EMERSON 5.32F12 Multi Zone Leak Detector User Manual

June 12, 2024
Emerson

EMERSON 5.32F12 Multi Zone Leak Detector

EMERSON-5.32F1-Multi-Zone-Leak-Detector

Product Information: Multi-Zone Leak Detector

The Multi-Zone Leak Detector is a device designed to detect refrigerant leaks in multiple zones. It is equipped with audible and visible alarms that can be set based on user-defined alarm and spill setpoints. Each zone has the capability to trigger a circuit shutdown in the event of a spill. The Leak Detector Panel comes with a local strobe and horn, and optional hardware includes remote horn and strobes, MRLDS Halo-carbon and CO2 sensors, and battery backup panel.

Parts and Ordering Information

The following table lists the replacement part ordering
information for the leak detector and its components:

Description Replacement Part Numbers
Programmed Leak Detector iPro-Genius with connectors Specify the 525-10xx

program found on the label affixed to the
currently installed iPro (also found on the panel part number label
on the top right corner of panel)
IPX206D Expansion Module for iPro| Emerson Part #: 618-8003
Visograph with the graphics loader, Display Interface for
iPro| Emerson Part #: 818-9205
120VAC to 24VAC, 50VA, Class 2 Transformer (T1-T8)| Emerson Part #: 640-0041
120VAC to 24VAC, 10VA, Class 2 Transformer (T9-T14)| Emerson Part #: 640-0039
Leak Detector Panel Relay Board| Emerson Part #: 638-1125
Zone MRLDS POWER Green LED Indicator, 24VAC| Emerson Part #: 150-4030
Panel Power ON Green LED Indicator, 120VAC| Emerson Part #: 150-4032
UPS CONNECTED Blue LED Indicator, 102VAC| Emerson Part #: 150-4034
Horn and Strobe| Emerson Part #: 118-5112
Push Button Silence| Emerson Part #: 851-4084

Note: Please note that some parts are compatible with specific panel versions. Refer to the part numbers for compatibility information.

Product Usage Instructions

Multi-Zone Leak Detector

  1. Ensure that the Leak Detector firmware is version 5.35F01 or higher.
  2. To view zone status screens, refer to page 13 of the user manual.
  3. To configure parameters, refer to the table of parameters on page 14 of the user manual.
  4. To upload the Multi-Zone Refrigerant Leak Detector Description File to E2, follow the steps on page 18 of the user manual.
  5. To license the Multi-Zone Leak Detector in the E2 system, refer to page 19 of the user manual.
  6. For device setup in the E2 system, follow the instructions on page 19 of the user manual.
  7. Each zone is capable of operating an audible and visible alarm based on user-defined alarm and spill setpoints. Adjust these settings according to your requirements.
  8. In the event of a spill, each zone has the ability to trigger a circuit shutdown. Ensure that this feature is enabled and properlyconfigured.
  9. If necessary, install optional hardware such as remote horn and strobes, MRLDS Halo-carbon and CO2 sensors, or battery backup panel.

For detailed information and step-by-step instructions, please refer to the Multi-Zone Leak Detector Application and Panel Manual.

Multi-Zone Leak Detector
Application and Panel Manual
For Leak Detector firmware 5.35F01 and higher

Overview

The Multi-Zone Leak Detector Application and Panel (P/N 851-4074) has a total of six (6) zones. The Visograph display provides a parts per million (PPM) reading. One MRLDS Halo-carbon and CO2 sensor can be connected in each zone. The Multi-Zone Leak Detector application is fully integrated with the E2, has relay outputs for third party devices, or can operate fully independently as a stand-alone device. Leak detector versions 5.32F12 and higher are BACnet MS/TP capable and can be used with E2E 4.09F04 and higher. The BACnet leak detector Description File for E2 is P/N 527-0600.
Each zone is capable of operating an audible and visible alarm based on user defined alarm and spill setpoints. In addition, each zone has the ability to trigger a circuit shutdown in the event of a spill.
The Leak Detector Panel comes equipped with a local strobe and horn. Optional hardware includes remote horn and strobes, MRLDS Halo-carbon and CO2 sensors, and battery backup panel.
1.1 Parts and Ordering Information
The table Replacement Parts below lists the replacement part ordering information for leak detector and its components.

Component Replacement Part Numbers

Description
Programmed Leak Detector iPro-Genius with connectors
*When ordering this part, specify the 525-10xx program found on the label affixed to the currently installed iPro (also found on the panel part number label on the top right corner of panel)
IPX206D Expansion Module for iPro

Emerson Part #
618-8003
318-8004

Visograph with the graphics loader, Display Interface for iPro
120VAC to 24VAC, 50VA, Class 2 Transformer (T1-T8)
120VAC to 24VAC, 10VA, Class 2 Transformer (T9-T14)

818-9205 640-0041 640-0039

Leak Detector Panel Relay Board

638-1125

“Zone MRLDS POWER” Green LED Indicator, 24VAC
“Panel Power ON” Green LED Indicator, 120VAC
“UPS CONNECTED” Blue LED Indicator, 102VAC
Horn and Strobe

150-4030 150-4032 150-4034 118-5112

Push Button Silence

851-4084

Replacement Parts 1

Description
Break Glass Safety Switch
6 Zone Leak Detector Panel, All AC powered components
6 Zone Leak Detector Panel, DC gas detector power, AC horn/strobe power Leak Detector Panel Relay Board 24VDC Version (compatible with 851-4550 panel only) 120VAC to 24VDC power supply (compatible with 851-4550 panel only)
Replacement Parts

Emerson Part #
118-4122 851-4074
851-4550
638-1126
250-2541

Gas Detector Replacement Parts

Description
Emerson MRLDS 250 R22 Gas Specific

Emerson Part #
809-0031

Compatible Leak Panel
PART#

Emerson MRLDS 250 R404A Gas Specific

809-0034

Emerson MRLDS 250 R407A Gas Specific

809-0035

Emerson MRLDS 250 R407C Gas Specific

809-0036

Emerson MRLDS 250 R407F Gas Specific

809-0037

Emerson MRLDS 250 R410A Gas Specific
Emerson MRLDS 250 R422A Gas Specific
Emerson MRLDS 250 R422D Gas Specific
Emerson MRLDS 250 R448A Gas Specific
Emerson MRLDS 250 R449A Gas Specific
Emerson MRLDS 250 R513A Gas Specific
Emerson MRLDS 250 R513A Gas Specific
Emerson SC 404A Gas Specific
Emerson SC 407A Gas Specific
Emerson SC 448A Gas Specific
Emerson IR 0-5000ppm Carbon Dioxide
Emerson IR 0-10000ppm Carbon Dioxide

809-0038 809-0039 809-0040 809-0041 809-0042 809-0043 809-0044 809-1201 809-1202 809-1203 809-1215 809-1216

851-4074 or 851-4550
851-4550 Only
851-4074 or 851-4550

Replacement Parts

1.2 Operation
Each zone will operate a horn and strobe in the event of a leak. If the PPM reading that is sent to the panel has reached the user-configured parameter, the horn and strobe will be activated by a relay output. If a leak is present and it is large enough to reach the spill parameter set by the user, the panel will trigger another set of relay outputs. Through the E2 software or third party system, a spill alarm can trigger a circuit shutdown. In the event that an alarm has been triggered, the user will be able to silence that alarm for a period of time that is user-configurable.
1.3 Panel
The user interface is located on the front panel. From here the user can view status, set parameters, and silence alarms from (in addition to alarm silence buttons located in each zone). Also located on the front panel are power indication lights for the system, each zone, and battery backup status (if an uninterruptible power supply UPS is required).
Front Lamps
2

1.4 Zone Terminal Blocks
Each zone has a dedicated control board to interface field wiring connections with factory wiring connections in the panel. The 538-1125 AC Zone Relay Board and Terminals (for 851-4074 panel only) illustration below shows an example of zone 1 board, terminal strip, and terminal descriptions.

