OSRAM QUICKTRONIC POWERSENSE T8 Universal Voltage Dimming System Instruction Manual
- June 12, 2024
- OSRAM
Table of Contents
- QUICKTRONIC POWERSENSE T8 Universal Voltage Dimming System
- Product Information
- Product Usage Instructions
- Application Information
- QUICKTRONIC High-Efficiency
- System Information
- SPECIFICATION DATA
- POWER SENSE WIRING & CONTROLS
- Wiring Diagrams
- Specifications
- Control Information
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
QUICKTRONIC POWERSENSE T8 Universal Voltage Dimming System
Product Information
The T8 Universal Voltage Dimming Systems High Efficiency Series is a fluorescent controllable lighting system. It includes the POWERSENSE T8 DIM lamp/ballast guide and is compatible with primary lamp types F32, FB32, and FB31. It can also operate with F30/SS, F28/SS, F25/SS, F25, F17, FB24, and FB16 lamps.
The QUICKTRONIC POWERSENSE ballasts are high-efficiency electronic ballasts that offer several advantages. They are RoHS compliant, featuring lead-free solder and manufacturing processes.
These ballasts operate from standard low voltage (0-10VDC) fluorescent controllers or compatible 2-wire power line fluorescent dimmers. They are ideal for individual office lighting or automated building applications in both new construction and retrofit projects. For individual offices or conference rooms, installation can be streamlined by using a 2-wire power line fluorescent dimmer, eliminating the need for additional control wires.
For more advanced systems like daylight harvesting or building automation applications, standard low voltage devices (0-10VDC, Class 1 or 2) are used to control the lighting system. In daylight harvesting scenarios, each lighting fixture or fixture row is controlled by its own photosensor, regulating the light output to compensate for changes in natural daylight. Energy savings of up to 60% compared to fixed output T8 electronic systems can be realized depending on the specific application.
All QUICKTRONIC POWERSENSE ballasts include a line voltage protection circuit to protect the ballast in case line voltage is inadvertently applied to the low voltage control inputs.
Product Usage Instructions
To use the T8 Universal Voltage Dimming Systems High Efficiency Series:
- Choose the appropriate lamp type for your application, such as F32, FB32, or FB31.
- Install the QUICKTRONIC POWERSENSE ballast.
- If using individual office lighting or automated building applications, connect the ballast to a standard low voltage (0-10VDC) fluorescent controller or compatible 2-wire power line fluorescent dimmer.
- If using more advanced systems like daylight harvesting or building automation applications, connect the ballast to standard low voltage devices (0-10VDC, Class 1 or 2) for control.
- In a daylight harvesting scenario, install photosensors for each lighting fixture or fixture row to regulate light output based on changes in natural daylight.
- Ensure that all connections are properly insulated and follow the wiring diagram provided in the user manual.
By following these instructions, you can achieve energy savings and efficient lighting control with the T8 Universal Voltage Dimming Systems High Efficiency Series.
Lamp / Ballast Guide
- 32W T8 – fluorescent lamps
- 1-lamp QHE 1x32T8 UNV DIM
- 2-lamp QHE 2x32T8 UNV DIM
- 3-lamp QHE 3x32T8 UNV DIM
- 4-lamp QHE 4x32T8 UNV DIM
- Primary Lamp Types
- F32, FB32 & FB31
- Also operates:
- F30/SS, F28/SS, F25/SS, F25,
- F17, FB24 & FB16
Application Information
QUICKTRONIC
POWER SENSE ballasts are ideally suited for:
- Occupancy sensors
- Daylight harvesting
- Energy management
- Load shedding
- New construction
- Retrofi
QUICKTRONIC High-Efficiency
POWERSENSE T8 electronic ballasts offer several advantages:
- Wide Dimming Range: operate linear fluorescent T8 lamps over a 100-5% dimming range and provide true versatility in controls selection.
Industry’s Most Adaptable Dimming Ballast: ballasts feature micro-controller technology for compatibility with:
- low voltage controls
- power line fluorescent dimmers
- any line voltage from 120V to 277V
Unmatched Performance: patented lamp detection technology that virtually
eliminates variations in brightness from lamp-to-lamp and provides uniform
lighting throughout the dimming range.
At light levels of >75% unnecessary lamp-coil power is turned off, delivering
energy efficiences comparable to nondimming
Instant start electronic ballast.
