT CALL
AVAILABLE SPEEDS
F01
W/W1
F02 (DEFAULT)
F03
F04
Heating Speed Table for 1 Stage IFC
Continuous Fan Mode Speed Selection
To change the main blower speed in circulation mode, follow the following
steps: 1. Press the left or right switch until LED displays “FSd”.
Press the center switch and LED will display the selected speed number as Fxx
(xx: Blower speed number from 1 to 9). F01 is the default speed for
circulation. 2. The control will rotate available speed number every time
left/right switches are pressed. All 9 speeds are available for circulation.
3. When the center switch is pressed, the current displayed speed will be
selected, and control will immediately apply that speed setting.
THERMOSTAT CALL
AVAILABLE SPEEDS
F01 (DEFAULT)
F02
F03
F04
G
F05
F06
F07
F08
F09
Circulation Speed Table
18
Cooling Mode Sequence of Operation
Low Stage Cooling Mode Sequence: On a call for low stage cooling, the Y/Y1 or
Y/Y1 and G thermostat contacts close signaling the furnace control board with
24 VAC on Y/Y1 or Y/Y1 and G terminals.
· The 7-Segment will display the cool mode: · The compressor and condenser fan
are energized. · The circulator fan is energized at low cool speed after
a cool on delay. The electronic air cleaner will also be energized. · After
the thermostat is satisfied, the compressor is deenergized and the Cool Mode
Fan Off Delay period begins. · Following the Cool Mode Fan Off Delay period,
the cool circulator and air cleaner relay are de-energized.
2nd Stage Cooling Mode Sequence: On a call for 2nd stage cooling, the Y2 or Y2
and G thermostat contacts close signaling the furnace control board with 24
VAC on Y2 or Y2 and G terminals.
· The 7-Segment will display the cool mode: · The compressor and condenser fan
are energized. · The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner will also be energized. · After the
thermostat is satisfied, the compressor is de-energized and the Cool Mode Fan
Off Delay period begins. · Following the Cool Mode Fan Off Delay period, the
cool circulator and air cleaner relay are de-energized
Cooling Mode Speed Selection
To change the main blower speed in COOLING mode, follow the following steps:
- Press the left or right switch until LED displays “AC1
“(for single stage COOLING) or “AC2 “(for two-stage COOLING). Press the center switch and LED will display the selected speed number as Fxx (xx: Blower speed number from 1 to 9). 2. The control will rotate available speed number every time left/right switches are pressed. All 9 speeds are available for both Single and Two Stage cooling. 3. When the center switch is pressed, the current displayed speed will be selected, and control will apply the newly selected speed in next cooling call.
THERMOSTAT CALL AVAILABLE SPEEDS
F01
F02
F03
F04
Y2
F05 (DEFAULT)
F06
F07
F08
F09
Two-Stage Cooling Speed Table for 2 Stage IFC
Furnace Shutdown
1. Set the thermostat to the lowest setting. The integrated control will
close the gas valve and extinguish flame. Following a 15 second delay, the
induced draft blower will be de-energized. After the blower off delay time
expires, the blower de-energizes.
2. Remove the burner compartment door and move the furnace gas valve manual
control to the OFF position.
3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.
Gas Supply Pressure Measurement Gas Valve ON/OFF Selector Switch
Inlet Pressure
OUTLET
INLET
Regulator Cover Screw
Outlet Pressure
White-Rogers Model 36J22Y-204 Figure 16
Regulator Cover Screw
THERMOSTAT CALL AVAILABLE SPEEDS
F01
F02
F03
Y/Y1
F04 (DEFAULT) F05
F06
F07
F08
F09
Single-Stage Cooling Speed Table for 2 Stage IFC
.
White-Rogers Model 36J22Y-204 Connected to Manometer Figure 17
19
INLET GAS SUPPLY PRESSURE Natural Gas Minimum: 4.5″ w.c. Maximum: 10.0″ w.c.
Propane Gas Minimum: 11.0″ w.c. Maximum: 13.0″ w.c.
CAUTION
To prevent unreliable operation or equipment damage, the gas manifold pressure
must be as specified on the unit rating plate with all other household gas
fired appliances operating.
2. Turn off all electrical power to the system. 3. Outlet pressure tap
connections:
White-Rodgers 36J54 valve: Back outlet pressure test screw (inlet/outlet
pressure tap) out one turn (counterclockwise, not more than one turn). 4.
Attach a hose and manometer to outlet pressure tap. 5. Turn ON the gas supply.
The line pressure supplied to the gas valve must be within the range specified
below. The supply pressure can be measured at the gas valve inlet pressure tap
or at a hose fitting installed in the gas piping drip leg. The supply pressure
must be measured with the burners operating. To measure the gas supply
pressure, use the following procedure.
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the
furnace.
2. Connect a calibrated manometer (or appropriate gas pressure gauge) at
either the gas valve inlet pressure tap or the gas piping drip leg. See White-
Rodgers 36J54 gas valve (Figure 17) to locate the inlet pressure tap.
NOTE: If using the inlet pressure tap on the White-Rodgers 36J54 gas valve,
then use the 36G/J Valve Pressure Check Kit, Part No. 0151K00000S.
3. Turn ON the gas supply and operate the furnace and all other gas consuming
appliances on the same gas supply line.
4. Measure furnace gas supply pressure with burners firing. Supply pressure
must be within the range specified in the Inlet Gas Supply Pressure table.
.
Measuring Inlet Gas Pressure (Alt. Method) Figure 18
NOTE: When converting from natural gas to L.P. consult your distributor for
proper conversion kit.
If supply pressure differs from table, make the necessary adjustments to
pressure regulator, gas piping size, etc., and/
or consult with local gas utility. 5. Turn OFF gas to furnace at the manual
shutoff valve and disconnect manometer. Reinstall plug before turning on
gas to furnace. 6. Turn OFF any unnecessary gas appliances stated in
step three.
Manifold Gas Pressure
Gas
Range
Natural
High Stage 3.2 – 3.8″ w.c.
Nominal 3.5″ w.c.
Propane
High Stage 9.7 – 10.3″ w.c. 10.0″ w.c.
Gas Manifold Pressure Measurement and Adjustment
CAUTION
To prevent unreliable operation or equipment damage, the gas manifold pressure
must be as specified on the unit rating plate. Only minor adjustments should
be made by adjusting the gas valve pressure regulator.
Only small variations in gas pressure should be made by adjusting the gas
valve pressure regulator. The manifold pressure must be measured with the
burners operating. To measure and adjust the manifold pressure, use the
following procedure.
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the
furnace.
