Cooper Hunter CHV-09SCC4W 4-Way Cassette Type Installation Guide
- June 12, 2024
- Cooper Hunter
Table of Contents
Cooper Hunter CHV-09SCC4W 4-Way Cassette Type
Product Information
This is a 4-Way Cassette Type Central Air Conditioner. The model numbers available are CHV-09SCC4W, CHV-12SCC4W, CHV-15SCC4W, CHV-19SCC4W, CHV-22SCC4W, CHV-24SCC4W, CHV-27SCC4W, CHV-30SCC4W, CHV-38SCC4W, CHV-48SCC4W, and CHV- 54SCC4W.
This air conditioner is designed for standard air conditioning purposes only. It is not meant to be used for other purposes such as drying clothes, refrigerating food, or any other cooling or heating processes.
The installation and service engineering of this air conditioner must comply with local standards, laws, and regulations. It is recommended to have the air conditioner installed by professionals or authorized dealers to avoid water leakage, electric shock, or fire hazards.
The indoor unit of the air conditioner should be installed at a minimum height of 8.2ft (2.5m) and it is not suitable for public access.
For environmental protection, please do not dispose of the product casually. Our company provides recycling services based on relevant regulations and can provide replacement parts if needed.
The heat pump air conditioner is designed to operate within specific temperature ranges for cooling and heating. Please ensure that the air conditioner is operated within these temperature ranges to ensure optimal performance.
Product Usage Instructions
- Before using the air conditioner, please read and understand the entire user manual for proper usage and maintenance.
- Ensure that the installation and service engineering of the air conditioner comply with local standards, laws, and regulations.
- Do not use the air conditioner for purposes other than standard air conditioning, such as drying clothes or refrigerating food.
- Avoid installing the air conditioner in environments with spatter of oil, inflammable gases, sulfurated gases, silicon, coastal areas with salt, or places exposed to strong acids or bases.
- Do not direct the air outlet towards animals or plants to avoid adverse effects.
- Only allow professionals or authorized dealers to install the air conditioner to prevent water leakage, electric shock, or fire hazards.
- If you have any questions or concerns, consult the dealer or service center designated by the company.
- Dispose of the product responsibly and consider utilizing the recycling services provided by the company.
- Operate the heat pump air conditioner within the specified temperature ranges for optimal performance.
Operation, Installation & Maintenance Manual
4-WAY CASSETTE TYPE
CHV-09SCC4W CHV-12SCC4W CHV-15SCC4W CHV-19SCC4W CHV-22SCC4W CHV-24SCC4W CHV-
27SCC4W CHV-30SCC4W CHV-38SCC4W CHV-48SCC4W CHV-54SCC4W
/3658:’4:
THANK YOU FOR PURCHASING THIS CENTRAL AIR CONDITIONER. PLEASE READ AND
UNDERSTAND THIS MANUAL BEFORE USING THE AIR CONDITIONER. KEEP THIS MANUAL FOR
FUTURE REFERENCE.
ORIGINAL INSTRUCTIONS
Dear user: Thank you for choosing and using our product. To better understand
and use this product, please be sure to read and observe the following related
issues before use.
IMPORTANT NOTICE
Signal words (DANGER, WARNING and CAUTION) are used to indicate hazard
seriousness. Definitions of the hazard levels are provided below with
respective signal words.
DANGER : Immediate hazard that WILL result in severe personal injury or death.
:$51,1* : Hazards or unsafe practices that COULD result in severe personal injury or death.
&$87,21 : Hazards or unsafe practices which COULD result in minor personal injury or damage to property damage.
45:+
: Useful information for operation and/or maintenance.
This manual should be considered as a permanent part of the air conditioning
equipment. Please keep it properly.
Our company pursues a policy of continuous improvement in design and
performance of products. The right is therefore reserved to change
specifications without notice.
Our company shall not be held responsible for any occasional damage to the air
conditioner that arises during its operation in specific environment. This air
conditioner is designed for standard air conditioning only. Do not use it for
other purposes such as drying cloth, refrigerating foods or for any other
cooling or heating processes. Please don’t install the air conditioner in the
following environments. Otherwise, fire, machine deformation or failure may
arise.
Places with spatter of oil (including machine oil). Places with inflammable gases.