Green #14 (3″)

White + Black Shield

Pilot Relay Coil Power

Power Power

MRLDS Signal Out

Analog MRLDS Hrm/Strb

Shield
24VAC 24VAC Common 24VAC Relay N Horn(s) Strobe(s) Dry Cont

ZONE 1
K1
K2
K3
K4

Shield
24VAC 24VAC Common Horn(s) Strobe(s) Indicator Silence NO Cont C Cont NO Cont Ext. Fan Ctrl Ext. Fan Ctrl

Dry Contact 10A @ 120V MAX

Remote Devices 24VAC, 50VA MAX

MRLDS Power 10VA MAX

Analog Out MRLDS Signal

851-4074 Multi-zone Leak Detector Panel Terminal Legend

Brd #1

Zone

1

MRLDS 1 +

Description

Voltage/Rating 1-5V IN

2

MRLDS 1 –

0V

3

MRLDS 1 Shield (Ground)

Ground

4

iPro Analog Out 1 –

24VAC 10 mA MAX

5

iPro Analog Out 1 +

24VAC 10 mA MAX

6

MRLDS 1 24VAC Power Out

24VAC 1/2A MAX

7

MRLDS 1 24VAC Power Out

Zone 1

8

Remote Horn/Strobe 24VAC Neutral

24VAC 1/2A MAX 24VAC 4A MAX

9

Remote Horn Out 24VAC Hot

24VAC 1A MAX

10

Remote Strobe Out 24VAC Hot

24VAC 1A MAX

11

Indicator on 851-4084 Alarm Silence 24VAC Hot 24VAC 1A MAX

12

Zone 1 Dry Out – Normally Open Contact

120VAC @ 10A MAX

13

Zone 1 Dry Out – Common

120VAC @ 10A MAX

14

Zone 1 Dry Out – Normally Closed Contact

120VAC @ 10A MAX

538-1125 AC Zone Relay Board and Terminals (for 851-4074 panel only)
The 851-4550 Leak Detector Panel with DC powered gas detectors has a slightly different leak detector control board than the 851-4074 panel. The 851-4550 panel has a DC control board that is colored red for easy identification from its green AC counterpart in the 851-4074 panel. Additionally, the red 538-1126 DC control board is configured to provide DC power for installations using DC gas detectors. The red 538-1126 DC control board can only be used in the panel designed for it, P/N 851-4550.

MRLDS Signal Analog MRLDS Hrn/Strb

Out

Power

Power

Pilot Relay Coil Power

+ Shield + 24VAC 24VAC Common 24VAC Relay Horn(s) Strobe(s) Dry Cont

538-1126

851-4550 Multi-zone Leak Detector Panel Terminal Legend

MRLDS Signal

K1

Brd #1

Zone

Description

Voltage/Rating

_

1

MRLDS 1 +

1-5V IN

Shield

2

MRLDS 1 –

0V

Analog Out

_

3

MRLDS 1 Shield (Ground)

Ground

MRLDS Power 10VA MAX

K2

24VAC

4

iPro Analog Out 1 –

24VAC 10 mA MAX

24VAC

5

iPro Analog Out 1 +

24VAC 10 mA MAX

Remote Device 24VAC, 50VA MAX

Common

6

MRLDS 1 24VAC Power Out

24VAC 15VA MAX

Horn(s)

Strobe(s)

7

MRLDS 1 24VAC Power Out

Zone 1

24VAC 15VA MAX

K3

Indicator Silence

8

Remote Horn/Strobe 24VAC Neutral

24VAC 4A MAX

NO Cont

9

Remote Horn Out 24VAC Hot

24VAC 1A MAX

Dry Contact 10A@ 120V MAX

C Cont

10

Remote Strobe Out 24VAC Hot

24VAC 1A MAX

NO Cont

11

Indicator on 851-4084 Alarm Silence 24VAC Hot 24VAC 1A MAX

Ext. Fan Ctrl

12

Zone 1 Dry Out – Normally Open Contact

120VAC @ 10A MAX

K4

Ext. Fan Ctrl

13

Zone 1 Dry Out – Common

120VAC @ 10A MAX

14

Zone 1 Dry Out – Normally Closed Contact

120VAC @ 10A MAX

538-1126 DC Zone Relay Board and Terminals (for 851-4550 panel only)

3

The full description of all terminals and connections is affixed to the inside of each panel door and is shown in the Zone Terminal Descriptions below.

Brd #1 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Brd #2 1 2 3 4 5 6 7 8 9 10
11
12 13 14

851-4074 Multi-zone Leak Detector Panel Terminal Legend

Zone

MRLDS 1 +

Description

Voltage/Rating 1-5V IN

MRLDS 1 –

0V

MRLDS 1 Shield (Ground)

Ground

iPro Analog Out 1 –

24VAC 10 mA MAX

iPro Analog Out 1 +

24VAC 10 mA MAX

MRLDS 1 24VAC Power Out

24VAC 1/2A MAX

Zone 1

MRLDS 1 24VAC Power Out Remote Horn/Strobe 24VAC Neutral

24VAC 1/2A MAX 24VAC 4A MAX

Remote Horn Out 24VAC Hot

24VAC 1A MAX

Remote Strobe Out 24VAC Hot

24VAC 1A MAX

Indicator on 851-4084 Alarm Silence 24VAC Hot

24VAC 1A MAX

Zone 1 Dry Out – Normally Open Contact

120VAC @ 10A MAX

Zone 1 Dry Out – Common

120VAC @ 10A MAX

Zone 1 Dry Out – Normally Closed Contact 120VAC @ 10A MAX

Zone

MRLDS 2 +

Description

Voltage/Rating 1-5V IN

MRLDS 2 –

0V

MRLDS 2 Shield (Ground)

Ground

iPro Analog Out 2 –

24VAC 10 mA MAX

iPro Analog Out 2 +

24VAC 10 mA MAX

MRLDS 2 24VAC Power Out

24VAC 1/2A MAX

Zone 2

MRLDS 2 24VAC Power Out Remote Horn/Strobe 24VAC Neutral

24VAC 1/2A MAX 24VAC 4A MAX

Remote Horn Out 24VAC Hot

24VAC 1A MAX

Remote Strobe Out 24VAC Hot

24VAC 1A MAX

Indicator on 851-4084 Alarm Silence 24VAC Hot

24VAC 1A MAX

Zone 2 Dry Out – Normally Open Contact

120VAC @ 10A MAX

Zone 2 Dry Out – Common

120VAC @ 10A MAX

Zone 2 Dry Out – Normally Closed Contact 120VAC @ 10A MAX

Input Field Connections

7

1 NO 2 3 NO 4
C 56

BAS Remote Zone Alarm Silence normally open dry contact. Same input wired to 851-4084 Remote Zone Silence panels.
Zone 1 Zone 2 Zone 3
Zone 4 Zone 5 Zone 6
24VAC Hot
Batt Mode 24Vac Neu
From 851-4071 UPS Panel

Zone 5
Zone 6
Field Installed Break Glass Panel

24VAC Hot 24VAC Hot

R2

8

Recommended Specification Torque: 0.5-0.6 Nm Wire Sizes: 24-10 AWG
BAS Zone 1 Silence

FUSE

BAS Zone 2 Silence

BAS Zone 3 Silence

BAS Zone 4 Silence

BAS Zone 5 Silence BAS Zone 6 Silence

BAS Zone Silence Cmn

Battery Mode Neutral Battery Mode Hot
Break Glass 1 Input Break Glass 1 Input Break Glass 2 Input Break Glass 2 Input

