aerl SRX 600/55-48 CoolMax Charge Controller User Manual

June 4, 2024
aerl

CoolMax SRX
Charge Controller
Installation and Operation User Manual

Models
SRX 600/55-48/SRX 600/70-48
SRX 600/30-120

About AERL
Australian Energy Research Laboratories (AERL) was founded by Stuart Watkinson (BE Elec. Eng., Grad. M.I.E.A) in 1985 to commercialize the “Power Optimizer”, a revolutionary solution to a complex problem, developed while studying at the University of Queensland in Brisbane, Australia.
Unlike many inventors, Stuart possessed not only a great idea but also the entrepreneurial skill to turn it into a commercially viable product. The “Power Optimizer” would eventually come to be known as the AERL MAXIMIZER™, the world’s first truly Universal Maximum Power Point Tracker (MPPT).
Today, AERL manufactures a range of highly reliable and efficient specialized power electronic controllers for use in Solar, Micro Hydro, Micro Wind, and Cathodic Protection applications.

Contact Information

Address:
2/75 Bluestone Circuit,
Seventeen Mile Rocks, 4073,
Queensland, Australia
Phone: +61 1800 950 865
Email: sales@aerl.com.au
Website: https://www.aerl.com.au

Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, AUSTRALIAN ENERGY RESEARCH LABORATORIES:
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY, OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL, OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.

Notice of Copyright
CoolMax SRX Charge Controller User Manual © 2022 by AERL Pty. Ltd. All Rights Reserved.
Trademark
AERL and the AERL Logo are trademarks owned by AERL Holdings Pty. Ltd. and used by AERL Pty. Ltd under license.
These trademarks may be registered in Australia and other countries.
Effective Date
July 2022 (07/2022)

Important Safety Information

This Installation Manual contains important safety information and installation instructions for the AERL COOLMAX SRX MPPT Solar Charge Controller.
The following symbols are used throughout this user manual to indicate ideal installation methods, potentially dangerous conditions, and important operational information.

IMPORTANT
Indicates information that must be followed to ensure proper operation of the COOLMAX SRX.
CAUTION
Indicates a critical procedure for the safe installation of the COOLMAX SRX. Use extreme caution when performing this task.

About this Manual
IMPORTANT

  • This User Manual provides detailed installation and usage instructions for the COOLMAX SRX unit. It is recommended that all the Instructions and Cautions in this User Manual be read before beginning installation.
  • Only qualified electricians and technicians should install the COOLMAX SRX. This manual is intended for all installation technicians and the system owner.
  • Do not disassemble or attempt to repair the COOLMAX SRX unless you are a qualified technician and have authority in writing from AERL to do so.
  • AERL will not be held responsible in any way for the mishandling of this product or for the installation of the product in a manner that does not follow the instructions in this manual or as advised by an AERL technician.

Warranty Conditions

1Warranty Duration from the Date of Purchase

Warranty Requirements Total Warranty Duration
1. You are the original purchaser of the CoolMax SRX. 3 Years

2. You are the original purchaser and registered your warranty online within 60 days of installation.| 5 Years

Our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure.
AERL will bear the cost of parts and labor to repair any manufacturing faults found within the terms and period of this warranty. For claims under warranty, the faulty product(s) must be returned to AERL’s facility at 2/75 Bluestone Circuit, Seventeen Mile Rocks, Australia, after contacting AERL and receiving the appropriate RMA documentation from AERL. No allowance is made for labor or traveling time required to disconnect or reinstall faulty parts. AERL will pay the cost of freight to return the repaired charge controller to the customer within Australia or New Zealand only. The method of freight will be determined by AERL.
All installation and user conditions as set down in the instruction manual must be strictly adhered to as failure to do so may void your warranty. Any faults or like faults caused by lightning, water or moisture ingress, vermin infestation, improper voltage, faulty installation, use of the product in a manner for which it is not intended, alterations that affect the reliability or performance of the unit but are not attributable to faulty manufacture, failure to act on service warning from the AERL charge controller, or damage caused by other system components will not be covered under warranty.
In the event of the product being out of service, AERL shall bear no responsibility for any consequential loss or expense. AERL will not be held responsible for any misleading or incorrect information conveyed by anyone not directly employed by AERL.
Visit https://core.aerl.com.au/register-product/ and fill out the associated form to activate your full AERL warranty.
Note: Warranty conditions remain current until the next revision of this document is published. Proof of purchase is required when making a warranty claim.