Places with sulfurated gases or silicon (e.g. hot spring, etc.). Coastal areas
with much salt or places exposed to strong
acids or bases that may cause corrosion to machine.
Do not have the air outlet directly faced towards animals or plants, since this may bring about an adverse effect thereon.
The installation and service engineering have to comply with local standards, laws and regulations.
As an “appliance inaccessible to the public”, the installation height of indoor unit of the air conditioner shall be at least 8.2ft.(2.5m).
This air conditioner can only be installed by dealers or professionals. The installation by user may lead to water leakage, electric shock or fire.
In case of any question, please consult the dealer or the service center designated by our company.
For environmental protection, please don’t dispose of the product casually. Our company can provide recycling service based on relevant regulations, and provide replacement parts according to
t t d d.
This heat pump air conditioner has been designed for the following temperatures. Be sure to operate the heat pump air conditioner within this range.
Temperature
Cooling
Indoor
Operation Outdoor
Heating
Indoor
Operation Outdoor
Maximum 9 oF DB/73oF WB (32oC DB/23oC WB)
110oF DB (43oC DB) 80oF DB (27oC DB)
9oF WB ( oC WB)
Minimum oF DB/59oF WB (21oC DB/15oC WB)
23oF DB (-5oC DB) 59oF DB ( 15oC DB) -4oF WB (-20oC WB)
This temperature may vary with outdoor unit.
DB: Dry Bulb, WB: Wet Bulb
Refer to the instruction manual for complete machine (outdoor unit) for information about the product standards to which the indoor unit is subject.
DANGER
Please don’t perform installation works such as refrigerant piping connection,
drain pipe connection, and wiring connection. Violations may result in system
leakage, electrical failure or fire. In the case of fire, please turn off the
power immediately; please don’t touch electrical parts with the hands, or
electric shock may arise.
-
Do not pour water into the indoor or outdoor unit. This machine is an electric product that may develop serious electric failure when exposed to water.
-
Do not open the service cover of indoor or outdoor units without turning OFF the main power supply; otherwise, this may bring about serious safety accident.
-
Do not touch or adjust safety devices inside the indoor or outdoor units. If they are touched or readjusted, serious accident may arise.
-
Refrigerant R410A is non-flammable, non-toxic, and odorless, and may produce toxic gases when exposed to open flame. Since this refrigerant gas is heavier than air, it may result in lack of oxygen, thereby leading to breathing difficulties when the area near the ground is filled with this gas. If that’s the case, please turn off the main switch immediately, cut off the power supply, and open the doors and windows for ventilation. Put out any open flame, and contact your service dealer. Performing leak detection and gas tightness test with oxygen, acetylene or other flammable and toxic gases may cause explosion, so nitrogen is recommended for this test.
-
The standards for safe refrigerant leakage in construction and system operation are determined based on local regulations or standards.
-
Use ELB with medium or higher sensing speed (ELB with an operating time of 0.1 seconds or less), or electric shock or fire may arise.
-
For installation, the refrigerant piping must be firmly connected before the operation of compressor. For repair, the refrigerant piping must be moved, handled and removed after the stop of compressor.
-
Please don’t short-circuit the protective device (e.g., the pressure switch, etc.) during operation, since this may cause fire or explosion.
:$51,1* -
Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within approximately one 3.3ft.(1m) from the system.
-
If the earth leakage breaker (ELB) is frequently activated, please stop the system and contact your local dealer or customer services.
-
Make sure the ground wire is securely connected. The improper grounding of machine may lead to electrical failure. Please don’t connect the ground wire to gas pipes, tap water pipes, lightning rods or phone ground wires.
-
Make sure there are no flammable materials around during brazing operation. Please wear leather gloves to prevent frostbite when filling refrigerant.
-
Prevent rats or other small animals damaging the wiring and electrical components. Bitten unprotected parts may cause a fire.
-
Firmly fix the connection wires. The external force of terminal may result in looseness of terminal that may cause a fire.
-
Make sure the air conditioner is installed with enough strength of fixation; otherwise, the air conditioner may fall or topple over, which may bring about machine damage or personal injury.
-
Please follow the installation instructions and related regulations and standards for electrical construction; otherwise, electrical failure or fire may occur due to inadequate capacity or inconsistent specifications.