20
Airflow Tables
MODEL
THERMOSTAT CALL
M9S800403A
Y/Y1
M9S800603A
Y/Y1
M9S800603B
Y/Y1
M9S800604B
Y/Y1
M9S800803B
Y/Y1
M9S800804B
Y/Y1
M9S800804C
Y/Y1
M9S800805C
Y/Y1
M9S801005C
Y/Y1
M9S801205D
Y/Y1
TAP #
F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01
F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02
F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03
F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^
F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09
0.1 CFM 658 749 925 882 1330 1130 1158 1270 1417 659 1268 1087 1118 1308 868
922 1382 1492 720 1289 1125 1252 922 1146 1370 1413 1544 764 1287 1339 1396
1185 1500 1591 1675 1790
710 1298 1209 1138 1391 977 1036 1456 1533
841 1141 1311 1395 1490 1553 1593 1776 1853
831 1214 1303 1426 1518 1588 1710 1785 1845
837 1316 1353 1587 1731 1794 1861 1910 2110
802 1405 1574 1619 1688 1811 1857 1892 2116
851 1677 1537 1416 1154 1806 1869 1947 2107
LOW STAGE COOLING AIFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.2
0.3
0.4
0.5
0.6
0.7
CFM
CFM
CFM
CFM
CFM
CFM
585 697 881 841 1295 1090 1113 1235 1380 599 1221 1044 1070 1262 823 877 1341 1448 660 1260 1089 1198 872 1113 1345 1386 1500 695 1235 1301 1346 1135 1460 1539
545 652 840 800 1273 1059 1090 1208 1359 542 1188 1008 1033 1224 780 835 1311 1409 614 1232 1052 1153 830 1076 1317 1360 1459 630 1191 1258 1298 1088 1420 1493
495 607 800 760 1251 1022 1057 1179 1336 490 1154 973 997 1197 741 795 1291 1381 542 1194 1013 1110 786 1039 1286 1330 1419 559 1147 1217 1257 1040 1360 1454
444 554 760 719 1223 991 1024 1147 1314 437 1122 938 963 1167 699 757 1263 1354 468 1161 973 1069 736 1002 1260 1302 1387 485 1104 1174 1217 992 1380 1416
390 509 721 678 1195 957 996 1119 1288 383 1091 905 929 1141 662 718 1234 1332 413 1125 947 1028 683 969 1224 1270 1349 415 1062 1131 1175 947 1294 1379
332 459 681 641 1168 926 964 1088 1261 320 1060 871 896 1117 624 679 1206 1310 359 1087 909 990 616 933 1187 1242 1317 358 1020 1090 1135 901 1256 1347
1622
1583
1545
1510
1474
1440
1741
1701
1668
1631
1599
1567
646
580
515
432
367
314
1255
1216
1178
1140
1102
1067
1166
1124
1083
1045
1005
964
1091
1045
1001
959
920
876
1352
1314
1278
1241
1209
1175
931
880
836
785
734
683
985
940
895
848
799
751
1414
1376
1341
1302
1270
1238
1488
1452
1415
1383
1350
1317
657
595
522
439
367
315
1089
1045
1001
958
914
869
1267
1226
1189
1150
1114
1072
1347
1309
1270
1233
1199
1164
1447
1407
1373
1336
1303
1269
1510
1469
1435
1401
1368
1335
1548
1508
1474
1440
1409
1376
1735
1695
1661
1628
1601
1570
1812
1773
1739
1708
1679
1650
750
671
588
501
405
348
1158
1103
1045
989
936
883
1249
1191
1136
1081
1028
974
1375
1324
1277
1229
1177
1124
1465
1418
1372
1328
1284
1237
1539
1494
1447
1401
1358
1313
1666
1632
1595
1554
1512
1473
1751
1717
1675
1639
1596
1557
1805
1771
1733
1695
1655
1618
752
671
576
501
426
361
1270
1218
1166
1114
1061
1000
1323
1286
1235
1183
1131
1085
1544
1506
1459
1416
1372
1323
1673
1632
1587
1546
1506
1463
1744
1709
1671
1632
1591
1555
1805
1761
1720
1681
1642
1603
1873
1839
1798
1761
1723
1686
2055
2035
2003
1973
1946
1907
724
637
551
468
389
342
1356
1308
1262
1210
1182
1155
1531
1484
1440
1392
1357
1306
1575
1526
1489
1446
1404
1355
1641
1600
1557
1513
1477
1428
1769
1730
1686
1649
1610
1572
1812
1774
1733
1697
1662
1622
1850
1805
1774
1735
1692
1658
2073
2039
2005
1981
1945
1909
774
692
615
535
470
411
1629
1583
1540
1498
1449
1399
1489
1444
1404
1365
1322
1272
1365
1315
1267
1220
1163
1106
1098
1043
983
932
874
819
1764
1729
1688
1654
1615
1578
1816
1773
1731
1693
1661
1629
1903
1865
1833
1802
1769
1743
2066
2030
1996
1963
1932
1899
NOTE: ^ Default Speed
21
GM9S80
0.8 CFM 151 406 645 602 1142 895 935 1060 1238 N/A 1029 841 865 1089 584 642
1177 1288 313 1073 863 953 565 891 1168 1211 1286 N/A 979 1048 1098 855 1219
1311 1402 1532 274 1028 923 832 1140 626 705 1200 1286 N/A 823 1034 1125 1237
1300 1343 1542 1623 300 823 928 1078 1195 1267 1431 1516 1576 315 962 1040
1281 1421 1513 1565 1648 1890 294 1102 1256 1313 1381 1525 1586 1621 1879 359
1349 1211 1048 755 1535 1589 1708 1867
Airflow Tables
MODEL
THERMOSTAT CALL
M9S800403A
Y2
M9S800603A
Y2
M9S800603B
Y2
M9S800604B
Y2
M9S800803B
Y2
M9S800804B
Y2
M9S800804C
Y2
M9S800805C
Y2
M9S801005C
Y2
M9S801205D
Y2
TAP #
F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01
F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02
F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03
F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04
F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09
HIGH STAGE COOLING AIFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
CFM
CFM
CFM
CFM
CFM
CFM
CFM
658
585
545
495
444
390
332
749
697
652
607
554
509
459
925
881
840
800
760
721
681
882
841
800
760
719
678
641
1330
1295
1273
1251
1223
1195
1168
1130
1090
1059
1022
991
957
926
1158
1113
1090
1057
1024
996
964
1270
1235
1208
1179
1147
1119
1088
1417
1380
1359
1336
1314
1288
1261
659
599
542
490
437
383
320
1268
1221
1188
1154
1122
1091
1060
1087
1044
1008
973
938
905
871
1118
1070
1033
997
963
929
896
1308
1262
1224
1197
1167
1141
1117
868
823
780
741
699
662
624
922
877
835
795
757
718
679
1382
1341
1311
1291
1263
1234
1206
1492
1448
1409
1381
1354
1332
1310
720
660
614
542
468
413
359
1289
1260
1232
1194
1161
1125
1087
1125
1089
1052
1013
973
947
909
1252
1198
1153