Specifications

General Specifications

Parameter Typical
Weight 5 kg
Dimensions (L x W x H) 432 x 192 x 89 mm
Enclosure Type Indoor Type 1 / IP20
Input / Output Power Connectors Screw Terminals (8 mm²-> 42mm²)
Characteristics SRX 600/55-48

600/30-120
---|---|---|---
Nominal Battery Voltage / Vdc Range|
24 V | 48 V / 20 – 60| 24 V | 48 V / 20 – 60| 120 V / 90 – 170
Max Charge Current| 55 A| 70A| 30 A
Nominal PV Power|
3168 W @ 48 V 1584 W @ 24 V| 4032 W @ 48 V 2016 W @ 24 V| 4320 W @ 120 V
Max PV Input Current| 12 A| 12 A| 12 A
Max PV Short Circuit Current| 18 A| 18 A| 18 A
Max PV Input Voltage| 600 V| 600 V| 600 V
MPP Voltage Range| 170 – 540 V| 170 – 540 V| 215 – 540 V
Max Conversion Efficiency| 97.3%| 98.2%| 98.7%
Overload Behaviour| Operating Point Shift
(Power Limitation)| Operating Point Shift
(Power Limitation)| Operating Point Shift
(Power Limitation)
PV Reverse Polarity Protection| Yes| Yes| Yes
Earth Leakage Current Detection| Yes| Yes| Yes
Safety Protection Class| I| I| I
Pollution Degree (Internal)| I| I| I
Pollution Degree (External)| III| III| III
Ambient Operating Range
(Full Rated Output up to 40 ° C)| -20 to 60 °C| -20 to 60 °C| -20 to 60 °C
Storage Temperature| -30 to 70 °C| -30 to 70 °C| -30 to 70 °C
Self-Consumption (Idle)| 3 W| 3 W| 3 W
Allowable Relative Humidity| 4 – 95% (non-Condensing)| 4 – 95% (non- Condensing)| 4-95% (non-Condensing)
Cooling Method| Active (User Serviceable)| Active (User Serviceable)| Active (User Serviceable)
Display| Indication LED Strip| Indication LED Strip| Indication LED Strip
Required Cabinet Air Exchange
Rate (Intake @ 40 ° C)| 14 m3/hour| 14 m3/hour| 14 m3/hour
Heatsink Temperature @ Full Power| 30°C Rise @ STC (25°C)| 30°C Rise @ STC (25°C)| 35°C Rise @ STC (25°C)
Communications| RS485 / CAN Bus| RS485 / CAN Bus| RS485 / CAN Bus
**
Certifications| IEC62109-1:2010 IEC62509:2010
EN61000.6.3:2012
EN61000.6.4:2012| IEC62109-1:2010 IEC62509:2010
EN61000.6.3:2012
EN61000.6.4:2012| IEC62109-1:2010 IEC62509:2010
EN61000.6.3:2012
EN61000.6.4:2012

Introduction

Thank you for purchasing an Australian-made CoolMax 600 Series Charge Controller.
CoolMax Charge Controllers offer an efficient and reliable charging process that not only maintains battery efficiency and life but maximizes power generation by utilizing the full potential of your PV array.
Features
CoolMax Charge Controllers utilize an advanced form of Maximum Power Point Tracking (MPPT) technology to extract the maximum power available from your PV array, efficiently charging your batteries and maximizing power generation.
AERL’s Maximum Power Point Tracking (MPPT) algorithm has been proven to be highly robust, resistant to local extremes, and results in power losses of less than 0.5% over the whole operating temperature range of a PV Array.

  • High Input Voltage for Ease of Install
  • On-Board Ground Fault Detection
  • PV Array Oversizing Support (+33%)
  • Superior Peak Power Efficiency
  • Built-In Overload and Thermal Protection
  • Reverse Polarity and Current Protection
  • Master/Slave Operational Mode
  • Designed for Long Term Reliability
  • Australian Made

Firmware
This user manual covers CoolMax SRX Control Firmware Revisions v1.3.1 and above.

Installation

IMPORTANT
The CoolMax SRX must be installed in a clean, dry location away from direct sunlight. Optimal cooling is achieved when the COOLMAX SRX is mounted vertically. A minimum of 15cm should be kept clear above the COOLMAX SRX to allow for cooling.
CAUTION – Equipment Damage CoolMax Charge Controllers are not designed to be used in parallel with other ThirdParty Charge Controllers and this will void your warranty.

Standards & Requirements
All installations must comply with national and local electrical standards and codes of practice. AERL recommends professional installation.

Grounding
CoolMax Charge Controllers are designed to be installed in floating systems but contain provisions for positive functional earthing for telecom applications if required.

