BOSCH FPE8000SPC Panel Controller Installation Guide
- June 12, 2024
- Bosch
Table of Contents
BOSCH FPE8000SPC Panel Controller
Product Information
The AVENAR panel series is a product manufactured by Bosch Sicherheitssysteme GmbH. It comes in different models: FPE8000SPC, FPE8000PPC, FPE2000SPC, and FPE2000PPC. The panel series is designed for installation and is equipped with various interfaces such as CAN1, CAN2, IN1/2, ETH1, ETH2, ETH3, ETH4, USB, and bus interfaces. It features an LCD display and has a weight of 2.4 kg. The panel series operates at a temperature range of -20 to +70 degrees Celsius and requires a current of mA at 24V DC. The product is available in RAL7016 antracit color and has UL94-V0 fire resistance rating.
Product Usage Instructions
- Before using the AVENAR panel series, make sure to read the installation guide provided by Bosch Sicherheitssysteme GmbH.
- Ensure that the panel series is installed correctly according to the instructions provided in the installation guide.
- Connect the necessary interfaces such as CAN1, CAN2, IN1/2, ETH1, ETH2, ETH3, ETH4, and USB to the respective devices or systems.
- Power the panel series with a 24V DC power supply, ensuring that the current does not exceed the specified mA.
- Monitor the LCD display for any status or error messages during operation.
- If using the touch screen feature, handle it with care to avoid damage. Refer to the user manual for proper operation guidelines.
- For any technical issues or inquiries regarding the AVENAR panel series, refer to the contact information provided by Bosch Sicherheitssysteme GmbH.
Safety Instructions
Warning!
Live components and stripped cable! Risk of injury from electric shock. The
system must be current-free during connection work.
Warning!
The power button must be used to switch off the device before removing the
power supply. It may not be disconnected from power supply while system is
running. The device may be damaged if this procedure is violated. Not
following this procedure may result in loss of warranty. Refer to user guide
for further information.
Notice!
Installation must only be carried out by authorized specialist personnel
Notice!
Bosch Sicherheitssysteme GmbH uses Open Source Software. For more information
see: http://www.boschsecurity.com/oss Information about the Open Source
Software used in this product can be found on
Notice!
Use the Panel Controller only with the PRS-0002-C Panel Rail Short. Use solely
the 5-wire cable of the Panel Controller for connection to the PRS-0002-C
Panel Rail Short
Notice!
Do not remove the security labels. This will void the warranty.
Notice!
Do not use tools with sharp edges (e.g. screw drivers or pens) to operate the
device or its touchscreen.
Notice!
The device may not be exposed to direct sunlight
Notice!
Touchscreen recalibration is required to be performed at least once a year.
Otherwise operating the device may be difficult or even not possible without
prior re-calibration. For further information, see the necessary procedure in
the user guide.
Functional Description
The panel controller controls every component connected to the panel and features the following functional elements (see 01,page 4):
Pos. | Designation | Function |
---|---|---|
A | Interfaces | CAN1, CAN2, IN1/2, Rail |
B | Touchscreen | Operating the networked system through virtual buttons and |
variable display windows
C| 6 fixed buttons| Standard entries
D| Power button| Shutdown and restart of the device
E| Memory card slot| Memory card reader for maintenance services
F| Network label| Label assigning the different network connectors
G| DIP switch label| DIP switch label with areas to write down the PNA
(Physical Node Address) and the IP address
Pos.| Designation| Function
---|---|---
H| Interface label| Label including connector assignment
I| 6-pin DIP switch| DIP switch settings for CAN bus networking & panel
redundancy
J| Product label| Important product data
K| 18 LEDs| Indicating the operating status
Installation
The panel controllers may be mounted into the following housings:
CPH 0006 A, MPH 0010 A, HCP 0006 A and HBC 0010 A.
For the installation, follow these instructions
-
Make sure that the PRS-0002-C Panel Rail Short is mounted before you start installing the Panel Controller.
-
Start assembling the hinge and the mounting bracket (see 02, page 5).
-
Connect the ground wire to the screw on the housing (see 04, page 7).
-
Plug the cable into the slot labeled IN of the PRS-0002-C Panel Rail Short (see 05, page 8).
Note : Do not plug the cable into the slot labeled OUT nor into the slots of the PRD 0004 A Panel Rail Long (exception: cable to redundant panel). -
Plug the EOL resistor for the databus into the slot labeled OUT of the last PRD 0004 A Panel Rail Long in use (see 06, page 9).
-
Attach the supplied label to the side of the housing (see 06, page 9).
-
Set the DIP switch according to the designated application.
You can write down the Physical Node Address (PNA) and the IP address on the label (see 07, page 10).
Wiring
Notice!
Do not modify the fire alarm control panel to extend USB and IN1/2 cables
outside the housing. Only use cables for USB and IN1/2 with a maximum length
of 3 m.
Notice!
You will find detailed information about the CAN and Ethernet networking of
the panels in the Networking Guide available for download at
https://www.boschsecurity.com .
Notice!
The manufacturer’s specifications for the minimum bending radius of the
network and fiber optic cables used must be observed during installation.
The panel controller features
- 2 CAN interfaces (CAN1/CAN2) for networking
- 1 Rail connector
- 4 Ethernet interfaces (1 / 2 / 3 / 4) for networking, prescribed usage:
- 1 and 2 (blue): Panel network
- 3 (green): Building management system, hierarchy panel, voice alarm system
- 4 (red): Remote Services
- 2 signal inputs (IN1/IN2)
- USB function interface for configuration via FSP-5000-RPS
- 1 Memory card interface
Fixing the Ethernet cables to the panel controller
The housing in which the panel controller is installed must be open. Lift and
swing out the panel controller if already mounted.
- Look at the back of the device.
- Use cable ties to attach the Ethernet cables to the fixing points as shown in the figure (see 09, page 12).
- Check the routing of the cables. They must not be crushed or trapped.
The cables are fixed to the panel controller.
Fixing the Ethernet cables to the housing
The housing in which the panel controller is installed must be open. Lift and
swing out the panel controller if already mounted.
- Look at the top area of the housing.
- Use cable ties to attach the Ethernet cables to the fixing points as shown in the figure (see 10, page 13).
- Check the routing of the cables. They must not be crushed or trapped.
Technical Specifications
Electrical
Current consumption (mA at 24 VDC)| – standby: 190
– alarm: 420
---|---
Maximum power loss (W)| 11
Max. CAN cable length in networks| Lmax = 1000 m, depending on configuration,
cable type and topology
---|---
Mechanical
Housing material | Polycarbonate (PC) |
---|---|
Color | RAL7016, Anthracite |
Weight (kg) | 2.4 |
Dimensions H x W x D (mm) | 190 x 404 x 60 |
Flammability rating | UL94-V0 |
LCD display (pixels) | 7″ color WVGA 800 x 480 |
Operating and display elements | – 6 keys |
– 18 LEDs
Interfaces| CAN1, CAN2, ETH1, ETH2, ETH3, ETH4, USB , Rail
Signal inputs| IN1/IN2
Environmental
Protection class as per EN 60529 | IP 30 |
---|---|
Permissible operating temperature (°C) | -5 to +50 |
Relative humidity at 25°C (%) | ≤95 (non-condensing) |
Storage
Permissible storage temperature (°C) -20 to +70
Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 5 85630 Grasbrunn Germany www.boschsecurity.com
© Bosch Sicherheitssysteme GmbH, 2022 Building solutions for a better life. 202212081427