1110
1069
1028
990
922
872
830
786
736
683
616
1146
1113
1076
1039
1002
969
933
1370
1345
1317
1286
1260
1224
1187
1413
1386
1360
1330
1302
1270
1242
1544
1500
1459
1419
1387
1349
1317
764
695
630
559
485
415
358
1287
1235
1191
1147
1104
1062
1020
1339
1301
1258
1217
1174
1131
1090
1396
1346
1298
1257
1217
1175
1135
1185
1135
1088
1040
992
947
901
1500
1460
1420
1360
1380
1294
1256
1591
1539
1493
1454
1416
1379
1347
1675
1622
1583
1545
1510
1474
1440
1790
1741
1701
1668
1631
1599
1567
710
646
580
515
432
367
314
1298
1255
1216
1178
1140
1102
1067
1209
1166
1124
1083
1045
1005
964
1138
1091
1045
1001
959
920
876
1391
1352
1314
1278
1241
1209
1175
977
931
880
836
785
734
683
1036
985
940
895
848
799
751
1456
1414
1376
1341
1302
1270
1238
1533
1488
1452
1415
1383
1350
1317
841
657
595
522
439
367
315
1141
1089
1045
1001
958
914
869
1311
1267
1226
1189
1150
1114
1072
1395
1347
1309
1270
1233
1199
1164
1490
1447
1407
1373
1336
1303
1269
1553
1510
1469
1435
1401
1368
1335
1593
1548
1508
1474
1440
1409
1376
1776
1735
1695
1661
1628
1601
1570
1853
1812
1773
1739
1708
1679
1650
831
750
671
588
501
405
348
1214
1158
1103
1045
989
936
883
1303
1249
1191
1136
1081
1028
974
1426
1375
1324
1277
1229
1177
1124
1518
1465
1418
1372
1328
1284
1237
1588
1539
1494
1447
1401
1358
1313
1710
1666
1632
1595
1554
1512
1473
1785
1751
1717
1675
1639
1596
1557
1845
1805
1771
1733
1695
1655
1618
837
752
671
576
501
426
361
1316
1270
1218
1166
1114
1061
1000
1353
1323
1286
1235
1183
1131
1085
1587
1544
1506
1459
1416
1372
1323
1731
1673
1632
1587
1546
1506
1463
1794
1744
1709
1671
1632
1591
1555
1861
1805
1761
1720
1681
1642
1603
1910
1873
1839
1798
1761
1723
1686
2110
2055
2035
2003
1973
1946
1907
802
724
637
551
468
389
342
1405
1356
1308
1262
1210
1182
1155
1574
1531
1484
1440
1392
1357
1306
1619
1575
1526
1489
1446
1404
1355
1688
1641
1600
1557
1513
1477
1428
1811
1769
1730
1686
1649
1610
1572
1857
1812
1774
1733
1697
1662
1622
1892
1850
1805
1774
1735
1692
1658
2116
2073
2039
2005
1981
1945
1909
851
774
692
615
535
470
411
1677
1629
1583
1540
1498
1449
1399
1537
1489
1444
1404
1365
1322
1272
1416
1365
1315
1267
1220
1163
1106
1154
1098
1043
983
932
874
819
1806
1764
1729
1688
1654
1615
1578
1869
1816
1773
1731
1693
1661
1629
1947
1903
1865
1833
1802
1769
1743
2107
2066
2030
1996
1963
1932
1899
NOTE: ^ Default Speed
22
GM9S80
0.8 CFM 151 406 645 602 1142 895 935 1060 1238 N/A 1029 841 865 1089 584 642
1177 1288 313 1073 863 953 565 891 1168 1211 1286 N/A 979 1048 1098 855 1219
1311 1402 1532 274 1028 923 832 1140 626 705 1200 1286 N/A 823 1034 1125 1237
1300 1343 1542 1623 300 823 928 1078 1195 1267 1431 1516 1576 315 962 1040
1281 1421 1513 1565 1648 1890 294 1102 1256 1313 1381 1525 1586 1621 1879 359
1349 1211 1048 755 1535 1589 1708 1867
Airflow Tables
MODEL
THERMOSTAT CALL
M9S800403A
G
M9S800603A
G
M9S800603B
G
M9S800604B
G
M9S800803B
G
M9S800804B
G
M9S800804C
G
M9S800805C
G
M9S801005C
G
M9S801205D
G
TAP #
F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01
F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02
F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03
F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04
F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09
0.1 CFM 658 749 925 882 1330 1130 1158 1270 1417 659 1268 1087 1118 1308 868 922 1382 1492 720 1289 1125 1252 922 1146 1370 1413 1544 764 1287 1339 1396 1185 1500 1591 1675 1790 710 1298 1209 1138 1391 977 1036 1456 1533 841 1141 1311 1395 1490 1553 1593 1776 1853 831 1214 1303 1426 1518 1588 1710 1785 1845 837 1316 1353 1587 1731 1794 1861 1910 2110 802 1405 1574 1619 1688 1811 1857 1892 2116 851 1677 1537 1416 1154 1806 1869 1947 2107
CIRCULATION AIRFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.2
0.3
0.4
0.5
0.6
0.7
CFM
CFM
CFM
CFM
CFM
CFM
585 697 881 841 1295 1090 1113 1235 1380 599 1221 1044 1070 1262 823 877 1341 1448 660 1260 1089 1198 872 1113 1345 1386 1500
545 652 840 800 1273 1059 1090 1208 1359 542 1188 1008 1033 1224 780 835 1311 1409 614 1232 1052 1153 830 1076 1317 1360 1459
495 607 800 760 1251 1022 1057 1179 1336 490 1154 973 997 1197 741 795 1291 1381 542 1194 1013 1110 786 1039 1286 1330 1419
444 554 760 719 1223 991 1024 1147 1314 437 1122 938 963 1167 699 757 1263 1354 468 1161 973 1069 736 1002 1260 1302 1387
390 509 721 678 1195 957 996 1119 1288 383 1091 905 929 1141 662 718 1234 1332 413 1125 947 1028 683 969 1224 1270 1349
332 459 681 641 1168 926 964 1088 1261 320 1060 871 896 1117 624 679 1206 1310 359 1087 909 990 616 933 1187 1242 1317
695 1235 1301 1346 1135 1460 1539 1622 1741 646 1255 1166 1091 1352 931 985 1414 1488 657 1089 1267 1347 1447 1510 1548 1735 1812
630 1191 1258 1298 1088 1420 1493 1583 1701 580 1216 1124 1045 1314 880 940 1376 1452 595 1045 1226 1309 1407 1469 1508 1695 1773
559 1147 1217 1257 1040 1360 1454 1545 1668 515 1178 1083 1001 1278 836 895 1341 1415 522 1001 1189 1270 1373 1435 1474 1661 1739
485 1104 1174 1217 992 1380 1416 1510 1631 432 1140 1045 959 1241 785 848 1302 1383 439 958 1150 1233 1336 1401 1440 1628 1708
415 1062 1131 1175 947 1294 1379 1474 1599 367 1102 1005 920 1209 734 799 1270 1350 367 914 1114 1199 1303 1368 1409 1601 1679
358 1020 1090 1135 901 1256 1347 1440 1567 314 1067 964 876 1175 683 751 1238 1317 315 869 1072 1164 1269 1335 1376 1570 1650