This technology also eases installation and troubleshooting by recognizing
failed lamps, faulty wiring or loose connections, and shutting down. When the
problem is corrected, the system restarts automatically.
These ballasts are RoHS compliant and feature lead-free solder and manufacturing process.
System Information
QUICKTRONIC POWERSENSE ballasts operate from standard low voltage (0-10VDC)
fluorescent controllers or compatible 2-wire power line fluorescent dimmers,
making them ideal for individual office lighting or automated building
applications, both in new construction and retrofit projects.
For the individual office or conference room, installation can be streamlined
by using a 2-wire power line fluorescent dimmer; eliminating the need for
additional control wires.
For more advanced systems, such as daylight harvesting or building automation
applications, standard low voltage devices (0-10VDC, Class 1 or 2) are used to
control the lighting system. In this daylight harvesting example, each
lighting fixture (or fixture row) is controlled by its own photosensor;
regulating the light output to compensate for changes in natural daylight.
Depending upon the specific application, energy savings of up to 60% compared
to fixed output T8 electronic systems can be realized.
All QUICKTRONIC POWERSENSE ballasts include a line voltage protection circuit, which protects the ballast in the event that line voltage is inadvertently applied to the low voltage control inputs.
FO32/XP lamps with QUICKTRONIC T8 POWERSENSE ballast
Based on 4000 hrs/yr, $0.11/kWh, and 120V operation
Savings per Year (@Light Level) = Cost of operation (100% Light Level) – Cost
of operation (@Light Level)
SPECIFICATION DATA
Catalog # Date Type
Project Prepared by
Comments
QUICKTRONIC® POWERSENSE® Dimming UNV – Dimming Control Wiring Examples
POWER SENSE WIRING & CONTROLS
Industry’s 1st Ballast That Allows POWERLINE Fluorescent Control & 0-10Vdc Control Input Simultaneously
Wallbox Style 2-wire Powerline Control Wiring Example
2-wire Powerline Control with POWERSENSE Ballasts
Examples: Leviton IPX series operate as single pole or 3-way models. Available in 120V and 277V models. Leviton 6668-1W (white) 120V single pole fluorescent dimmer.
Powerline Control Specs:
Specification-grade controls are available for 120V or 277V operation of
controllable analog electronic fluorescent ballasts.
Controls must be suitably rated for both the type (e.g. Fluorescent Phase-
control) and size (e.g. 600W of the connected load.
Wallbox Style 0-10V Control with Power Switch Wiring Example
0-10V DC Control with POWERSENSE Ballasts
Examples: Lithonia model ISD BC or Leviton IP 710 Series (This 0-10V dc, 120/277V models can be wired for single pole application (shown); these models can also be wired for 3-way applications.)
Photo Sensor 0-10V Wiring Example
0-10V DC Control with POWERSENSE Ballasts
QUICKTRONIC® POWERSENSE® Controls Information
Please contact controls manfacturer to order/specify controls. For the latest controls list go to www.quicktronic.com Also, for more information, refer to the LCA (Lighting Controls Association) site: http://lightingcontrolsassociation.org
Dimensions:
TC enclosure
- Overall: 9.5″ L x 1.68″ W x 1.0″ H (241 x 43 x 25 mm)
- Mounting: 8.90″ (226 mm)
- Weight: 1.1 lbs each (500 g)
- Wiring:
Leads Only
Dimensions:
TCL enclosure
- Overall: 16.7″ L x 1.68″ W x 1.0″ H (425mm x 43mm x 25mm)
- Mounting:16.2″ (411 mm)
- Weight: 2.1 lbs each (950 g)
Control Specifications/model numbers may change.
Please consult manufacturers listed for their latest control models and to
order their controls.
T8 POWERSENSE®
High Efficiency
Controls Guide
Contact the companies listed for their 2-wire Fluorescent/Powerline controls
and/or 0-10V controls information.
T8 POWERSENSE Dimming Ballast
50735 QHE 1x32T8 UNV DIM TC
50736 QHE 2x32T8 UNV DIM TC
50737 QHE 3x32T8 UNV DIM TCL
50738 QHE 4x32T8 UNV DIM TCL
WARNING:
Install and wire these ballast and controls in accordance with the National
Electrical Code (NEC), all applicable Federal, State and local electrical
codes, as well as the specific instructions provided with the compatible
control that you purchased. Installation should be performed by qualified
personnel only.