-
Never fail to use specified wiring and select correct wiring, since failure to do so may cause electrical failure or fire.
-
Please make sure the outdoor unit is not covered with snow or ice before use. The A-weighted emission sound pressure level at workstations, where this exceeds 70 dB(A). This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
,03257$17127,&( Correct Disposal of this product
This marking indicates that this product should not be disposed with other
household wastes. To prevent possible harm to the environment or human health
from uncontrolled waste disposal, recycle it responsibly to promote the
sustainable reuse of material resources. To return your used device, please
use the return and collection systems or contact the retailer where the
product was purchased. They can take this product for environmental safe
recycling.
CHECKING PRODUCT RECEIVED
Upon receipt of this product, check it for any shipping damage. Claims for
damage, either apparent or concealed, should be filed immediately with the
shipping company.
Check the model number, electrical parameters (power supply, voltage, and
frequency) and accessories to determine if they are correct. Please contact
your local dealer in case of problem. Our company shall not be held
responsible for any consequence arising from the modification to equipment
without our written consent.
:'(2+5,)54:+4:9
- Safety Precautions
- Tools & Instruments for Installation
- Transportation & Handling
- Transportation
- Handling of Indoor Unit
- Installation of Indoor Unit
- Factory-Supplied Accessories
- Initial Check
- Installation
- Refrigerant Piping Work
- Piping Materials
- Piping Connection
- Drain Pipe
- Electrical Wirin
- General Check
- Wiring
- Field Wire Size for Power Source Line
- Test Run
- Protection Control Device
- Field Operatio
- Setting of DIP Switch
- Setting of Fan Speed
6DIHW3UHFDXWLRQV
:$51,1*
Do not perform installation work, refrigerant piping work, drain piping and
electrical wiring connection without referring to the installation manual.
Check that the ground wire is securely connected. Connect a fuse of specified
capacity.
&$87,21
Do not install the indoor unit, outdoor unit, remote control switch and cable
within approximately 9.8ft.(3m) from strong electromagnetic wave radiators
such as medical equipment.
7RROV ,QVWUXPHQWVIRU,QVWDOODWLRQ
No.
Tool
1
Handsaw
2
Screwdriver
3
Vacuum Pump
4
Refrigerant Gas Hose
5
Megohmmeter
6
Copper Pipe Bender
7
Water Pump
8
Pipe Cutter
9
Brazing Kit
10
Hexagon Wrench
No.
Tool
11
Spanner
12
Charging Cylinder
13
Multi-purpose Measuring Instrument
14
Cutter for Wires
15
Gas Leak Detector
16
Leveller
17
Clamper for Solderless Terminals
18
Hoist (for Indoor Unit)
19
Ammeter
20
Voltage Meter
Note: When in immediate contact with refrigerant, please use the installation tools and instruments dedicated to the new refrigerant.
‘$1*(5
Since the pressure of new refrigerant R410A is 1.4 times that of traditional refrigerant, its performance is susceptible to impurities like moisture, scale and grease, etc. It’s essential to remove the moisture, dust, other refrigerants or refrigerant oils from the refrigeration system. Hence, the failure to use specified materials and tools may result in explosion, personal injury, refrigerant leakage, electrical failure or fire.
7UDQVSRUWDWLRQ +DQGOLQJ 3.1 Transportation
Transport the product as close to the installation location as practical
before unpacking.
&$87,21
Do not put any material on the product. 3.2 Instructions for Handling
:$51,1*
Do not put any foreign material into the indoor unit and check to ensure that
none exists in the indoor unit before the installation and test run.
Otherwise, a fire or failure, etc. may occur.
&$87,21
Be careful not to cause damage to insulation materials of the unit surface
when it’s lifted.
,QVWDOODWLRQRI,QGRRU8QLW
Install the indoor unit as per national standard
‘$1(5
Do not install the indoor unit in a flammable environment since this may cause
fire or an explosion.
:$51,1
Do not install the indoor unit outdoors. If installed outdoors, an electric
hazard or electric leakage will occur. 4.1 Factory-Supplied Accessories Check
to ensure that the accessories are packed with indoor unit. Please refer to
the packing list on the end page of this manual for standard accessories.
&$87,21
If any of these accessories are not packed with the unit, please contact your
dealer.
1
4.2 Initial Check
Install the indoor unit in a space for easy operation and maintenance as shown
in Fig. 4.1.