750 1158 1249 1375 1465 1539 1666 1751 1805 752 1270 1323 1544 1673 1744 1805 1873 2055 724 1356 1531 1575 1641 1769 1812 1850 2073
671 1103 1191 1324 1418 1494 1632 1717 1771 671 1218 1286 1506 1632 1709 1761 1839 2035 637 1308 1484 1526 1600 1730 1774 1805 2039
588 1045 1136 1277 1372 1447 1595 1675 1733 576 1166 1235 1459 1587 1671 1720 1798 2003 551 1262 1440 1489 1557 1686 1733 1774 2005
501 989 1081 1229 1328 1401 1554 1639 1695 501 1114 1183 1416 1546 1632 1681 1761 1973 468 1210 1392 1446 1513 1649 1697 1735 1981
405 936 1028 1177 1284 1358 1512 1596 1655 426 1061 1131 1372 1506 1591 1642 1723 1946 389 1182 1357 1404 1477 1610 1662 1692 1945
348 883 974 1124 1237 1313 1473 1557 1618 361 1000 1085 1323 1463 1555 1603 1686 1907 342 1155 1306 1355 1428 1572 1622 1658 1909
774 1629 1489 1365 1098 1764 1816 1903 2066
692 1583 1444 1315 1043 1729 1773 1865 2030
615 1540 1404 1267 983 1688 1731 1833 1996
535 1498 1365 1220 932 1654 1693 1802 1963
470 1449 1322 1163 874 1615 1661 1769 1932
411 1399 1272 1106 819 1578 1629 1743 1899
23
GM9S80
0.8 CFM 151 406 645 602 1142 895 935 1060 1238 N/A 1029 841 865 1089 584 642
1177 1288 313 1073 863 953 565 891 1168 1211 1286 N/A 979 1048 1098 855 1219
1311 1402 1532 274 1028 923 832 1140 626 705 1200 1286 N/A 823 1034 1125 1237
1300 1343 1542 1623 300 823 928 1078 1195 1267 1431 1516 1576 315 962 1040
1281 1421 1513 1565 1648 1890 294 1102 1256 1313 1381 1525 1586 1621 1879 359
1349 1211 1048 755 1535 1589 1708 1867
Airflow Tables
MODEL
THERMOSTAT TAP #
0.1
CALL
CFM RISE
F01^^ 658 N/A
M9S800403A
W/W1
F02^ 749 40 F03 925 32
F04 882 34
F01^^ 659 N/A
M9S800603A
W/W1
F02^ 1268 35 F03 1087 41
F04 1118 40
F01^^ 720 N/A
M9S800603B
W/W1
F02^ 1289 34 F03 1125 40
F04 1252 36
F01^^ 764 N/A
M9S800604B
W/W1
F02^ 1287 35 F03 1339 33
F04 1396 32
F01^^ 710 N/A
M9S800803B
W/W1
F02^ 1298 46 F03 1209 49
F04 1138 52
F01^^ 841 N/A
M9S800804B
W/W1
F02^ 1141 52 F03 1311 45
F04 1395 42
F01^^ 831 N/A
M9S800804C
W/W1
F02^ 1214 49 F03 1303 45
F04 1426 42
F01^^ 837 N/A
M9S800805C
W/W1
F02^ 1316 45 F03 1353 44
F04 1587 37
F01^^ 802 N/A
M9S801005C
W/W1
F02^ 1405 53 F03 1574 47
F04 1619 46
F01^^ 851 N/A
M9S801205D
W/W1
F02^ 1677 53 F03 1537 58
F04^^ 1416 N/A
HEATING AIFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.2
0.3
0.4
0.5
0.6
CFM RISE CFM RISE CFM RISE CFM RISE CFM
585 N/A 545 N/A 495 N/A 444 N/A 390
697 42 652 45 607 49 554 53 509
881 34 840 35 800 37 760 39 721
841 35 800 37 760 39 719 41 678
599 N/A 542 N/A 490 N/A 437 N/A 383
1221 36 1188 37 1154 38 1122 40 1091
1044 43 1008 44 973 46 938 47 905
1070 42 1033 43 997 45 963 46 929
660 N/A 614 N/A 542 N/A 468 N/A 413
1260 35 1232 36 1194 37 1161 38 1125
1089 41 1052 42 1013 44 973 46 947
1198 37 1153 39 1110 40 1069 42 1028
695 N/A 630 N/A 559 N/A 485 N/A 415
1235 36 1191 37 1147 39 1104 40 1062
1301 34 1258 35 1217 37 1174 38 1131
1346 33 1298 34 1257 35 1217 37 1175
646 N/A 580 N/A 515 N/A 432 N/A 367
1255 47 1216 49 1178 50 1140 52 1102
1166 51 1124 53 1083 55 1045 57 1005
1091 54 1045 57 1001 59 959 62 920
657 N/A 595 N/A 522 N/A 439 N/A 367
1089 54 1045 57 1001 59 958 62 914
1267 47 1226 48 1189 50 1150 52 1114
1347 44 1309 45 1270 47 1233 48 1199
750 N/A 671 N/A 588 N/A 501 N/A 405
1158 51 1103 54 1045 57 989 60 936
1249 47 1191 50 1136 52 1081 55 1028
1375 43 1324 45 1277 46 1229 48 1177
752 N/A 671 N/A 576 N/A 501 N/A 426
1270 47 1218 49 1166 51 1114 53 1061
1323 45 1286 46 1235 48 1183 50 1131
1544 38 1506 39 1459 41 1416 42 1372
724 N/A 637 N/A 551 N/A 468 N/A 389
1356 55 1308 57 1262 59 1210 61 1155
1531 48 1484 50 1440 51 1392 53 1357
1575 47 1526 49 1489 50 1446 51 1404
774 N/A 692 N/A 615 N/A 535 N/A 470
1629 55 1583 56 1540 58 1498 59 1449
1489 60 1444 62 1404 63 1365 65 1322
1365 N/A 1315 N/A 1267 N/A 1220 N/A 1163
GM9S80
0.7 CFM 332 459 681 641 320 1060 871 896 359 1087 909 990 358 1020 1090 1135 314 1067 964 876 315 869 1072 1164 348 883 974 1124 361 1000 1085 1323 342 1102 1306 1355 411 1399 1272 1106
0.8 CFM 151 406 645 602 N/A 1029 841 865 313 1073 863 953 N/A 979 1048 1098 274 1028 923 832 N/A 823 1034 1125 300 823 928 1078 315 962 1040 1281 294 1057 1256 1313 359 1349 1211 1048
TEMP RANGE 25-55 20-50 20-50 20-50 35-65 35-65 35-65 35-65 35-65 40-70
NOTE: ^DEFAULT & RECOMMENDED ^^NOT RECOMMENDED FOR
24
Airflow Tables
MODEL
THERMOSTAT CALL
C9S800403A Y/Y1
C9S800603A Y/Y1
C9S800804B Y/Y1
C9S800805C Y/Y1
C9S801005C Y/Y1
TAP #
F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01
F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01
F02
F03
F04^
F05
F06
F07
F08
F09
NOTE: ^ Default Speed
GC9S80
LOW STAGE COOLING AIFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
712
663
610
559
514
462
395
337
1120
1081
1053
1022
990
955
918
887
929
891
858
815
772
737
699
664
1073
1031
1003
969
922
891
854
822
1212
1198
1161
1138
1103
1076
1037
1007
871
830
789
743
702
665
628
583
825
784
741
694
650
609
563
520
1274
1252
1220
1195
1169
1145
1110
1084
1362
1342
1307
1273
1252
1237
1211
1185
706
655
604
555
505
455
395
328
1035
991
951
913
876
844
807
770
932
887
844
806
767
728
689
651
897
851
808
764
725
686
646
603
1123
1077
1041
1006
973
941
907
875
1155
1113
1074
1039
1006
974
945
913
1255
1214
1181
1147
1116
1087
1056
1028
1388
1331
1298
1266
1235
1207
1179
1151
1421
1380
1348
1318
1289
1262
1233
1207
760
697
636
569
481
402
349
300
1286
1238