CAUTION – Hazard
DO NOT FUNCTIONALLY EARTH THE ARRAY if negative earth is used for the batteries, load, or DC system.
IMPORTANT
The Chassis Ground (located inside the enclosure) is marked with the following symbol:
CAUTION – Hazard
If damaged or malfunctioning, the AERL controller should only be disassembled and repaired by a qualified service center. Please contact your local authorized distributor for
assistance.
Incorrect reassembly risks malfunction, electric shock, or fire.

Mounting the Controller

Use the mounting plate included with the controller to mount the SRX on a vertical surface as demonstrated in Figure 1A below.

Figure 1A: SRX Mounting Hole Locations

Mounting Clearances
When mounting the SRX, a clearance zone around the device must be adhered to for optimal cooling of the controller under full load. Please refer to Figure 1B below.

Figure 1B: SRX Mounting Clearances

Wiring Information

This section will provide information and instructions for safely wiring up the CoolMax SRX.
Wire and Disconnect Sizing

IMPORTANT

  • Wire sizes must comply with local and national standards. Input conductors and circuit breakers must be rated at 1.56 times the short-circuit current of the PV array.
  • Copper wiring must be rated at 75°C or higher.

Use a minimum of #6 AWG (16 mm2) wire for the output between the CoolMax and the battery bus bar or termination, and we recommend you use an appropriately sized insulated crimp ferrule when terminating both the input and output connections.

Torque all CoolMax wire and ground terminals to 1.7 Nm (15 in-lb).

CoolMax 600/55-48

  • The output current limit of the CoolMax 600/55-48 is 55 amps.
  • Use a 63A Non-Polarized DC Circuit Breaker between the controller output and load.
    o Recommended Option: Beny BB1-63 63A 600V 2-Pole Circuit Breaker

CoolMax 600/70-48

  • The output current limit of the CoolMax 600/70-48 is 70 amps.
  • Use a 125A Non-Polarized DC Circuit Breaker between the controller output and load.
    o Recommended Option: Beny BD-125 125A 1000V 4-Pole Circuit Breaker

CoolMax 600/30-120

  • The output current limit of the CoolMax 600/30-120 is 30 amps.
  • Use a 50A Non-Polarized DC Circuit Breaker between the controller output and load.
    o Recommended Option: Beny BB1-63 50A 600V 2-Pole Circuit Breaker

Please refer to the relevant IEC or AS/NZS electrical code for recommendations on PV array cable sizing, length, and ampacity.

Wiring Compartment

CAUTION – Hazard
All CoolMax SRX wiring must enter the unit through the entry ports located in the base and rear of the enclosure.
Under absolutely no circumstances should holes be drilled anywhere into the unit to make other cable entry points. Doing so can cause metal swarf or fillings to enter the internal electronics and damage the unit once powered up.
Drilling any holes into the unit will void all product warranties.

To install cabling, the access panel of the COOLMAX SRX must be removed. This is done by removing the two M4 countersunk Phillips screws on the bottom of the enclosure and the four M3 countersunk Phillips screws on either side of the access panel. Refer to Figure 2 below.

Wiring Polarity

CAUTION – Equipment Damage
Reversing the polarity of either the input or output may damage the CoolMax SRX and void the product warranty.
Confirm polarity with a multi-meter prior to closing the input and output circuit breakers.

With the access cover removed, the internal PV Input and Battery Output terminals will be visible. Refer to Figure 3 below.

Operation

Powering Up
The CoolMax SRX will power up when a PV Voltage above 60Vdc is applied.
CAUTION – Equipment Damage
Ensure that the battery is connected to the output prior to powering the device up from the PV.

Programming the Device
When the CoolMax SRX is first powered the on, the device will run a self-test and then the LED Indication strip will appear yellow to indicate no charge profile has been configured.
The CoolMax SRX is programmed via the USB-C port located inside the access cover as demonstrated in Figure 4 to the right.
The AERL Link Software for Windows 10/11 can be downloaded at the URL/QR below.

https://link.aerl.com.au

Instructions for setting the charge profile are located on Page 18.

Device Status Indicator

Green OK
Blue START-UP / SLEEP
Yellow WARNING
Red FAULT

Figure 5: LED Indication States

Battery Charge Profile

IMPORTANT
The CoolMax SRX default charge profile is intended for a generic LiFePo4 battery solution.
AERL supports most other battery chemistries that do not require external BMS communications.
AERL is working with various battery manufacturers to expand out-of-the-box comms support for Lithium batteries that require communication with the Charge Controller.
Please contact AERL support to confirm compatibility prior to installation. Additional battery support will be rolled out via Over-The-Air firmware updates.