Brd #3 1 2 3 4 5 6 7 8 9 10
11
12 13 14 Brd #4 1 2 3 4 5 6 7 8 9 10 11 12 13 14

851-4074 Multi-zone Leak Detector Panel Terminal Legend

Zone

MRLDS 3 +

Description

Voltage/Rating 1-5V IN

MRLDS 3 –

0V

MRLDS 3 Shield (Ground)

Ground

iPro Analog Out 3 –

24VAC 10 mA MAX

iPro Analog Out 3 +

24VAC 10 mA MAX

MRLDS 3 24VAC Power Out

24VAC 1/2A MAX

Zone 3

MRLDS 3 24VAC Power Out Remote Horn/Strobe 24VAC Neutral

24VAC 1/2A MAX 24VAC 4A MAX

Remote Horn Out 24VAC Hot

24VAC 1A MAX

Remote Strobe Out 24VAC Hot

24VAC 1A MAX

Indicator on 851-4084 Alarm Silence 24VAC Hot

24VAC 1A MAX

Zone 3 Dry Out – Normally Open Contact

120VAC @ 10A MAX

Zone 3 Dry Out – Common

120VAC @ 10A MAX

Zone 3 Dry Out – Normally Closed Contact 120VAC @ 10A MAX

Zone

MRLDS 4 +

Description

Voltage/Rating 1-5V IN

MRLDS 4 –

0V

MRLDS 4 Shield (Ground)

Ground

iPro Analog Out 4 –

24VAC 10 mA MAX

iPro Analog Out 4 +

24VAC 10 mA MAX

MRLDS 4 24VAC Power Out

24VAC 1/2A MAX

Zone 4

MRLDS 4 24VAC Power Out Remote Horn/Strobe 24VAC Neutral

24VAC 1/2A MAX 24VAC 4A MAX

Remote Horn Out 24VAC Hot

24VAC 1A MAX

Remote Strobe Out 24VAC Hot

24VAC 1A MAX

Indicator on 851-4084 Alarm Silence 24VAC Hot

24VAC 1A MAX

Zone 4 Dry Out – Normally Open Contact

120VAC @ 10A MAX

Zone 4 Dry Out – Common

120VAC @ 10A MAX

Zone 4 Dry Out – Normally Closed Contact 120VAC @ 10A MAX

COMPONENT REPLACEMENT PART NUMBERS
Description Programmed Leak Detector iPro-Genius with connectors *When ordering this part, specify the 525-10XX program found on the label affixed to the currently installed iPro (also found on the panel part number label on the top right corner of panel) IPX206D Expansion Module for iPro Visograph with graphics loader, Display Interface for iPro 120VAC to 24VAC, 50VA, Class 2 Transformer (T1-T8) 120VAC to 24VAC, 10VA, Class 2 Transformer (T9-T14) Leak Detector Panel Relay Board “Zone MRLDS POWER” Green LED Indicator, 24VAC “Panel Power ON” Green LED Indicator, 120VAC “UPS CONNECTED” Blue LED Indicator, 120VAC

EMERSON PART #
618-8003
318-8004 818-9205 640-0041 640-0039 638-1125 150-4030 150-4032 150-4034

Brd #5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Brd #6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 89
90

851-4074 Multi-zone Leak Detector Panel Terminal Legend

Zone Zone 5

Description MRLDS 5 + MRLDS 5 MRLDS 5 Shield (Ground) iPro Analog Out 5 iPro Analog Out 5 + MRLDS 5 24VAC Power Out MRLDS 5 24VAC Power Out Remote Horn/Strobe 24VAC Neutral Remote Horn Out 24VAC Hot Remote Strobe Out 24VAC Hot Indicator on 851-4084 Alarm Silence 24VAC Hot Zone 5 Dry Out – Normally Open Contact Zone 5 Dry Out – Common Zone 5Dry Out – Normally Closed Contact Zone 5 Exhaust Fan Control Normally Open Zone 5 Exhaust Fan Control Normally Open

Voltage/Rating 1-5V IN 0V Ground 24VAC 10 mA MAX 24VAC 10 mA MAX 24VAC 1/2A MAX 24VAC 1/2A MAX 24VAC 4A MAX 24VAC 1A MAX 24VAC 1A MAX
24VAC 1A MAX
120VAC @ 10A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX

Zone
Zone 6
All Zones

Description MRLDS 6 + MRLDS 6 MRLDS 6 Shield (Ground) iPro Analog Out 6 iPro Analog Out 6 + MRLDS 6 24VAC Power Out MRLDS 6 24VAC Power Out Remote Horn/Strobe 24VAC Neutral Remote Horn Out 24VAC Hot Remote Strobe Out 24VAC Hot Indicator on 851-4084 Alarm Silence 24VAC Hot Zone 6 Dry Out – Normally Open Contact Zone 6 Dry Out – Common Zone 6 Dry Out – Normally Closed Contact Zone 6 Exhaust Fan Control Normally Open Zone 6 Exhaust Fan Control Normally Open General Alarm Out – Common – Dry Contact General Alarm Out – Normally Open – Dry Contact

Voltage/Rating 1-5V IN 0V Ground 24VAC 10 mA MAX 24VAC 10 mA MAX 24VAC 1/2A MAX 24VAC 1/2A MAX 24VAC 4A MAX 24VAC 1A MAX 24VAC 1A MAX 24VAC 1A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX 120VAC @ 10A MAX
120VAC @ 10A MAX

91

UPS Panel

120VAC in from UPS Status Indicator Output

Status

Indica- 120VAC in from UPS Status Indicator

92

tor

Output

Connect UPS Status Indicator Output here. Controls Blue Indicator on this Panel Door.

GRD
120V NEUT
120V HOT

Earth Ground

Panel
Control Power

120VAC Neutral – IN (Line or Optional UPS Panel 851-4071)
120VAC HOT – IN (Line or Optional UPS Panel 851-4071)

120VAC, 60Hz, Single Phase, 15A
(Connect UPS Power Out here if using 851-4071 UPS Panel)

Zone Terminal Descriptions NOTE: Zones 5 and 6 have additional terminals for an optional break glass device and exhaust fan output.

4

1.5 Additional I/O Terminals

Input Field Connections

7

1 3

C 56

BAS Remote Zone Alarm Silence normally open dry contact. Same input wired to 851-4084 Remote Zone Silence panels.
Zone 1 Zone 2 Zone 3
Zone 4 Zone 5 Zone 6
24VAC Hot
Batt Mode 24Vac Neu
From 851-4071 UPS Panel

Zone 5
Zone 6
Field Installed Break Glass Panel

24VAC Hot 24VAC Hot

NO NO

R2

2 4

8

Recommended Specification Torque: 0.5-0.6 Nm Wire Sizes: 24-10 AWG
BAS Zone 1 Silence

FUSE

BAS Zone 2 Silence

BAS Zone 3 Silence

BAS Zone 4 Silence

BAS Zone 5 Silence BAS Zone 6 Silence

BAS Zone Silence Cmn

Battery Mode Neutral Battery Mode Hot
Break Glass 1 Input Break Glass 1 Input Break Glass 2 Input Break Glass 2 Input

Inputs
1.6 Power Connection Terminals
The field connections for supply power to the panel are made on the 120 VAC HOT IN/UPS POWER IN terminal block below the zone board.