Provide a service access door near the unit piping connection area on the
ceiling.
Check to ensure that the ceiling is strong enough to hang the indoor unit.
Check if the ceiling surface is flat for the air panel installation.
4.9ft. (1.5m)
4.9ft. (1.5m)
4.9ft. (1.5m)
4.9ft. (1.5m)
4.9ft. (1.5m)
4.9ft. (1.5m)
9.8ft.(3m)
29 32 . ( mm)
4.9ft. (1.5m)
4.9ft. (1.5m)
4.9ft. (1.5m)
4.9ft. (1.5m)
Piping Connection
Service Access Door 23 32 .(450mm)
Piping Connection
Service Access Door 23 32 .( mm)
Piping Connection
Service Access Door 23 32 .( mm)
Distance from Wall Side
9
.( mm)
3
.( mm)
Piping Connection 3
.( mm) 39 3 8 .(
9 mm)
Service Space
.( mm)
Space around Indoor Unit
The indoor unit must be installed at an appropriate location so that the
indoor temperature can be evenly distributed.
There should be no obstruction of air flow at the vent.
Do not install the indoor unit in a machinery shop or kitchen where vapor from
oil or its mist flows to the indoor unit. Once the oil deposits on the heat
exchanger, it may impair the performance of indoor unit and cause damage to
plastic parts therein.
Pay attention to the following points when the indoor unit is installed in a
hospital or other facilities where there are electronic waves from medical
equipment, etc. (A) Do not install the indoor unit where the electromagnetic
wave is directly radiated to the electrical box, remote control cable or
remote control. (B) Install the indoor unit and components as far as practical
or at least 9.8ft.(3m) from the electromagnetic wave radiator. (C) Install the
remote control switch in an iron box. Arrange the remote control cable in an
iron tube. Ground the iron box and iron tube. (D) Install a noise filter when
the power supply emits harmful noises.
To avoid any corrosive action to the heat exchangers, do not install the
indoor unit in an acid or alkaline environment.
Select the installation location as follows:
Installation
(A) Minimum Space
4.3.1 Opening of False Ceiling and Suspension Bolts
(B) Down Slope Pitch of Drain Pipe: 1/25~1/100
(1) Select appropriate location and direction for installation of indoor unit, and determine its location. Pay careful attention to the space for the piping, wiring and maintenance.
2
2 32 .(10~20 mm) ( )
92
.(260 mm)
2
2
.(310 mm)
Indoor Unit Height in Ceiling
2 32(2 )
33
3 3 (8 9 )
(m
f
)
33 (8 )
(m
fd
t)
29 9 ( )
(Dimension of Suspension Bolts)
2 32(2 )
.(mm) Suspension Bolts
2 32(2 )
Drain Pipe
1/25~1/100 Down Slope
33 (840 (Dimension of Indoor Unit)
860-910 (Dimension of Opening )
29 9 (760) (Dimension of Suspension Bolts)
Fig. 4.2 Installation Location of Indoor Unit
The figure on the right shows the sensing area of motion detector when the
motion detector in panel is in service.
2 32(2 )
8.2ft.(2.5m)
. ft.( m)
a
Approx. 9. ft.(6m) Approx. 28.9ft.( m)
m mt
4 location of Suspension Bolts 0
Motion detector
Fig. 4.3 Opening of False Ceiling and Suspension Bolts
(3) Ensure that the ceiling is horizontally level; otherwise, proper drainage
flow would be impossible.
(4) Strengthen the opening parts of the ceiling. (5) Mount suspension bolts,
as shown in the figure.
2.6ft.(0.8m) above the ground
2
For Concrete Slab
For Steel Beam
5-29/32~6-19/64in.(150~160mm) Screw in 220~331lbs(100~150kg)
Concrete
Fixing Point
Suspension Bolt
(W3/8 or M10)
, Beam
Suspension Bolt
(W3/8 or M10)
For Wooden Beam
Suspension Wooden Rib
(2 23 .(60mm) to
33
.(90mm)
lumber)
Nut Square Washer
Wooden Beam
Square Washer Nut
Suspension Bolt
Fig. 4.4 Mounting the Suspension Bolts
4.3.2 Connection Points of Suspension Bolts and Pipes
in.(mm) Pipe
Pipe
Drain Pipe
4.3.3 Mounting the Indoor Unit
Mount the indoor unit as shown in Fig. 4.6.
Mount field-supplied parts
Suspension bolt
4-M10 or W3/8
Nut
8-M10 or W3/8
Washer
8-M10 or W3/8
(1) Mount nuts and washers to the suspension bolts.
Suspension Bolt (Field Supplied)
Nut (Field Supplied) * Insulating Washer
(Accessory) Bracket (for Fixing Indoor Unit)
Washer (Accessory) Nut (Field Supplied)
Approx. 2(50)
in.(mm)
Approx. 2(50) 4-21/64( )
Surface of Ceiling *Mount the washer with its insulating surface
facing down
Fig. 4.6 Mounting Nuts and Washers
(2) Lift the indoor unit by hoist, and do not put any force on the water pan.
(3) Secure the indoor unit using the nuts and washers.
(1 ( 3 (167) (Liquid Pipe) 29 32(150) (Gas Pipe)
4-21/64(110) 1-3/16(30)
Suspension Bolt
3 (3 ) Surface of Ceiling
Confirm the distance between the bottom surface of indoor unit andthe surface
of ceiling.
unit(kBTU) 09 12 15 19 22 24 27 30 38 48 54
a 1/2(12.7 1/2(12.7 1/2(12.7 1/2(12.7 1/2(12.7 5/8(15.88) 5/8(15.88) 5/8(15.88) 5/8(15.88) 5/8(15.88) 5/8(15.88)
b 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.53) 3/8(9.53) 3/8(9.53) 3/8(9.53) 3/8(9.53) 3/8(9.53)
in.(mm)
c 10-15/64(260) 10-15/64(260) 10-15/64(260) 10-15/64(260) 10-15/64(260)
10-15/64(260) 12-13/64(310) 12-13/64(310) 12-13/64(310) 12-13/64(310)
12-13/64(310)
Fig. 4.5 Mounting Suspension Bracket
Suspension Bracket
Water Pan
Fig. 4. Mounting the Indoor Unit
Note: If a false ceiling has already been installed, be sure to complete all piping and wiring works inside the ceiling before hooking-up the indoor unit.
3
4.3.4 Adjust the Distance between Indoor Unit and Ceiling
&$87,21
Please cover the machine with plastic cloth to keep it clean during
installation. Check the level of water pan using a water
level to avoid incorrect installation of drain discharge mechanism. The drain
pipe side must be approximately 5mm lower than other parts. Tighten the nuts
of the suspension brackets after the adjustment is completed. Apply LOCK-TIGHT
paint to the bolts and nuts in order to prevent them loosening. Otherwise,
abnormal noise or sounds may occur and the indoor unit may fall down. (1) The
pattern board for installation is in the packing carton. Please cut it off.
(b) For ceiling without panel
Opening Size
Opening Size
Indoor Unit Surface of Ceiling
Suspension Bolt
Bolt (M6) Pattern Board for Installation
4. Mounting Indoor Unit
(2) Adjust the indoor unit to the correct position using the factory-supplied
inspection ruler
Ceiling
in.(mm)
21/64~1-3/8 ( 0~ )
21/64~1-3/8 ( 0~ )
21/64~1-3/8 ( 0~ )
Indoor Unit
55/64(22)
21/64~1-3/8 ( 0~ )
Flange Surface
Indoor Unit (Bottom View)
Surface of Suspended Ceiling
(a) For suspended ceiling with panel installed
Put the inspection ruler below the indoor unit
Put the inspection ruler at surface of suspended ceiling
Opening size of inspection ruler
Check the heights of suspended ceiling and indoor unit at each corner Check
the size of each side
Installation Details for Air Panel
The details of installation work for air panel shall be according to the
Installation Manual.
Check to ensure the proper connection of connectors between the indoor unit
and air panel.
5HIULJHUDWLRQ3LSLQJ
‘$1*(5
Use refrigerant R410A in the refrigerant cycle. Do not charge oxygen,
acetylene or other flammable and poisonous gases into the refrigerant cycle
when performing a leakage test or an air-tight test. These gases are extremely
dangerous and can cause an explosion. It is recommended nitrogen be used for
those tests.
5.1 Piping Materials (1) Prepare locally-supplied copper pipes. (2) Select
clean copper pipes. Make sure there is no
dust and moisture inside. Blow the inside of the pipes with nitrogen or dry
air, to remove any dust or foreign matters before connecting pipes. (3) Select
copper pipes based on Fig. 5.2.
4
5.2 Piping Connection
(1) The connection point and diameter of piping are shown in Figs. 5.1 and
5.2.
(2) As shown in Fig. 5.4, two spanners shall be used for
33-5/64( 0) (
6-19/64(160) (Liquid Pipe) 3-47/64(9 ) (Gas Pipe)
Unit: in.(mm) )
6-37/64(167) (Connected to Liquid Pipe)
5-29/32(150) (Connected to Gas Pipe)
Fig. 5.1 Pipe Connection Points
Capacity of indoor unit(kBtu/h) 09~22 24~54
Gas Pipe 1/2(12.7) 5/8(15.88)
Unit: in.(mm) Liquid Pipe 1/4(6.35) 3/8(9.53)
Fig. 5.2 Pipe Diameter
Since the nut cap connected at gas pipe is designed exclusively for R410A, the piping flaring connected for off-factory installation is adjusted as compared with R22 and R407C. Please perform the processing operation based on the dimensions shown below: (See Fig. 5.3)
900 ±20 450 ±20
R0.4~0.8
a D0-0.4
Outside Diameter of Piping (a)
Outside Diameter
R22R407C
of Flaring
(D)
R410A
Unit: in. (mm)
1/2
5/8
(12.7) (15.88)
41/64 49/64 (16.2) (19.4)
21/32 25/32 (16.6) (19.7)
Fig. 5.3 Flaring
Pipe Size .(mm) Tightening Torque ft· (N.m)
1/4(6.35)
10.3~13.3(14~ )
3/8(9.53)
29.5(40)
1/2(12.7)
44.3(60)
5/8(15.88)
48.7~56.8(63~77)
3/4(19.05)
73.8(100)
Fig. 5.4 Nut tightening torque (3) Insulate the refrigeration piping with
field-
supplied insulating pipe upon completion of refrigerant pipe connection. See
Fig. 5.5.
Cord Clamp (Factory-Supplied)
Insulating Pipe (Field-Supplied)
Refrigeration Piping
(Field-Supplied)
Unit Side
Insulating Pipe
Insulating Pipe (Field-Supplied)
Fig. 5.5 Insulation on Pipes
&$87,21
Cap the end of the pipe when the pipe is to penetrate a hole.
Do not put pipes on the ground directly without a cap or vinyl tape arranged
at the end of the pipe.
Do not put pipes on the ground directly
Correct
Incorrect Blocked with Tape or Plug
(4) Discharging and Charging Refrigerant Follow the Installation & Maintenance
Manual for outdoor unit.
&$87,21
Excessive and inadequate refrigerant is a leading cause of system anomaly.
Please inject the right amount of refrigerant.
5
‘UDLQ3LSH
(1) The position of the drain pipe connection is shown .
t in.(mm)
2-11/64(55)
Connected to Drain Pipe
3-15/64(82)
&$87,21
Where the relative humidity of air inlet or ambient air exceeds 80%, an
auxiliary water pan shall be fabricated at installation site and placed under
the indoor unit, as shown in Fig. 6.2.
Indoor Unit
7-41/64(194)
(2) Prepare a polyvinyl chloride pipe with a 32mm outer diameter.
(3) Fasten the tubing to the drain hose with the adhesive agent and the
factory-supplied clamp. The drain pipe must be performed with a down-slope
pitch of 1/25 to 1/100.
a (11-13/16(300) max.)
Hose Clamp (Accessory)
t in.(mm)
c (1-31/32(50) max.)
33 32(850)Max.
Drain Pipe Connection
Hose Clamp (Accessory)
1/25 to 1/100 Down-Slope Drain Hose (Accessory)
Drain Hose (Accessory)
Vinyl Chloride VP25 (Field Supplied)
Upward Slope
Rising Part
Unit
Condensate Pan
Field-Supplied
Water Outlet Fig. 6.2 Auxiliary Water Pan
&$87,21
(1) The drain pipe installed shall slope down; otherwise, the condensate may
flow back and leak into the room when the indoor unit is turned off.
(2) The drain pipe shall not be connected with sewage pipe or other drain
pipes.
(3) Where the main drain is connected to other indoor units, each indoor unit
must be higher than the main. Select drain pipes in ample size depending on
the refrigerating capacity and quantity of indoor units.
(4) Check if water flows without obstruction following the procedure shown
below after the proper connection of wires and drain pipes.
3-15/16(100) Min.
1/25 to 1/100Down-Slope
Drain Pipe Connection
Common Drain Pipe
This drain pipe shall be separating from other pipes.
Fig. 6.1 Drain Pipe
The total length a+b+c shall be 3.6ft.(1.1m). In case of lifting the drain
pipe at the outlet part,
perform the drain piping work as shown in the figure above. (4) Insulate the
drain pipe after connecting the drain hose. Hose Clamp (Accessory)
a.Turn on the power.
b.Fill the water pan with 2L or 2.5L of water. c.Check and ensure the water
flows without
obstruction and no leakage exists. Pour 2L of water if no water flows out of
pipe end.
Inject water via access opening.
Insert the end of hose between heat exchanger and water pan.
Access Opening Water Pump Water (2L or 2.5L)
Inject water via air outlet.
Insert the end of hose between heat exchanger and water pan.
Packing(Accessory)
Water Pan Water Pump
Water (2L or 2.5L)
6
:LULQJ
7.2 Wiring
:$51,1*
Turn OFF the main power switches to the indoor
unit and outdoor unit before electrical wiring or
periodical check, and wait for at least three
minutes.
Check to ensure the indoor and outdoor fans
have stopped before electrical wiring or
periodical check.
Protect the wires, drain pipes, electrical parts,
etc. from rats or other small animals. If not
protected, rats may gnaw at unprotected parts,
which may lead to a fire.
Avoid the contact of wires with the refrigerant
piping, sheet metal edges and electrical
components in unit. Otherwise, the wires may get
damaged or even cause a fire.
Use ELB with medium sensing rate (earth
leakage breaker with action time being equal to
0.1 seconds or less). The failure to do so may
result in electric shock or fire.
The wires must be firmly secured. External force
applied to terminals may cause a fire.
t f dd t
t
tf
t
tm
. At the indoor
unit side of air conditioner, power wiring can be
extended through a power distribution box. Be
sure to calculate the wiring capacity carefully,
since excessively low wiring capacity may
frequently cause fire.
Do not start the system before all check points
are thoroughly checked.
CAUTION
The electrical wiring connection for indoor unit is shown in Fig. 7.1. (1)
Connect transmission wiring to the PBC
in electrical box through the connection hole on electrical box. (2) Connect
the power ZLULQJ and earth wires to the terminals in the electrical box. (3)
Connect the wires between the indoor unit and the outdoor unit to the
terminals in
electrical box.
Wrap the wires with adhesive tape or other materials
and plug the wiring connection hole with seal
material to protect the product from any
condensate water or insects.
The electrical box entrance hole shall be
designed with wire clamp that must be tightened
to address tension requirements when penetrated by wires.
B
Secure the remote controller wire in electrical box
with wire tie.
Tighten screws to the following torques.
M4: 0.7(1.0)~1(1.3) M5: 1.5 2.0)~1.8(2.4) M6: 3(4.0)~3.7(5.0) M8: 6.6(9.0)~8.1(11.0) M10: 13.3(18.0)~17(23.0)
t ft ( m)
L1 L2
08/230
7.1 General Check (1) Make sure that the field-selected electrical components (main power switches, circuit breakers, wires, conduit connectors and wire terminals) comply with the National Electrical Code. (2) Check to ensure that the power supply voltage is within ±10% of the rated voltage. The system can’t be started in the case of excessively low supply voltage. (3) Check the power capacity. (4) Ensure the ground wire is connected.
7
Connecting Hole for Communication Cables and Wire Controller Cables
7/8 in.(22.2mm) Conduit Hole
Connecting Hole for Power Supply Wiring
CAUTION
7.3 d
Fig. 7.1 Electrical Wiring Connection for Indoor Unit f
Model (kBtu/h) CHV-09~30SCC4W CHV-38~54SCC4W
Units Hz
60
Volts
Voltage range
Power supply
MCA
MOP
Max.253V 1.19
15
208/230V
Min.187V
2.15
15
Power supply Communication
wiring size
Cable Size
Wiring size and length must
comply with local codes.
AWG18*1 (0.82mm2)
Fan motor
kW
FLA
0.06
0.26
0.13
0.65
Note: MCA: Min. Circuit Amps (A) MOP: Max. Overcurrent Protective Device (A) kW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A)
(1) Use a shielded cable for the transmitting circuit and connect it to ground.
(2) Field wiring shall be in conformity to local laws and regulations, and all wiring operations
mt
f md
fd f
.
(3) Once the power cord is damaged, the dealer or the professionals from designated
maintenance department must be contacted in a timely manner for repair and replacement.
8
7HVW5XQ
Test run should be performed according to the Installation & Maintenance
Manual.
:$51,1*
Do no operate the system until all the check points are cleared.
(A) Check to ensure the electrical resistance between terminal and ground is
more than 1 M. If this is not the case, do not operate the system until the
electrical leakage is found and repaired.
(B) Check to ensure the stop valves of outdoor unit are fully opened, and then
start the system.
(C) Check to ensure the switch on main power source has been ON for more than
4 hours to warm the compressor by heater.
Pay attention to the following items while the system is running. (A) Do not
touch any of the parts by hand at the discharge gas side, since the
temperatures of compressor chamber and the pipes at the discharge side are
higher than 194°F(90°C). (B) DO NOT PUSH THE BUTTON OF THE AC
CONTACTOR. It will cause a serious accident.
3URWHFWLRQ &RQWURO’HYLFHV
Indoor Unit
Capacity of Indoor Unit t
Capacity of Fuse on Indoor Unit Control
Circuit
‘
Freeze Protection Temperature
Cut-out Cut-in
°F(°C) °F(°C)
0~
5 32(0) 58(14)
9
)LHOG2SHUDWLRQ
10.1 Setting of D Switches
(1) DIP switch must be set with power sources of the indoor and outdoor units
in OFF state. Otherwise, the settings are invalid.
(2) The DIP switches are located as shown in the figure below.
(3) 6 dip switches are arranged on the PCB of indoor unit, and must be set
based on the following instructions before test run. The system shall not be
started before the completion of dip switch setup.
(a) $GGUHVVRILQGRRUXQLWV (DSW6): All indoor units must be numbered in sequence
based on the diagram below. Outdoor units must be numbered from “0”.
Setting Method
DSW6 (Setting 0~63)
123
ON OFF
Note: 8421 coding method
Ex.) SetDGGUHVV1R
DSW6 ON
1 2 3 4 5 6 OFF No. isON
(b) Refrigeration system cycle No. (RSW2 & DSW5) is required to be set. All
are set
to OFF before shipment.
(c) Safety reset (DSW7) Factory settings
Once strong current is accidentally connected to Terminals 1 and 2 of TB2, the
PCB fuse will be blown. In such a case, it’s essential to correct the wiring
and then to set switch No. 1 to ON position.
Note:
Symbol ” ” indicates the location of DIP switch. The position indicated in the
diagram is in the factory-set state.
&$87,21
The power supply shall be turned off before the setup of DIP switch.
Otherwise, the settings will be invalid.
10.2 Setting of Fan Speed
The air volume can be changed by performing external static pressure setup (“C5”) on wired controller. Please refer to the wired controller Installation & Maintenance Manual.
Height of Ceiling
Setting of Wire
0~ ( t )
~ ( t ) Controller
8.9ft.(2.7m)SG^ 10.5ft.( m)SG^
8.9~9.8ft.(dS) 9.8~11.5ft.(3.0~3.5m)
10.5~11.8ft. (3.2d6S)
11.8~13.8ft. (3.6~ m)
& )# )#
Setting Method 2
DSW5 (Setting 0~63) ON
1 2 3 4 5 6 OFF
Note: 8421 coding method
Ex.) Set system No
DSW ON
1 2 3 4 5 6 OFF No. isON
10
3DFNLQJ/LVW
Details Indoor Unit: Operation Installation & Maintenance Manual:
: :
Pipe Clamp:
1 Set 1 pc
1 pc 1 pc 6 pcs 2 pcs 1 pc 1 pc
pc pcs pc 1 pc
Remarks
08.20 V01