1196
1157
1117
1077
1036
998
1393
1348
1308
1270
1230
1196
1158
1123
1459
1414
1371
1336
1297
1264
1229
1193
1753
1713
1677
1642
1611
1576
1549
1518
1309
1261
1218
1182
1142
1103
1064
1025
1580
1534
1495
1459
1429
1390
1356
1324
1523
1483
1438
1403
1370
1336
1299
1266
1643
1599
1562
1525
1491
1462
1431
1394
1022
813
674
585
511
431
334
282
1453
1407
1332
1259
1190
1143
1064
1003
1176
1105
1020
935
864
797
729
673
1710
1660
1613
1560
1505
1424
1353
1296
1843
1786
1747
1690
1643
1575
1497
1435
1859
1819
1779
1734
1691
1641
1593
1520
2028
1982
1946
1907
1861
1814
1749
1683
2096
2045
2006
1974
1927
1882
1818
1765
2203
2170
2138
2113
2074
2032
1990
1948
956
777
675
587
468
377
324
296
1460
1404
1350
1299
1251
1203
1150
1098
1561
1499
1441
1385
1336
1289
1243
1197
1628
1571
1521
1472
1425
1380
1337
1291
1714
1659
1611
1564
1519
1473
1432
1387
1833
1784
1735
1688
1645
1605
1562
1520
1899
1853
1804
1761
1720
1681
1640
1602
1926
1894
1849
1807
1764
1720
1683
1642
2222
2174
2132
2090
2053
2013
1976
1944
25
Airflow Tables
MODEL
THERMOSTAT CALL
C9S800403A
Y2
C9S800603A
Y2
C9S800804B
Y2
C9S800805C
Y2
C9S801005C
Y2
TAP #
F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01
F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02
F03 F04 F05^ F06 F07 F08 F09
NOTE: ^ Default Speed
GC9S80
HIGH STAGE COOLING AIFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
712
663
610
559
514
462
395
337
1120
1081
1053
1022
990
955
918
887
929
891
858
815
772
737
699
664
1073
1031
1003
969
922
891
854
822
1212
1198
1161
1138
1103
1076
1037
1007
871
830
789
743
702
665
628
583
825
784
741
694
650
609
563
520
1274
1252
1220
1195
1169
1145
1110
1084
1362
1342
1307
1273
1252
1237
1211
1185
706
655
604
555
505
455
395
328
1035
991
951
913
876
844
807
770
932
887
844
806
767
728
689
651
897
851
808
764
725
686
646
603
1123
1077
1041
1006
973
941
907
875
1155
1113
1074
1039
1006
974
945
913
1255
1214
1181
1147
1116
1087
1056
1028
1388
1331
1298
1266
1235
1207
1179
1151
1421
1380
1348
1318
1289
1262
1233
1207
760
697
636
569
481
402
349
300
1286
1238
1196
1157
1117
1077
1036
998
1393
1348
1308
1270
1230
1196
1158
1123
1459
1414
1371
1336
1297
1264
1229
1193
1753
1713
1677
1642
1611
1576
1549
1518
1309
1261
1218
1182
1142
1103
1064
1025
1580
1534
1495
1459
1429
1390
1356
1324
1523
1483
1438
1403
1370
1336
1299
1266
1643
1599
1562
1525
1491
1462
1431
1394
1022
813
674
585
511
431
334
282
1453
1407
1332
1259
1190
1143
1064
1003
1176
1105
1020
935
864
797
729
673
1710
1660
1613
1560
1505
1424
1353
1296
1843
1786
1747
1690
1643
1575
1497
1435
1859
1819
1779
1734
1691
1641
1593
1520
2028
1982
1946
1907
1861
1814
1749
1683
2096
2045
2006
1974
1927
1882
1818
1765
2203
2170
2138
2113
2074
2032
1990
1948
956
777
675
587
468
377
324
296
1460
1404
1350
1299
1251
1203
1150
1098
1561
1499
1441
1385
1336
1289
1243
1197
1628
1571
1521
1472
1425
1380
1337
1291
1714
1659
1611
1564
1519
1473
1432
1387
1833
1784
1735
1688
1645
1605
1562
1520
1899
1853
1804
1761
1720
1681
1640
1602
1926
1894
1849
1807
1764
1720
1683
1642
2222
2174
2132
2090
2053
2013
1976
1944
26
Airflow Tables
MODEL
THERMOSTAT CALL
C9S800403A
G
C9S800603A
G
C9S800804B
G
C9S800805C
G
C9S801005C
G
TAP #
F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01
F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02
F03 F04 F05 F06 F07 F08 F09
GC9S80
CIRCULATION AIFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
712
663
610
559
514
462
395
337
1120
1081
1053
1022
990
955
918
887
929
891
858
815
772
737
699
664
1073
1031
1003
969
922
891
854
822
1212
1198
1161
1138
1103
1076
1037
1007
871
830
789
743
702
665
628
583
825
784
741
694
650
609
563
520
1274
1252
1220
1195
1169
1145
1110
1084
1362
1342
1307
1273
1252
1237
1211
1185
706
655
604
555
505
455
395
328
1035
991
951
913
876
844
807
770
932
887
844
806
767
728
689
651
897
851
808
764
725
686
646
603
1123
1077
1041
1006
973
941
907
875
1155
1113
1074
1039
1006
974
945
913
1255
1214
1181
1147
1116
1087
1056
1028
1388
1331
1298
1266
1235
1207
1179
1151
1421
1380
1348
1318
1289
1262
1233
1207
760
697
636
569
481
402
349
300
1286
1238
1196
1157
1117
1077
1036
998
1393
1348
1308
1270
1230
1196
1158
1123
1459
1414
1371
1336
1297
1264
1229
1193
1753
1713
1677
1642
1611
1576
1549
1518
1309
1261
1218
1182
1142
1103
1064
1025
1580
1534
1495
1459
1429
1390
1356
1324
1523
1483
1438
1403
1370
1336
1299
1266
1643
1599
1562
1525
1491
1462
1431
1394
1022
813
674
585
511
431
334
282
1453
1407
1332
1259
1190
1143
1064
1003
1176
1105
1020
935
864
797
729
673
1710
1660
1613
1560
1505
1424
1353
1296
1843
1786
1747
1690
1643
1575
1497
1435
1859
1819
1779
1734
1691
1641
1593
1520
2028
1982
1946
1907
1861
1814
1749
1683
2096
2045
2006
1974
1927
1882
1818
1765
2203
2170
2138
2113
2074
2032
1990
1948
956
777
675
587
468
377
324
296
1460
1404
1350
1299
1251
1203
1150
1098
1561
1499
1441
1385
1336
1289
1243
1197
1628
1571
1521
1472
1425
1380
1337
1291
1714
1659
1611
1564
1519
1473
1432
1387
1833
1784
1735
1688
1645
1605
1562
1520
1899
1853
1804
1761
1720
1681
1640
1602
1926
1894
1849
1807
1764
1720
1683
1642
2222
2174
2132
2090
2053
2013
1976
1944
27
Airflow Tables
MODEL
THERMOSTAT TAP # CALL
C9S800403A W/W1 C9S800603A W/W1 C9S800804B W/W1 C9S800805C W/W1 C9S801005C W/W1
F01^^ F02^ F03 F04 F01^^ F02^ F03 F04^^ F01^^ F02^ F03 F04 F01^^ F02^ F03^^ F04 F01^^ F02^ F03 F04