The CoolMax SRX charge output will not automatically activate for safety reasons. Prior to activating the charge output, the charge profile must be configured for the relevant battery solution being utilized. The SRX operates using an advanced three-stage charging process and has pre-set charge voltage profiles for each supported nominal battery voltage. That said, AERL always recommends referring to the battery manufacturers’ specifications regarding charge voltages for optimal battery life and performance. These voltages can be adjusted in the charge profile settings. Refer to Page 18 for instructions.

Charge Profile Configuration
The CoolMax SRX allows for extensive flexibility when it comes to charging profile parameters to suit numerous different modern battery chemistries and manufacturers’ requirements.
Our programmable charge profile allows for the configuration of the Battery Charge Rate, and the Absorb, Float Re-Bulk, and Equalization voltage points.

IMPORTANT
An Equalization is only normally required for Flooded Lead-Acid cells that experience sulfation because of poor charging practices over the lifetime of said cell.
Equalization is not required, nor recommended for LiFePo4 or other lithium- based battery solutions and will likely cause damage unless otherwise advised by the battery manufacturer.

The default charge profile is suitable for most applications but to determine the optimal charge profile for your application, please refer to your battery manufacturer’s user manual or datasheet.

The CoolMax SRX Default Charge Profiles are as follows:

| SRX 600/55-48| SRX 600/70-48
---|---|---
Nominal Battery voltage| 48 V| 48 V
Max Charge current| 55 A| 70 A
Absorption voltage| 57.6 V| 57.6 V
Absorption time| 2 Hours| 2 Hours
Float Voltage| 55.2 V| 55.2 V
Re-Bulk Voltage| 52 V| 52 V
| SRX 600/30-120
---|---
Nominal Battery voltage| 120 V
Max Charge current| 30 A
Absorption voltage| 144 V
Absorption time| 2 Hours
Float Voltage| 138 V
Re-Bulk Voltage| 126 V

Setting the Battery Charge Profile with AERL Link
Connect to the USB-C Port on the CoolMax and Select the Device from the available local devices list.

Select the Settings button to access the battery charging settings. Charge settings are changed by clicking on the setting value and using the plus/minus arrows or the keyboard to enter a new value.

Once the required settings have been set, Apply the Changes to the CoolMax SRX by clicking on the Apply button.

Note – Further instructions for more complex functionality can be found in the AERL Link User Manual.

Battery Temperature Compensation

IMPORTANT
To utilize the CoolMax SRX battery temperature compensation functionality, an AERL Battery Sense Remote Temperature and Voltage Sensor will be required.

Part Number: BATT-SENSE

Temperature compensation measures the temperature of the batteries and adjusts the float and absorb voltage set points to the ideal voltage for batteries at that temperature.
Using the temperature of the batteries, the COOLMAX SRX adjusts voltages by a user-specified factor in millivolts per °C. The temperature compensation factor can be set using the AERL Link Software. The compensation factor is per bank, not per cell.

Please refer to Page 18 of this User Manual for instructions on how to edit settings in the charge profile.
Connecting the Temperature Sensor

IMPORTANT
A temperature compensation value must be set in the charge profile before the CoolMax SRX will begin to utilize the battery temperature.

To connect your remote temperature sensor to the CoolMax SRX, plug the sensor into one of the CAN RJ45 ports labeled “CAN” and located between the power terminals. Insert the remote temperature sensor connector into the RJ45 connection (Make sure the orientation is correct and do not force the connection).
Once the connector is inserted, it will click into place.

Temperature Sensor Location
The CoolMax SRX remote temperature sensor must be near the battery cells for accurate results. Securing the temperature sensor in a central location near the top of the bank is recommended.

CAUTION – Equipment Damage
Do not place the Battery Sense Remote Temperature and Voltage Sensor in a location where it may be exposed to water, moisture, direct sunlight, or chemical material.

Ground Fault Detection

The CoolMax SRX features industry-first onboard PV and Battery system ground fault detection, with all connected electrical poles checked for insulation degradation during the device’s start-up routine.
The device chassis must be connected to the same earth as the PV array for the ground fault detection to function. The chassis earth point is located inside the access cover and indicated with the symbol demonstrated below.

IMPORTANT
The system earth configuration (Ground Fault Mode) must be adjusted in the AERL Link software for use with functionally earthed systems otherwise an earth fault will be detected on the earthed pole.

Ground Fault Sensitivity
The SRX ground fault detection offers three levels of sensitivity, all of which are compliant with the Australian PV installation standards.

Low 100kΩ
Medium 50kΩ
High 30kΩ

The sensitivity of the ground fault detection can be configured in AERL Link as demonstrated in Figure 11 below.