MRLDS Signal

Analog MRLDS Signal Out

R1

Pilot Relay Coil Power

Power

Power

MRLDS Hrm/Strb

Shield
24VAC 24VAC Common 24VAC Relay N Horn(s) Strobe(s) Dry Cont

K1 K2 K3 K4

Shield

Analog Out

MRLDS Power 10VA MAX

89
90 91 92
GND
120VAC Neutral 120VAC
HOT

24VAC 24VAC Common Horn(s) Strobe(s) Indicator Silence NO Cont C Cont NO Cont Ext. Fan Ctrl Ext. Fan Ctrl

Dry Contact 10A @ 120V MAX

Remote Devices 24VAC, 50VA MAX

ZONE 6
Upstream disconnect and branch circuit protection (MCCB, 20A Max.) supplied by the installer, is required
for each lighting/power circuit.

Tighten all connections to recommended specifications before applying power.
Use recommended field conductor wire sizes. Copper conductor only, 60° Celsius minimum.
120VAC HOT IN/ IPS POWER IN

Recommended Specification Torque: 0.6-0.8 Nm Wire Sizes: 24-10 AWG

Power In 5

2 Set Up Instructions
NOTE: When updating screen parameters on the Visograph, only one Visograph at a time may be connected to the Multi-Zone Leak Detector.
Press the corresponding button along the bottom labeled (T1-T8) to navigate to the desired item. Press SET once to enter edit mode, and use the up and down arrow keys to change values and press SET once to save the selected value.
Main Screen
The main screen shows the associated refrigerated rack system and circuit number of each detector zone, which is listed under the System column. The zone status is shown under the Status column. Active alarms will cause the bell icon to flash in the upper left corner. Press and hold OFF (T8) to silence the alarm located on the panel. The strobe will remain on until the condition no longer exists and the alarm is manually reset. The zones in alarm condition are indicated by flashing AL1 through AL6, respectively. Each zone can be silenced by pressing the corresponding T2 through T7. The zone alarm can be reset by holding the corresponding button for three (3) seconds.
NOTE: Alarm silence and reset functions on the main screen: T2 = AL1, T3 = AL2, T4 = AL3, T5 = AL4, T6 = AL5, T7 = AL5, T8 = OFF
2.1 Configuring Modbus Settings

If the communication to the E2 will be using Modbus protocol, the Modbus address and baud rate must be configured before successful communication will occur.
To set controller information from the Detector Status screen:
1. Press and hold T4 and T5 for three (3) seconds. 2. The Setup screen will appear. 3. Use the up and down arrow keys to highlight and
select Controller Info and press SET. 4. The Controller Info screen will appear. 5. Use the up and down arrow keys to highlight and set
the date, time, and Modbus address. 6. Press SET after each selection to save changes. 7. After all Modbus settings have been configured, a
controller reboot must be performed. Use the down arrow key to select No next to Reboot Controller, press SET to edit and use the arrow keys to select Yes. Press SET again. The controller will reboot and boot back up with the new settings applied.
NOTE: Set the Modbus address to the next available address. Press SET after making each change to save your entries.
2.2 Configuring BACnet Settings
If the communication to the E2 will be using BACnet MS/TP protocol, the BACnet MS/TP settings must be configured before successful communication will occur.
To configure the BACnet Settings from the Detector Status screen:
1. Press and hold T4 and T5 for three (3) seconds. 2. The Setup screen will appear.

Controller Info Screen 6

BACnet Setup Screen

3. Scroll to 3. BACnet Settings and press SET to enter.

Pressing SAVE will apply the changes made and the system will reboot.

BACnet Settings Screen
4. MS/TP MAC: This parameter specifies the MS/TP network MAC address of the Leak Detector. Each BACnet device on the bus must have a unique number here. Enter a unique number between 0-127 and press SET to save.
5. Baud Rate: This parameter specifies how fast data is sent over the serial line. Set to match the baud rate of the serial port of the E2 controller.
6. Max Master: This parameter defines the value of the highest allowable address for master nodes on the network. Determine the highest MS/TP MAC address used on the bus and set Max Master equal to this value. Example: If there are 40 controllers on the bus and
the highest address is 40, set the max master of all 40
controllers to 40.
7. Device ID: Enter the BACnet device identifier here. Enter a unique number for the MS/TP network in the range of 0-4, 194, 303.
8. When at least one (1) setting has been edited, a CANCEL option will appear above the T7 key and a SAVE option above the T8 key. Pressing Cancel will revert the system back to the previous settings and no change will be applied.

BACnet Reboot Screen
Once the Leak Detector is booted back up, it is ready for connection to E2.
2.3 Configuring Each Leak Detector Zone
To configure the parameters, from the Detector Status Screen:
1. Press and hold T4 and T5 for three (3) seconds. 2. The Setup screen will appear.
Leak Detector Setup Screen
3. Use the up and down arrow keys to highlight and select Config Param.

BACnet Save Settings

Leak Detector Configuration Screen 7

4. To configure each zone, select the corresponding Zone X Setup. This example will configure Zone 1 Setup, the steps are the same for Zones 1-6. Select Zone 1 and press SET.

Leak Detector Zone 1 Setup Parameters Screen 1
On the Zone 1 Setup screen, each parameter in the table below can be edited by using the T4/T6 keys to change values and the T5 SET key to save the selection. Scrolling between pages within the zone setup is done by using T7/T8 keys. To advance to next or previous zone setup menu, use T2 or T3 shortcut keys. Configure each parameter in the Zone 1 Parameters Page 1 table and see the instruction column of the table for required action.

Parameter Name
WI Name Rack ID
Circuit # Refrigerant AID1
DT1
8

Description

Instruction

Represents the walk in cooler/freezer box name for the associated leak detection zone.

Select a walk in box name from the list and press SET to save.

Selects the corresponding refrigeration rack system that this zones refrigeration is physically piped to.
Represents the corresponding refrigeration circuit number for this leak detection zone.

Select a rack system name from the list and press SET to save.
Enter a circuit number and press SET to save.

Selects the refrigerant gas type used for this zone.

Choose the gas type for this zone from the list and press SET to save.

AID1 selects which analog input will be used for the leak sensor signal input for zone 1.
DT1 selects the voltage scale for the leak sensor signal input.

Preset from factory, no action.
All Emerson MRLDS 250 Gas Specific Sensors, set 1-5V.
For Emerson SC Gas Specific Sensors, set 0-10V Nonlinear.*
For Emerson IR R744 Sensors, set 0-10V.

Zone 1 Parameters Page 1

Parameter Name

Description

DT1 Min/DT 1 Max

DT1 Min represents the PPM minimum value when the leak sensor is at minimum signal voltage.
DT1 Max represents the PPM maximum value when the leak sensor is at maximum signal voltage.

PPMn1 PPMa1 PPMs1

PPMn1 Represents the PPM level that must be reached by the leak sensor to trigger a notification.
PPMa1 Represents the PPM level that must be reached by the leak sensor to trigger an alarm.
PPMs1 Represents the PPM level that must be reached by the leak sensor to trigger a spill alarm.

Instruction
Depending on sensors used, set Emerson part numbers to:
809-1001 = 1 PPM min. 1000 PPM max.
809-1012 = 1 PPM min. 3500 PPM max.
809-0035 = 1 PPM min. 3500 PPM max.
809-1020 = 1 PPM min. 5000 PPM max.
809-1201-1203 = Parameter not used, will be hidden on screen. Automatically calculated by equation.
809-1215 = 1 DT Min. 5000 DT Max.
809-1216 = 1 DT Min. 10000 DT Max.
Depending on sensors used, set Emerson part numbers to:
For Walk-In Boxes using 809-1001, set 999 PPMn1, PPMa1, PPMs1.
For Walk-In Boxes using 809-1012, 809-0031 to 0044, set 1000 PPMn1, PPMa1, PPMs1.
For rack and/or machine rooms using 809-1012, 809-0031, to 0044 = 3000 PPMn1, PPMa1, PPMs1.
For Walk In Boxes Using 809-1020, 809-1215, set 4999 PPMn1, PPMa1, PPMs1.
For Walk In Boxes Using 809-1020, 809-1216, set 5000 PPMn1, PPMa1, PPMs1.