0.1 CFM RISE 712 N/A 1120 26 929 32 1073 28 706 N/A 1035 43 932 48 897 N/A 760 N/A 1286 46 1393 43 1459 41 1022 N/A 1453 41 1176 N/A 1710 35 956 N/A 1460 51 1561 47 1628 46
HEATING AIFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.2
0.3
0.4
0.5
0.6
CFM RISE CFM RISE CFM RISE CFM RISE CFM
663 N/A 610 N/A 559 N/A 514 N/A 462
1081 27 1053 28 1022 29 990 30 955
891 33 858 35 815 36 772 38 737
1031 29 1003 30 969 31 922 32 891
655 N/A 604 N/A 555 N/A 505 N/A 455
991 45 951 47 913 49 876 51 844
887 50 844 53 806 55 767 58 728
851 N/A 808 N/A 764 N/A 725 N/A 686
697 N/A 636 N/A 569 N/A 481 N/A 402
1238 48 1196 50 1157 51 1117 53 1077
1348 44 1308 45 1270 47 1230 48 1196
1414 42 1371 43 1336 44 1297 46 1264
813 N/A 674 N/A 585 N/A 511 N/A 431
1407 42 1332 45 1259 47 1190 50 1143
1105 N/A 1020 N/A 935 N/A 864 N/A 797
1660 36 1613 37 1560 38 1505 39 1424
777 N/A 675 N/A 587 N/A 468 N/A 377
1404 53 1350 55 1299 57 1251 59 1203
1499 49 1441 51 1385 53 1336 55 1289
1571 47 1521 49 1472 50 1425 52 1380
GC9S80
0.7 0.8 TEMP RANGE
CFM CFM 395 337 918 887 25-55 699 664 854 822 395 328 807 770 30-60 689 651
646 603 349 300 1036 998 35-65 1158 1123 1229 1193 334 282 1064 1003 35-65 729
673 1353 1296 324 296 1150 1098
40-70 1243 1197 1337 1291
NOTE: ^DEFAULT & RECOMMENDED ^^NOT RECOMMENDED FOR H
28
1 Stage Status Codes
Menu Description
Active Alaram menu Last 6 Faults Code Release Number
LED Display
Main Menu
F
Option Menu
xx xx
CR Number
Notes
( xx: code numbers ) ( xx: code numbers )
Reset to Factory Default
F
Blower Speed for Continous Fan Mode F
Blower Speed for 1st Stage
Compressor Mode
Blower Speed for 2nd Stage
Compressor Mode
Cool On Delay
Cool Off Delay
Blower Speed for Gas Heat Mode
F
Gas Heat On Delay
yes, no Fxx Fxx Fxx
Delay, Seconds
Delay, Seconds Fxx
Delay, Seconds
( xx: Blower Speed Number F01, F02.. )
( xx: Blower Speed Number F01, F02.. )
( xx: Blower Speed Number F01, F02.. )
Default set at 7 Secs, Adjustments can be made in 7 Secs increments from 0 to
35 Secs Default set at 65 Secs, Adjustments can be made in 5 Secs increments
from 0 to 120 Secs ( xx: Blower Speed Number F01, F02.. )
Default set at 30 Secs, Adjustments can be made in 5 Secs increments from 5 to
30 Secs
Gas heat Off Delay
Default set at 90 Secs, Adjustments
F
Delay, Seconds
can be made in 30 Secs increments from 30 to 180 Secs
Automatic Heat Staging – For Two Stage Control
no, 10, 20, 30, Refer to Section ” CHANGING
HEATING MODE SETTING”
60, AUt
29
1 Stage Status Codes
Mode
Main Menu
Idle
Continous Fan
F
Compressor Cooling, Low Stage
Compressor Cooling, High Stage
Gas heat – Single Stage Control
OEM test Mode
Status Menu
30
1 Stage Troubleshooting Codes
Symptom Normal operation
Furnace fails to operate
LED Status
TROUBLESHOOTING CHART
Fault Description Normal operation
Corrective Actions None
Locate and correct gas interruption Replace or realign igniter
Furnace lockout due to an excessive number
Check flame sense signal, clean sensor if coated or
of ignition “retries” (3 total)
Failure to establish flame
oxidized
Loss of flame after establishment
Check flue piping for blockage, proper length, elbows, and
term ination
Furnace fails to operate
Induced draft blower runs
continuously with no furnace
operation
Pressure switch circuit is closed at start of heating cycle
Pressure switch contacts sticking Short in pressure switch circuit wiring
Pressure switch circuit is not closed Pressure switch hose blocked pinched, or
connected improperly
Blocked flue and/or inlet air pipe, blocked drain system or weak induced draft
blower
Verify proper induced draft blower performance
Replace low stage pressure switch Repair short in wiring
Inspect pressure switch hose, repair/replace if necessary Inspect flue piping
for blockage, proper length, elbows, and termination
Check induced draft blower performance, correct as neces s ary
Circulator blower runs continuous ly
No furnace operation
Induced draft blower and circulator blower runs continuous ly No furnace
operation
No furnace operation
Incorrect pressure switch set point or malfunctioning switch contacts
Loose or improperly connected wiring
Check pressure switch operation, replace as needed Tighten or correct wiring connection
Primary limit circuit is open
Check filters and ductwork for blockage Clean filters or
remove obstruction
Insufficient conditioned air over the heat
Check circulator blower speed and performance
exchanger
Blocked filters, restrictive ductwork, improper
Correct speed or replace blower motor if necessary
circulator blower speed, or failed circulator
blower motor
Loose or improperly connected wiring in high
Tighten or correct wiring connection
limit circuit
Flame sensed with no call for heat
Correct short at flame sensor or in flame sensor wiring
Short to ground in flame sense circuit
Check for lingering or lazy flame Verify proper operation of
Lingering burner flame Slow closing gas
gas valve
valve
Open fuse
Short in low voltage wiring
Replace fuse Locate and correct short in low voltage wiring
To View & Clear Fault Codes
· Press either the Left or Right switch until F is displayed. · Press the
center switch to view stored faults. · Press and hold the center switch for 5
to 30 seconds. · All stored faults will be erased, and the display will flash
– – – three times and return to F.
31
1 Stage Troubleshooting Codes
Symptom Normal furnace operation
TROUBLESHOOTING CHART
LED Status
Fault Description
Corrective Actions
Flame sense micro amp signal is minimal
Flame sensor is coated/oxidized
Clean flame sensor if coated or oxidized Inspect for proper flame sensor alignment
Flame sensor incorrectly positioned in burner
fam e
Compare current gas pressure to rating plate and adjust
Lazy burner flame due to improper gas
as needed
pressure or combustion air
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate Furnace fails to operate. Integrated control module
LED display provides no
signal Furnace fails to operate
Furnace fails to operate
Furnace fails to operate Furnace fails to operate Twinning feature not working
Furnace fails to operate
None
Problem with igniter circuit
Check and correct wiring from integrated control module to igniter
Improperly connected or shorted igniter Diagnose and replace shorted igniter as needed Verify and
Poor unit ground
correct unit ground wiring if needed
Igniter relay fault on integrated control module Check igniter output from control, replace if necessary
Polarity of 115 volt AC is reversed Poor unit ground
Correct polarity, check and correct wiring if necessary Verify proper ground, correct if necessary
Gas valve is not energized when it should be
Check wiring in gas valve circuit
External Gas Valve Error
Replace integrated control board
Gas valve is energized when it should not be
Check wiring in gas valve circuit
Internal gas valve error
Replace integrated control board
No 115 power to furnace or no 24 volt power Restore high voltage power to furnace and integrated
to integrated control module.
control module.
Blown fuse or tripped circuit breaker
Correct condition which caused fuse to open, replace fuse
Integrated control module is non- functional
Replace non-functional integrated control module.
Grounding fault
Verify neutral wire connection to furnace & continuity to
Poor neutral connection
ground source
Check for correct gas pressure Check for correct burner
Open roll out switch
alignment
Check for and correct burner restriction
Ignitor Open
Inducer relay Error
Check for Ignitor wiring. Replace Damaged Ignitor Replace integrated control board
TWIN Error
Internal Faults or IRQ Loss in Control Board
Check for wiring connections. Replace integrated control board Replace integrated control board
32
Wiring Diagram
GN
GRD
HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
GY YL
BK WH
BL PU
WH BK
HOT SURFACE IGNITER
2 CIRCUIT 2 1 CONNECTOR
ID BLOWER PRESSURE SWITCH
C NO
C2
GY
GAS VALVE MI
BR
SOME UNITS MAY HAVE 1 ROLL OUT SWITCH
PU
PK
AUTO RESET PRIMARY LIMIT CONTROL
BURNER COMPARTMENT
BLOWER COMPARTMENT
AUTO RESET AUXILIARY LIMIT CONTROL
RD
INDUCED DRAFT
BLOWER
GND
RD PK
BK BK
BK
WH WH
WH
E39
E2
E1
EAC-H CIRC-H XFMR-H LINE-H
NEUT2
E15
NEUT1
E8
E7 CIRC-N
E6 EAC-N
E5 HUM-N
WH WH E4 XFMR-N
E3 LINE-N
2 1
BK BK
BL
T1
RD
T2
OR
T3
BK RD
T4
YL
T5
COM
YL
YL
JUNCTION BOX
YL
BK WH
DISCONNECT
GND L
TO
115 VAC/ 1 Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE
WARNING:DISCONNECT POWER BEFORE N SERVICING. WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED.
FLAME SENSOR
TO 115VAC/ 1Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE
WARNING:
L
GND N
DISCONNECT POWER BEFORE SERVICING. WIRING TO UNIT MUST BE PROPERLY
POLARIZED AND GROUNDED.
DISCONNECT
INTEGRATED CONTROL MODULE
INTEGRATED CONTROL MODULE
DOOR SWITCH
JUNCTION BOX
LINE
INDOOR AIR
CIRCULATOR BLWR
GND
GND NEUTRAL
HUM-OUT
HUM EAC
HUMIDIFIER ELECTRONIC AIR CLEANER
IND IGN IND LO
ID BLWR
HOT SURFACE IGNITER
FS
NEUTRAL NEUTRAL
NEUTRAL NEUTRAL
LINE
FLAME SENSOR 115 VAC
NEUTRAL
TH (3)
24 VAC
40 VA TRANSFORMER
RLO (6)
MANUAL RESET ROLLOUT LIMIT SWITCH
R RLI (12)
AUTO RESET
TO
AUTO RESET AUX LIMIT
PRIMARY LIMIT
+VDC
Y1 HLO (1)
RD
E20 TWIN DEHUM 24V HUM
24V THERMOSTAT CONNECTIONS N.E.C. CLASS 2 WIRE
BR PK
BL
RD
LEFT CENTER
RIGHT
3 SW1 1
6 R223 3 SW2 1
R226 3 SW3
W1
PS1(5)
C
NO
10 7 4 1
11 8 5 2
12 9 6 3
PU
PRESS. SWTICH.
READ CODES FROM LEFT TO RIGHT
TO Y2 MICRO
G
HLI (8)
PU OR
GY
GY
O
MV (10)
HI
BK
RD OR YL
BL
5
4
3
12
E21 E34 E24
W/W1 R G R Y/Y1 Y2
ECM MTR HARNESS
N WH
G
GN
L
BK
C RD
GND
CIRCULATOR BLOWER
CHASSIS GROUND
WH 40 VA TRANSFORMER GN
WH
BK
115 VAC 24 VAC
BK BK
BLOWER COMPARTMENT DOOR SWITCH (OPEN WHEN DOOR OPEN)
Error Code Status
Internal Faults or IRQ Loss Lockout Due to Excessive Retries or Recycles
Pressure Switch Stuck Closed Pressure Switch Open Open High Limit Switch Flame
Detected When no Flame Should be Present Open Fuse Low Flame Signal Ignitor
Relay Fault Reversed Line Polarity or Grounding Error Internal Gas Valve Error
External Gas Valve Error Open Rollout Switch Ignitor Open Inducer Relay Error
TWIN Error Grounding Error
Seven Segment Display
Seg#3
Seg#2
Seg#1
E
E
E
E
E
0
E
E
1
E
E
2
E
E
3
E
E
4
E
E
5
E
E
6
E
E
L
E
E
A
E
E
b
E
E
C
E
1
1
E
E
n
E
E
j
E
E
H
E
1
0
DEHUM C
TO R
MVC (11) TR (7)
C
GAS VALVE
TO MICRO
INDOOR AIR
CIRCULATOR BLWR
GND
INTERGRATED CONTROL MODULE
NOTES: 1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS. 2.
MANUFACTURER’S SPECIFIED REPLACEMENT PARTS MUST BE USED
WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE
MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE
RATING OF AT LEAST 105v C. USE COPPER CONDUCTORS ONLY. 4. UNIT MUST BE
PERMANENTLY GROUNDED AND CONFORM TO N.E.C.
AND LOCAL CODES. 5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT,
DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)
COLOR CODES: PK PINK BR BROWN WH WHITE BL BLUE GY GRAY RD RED YL YELLOW OR
ORANGE PU PURPLE GN GREEN BK BLACK
0140F02625-A
EQUIPMENT GND FIELD GND
FIELD SPLICE SWITCH (TEMP.)
IGNITER
SWITCH (PRESS.) OVERCURRENT PROT. DEVICE JUNCTION
TERMINAL INTERNAL TO INTEGRATED CONTROL PLUG CONNECTION LOW VOLTAGE (24V) LOW
VOLTAGE FIELD HI VOLTAGE (115V)
HI VOLTAGE FIELD
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 33
Maintenance
WARNING
To avoid electric shock, injury or death, disconnect electrical power before
performing any maintanence. If you must handle the igniter, handle with care.
Touching the igniter element with bare fingers, rough handling or vibration
could damage the igniter resulting in premature failure. Only a qualified
servicer should ever handle the igniter.
Annual Inspection The furnace should be inspected by a qualified installer, or
service agency at least once per year. This check should be performed at the
beginning of the heating season. This will ensure that all furnace components
are in proper working order and that the heating system functions
appropriately. Pay particular attention to the following items. Repair or
service as necessary.
· Flue pipe system. Check for blockage and/or leakage. Check the outside
termination and the connections at and internal to the furnace.
· Heat exchanger. Check for corrosion and/or buildup within the heat exchanger
passageways.
· Burners. Check for proper ignition, burner flame, and flame signal.
· Wiring. Check electrical connections for tightness and/ or corrosion. Check
wires for damage.
· Filters.
Filters
CAUTION
To ensure proper unit performance, adhere to the filter sizes given in the
recommended Minimum Filter Size Table or Specification Sheet applicable to
your model.
To remove filters from an external filter rack in an upright upflow
installation, follow the directions provided with external filter rack kit.
Horizontal Unit Filter Removal Filters in horizontal installations are located
in the central return register or the ductwork near the furnace.
To remove: 1. Turn OFF electrical power to furnace. 2. Remove filter(s) from
the central return register or ductwork. 3. Replace filter(s) by reversing the
procedure for removal. 4. Turn ON electrical power to furnace.
Media Air Filter or Electronic Air Cleaner Removal
Follow the manufacturer’s directions for service.
Burners Visually inspect the burner flames periodically during the heating
season. Turn on the furnace at the thermostat and allow several minutes for
flames to stabilize, since any dislodged dust will alter the flames normal
appearance. Flames should be stable, quiet, soft, and blue (dust may cause
orange tips but they must not be yellow). They should extend directly outward
from the burners without curling, floating, or lifting off. Flames must not
impinge on the sides of the heat exchanger firing tubes.
Induced Draft and Circulator Blowers The bearings in the induced draft blower
and circulator blower motors are permanently lubricated by the manufacturer.
No further lubrication is required. Check motor windings for accumulation of
dust which may cause overheating. Clean as necessary.
Filter Maintenance
Improper filter maintenance is the most common cause of inadequate heating or
cooling performance. Filters should be cleaned (permanent) or replaced
(disposable) as required.
Filter Removal
Depending on the installation, differing filter arrangements can be applied.
Filters can be installed in either the central return register or a side panel
external filter rack (upflow only). A media air filter or electronic air
cleaner can be used as an alternate filter. Follow the filter sizes given in
the Recommended Minimum Filter size table to ensure proper unit performance.
Flame Sensor (Qualified Servicer Only)
Under some conditions, the fuel or air supply can create a nearly invisible
coating on the flame sensor. This coating acts as an insulator causing a drop
in the flame sense signal. If the flame sense signal drops too low the furnace
will not sense flame and will lock out. The flame sensor should be carefully
cleaned by a qualified servicer using steel wool. Following cleaning, the
flame sense signal should be as indicated in the Specifications Sheet.
Flue Passages (Qualified Servicer Only)
The heat exchanger flue passageways should be inspected at the beginning of
each heating season.
34
Before Leaving an Installation
· Cycle the furnace with the thermostat at least three times. Verify cooling
and fan only operation.
· Review the Owner’s Manual with the homeowner and
discuss proper furnace operation and maintenance.
· Leave literature packet near furnace.
Repair and Replacement Parts
· When ordering any of the listed functional parts, be sure to provide the
furnace model, manufacturing, and serial numbers with the order.
· Although only functional parts are shown in the parts list, all sheet metal
parts, doors, etc. may be ordered by description.
· Parts are available from your distributor.
Functional Parts List
Gas Valve Gas Manifold Natural Gas Orifice Propane Gas Orifice Igniter Flame
Sensor Rollout Limit Switch Primary Limit Switch Pressure Switch Induced Draft
Blower Door Switch
Blower Motor Blower Wheel
Blower Mounting Bracket Blower Cutoff Blower Housing
Inductor Heat Exchanger
Auxiliary Limit Switch
Integrated Control Module Transformer
35
Furnace
ELECTRICAL Line Voltage (Measure L1 to N and N to Ground Voltage)
Secondary Voltage (Measure Transformer Output Voltage) Blower Amps
Model Number Serial Number
L – N N – G R – C
BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure Supply Air Static
Pressure Total External Static Pressure (Ignoring +/- from the reading above,
add total here)
TEMPERATURES Return Air Temperature (Dry bulb / Wet bulb) Cooling Supply Air
Temperature (Dry bulb / Wet bulb) Heating Supply Air Temperature Temperature
Rise Delta T (Difference between Supply and Return Temperatures)
GAS PRESSURES Gas Inlet Pressure Gas Manifold Pressure (Low Fire) Gas Manifold
Pressure (High Fire)
Gas Type (NG) = Natural Gas / (LP) = Liquid Propane
Additional Checks Check wire routings for any rubbing Check for kinked pressure switch tubing. Check flue elbow for alignment and clamp tightness. Check screw tightness on blower wheel. Check factory wiring and wire connections. Check product for proper clearances as noted by installtion instructions
°F to °C formula: (°F – 32) divided by 1.8 = °C
°C to °F formula: (°C multiplied by 1.8) + 32 = °F
IN. W.C. IN. W.C. IN. W.C.
DB °F DB °F DB °F DB °F DB °F
IN. W.C. IN. W.C. IN. W.C.
WB °F WB °F
36
THIS PAGE IS LEFT INTENTIONALLY BLANK.
37
THIS PAGE IS LEFT INTENTIONALLY BLANK.
38
THIS PAGE IS LEFT INTENTIONALLY BLANK.
39
CUSTOMER FEEDBACK We are very interested in all product comments. Please fill out the feedback on one of the following links: Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page.
GOODMAN® BRAND AMANA® BRAND
Product Registration Thank you for your recent purchase. Though not required to get the protection of the standard warranty, registering your product is a relatively short process, and entitles you to additional warranty protection, except that failure by California ad Quebec residents to register their product does not diminish their warranty rights.
For Product Registration please register by following this link:
GOODMAN® BRAND
Goodman® Brand Products: (https://www.goodmanmfg.com/product-registration).
Amana® Brand Products: (http://www.amana-hac.com/product-registration).
You can also scan the QR code on the right to be directed to the Product Registration Page.
AMANA® BRAND
Our continuing commitment to quality products may mean a change in
specifications without notice. © 2021 Goodman Manufacturing Company, L.P.
19001 Kermier Rd., Waller, TX 77484 www.goodmanmfg.com · www.amana-hac.com
40
References
- Quality, Durable Heating & Air Conditioning Systems From Amana
- Contact Amana Heating & Air Conditioning
- Register Your Amana Heating And Cooling Equipment Here
- Air Conditioning and Heating Systems| HVAC | Goodman
- Contact Us | Goodman Manufacturing
- Warranty Registration | Register Your Goodman HVAC Product
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>