Communications Protocols

The CoolMax SRX features both Controller Area Network (CAN bus) and Modbus RTU (RS485) compatible protocols for remote monitoring and control functionality. The relevant protocol registry maps for integration are available from AERL on request.
Both networking protocols can be accessed via the RJ45 connectors located inside the access cover.

The pin-outs for these connections are demonstrated in Figure 12 below.

Pin RS485 Connector Pin CAN Connector
1 +5V 1 +5V
4 RS485 B 4 CAN High
5 RS485 A 7 CAN Low
8 GND 8 GND

Figure 12: Comms Connector Pin-Outs

Troubleshooting – Error Codes

If the CoolMax SRX detects an issue, a warning, or fault code will be triggered.

Please refer to the table below for Warning Codes and the tables located on Page 25 & 26 for Fault Codes

Warning Code Warning Description Recommended Action
-26 Device Not Configured The initial setup process has not been completed and the device will not begin charging. Connect and configure the device with the AERL Link Software.

Refer to Page 14.
-1303| Charger Disabled| The charger has been disabled via the Settings in AERL Link.| Connect to the device and enable the charger to begin charging.
-1153| Low Input Voltage Detected (Sleep Mode)| The PV Voltage is below the minimum allowed PV Voltage or not adequate to charge the connected battery.| Confirm PV String Configuration is appropriate for the device and the sun is shining.
Note – This code may be shown during sunrise and sunset conditions.
-1304| Battery Sense Not Detected| The remote voltage and temperature sensor is either unplugged or faulty.| Refer to Battery Sense User Manual for troubleshooting.
-1301| CAN Master Lost| The device has not received information from the Master within the allowed time-out window.| Confirm your RJ45 connection has not been interrupted and the Master device is still active.
-1160| Set Points Out of Bounds| Set Point configuration is outside limits and may be dangerous for selected nominal battery voltage.| Confirm the Charge Profile is appropriate for the battery being charged. Refer to the Battery Manufacturer’s recommendations.

Please refer to the table below for Fault Codes.

Fault Code Error Description Recommended Action
-1to-100 **Generic Hardware Fault** **** A hardware fault has been detected. Please contact your distributor to organize a warranty replacement.
**** -1100 **Internal Temperature Critical** The device’s internal

systems have reached a critical temperature and shut down to prevent system damage.| The device will automatically restart when it’s safe to do so.
-1159| **Low Output Voltage| The low output voltage has been detected.| Confirm the battery is connected to the controller.
**
-1154| **High Output Voltage| ** High output voltage has been detected.| The battery may be being charged from a secondary source. Confirm all system battery charge parameters.
-1157| **High Output Current| ** High output current has been detected.| Confirm no short circuit is present on the output of the controller.
-1152| **High PV Voltage| High PV Voltage has been detected. The device has shut down to prevent system damage.| ** Confirm PV String Configuration is appropriate for the device.
-1156| **High PV Current| A high  PV input current has been detected.| Confirm PV String Configuration is appropriate for the device.
**
-1051
-1052| **Active Cooling Degraded| The degraded  active cooling capability has been detected.| ** Replace Fan Module.
Fault Code| Error| Description| Recommended Action
---|---|---|---
**** -1102| **High Battery Temperature Detected| The battery temperature sensor has detected a high battery temperature.
Operating the battery at a high temperature will greatly reduce its lifespan.| Consider increasing the battery temperature compensation factor with the AERL Link Software or reducing the ambient environment temperature.
**
-1103| **Low Battery Temperature Detected| The battery temperature sensor has detected a low battery temperature.
Operating the battery at a low temperature may greatly reduce its lifespan.| **
Consider a temperature-controlled battery environment if the battery regularly experiences low temperatures.
-1401| **Earth Fault (Positive)| ** An Earth Fault has been detected on the Positive Connection.| Disconnect the device, confirm the fault with a Megger, and repair the system.
-1402| **Earth Fault (Battery Negative)| ** An Earth Fault has been detected on the Battery Negative Connection.| Disconnect the device, confirm the fault with a Megger, and repair the system.
-1403| **Earth Fault (PV Negative)| ** An Earth Fault has been detected on the PV Negative Connection.| Disconnect the device, confirm the fault with a Megger, and repair the system.

USER MANUAL
COOLMAX SRX – Wall Mount
Australian Energy Research Labs
AER09 – Rev 1.27th
July 2022

Note: The CoolMax troubleshooting guide and documentation is being improved regularly. If the relevant situation is not documented, please contact AERL.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals