aerl SRX 600/70-48 CoolMax SRX Charge Controller Instruction Manual
- June 4, 2024
- aerl
Table of Contents
- aerl SRX 600/70-48 CoolMax SRX Charge Controller
- Disclaimer
- Important Safety Information
- Warranty Conditions
- Features
- Installation
- Mounting the Controller
- Wiring Compartment
- Operation
- Battery Charge Profile
- Battery Temperature Compensation
- Communications Protocols
- Troubleshooting – Error Codes
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
aerl SRX 600/70-48 CoolMax SRX Charge Controller
About Australian Energy Research Laboratories
Australian Energy Research Laboratories (AERL) was founded by Stuart Watkinson
(BE Elec. Eng., Grad. M.I.E.A) in 1985 to commercialize the “Power Optimizer”,
a revolutionary solution to a complex problem, developed while studying at the
University of Queensland in Brisbane, Australia.
Unlike many inventors, Stuart possessed not only a great idea, but also the
entrepreneurial skill to turn it in to a commercially viable product. The
“Power Optimizer” would eventually come to be known as the AERL MAXIMIZER™,
the world’s first truly Universal Maximum Power Point Tracker (MPPT).
Today, AERL manufactures a range of highly reliable and efficient specialised
power electronic controllers for use in Solar, Micro Hydro, Micro Wind and
Cathodic Protection applications.
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, AUSTRALIAN ENERGY RESEARCH LABORATORIES:
- MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
- ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL, OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION.
THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Notice of Copyright
CoolMax SRX Charge Controller Owner’s Manual © 2022 by Australian Energy
Research Laboratories Pty. Ltd. All Rights Reserved.
Trademark
AERL and the AERL logo are trademarks owned and used by Australian Energy
Research Laboratories Pty. Ltd.
These trademarks may be registered in Australia and other countries.
Effective Date
January 2022 (01/2022)
Important Safety Information
This Installation Manual contains important safety information and
installation instructions for the AERL COOLMAX SRX MPPT Solar Charge
Controller.
The following symbols are used throughout this user manual to indicate ideal
installation methods, potentially dangerous conditions and important
operational information.
IMPORTANT
Indicates information that must be followed to ensure proper operation of the
COOLMAX SRX.
CAUTION
Indicates a critical procedure for the safe installation of the COOLMAX SRX.
Use extreme caution when performing this task.
IMPORTANT
- This User Manual provides detailed installation and usage instructions for the COOLMAX SRX unit. It is recommended that all of the Instructions and Cautions in this User Manual be read before beginning installation.
- Only qualified electricians and technicians should install the COOLMAX SRX. This manual is intended for all installation technicians and the system owner.
- Do not disassemble or attempt to repair the COOLMAX SRX unless you are a qualified technician and have authority in writing from AERL to do so.
- AERL will not be held responsible in any way for the mishandling of this product or for installation of the product in a manner that does not follow the instructions in this manual or as advised by an AERL technician.
Warranty Conditions
1 Warranty Duration from the Date of Purchase
Our goods come with guarantees that cannot be excluded under the Australian
Consumer Law.
You are entitled to a replacement or refund for a major failure and
compensation for any other reasonably foreseeable loss or damage. You are also
entitled to have the goods repaired or replaced if the goods fail to be of
acceptable quality and the failure does not amount to a major failure.
AERL will bear the cost of parts and labour to repair any manufacturing faults
found within the terms and period of this warranty. For claims under warranty,
the faulty product(s) must be returned to AERL’s facility at 2/75 Bluestone
Circuit, Seventeen Mile Rocks, Australia, after contacting AERL and receiving
the appropriate RMA documentation from AERL.
No allowance is made for labour or travelling time required to disconnect or
reinstall faulty parts. AERL will pay the cost of freight to return the
repaired charge controller to the customer within Australia or New Zealand
only. The method of freight will be determined by AERL.
All installation and user conditions as set down in the instruction manual
must be strictly adhered to as failure to do so may void your warranty. Any
faults or like faults caused by lightning, water or moisture ingress, vermin
infestation, improper voltage, faulty installation, use of the product in a
manner for which it is not intended, alterations which affect the reliability
or performance of the unit but are not attributable to faulty manufacture,
failure to act on service warning from the AERL charge controller, or damage
caused by other system components will not be covered under warranty.
In the event of the product being out of service, AERL shall bear no
responsibility for any consequential loss or expense. AERL will not be held
responsible for any misleading or incorrect information conveyed by anyone not
directly employed by AERL.
Visit https://core.aerl.com.au/register-product/ and fill out the associated
form to activate your full AERL warranty.
Note: Warranty conditions remain current until the next revision of this document is published. Proof of purchase is required when making a warranty claim.
Specifications Introduction
Thank-you for purchasing an Australian made CoolMax Series Charge Controller.
CoolMax Charge Controllers offer an efficient and reliable charging process
that not only maintains battery efficiency and life but maximizes power
generation by utilizing the full potential of your PV array.
Features
CoolMax Charge Controllers utilize an advanced form of Maximum Power Point
Tracking (MPPT) technology to extract the maximum power available from your PV
array, efficiently charging your batteries and maximizing power generation.
AERL’s Maximum Power Point Tracking (MPPT) algorithm has been proven to be
highly robust, resistant to local extremes, and results in power losses of
less than 0.5% over the whole operating temperature range of a PV Array.
- High Input Voltage for Ease of Install
- On Board Ground Fault Detection
- PV Array Oversizing Support (+33%)
- Superior Peak Power Efficiency – Over 98%
- Built-In Overload and Thermal Protection
- Reverse Polarity and Current Protection
- Master/Slave Operational Mode
- Designed for Long Term Reliability
- Australian Made
Firmware
This installation and operating manual covers CoolMax SRX Control Firmware Revisions v1.00 and above.
Installation
IMPORTANT
The CoolMax SRX must be installed in a clean, dry location away from direct
sunlight.
Optimal cooling is achieved when the COOLMAX SRX is mounted vertically. A
minimum of 15cm should be kept clear above the COOLMAX SRX to allow for
cooling.
CAUTION – Equipment Damage
CoolMax Charge Controllers are not designed to be used in parallel with other
Third-
Party Ch arge Controllers and this will void your warranty.
Standards & Requirements
All installations must comply with national and local electrical standards and
codes of practice. AERL recommends professional installation.
Grounding
CoolMax Charge Controllers are designed to be installed in floating systems
but contain provisions for positive functional earthing for telecom
applications if required.
CAUTION – Hazard
DO NOT FUNCTIONALLY EARTH THE ARRAY if a negative earth is used for the
batteries, load or DC system.
IMPORTANT
The Chassis Ground (located inside the enclosure) is marked with the following
symbol:
CAUTION – Hazard
If damaged or malfunctioning, the AERL controller should only be disassembled
and repaired by a qualified service centre. Please contact the local renewable
energy dealer/installer for assistance.
Incorrect reassembly risks malfunction, electric shock, or fire.
Mounting the Controller
Use the mounting plate included with the controller to mount the SRX on a vertical surface as demonstrated in Figure 1A below.
Mounting Clearances
When mounting the SRX, a clearance zone around the device must be adhered to
for optimal cooling of the controller under full load. Please refer to the
Figure 1B below.
15 CM
Wiring Information
This section will provide information and instructions for safely wiring up
the CoolMax SRX.
Wire and Disconnect Sizing
IMPORTANT
- Wire sizes must comply with local and national standards. Input conductors and circuit breakers must be rated at 1.56 times the short-circuit current of the PV array.
- Copper wiring must be rated at 75°C or higher.
CoolMax 600/70-48
- The output current limit of the CoolMax 600/70-48 is 70 amps.
- Use a minimum of #4 AWG (20 mm2) wire for the output between the CoolMax and the battery bus bar or termination.
- Use an 125A Non-Polarized DC Circuit Breaker between the controller output and load.
- Recommended Option: Beny BD-125 125A 1000V 4-Pole Circuit Breaker
- We recommend you use an appropriately sized insulated crimp ferrule when terminating both the input and output connections.
- Torque all CoolMax wire and ground terminals to 1.7 Nm (15 in-lb).
Please refer to the relevant IEC or AS/NZS electrical code for recommendations on PV array cable sizing, length and ampacity.
Wiring Compartment
CAUTION – Hazard
All CoolMax SRX wiring must enter the unit through the entry ports located in
the base and rear of the enclosure.
Under absolutely no circumstances should holes be drilled anywhere into the
unit to make other cable entry points. Doing so can cause metal swarf or
fillings to enter the internal electronics and damage the unit once powered
up.
Drilling any holes into the unit will void all product warranty.
To install cabling, the access panel of the COOLMAX SRX must be removed. This is done by removing the two M4 countersunk Phillips screws on the bottom of the enclosure and the four M3 countersunk Phillips screws on either side of the access panel. Refer to Figure 2 below.
Wiring Polarity
CAUTION – Equipment Damage
Reversing the polarity of either the input or output may damage the CoolMax
SRX and void product warranty.
Confirm polarity with a multi-meter prior to closing the input and output
circuit breakers.
With the access cover removed, the internal I/O terminals will be visible. Refer to Figure 3 below.[![aerl -SRX 600-70-48 CoolMax -SRX Charge -Controller
- fig 6](https://manuals.plus/wp-content/uploads/2022/09/aerl-SRX-600-70-48 -CoolMax-SRX-Charge-Controller-fig-6.png)](https://manuals.plus/wp- content/uploads/2022/09/aerl-SRX-600-70-48-CoolMax-SRX-Charge-Controller- fig-6.png)
Operation
Powering Up
The CoolMax SRX will power up when a PV voltage above 30Vdc is applied.
When the COOLMAX SRX is first powered the on, the device will run a self-test and then the LED Indication strip will appear yellow to indicate no charge profile has been configured.
Programming the Device
The CoolMax SRX is programmed via USB-C port located inside the access cover.
The AERL Link Software that can be downloaded at the URL below with
instructions for setting the charge profile located on Page 18.
https://link.aerl.com.au
Battery Charge Profile
IMPORTANT
The CoolMax SRX default charge profile is intended for a generic LiFePo4
battery solution.
AERL supports most other battery chemistries that do not require external BMS
communications.
AERL is working with various battery manufacturers to expand out-of-the-box
comms support for Lithium batteries that require communication with the Charge
Controller.
Please contact AERL support to confirm compatibility prior to installation.
Additional battery support will be rolled out via Over-The-Air firmware
updates.
The CoolMax SRX charge output will not automatically activate for safety
reasons. Prior to activating the charge output, the charge profile must be
configured for the relevant battery solution being utilized.
The SRX operates using an advanced three-stage charging process and has pre-
set charge voltage profiles for each supported nominal battery voltage. That
said, AERL always recommends referring to the battery manufacturers
specifications regarding charge voltages for optimal battery life and
performance.
These voltages can be adjusted in the charge profile settings. Refer to Page
18 for instructions.
Charge Profile Configuration
The CoolMax SRX allows for extensive flexibility when it comes to charge
profile parameters to suit numerous different modern battery chemistries and
manufacturers requirements.
Our programmable charge profile allows for the configuration of the Battery
Charge Rate, and the Absorb, Float, Re-Bulk, and Equalization voltage points.
IMPORTANT
An Equalization is only normally required for Flooded Lead-Acid cells that
experience sulfation as a result of poor charging practices over the lifetime
of said cell.
Equalization is not required, nor recommended for LiFePo4 or other lithium-
based battery solutions and will likely cause damage unless otherwise advised
by the battery manufacturer.
The default charge profile is suitable for most applications but to determine the optimal charge profile for your application, please refer to your battery manufacturer’s user manual or datasheet.
The CoolMax SRX Default Charge Profiles are as follows:
Setting the Battery Charge Profile with AERL Link
Connect to the USB-C Port on the CoolMax and Select the Device from the available local devices list.
Select the Settings button to access the battery charging settings. Charge settings are changed by clicking on the setting value and using the plus/minus arrows or the keyboard to enter a new value.
Once the required settings have been set, Apply the Changes to the CoolMax SRX by clicking on the Apply button.
Note – Further instructions for more complex functionality can be found in the AERL Link User Manual.
Battery Temperature Compensation
IMPORTANT
To utilize the CoolMax SRX battery temperature compensation functionality, an
AERL Battery Sense Remote Temperature and Voltage Sensor will be required.
Part Number: BATT-SENSE
Temperature compensation measures the temperature of the batteries and adjusts
the float and absorb voltage set points to the ideal voltage for batteries at
that temperature.
Using the temperature of the batteries, the COOLMAX SRX adjusts voltages by a
user specified factor in millivolts per C. The temperature compensation
factor can be set using the AERL Link Software. The compensation factor is per
bank, not per cell.
Please refer to Page 18 of this User Manual for instructions on how to edit
settings in the charge profile.
Connecting the Temperature Sensor
IMPORTANT
A temperature compensation value must be set in the charge profile before the
CoolMax SRX will begin to utilize the battery temperature.
To connect your remote temperature sensor to the CoolMax SRX, plug the sensor
into one of the CAN RJ45 ports labelled “CAN” and located between the power
terminals.
Insert the remote temperature sensor connector into the RJ45 connection (Make
sure the orientation is correct and do not force the connection).
Once the connector is inserted, it will click into place.
Temperature Sensor Location
The CoolMax SRX remote temperature sensor must be in close proximity to the
battery cells for accurate results. Securing the temperature sensor in a
central location near the top of the bank is recommended.
CAUTION – Equipment Damage
Do not place the Battery Sense Remote Temperature and Voltage Sensor in a
location where it may be exposed to water, moisture, direct sunlight or
chemical material.
Communications Protocols
The CoolMax SRX features both Controller Area Network (CAN bus) and ModBus RTU (RS485) capabilities for remote monitoring and control functionality. The relevant protocol registry maps for integration are available from AERL on request. Both networking protocols can be accessed via the RJ45 connectors located inside the access cover. The pin-outs for these connections are demonstrated in Figure 9 below.
Troubleshooting – Error Codes
If the CoolMax SRX detects an issue, an alarm will be triggered.
Please refer to the table below for Warning Codes starting with “W” and the
table located on Pg. 23 for Fault Codes starting with “F”.
Note: The CoolMax troubleshooting guide and documentation is being improved regularly. If the relevant situation is not documented, please contact AERL.
References
- AERL – Ordering, Support and Warranty Management simplified.
- link.aerl.com.au
- Renewable Energy Power Solutions Since 1985 | AERL
- Renewable Energy Power Solutions Since 1985 | AERL
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>