These instructions are guidelines only. Installation may vary for different
controls/fixtures/applications. Be sure to follow the control instructions and
all applicable codes and standards when installing dimming systems.
Please contact controls manufacturer for compatible controls and instruction
wiring.
NOTES:
- Dimming ballasts source <0.5mA (0-10VDC control input).
- Powerline controls must be rated for the type (e.g. Fluorescent Phase-control) and size (e.g. 600W, 1000W, 1500W & 2000W etc.) of the connected load. Do NOT use incandescent powerline controls; incandescent dimmers are not rated for fluorescent loads and are NOT compatible with POWERSENSE ballasts.
High Efficiency, T8 Controllable Lighting Systems, UNV (120-277V)
Products are all 10-pack.
NAED in parentheses is provided as a cross reference for the new item number.
- System Efficacy calculation based on lowest input power value.
- Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
Wiring Diagrams
Output Wiring: Lamp wiring for dimming ballasts ca fer significantly from n-dimming ballasts and from other manufacturers dimming ballasts. Take care to connect lamp lead wires as shown on the applicable ballast diagram. Lamp Seasoning: For optimal performance, fluorescent lamps may require seasoning for up to 12 hours prior to low temperature starting & low level dimming. Refer to NEMA LSD 23-2002 Lighting Systems Division: Recommended Practice — Lamp Seasoning for Fluorescent Dimming Systems
Performance Guide
QUICKTRONIC® POWERSENSE ballasts are also compatible with other manufacturers
equivalent lamp types that meet ANSI specific tions, including F17, F25,
F32, U-Bend equivalent lamps and energy-saving lamps.
Specifications
Data based on F32T8
Starting Method: Programmed Rapid Start Circuit Type: Series
Lamp Frequency: >42 kHz
Lamp CCF: Less than 1.7
Starting Temp: 50°F/10°C minimum for T8 lamps
Input Voltage: 120-277V, ±10%
Input Frequency: 50/60 Hz
THD: <10% @ Full Output
Power Factor: >98% @ Full Output
UL Listed Class P, Type 1 Outdoor
CSA or C/UL Certifie
70°C Max Case Temperature
FCC 47CFR Part 18 Non-Consumer Class A Sound Rating
RoHS compliant3
ANSI C62.41 Cat. A Transient Protection Remote mounting (Max. wire length from
ballast case to lampholder)
- up to 8ft for full wattage T8s
- no remote mounting for energy-saving lamps
3 Complies with European Union Restriction of Hazardous Substances Directive (Directive EC 2002/95)
Control Information
QUICKTRONIC POWERSENSE ballasts are compatible with a wide range of low
voltage (0-10VDC) and power line fluorescent controllers available from
various manufacturers.
Low Voltage Control Specs: Ballast will source up to 0.5mA for 0-10VDC control
purposes. May be wired as a Class 1 or Class 2 circuit-consult Local and
National Electrical Codes.
Power Line Control Specs: Specific tion-grade fluorescent controls are
available for 120V or 277V operation of controllable analog electronic
fluorescent ballasts. Controls must be suitably rated for both the type (e.g.
Fluorescent Phase control) and size (e.g. 600W) of the connected load.
Warranty
QUICKTRONIC® Ballasts have a 5-year limited warranty. Complete warranty terms located at www.acuitybrands.com/support/warranty/terms-and- conditions
QUICKTRONIC North America
1-877-636-5267
techsupport@quicktronic.com
© 2022 Acuity Brands Lighting, Inc.
Specifications subject to change without notice. All trademarks referenced are
property of their respective owners. Actual performance may differ as a result
of end-user environment and application. Direct replacement LED lamps should
not be used unless they have been certified for electrical safety, are
compatible with the ballast and are suitable for the intended application
environment. Only replacement lamps that comply with applicable lamp and
ballast manufacturers’ ratings, compatibility listings and instructions should
be used.
ECS455R2 – 4-22
References
- applications.be
- Page Not Found
- Lighting Controls | Indoor & Outdoor | Acuity Brands
- Home-Blue Ridge Technologies
- Hunt Dimming - Since 1960
- Leviton | Switches, Dimmers, Outlets & Lighting Controls
- Quicktronic Ballasts | Acuity Brands
- Wattstopper Lighting Control Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>