Zone 1 Parameters Page 1
Advance to the next page of setup parameters by pressing T8.

Leak Detector Zone 1 Setup Parameters Screen 2

Parameter Name
AOD1

Description and Instruction
Selects the physical analog output number to be used for the zone analog output signal.

Instruction
Preset from factory, no action.

AO1Min/ AO1Max
AOP1Min/ AOP1Max
RDT1-R1 ATDT1-R1

AO1Min is the minimum signal level that AOD1 will output at the minimum PPM level set by AOP1Min. AO1Max is the maximum signal level that AOD1 will output at the maximum PPM level set by AOP1Max.
AOP1Min is the minimum PPM level that corresponds to the output signal of AO1Min. AOP1Max is the maximum PPM level that corresponds to the output signal of AO1Max.
Relay 1 output assignment for detector 1. Advisory type selection that would manage relay 1 for detector 1 (RDT1-R1.): Not Used, Notice, Alarm, Spill.

AO1Min – Set to 1.0 volts and press SET to save. AO1Max – Set to 5.0 volts and press SET to save.
All sensor part numbers, AO1P1Min: AOP1Min-Set to 0 PPM and press SET to save. Set AOP1Max according to the PPM value listed next to the part number of the gas detector installed: 809-1001 AOP1Max-Set to 1000 PPM and press SET to save. 809-1012, 809-0031 to 0044 (all MRLDS 250 Models): AOP1Max-Set to 3500 PPM and press SET to save. 809-1201 to 1203: AOP1Max-Set to 4000 PPM and press SET to save. 809-1020, 809-1215: AOP1Max-Set to 5000 PPM and press SET to save. 809-1216: AOP1Max-Set to 10000 PPM and press SET to save.
Preset from factory, no action.
Preset from factory, no action.

Zone 1 Parameters Page 2

Advance to the next page of setup parameters by pressing T8.

Leak Detector Zone 1 Setup Parameters Screen 3

Parameter Name
RDT1-R2
ATDT1-R2
RDT1-Horn

Description and Instruction

Instruction

Relay 2 output assignment for Detector 1.

Preset from factory, no action.

Advisory type selection that would manage relay 2 for detector 1: Not Used, Notice, Alarm, Spill.

Preset from factory, no action.

Relay output assignment for the horn associated with detector 1.

Preset from factory, no action.

DI1-S DI1-R DI1-O

Digital input of Detector 1 used for Horn Silence.

Preset from factory, no action.

Digital input of Detector 1 used for Alarm Reset.
Digital input of Detector 1 used for Alarm On.

Preset from factory, no action.
Preset from factory, no action.

Zone 1 Parameters Page 2

After all parameters for Zone 1 setup have been reviewed and set, use the T3 shortcut key to advance to the next zone, repeat the above setup steps for each installed Leak Detector zone.

9

2.4 Configuring Horn Silence Time
To configure the parameters from the Detector Status Screen:
1. Press and hold T4 and T5 for three (3) seconds. 2. The Setup screen will appear.

2.5 Configuring Relay Delays
1. To configure relay delay parameters, navigate to the Setup menu.

Horn Silence Time Setup Screen
3. Select Config Param.

Relay Delay Setup Screen
2. Select Config Param.

Horn Silence Time Configuration Screen
4. Select 10. Misc and press SET.

Relay Delay Configuration Screen
3. Select 9. Relay Delays and press SET.

Horn Silence Time Miscellaneous Screen
5. Scroll to DBTR and adjust desired silence time.
10

Set Delays Screen
4. Set all delays in all pages to 0 min for no delay. Press SET to save each selection.

2.6 Battery Backup Override
The OverBatCMD represents the command to override battery backup. The OverDIBat represents the digital input to the battery backup.
1. To configure battery backup override, navigate to the Setup menu.

2.7 Configuring a Break Glass Safety Switch
If the installation requires a Break Glass safety switch, the input will be connected to the alarm on digital inputs.
1. To configure a Break Glass safety switch, navigate to the Setup menu.

Battery Backup Override Setup Screen
2. Select Config Param.

Break Glass Safety Switch Setup Screen
2. Select Config Param.

Battery Backup Configuration Screen
3. Select 10. Misc. and press T8 to scroll over to page 2.

Break Glass Safety Switch Configuration Screen
3. Select 5. Zone 6 Setup and press T8 twice to scroll to screen 3.

Battery Backup Override Miscellaneous Screen
4. Set OverBatCMD and OverDIBat to OFF and press SET to save.

Break Glass Safety Switch Zone 5 Setup Screen 11

4. Scroll down to parameter DI5-0 and press SET to edit, select DI8 from the list and press SET to save.
5. If a second Break Glass safety switch is required, press button T3 to advance directly to Zone 6 Setup. Once in Zone 6 Setup, press T8 twice to scroll to screen 3.

3. Select Config Param.

Break Glass Safety Switch Zone 6 Setup Screen
6. Scroll down to parameter DI6-0 and press SET to edit, select DI9 from the list, and press SET to save.
7. Press Exit. The Break Glass configuration is complete.
2.8 Enabling and Disabling Zones
Once zone setup has been completed for Zone 1 setup through Zone 6 setup, make sure each zone is enabled for operation. Zones that are not physically installed or in use should be set to DISABLE.
NOTE: Setting a zone to DISABLE will inhibit all leak detection and alarming capabilities permanently until the zone is set back to ENABLE.
To configure the Zone Enables from the Detector Status screen:
1. Press and hold T4 and T5 for three (3) seconds. 2. The Setup screen will appear.

Enabling and Disabling Zones Configuration Screen
4. Select 7. Zone Enables and press SET.
Zone Enables Screen
5. Scroll through each zone and set each zone that needs to be placed in operation to ENABLE.

Enabling and Disabling Zones Setup Screen 12

3 Viewing Zone Status Screens
To view a quick status of current PPM levels within each zone, press T1 Status from the main Detector Status screen:

Zone Detector Status Screen
Pressing T1 Status jumps to the PPM level status. The rack name and circuit number can be quickly viewed next to the associated PPM level of that zone.

Detailed Zone Status Screen
Pressing the gear icon with button T3 is a shortcut to the Zone Setup menu.

PPM Level Status Screen
To enter the detailed individual zone status, scroll to the desired zone and press SET. For convenience the zone enable can be edited from the detailed zone status.

13

4 Table of Parameters

Parameter Name

Description

WI Name Zone 1 WI Name Zone 2 WI Name Zone 3 WI Name Zone 4 WI Name Zone 5 WI Name Zone 6 Rack ID Zone 1
Rack ID Zone 2 Rack ID Zone 3 Rack ID Zone 4
Rack ID Zone 5
Rack ID Zone 6 Circuit # Zone 1 Circuit # Zone 2 Circuit # Zone 3 Circuit # Zone 4 Circuit # Zone 5 Circuit # Zone 6 Refrigerant Zone 1 Refrigerant Zone 2 Refrigerant Zone 3 Refrigerant Zone 4 Refrigerant Zone 5
Refrigerant Zone 6 ENDT1 ENDT2 ENDT3 ENDT4 ENDT5

Selects the walk-in box name for Zone 1
Selects the walk-in box name for Zone 2
Selects the walk-in box name for Zone 3
Selects the walk-in box name for Zone 4
Selects the walk-in box name for Zone 5
Selects the walk-in box name for Zone 6
Selects the refrigeration system name to which this zone is physically piped
Selects the refrigeration system name to which this zone is physically piped
Selects the refrigeration system name to which this zone is physically piped Selects the refrigeration system name to which this zone is physically piped
Selects the refrigeration system name to which this zone is physically piped
Selects the refrigeration system name to which this zone is physically piped Selects the refrigeration circuit number for this zone Selects the refrigeration circuit number for this zone Selects the refrigeration circuit number for this zone Selects the refrigeration circuit number for this zone Selects the refrigeration circuit number for this zone Selects the refrigeration circuit number for this zone Selects the refrigerant gas type for this zone Selects the refrigerant gas type for this zone Selects the refrigerant gas type for this zone Selects the refrigerant gas type for this zone Selects the refrigerant gas type for this zone
Selects the refrigerant gas type for this zone
Leak detector # 1 is enabled
Leak detector # 2 is enabled
Leak detector # 3 is enabled
Leak detector # 4 is enabled
Leak detector # 5 is enabled

14

Parameter Name

Description

ENDT6 DT1 DT2 DT3 DT4 DT5 DT6 DT1Min DT1Max DT2Min DT2Max DT3Min DT3Max DT4Min DT4Max DT5Min DT5Max DT6Min DT6Max PPMn1 PPMa1 PPMs1

Leak detector # 6 is enabled
Leak detector 1 type. 1-5V, 0-10V, and 4-20mA
Leak detector 2 type. 1-5V, 0-10V, and 4-20mA
Leak detector 3 type. 1-5V, 0-10V, and 4-20mA
Leak detector 4 type. 1-5V, 0-10V, and 4-20mA Leak detector 5 type. 1-5V, 0-10V, and 4-20mA Leak detector 6 type. 1-5V, 0-10V, and 4-20mA
Leak detector 1 minimum PPM value at 1 or 0 V, depending on the type
Leak detector 1 maximum PPM value at 1 or 0 V, depending on the type
Leak detector 2 minimum PPM value at 1 or 0 V, depending on the type
Leak detector 2 maximum PPM value at 1 or 0 V, depending on the type
Leak detector 3 minimum PPM value at 1 or 0 V, depending on the type
Leak detector 3 maximum PPM value at 1 or 0 V, depending on the type
Leak detector 4 minimum PPM value at 1 or 0 V, depending on the type
Leak detector 4 maximum PPM value at 1 or 0 V, depending on the type
Leak detector 5 minimum PPM value at 1 or 0 V, depending on the type
Leak detector 5 maximum PPM value at 1 or 0 V, depending on the type
Leak detector 6 minimum PPM value at 1 or 0 V, depending on the type
Leak detector 6 maximum PPM value at 1 or 0 V, depending on the type
Leak detector 1 Notice parameter
Detector 1 Alarm parameter
Detector 1 Spill parameter

PPMn2

Detector 2 Notice parameter

PPMa2

Detector 2 Alarm parameter

PPMs2

Detector 2 Spill parameter

PPMn3

Detector 3 Notice parameter

PPMa3 PPMs3

Detector 3 Alarm parameter Detector 3 Spill parameter

Parameter Name

Description

PPMn4 PPMa4 PPMs4 PPMn5 PPMa5 PPMs5 PPMn6 PPMa6 PPMs6 PPNAH RDT1-R1 RDT2-R1
RDT3-R1
RDT4-R1
RDT5-R1
RDT6-R1 RHOR ATDT1-R1 ATDT2-R1 ATDT3-R1 ATDT4-R1 ATDT5-R1 ATDT6-R1 LOR RDT1-R2 RDT2-R2 RDT3-R2 RDT4-R2 RDT5-R2

Detector 4 Notice parameter
Detector 4 Alarm parameter
Detector 4 Spill parameter
Detector 5 Notice parameter
Detector 5 Alarm parameter
Detector 5 Spill parameter
Detector 6 Notice parameter
Detector 6 Alarm parameter
Detector 6 Spill parameter
Alarm-Spill Hysteresis
Relay 1 output assignment for detector 1. Controlled by selection in ATDT1-R1 Relay 1 output assignment for detector 2. Controlled by selection in ATDT2-R1
Relay 1 output assignment for detector 3. Controlled by selection in ATDT3-R1
Relay 1 output assignment for detector 4. Controlled by selection in ATDT4-R1
Relay 1 output assignment for detector 5. Controlled by selection in ATDT5-R1
Relay 1 output assignment for detector 6. Controlled by selection in ATDT6-R1
General horn relay assignment
Advisory type selection that would manage relay 1 for Detector 1 (RDT1-R1) Advisory type selection that would manage relay 1 for Detector 2 (RDT2-R1) Advisory type selection that would manage relay 1 for Detector 3 (RDT3-R1) Advisory type selection that would manage relay 1 for Detector 4 (RDT4-R1) Advisory type selection that would manage relay 1 for Detector 5 (RDT5-R1) Advisory type selection that would manage relay 1 for Detector 6 (RDT6-R1)
General advisory light relay assignment
Relay 2 output assignment for detector 1. Controlled by selection in ATDT1-R2 Relay 2 output assignment for detector 2. Controlled by selection in ATDT2-R2 Relay 2 output assignment for detector 3. Controlled by selection in ATDT3-R2
Relay 2 output assignment for detector 4. Controlled by selection in ATDT4-R2
Relay 2 output assignment for detector 5. Controlled by selection in ATDT5-R2

Parameter Name RDT6-R2 ATDT1-R2 ATDT2-R2 ATDT3-R2 ATDT4-R2 ATDT5-R2 ATDT6-R2 RBTA RDT1-Horn RDT2-Horn RDT3-Horn RDT4-Horn RDT5-Horn RDT6-Horn DIHL DTBR DI1-S DI1-R DI1-O DI2-S DI2-R DI2-O DI3-S DI3-R DI3-O DI4-S

Description
Relay 2 output assignment for detector 6. Controlled by selection in ATDT6-R2
Advisory type selection that would manage relay 2 for Detector 1 (RDT1-R2)
Advisory type selection that would manage relay 2 for Detector 2 (RDT2-R2)
Advisory type selection that would manage relay 2 for Detector 3 (RDT3-R2)
Advisory type selection that would manage relay 2 for Detector 4 (RDT4-R2)
Advisory type selection that would manage relay 2 for Detector 5 (RDT5-R2)
Advisory type selection that would manage relay 2 for Detector 6 (RDT6-R2)
Relay assignment for back up battery. Output managed by DIBT
Relay output assignment for the horn associated with Detector 1
Relay output assignment for the horn associated with Detector 2
Relay output assignment for the horn associated with Detector 3
Relay output assignment for the horn associated with Detector 4
Relay output assignment for the horn associated with Detector 5
Relay output assignment for the horn associated with Detector 6
Digital input assignment to silence the general horn
Horn delay time before activating
Digital input of Detector 1 used for Horn Silence
Digital input of Detector 1 used for Alarm Reset
Digital input of Detector 1 used for Alarm On Digital input of Detector 2 used for Horn Silence Digital input of Detector 2 used for Alarm Reset Digital input of Detector 2 used for Alarm On
Digital input of Detector 3 used for Horn Silence
Digital input of Detector 3 used for Alarm Reset
Digital input of Detector 3 used for Alarm On
Digital input of Detector 4 used for Horn Silence

15

Parameter Name
DI4-R
DI4-O
DI5-S
DI5-R
DI5-O
DI6-S
DI6-R
DI6-O DIBT REHR REASR ROD1 ROD2 ROD3 ROD4 ROD5 ROD6 ROD7 ROD8 RFD1 RFD2 RFD3 RFD4 RFD5 RFD6 RFD7 RFD8 ROD9 ROD10 ROD11 ROD12 ROD13 ROD14

Description
Digital input of Detector 4 used for Alarm Reset Digital input of Detector 4 used for Alarm On Digital input of Detector 5 used for Horn Silence Digital input of Detector 5 used for Alarm Reset Digital input of Detector 5 used for Alarm On Digital input of Detector 6 used for Horn Silence Digital input of Detector 6 used for Alarm Reset Digital input of Detector 6 used for Alarm On Digital input as battery backup alarm
Reactive Horn Relay
Reactive Alarm/Spill Relay
ON delay Relay 1
ON delay Relay 2
ON delay Relay 3
ON delay Relay 4
ON delay Relay 5
ON delay Relay 6
ON delay Relay 7
ON delay Relay 8
OFF delay Relay 1
OFF delay Relay 2
OFF delay Relay 3
OFF delay Relay 4
OFF delay Relay 5
OFF delay Relay 6
OFF delay Relay 7
OFF delay Relay 8
ON delay Relay 9
ON delay Relay 10
ON delay Relay 11
ON delay Relay 12
ON delay Relay 13
ON delay Relay 14

16

Parameter Name

Description

ROD15 RFD9 RFD10 RFD11 RFD12 RFD13 RFD14 RFD15 RLP1 RLP2 RLP3 RLP4 RLP5 RLP6 RLP7 RLP8 DIP1 DIP2 DIP3 DIP4 DIP5 DIP6 DIP7 DIP8 DIP9 DIP10 DIP11 RLP9 RLP10 RLP11 RLP12 RLP13 RLP14 RLP15 DIP12 DIP13

ON delay Relay 15 OFF delay Relay 9 OFF delay Relay 10 OFF delay Relay 11 OFF delay Relay 12 OFF delay Relay 13 OFF delay Relay 14 OFF delay Relay 15 Polarity of RL1 Polarity of RL2 Polarity of RL3 Polarity of RL4 Polarity of RL5 Polarity of RL6 Polarity of RL7 Polarity of RL8 Polarity of DI01 Polarity of DI02 Polarity of DI03 Polarity of DI04 Polarity of DI05 Polarity of DI06 Polarity of DI07 Polarity of DI08 Polarity of DI09 Polarity of DI010 Polarity of DI011 Polarity of RL9 Polarity of RL10 Polarity of RL11 Polarity of RL12 Polarity of RL13 Polarity of RL14 Polarity of RL15 Polarity of DI12 Polarity of DI13

Parameter Name

Description

DIP14 DIP15 DIP16 DIP17 DIP18 DIP19 DIP20 AID1 AID2 AID3 AID4 AID5 AID6 AOD1 AOD2 AOD3 AOD4 AOD5 AOD6 AO1Min AO1Max AO2Min AO2Max AO3Min AO3Max AO4Min AO4Max AO5Min AO5Max AO6Min AO6Max AOP1Min AOP1Max AOP2Min AOP2Max AOP3Min

Polarity of DI14 Polarity of DI15 Polarity of DI16 Polarity of DI17 Polarity of DI18 Polarity of DI19 Polarity of DI20 Analog input of Detector 1 Analog input of Detector 2 Analog input of Detector 3 Analog input of Detector 4 Analog input of Detector 5 Analog input of Detector 6 Analog output of Detector 1 Analog output of Detector 2 Analog output of Detector 3 Analog output of Detector 4 Analog output of Detector 5 Analog output of Detector 6 Min analog output of Detector 1 Max analog output of Detector 1 Min analog output of Detector 2 Max analog output of Detector 2 Min analog output of Detector 3 Max analog output of Detector 3 Min analog output of Detector 4 Max analog output of Detector 4 Min analog output of Detector 5 Max analog output of Detector 5 Min analog output of Detector 6 Max analog output of Detector 6 Min PPM of analog output of Detector 1 Max PPM of analog output of Detector 1 Min PPM of analog output of Detector 2 Max PPM of analog output of Detector 2 Min PPM of analog output of Detector 3

Parameter Name

Description

AOP3Max AOP4Min AOP4Max AOP5Min AOP5Max AOP6Min AOP6Max OVERT RODR1 RODR2 RODR3 RODR4 RODR5 RODR6 RFDR1 RFDR2 RFDR3 RFDR4 RFDR5 RFDR6 RLPR1 RLPR2 RLPR3 RLPR4 RLPR5 RLPR6

Max PPM of analog output of Detector 3 Min PPM of analog output of Detector 4 Max PPM of analog output of Detector 4 Min PPM of analog output of Detector 5 Max PPM of analog output of Detector 5 Min PPM of analog output of Detector 6 Max PPM of analog output of Detector 6 Override time ON delay IPX106D Relay 1 ON delay IPX106D Relay 2 ON delay IPX106D Relay 3 ON delay IPX106D Relay 4 ON delay IPX106D Relay 5 ON delay IPX106D Relay 6 OFF delay IPX106D Relay 1 OFF delay IPX106D Relay 2 OFF delay IPX106D Relay 3 OFF delay IPX106D Relay 4 OFF delay IPX106D Relay 5 OFF delay IPX106D Relay 6 Polarity of IPX106D Relay 1 Polarity of IPX106D Relay 2 Polarity of IPX106D Relay 3 Polarity of IPX106D Relay 4 Polarity of IPX106D Relay 5 Polarity of IPX106D Relay 6

Table of Parameters

17

5 Uploading the Multi-Zone Refrigerant Leak Detector Description File to E2

NOTE: UltraSite32 Software should be installed to perform uploading of Description Files.
1. Connect to E2 using UltraSite32 (refer to UltraSite32 TCP/IP Connection Manual (P/N 026-1002).
2. Launch the UltraSite program and Login. Type USER in the Username and PASS in the Password fields.
3. Double click to open the Directory Level to view the Site Level. Refer to Description File Upload graphic below.
4. Right click on Site Level and click Connect.
5. Double click on Site Level and locate the E2 Unit where the Multi-Zone Refrigerant Leak Detector will be installed.
6. Right click on the unit and select Upload Description File.

7. Click the Browse button.

E2 Description File Upload
8. Browse the computer and select the appropriate description (*.dsc) file for the Multi-Zone Refrigerant Leak Detector.
NOTE: Select the appropriate Description File for the communication type with E2. Leak Detector 5.32F12 and later supports BACnet MS/TP. The BACnet MS/TP file P/N is 527-0600 and the Modbus file P/N is 527-0389. To use BACnet MS/TP with Leak Detector and E2, the E2 must be 4.09F04 or later and Leak Detector 5.32F12 or later.

Description File Upload 18

E2 Description File Upload

9. Click OPEN.
10. Click UPLOAD. A window will appear with a message that the Description File was imported, click OK.

5.1 Licensing the Multi-Zone Leak Detector in the E2
If the BACnet description file (P/N 527-0600) will be used for leak detector communication, no license key is required, there will be 10 instances of Leak Detector available by default.
1. Log on to the E2 controller and Press . 2. Press to add the license for the Description File. 3. Enter the 16-digit number provided from Technical
Support.
4. Press .

E2 Description File Upload

11. The description (*dsc) file will appear inside the box.

Adding License
5.2 Device Setup in the E2 5.2.1 E2 Serial Port Setup – Modbus
1. Log into to E2 by pressing the button. 2. Type USER in the Username and PASS in the Password
fields. 3. Press to enter General Controller Info
setup. 4. Press twice move to C3: Serial Tab.

E2 Description File Upload
12. Once completed, disconnect from the E2 unit. 13. Reboot the E2 controller.

Serial Port Set Up 19

5. Highlight COM6 Connection value:
· Press for the Look Up menu and select MODBUS-1 (if MODBUS-1 is being used, select MODBUS-2 or MODBUS-3).
· Press the to set configuration. · Set the MODBUS Connection as follows: (Press
to select options and set the configuration.)
» COM2 Baud: 9600 » COM2 Data Size: 8 » COM2 Parity: None » COM2 Stop Bits: 1 6. Press to save changes. 7. Press to go back to the Home screen.
5.2.2 E2 Serial Port Set Up – BACnet MS/TP 1. Login to E2 with Username: user; Password: pass 2. Press + on the E2 keyboard to access the serial tab of the general controller setup screen. This screen will have a connection field for all available COM ports on the E2. Highlight the COM port connection you will be using for BACnet MS/TP and press (LOOKUP) and select BACnet MS/TP -1, -2, or -3 from the list of network types.

c. COM4 Baud – Default setting is 9600; this must be changed to 19.2k or 38.4k. (All devices connected to the same COM port should be set to the same baud rate).
4. Now the BACnet MS/TP specific settings must be configured. From the Home screen on E2 press + on the keypad to navigate to this screen:
BACnet TCP/IP Tab
5. Press + at the same time to reach the BACnet tab:

BACnet MS/TP Serial Port Set Up
3. Three fields will become visible underneath the COM4 Connection that pertain to the way the device communicates:
a. COM4 DevId – This is the E2 BACnet Device ID; set this to a unique number from all other BACnet nodes on the network in the range of 0-4194303.
b. COM4 MSTP MAC – This is the E2 BACnet MSTP MAC address; set this to a unique number for E2 in the range of 1-127. Each BACnet device on the network must have its own unique MS/TP MAC for successful communication.

BACnet General Setup Screen
6. These settings must be configured in the BACnet tab:
a. Max Master – The default setting is 127, edit and change the value to be equal to the highest BACnet MAC address that E2 will communicate with on any of its three (3) COM ports. Determine what BACnet MS/TP devices are connected to E2’s COM ports, then determine the highest MS/TP MAC address of all the devices. Set the E2 Max Master equal to the highest MS/TP MAC address determined.
b. Max Info Frames – This is the max number of BACnet frames E2 can transmit per token. Set to 36.

20

c. PDU Timeout – This is the amount of time in seconds between re- transmissions of an APDU requiring acknowledgment for which no acknowledgment has been received. Enter a value of 30 in this field.
d. APDU Retries – This is the maximum amount of times that an APDU shall be retransmitted. Enter a value of 3 in this field.
e. TimeSync Period – This is the number of minutes between time synchronization broadcasts. Enter a value of 1440 here.
f. UTC TimeSync – This toggles the time sync broadcast to use coordinated universal time mode. Toggle this field to NO.
5.3 Device Wiring
Device Wiring 21

5.4 Connecting Communication Wires – Modbus
If the communication protocol between Leak Detector and E2 is using Modbus, connect the RS485 wiring to the RS485 slave terminal on the iPro controller, terminals 97, 98, 99. The polarity of the + and – wires is reversed between the E2 serial port and the leak detector serial port.

5.5 Adding the Multi- Zone Refrigerant Leak Detector in E2
1. Press to open the Connected I/O Boards and Controllers setup.
2. Press twice to move to C4: Third Party tab. Highlight the Multi-Zone Refrigerant Leak Detector application and enter the number of devices under Quantity.

Multi-Zone Leak Detector Wiring
NOTE: The polarity of the MODBUS connection between E2 and the Multi-Zone Refrigerant Leak Detector is reversed.
5.4.1 Connecting Communication Wires – BACnet MS/TP
The BACnet MS/TP connection should be wired in a daisy chain topology, no star or T configurations are allowed. Connect the BACnet network cable to the three terminal connector on the E2 COM port you wish to assign as BACnet MS/TP. Connect the network cable to the leak detector on the RS485 master port terminals 94, 95, 96.
Reverse the polarity of +/- on the RS485 cable between the E2 serial port and the leak detector serial port. Emerson specs General Cable 92454A (Emerson P/N 135-0600) shielded twisted pair cables for use as BACnet MS/TP wiring.

Third Party Tab
3. Press to save changes. 4. Press to go back to the Home screen.
5.6 Commissioning Multi-Zone Refrigerant Leak Detector – Modbus
1. Press to enter the Network Summary screen.
2. Highlight the Multi-Zone Refrigerant Leak Detector to be commissioned and press .

Network Summary Screen
3. If a box with Select Network appears on the screen, select the MODBUS number where the device was configured.
22

4. Select address for the device and press .

5.7 Commissioning Multi-Zone Refrigerant Leak Detector – BACnet MS/TP
1. Login to the E2 and press + to reach the Network Summary screen.

Network Summary Screen
5. This screen will appear. Press to continue.

BACnet MS/TP Network Summary Screen
2. Press (Setup) to enter device setup in the General tab. Set Do Initial Sync to Yes, Initial Action to Send Device Cfg to E2, and Cfg Sync Action to Send Device Cfg to E2. Press to save and exit back to Network Summary screen.

Network Summary Screen
6. Press to save the assigned address. 7. Press button to return to the Home screen.
Press to enter the Network Summary screen. 8. The Multi-Zone Refrigerant Leak Detector should appear ONLINE after a few seconds.

BACnet MS/TP General Screen
3. Highlight the device and press commission for a list of networks. Select the BACnet MS/TP route assigned to the COM port.

Network Summary Screen

BACnet MS/TP Select Network 23

4. E2 will scan for available BACnet MS/TP devices.

7. Press to save and exit back to the Network Summary screen:

BACnet MS/TP Device Commission
5. E2 will display a list of the MS/TP devices discovered during the scan. The number in parenthesis is the BACnet MAC address and the 6-digit number adjacent to it is the BACnet Device ID. Select the device you want to commission and press on the E2 keypad.

BACnet MS/TP Device Status Online
8. The device status should now change to Online in green. Allow approximately five (5) minutes for initial communication startup and synchronization to complete before editing parameters.
5.8 Viewing E2 Status Screen
Press + to reach the Network Summary page. Highlight the Multi-Zone Refrigerant Leak Detector and press .

BACnet MS/TP Devices
6. Press again on E2 keypad and then E2 will display BACnet Device ID is set:

Viewing Status

BACnet MS/TP Device ID is Set 24

5.9 Resetting Spill Alarm
When the Leak Detector version 5.32F12 or later is communicating with E2, the zone spill alarms can be reset from E2. Once the zone PPM has fallen back below the spill setpoint (PPMs), the alarm can be reset.
Perform the following steps at E2 to reset a zone spill alarm:
1. Login to the E2 controller and press + keys at the same time to reach the Network Summary page:

3. With the Leak Detector controller name highlighted, press on the E2 keyboard.
4. A pop-up window will appear, select 9. Application Commands.

Resetting Spill Alarm Network Summary Screen
2. Scroll down and highlight the Leak Detector and press STATUS to reach the status screen.

Resetting Spill Alarm Application Commands Screen
5. The zone alarm resets are performed by using the Zone1 Alarm Reset-Zone6 Alarm Reset application command. After selecting the desired application command, the window will automatically close and E2 will perform the application command.
6. After a zone alarm resets the status, the zone box should go back to OK and the horn, strobe and E2 relays should return to off in the Relay Status box.
NOTE: In order to reset a zone spill alarm, the zone PPM level must be below the PPM level set by parameter PPMs in the Leak Detector.

Resetting Spill Alarm Status Screen

25

026-1313 R5
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. ©2023 Emerson is a trademark of Emerson Electric Co.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals