Carrier 25SPA5 Single Stage Heat Pump Instruction Manual
- June 12, 2024
- Carrier
Table of Contents
Carrier 25SPA5 Single Stage Heat Pump
Product Information
The product is an installation unit intended for use in a variety of applications. It is designed to be installed in locations that are 10,000 feet (3000 meters) above sea level or lower. The unit should be installed following all safety considerations and local building codes. It is important to read the entire instruction manual before starting the installation.
The product is equipped with safety features to protect against electrical shock and explosion hazards. Before installing, modifying, or servicing the system, the main electrical disconnect switch must be in the OFF position. It is also important to avoid using air or gases containing oxygen for leak testing or operating refrigerant compressors, as pressurized mixtures of air or gases containing oxygen can lead to an explosion.
Product Usage Instructions
- Locate the unit away from windows, patios, decks, or any other area where the operation sound may disturb customers.
- Ensure that the vapor and liquid tube diameters are appropriate for the unit’s capacity.
- Run refrigerant tubes with no bends, and ensure that the centerline bend radius is less than 2.5 times the external pipe diameter.
- Leave some slack between the structure and the unit to absorb vibration.
- When passing refrigerant tubes through the wall, seal the opening with RTV or other pliable silicon-based caulk.
- Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
- Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap that comes in direct contact with the tubing.
- Ensure that tubing insulation is pliable and completely surrounds the vapor tube.
- Use hanger straps that are 1 in. (25 mm) wide and conform to the shape of the tubing insulation when necessary.
- Isolate hanger straps from insulation by using metal sleeves bent to conform to the shape of the insulation.
- Provision shall be made for expansion and contraction of long runs of piping.
- Piping and fittings shall be protected as much as possible against adverse environmental effects, such as the accumulation of dirt and debris.
- Piping should be installed to reduce the likelihood of hydraulic shock damaging the system.
- Use certified piping and components to protect against corrosion.
- Flexible pipe elements should be protected against mechanical damage and excessive stress by torsion or other forces. They should be checked for mechanical damage annually.
- Piping material, routing, and installation should include protection from physical damage in operation and service, and comply with the national and local codes and standards of the installation site.
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause explosion, fire, electrical shock, or other conditions which may
cause death, personal injury, or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory–authorized kits
or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work
gloves. Use quenching cloth for brazing operations. Have fire extinguisher
available. Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult local
building codes and current editions of the National Electrical Code (NEC) NFPA
70. In Canada, refer to current editions of the Canadian electrical code CSA
22.1.
Recognize safety information. This is the safety–alert symbol . When you see
this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand these signal words; DANGER, WARNING, and CAUTION. These words are
used with the safety–alert symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION is used to
identify unsafe practices which may result in minor personal injury or product
and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect
switch must be in the OFF position. There may be more than 1 disconnect
switch. Lock out and tag switch with a suitable warning label.
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen for leak testing or operating
refrigerant compressors. Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
INSTALLATION RECOMMENDATIONS
In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.
- This unit is intended to be installed in a location that is 10,000 feet (3000 meters) above sea level or lower.
- Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
- Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
- Run refrigerant tubes with no bends with centerline bend radius less than 2.5 times the external pipe diameter.
- Leave some slack between structure and unit to absorb vibration.
- When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 1.)
- Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
- Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing (see Fig. 1).
- Ensure that tubing insulation is pliable and completely surrounds vapor tube.
- When necessary, use hanger straps which are 1 in. (25 mm) wide and conform to shape of tubing insulation. (See Fig. 1.)
- Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
- Provision shall be made for expansion and contraction of long runs of piping.
- Piping and fittings shall be protected as far as possible against adverse environmental effects. For example, the accumulation of dirt and debris.
- Piping should be installed to reduce the likelihood of hydraulic shock damaging the system.
- Certified piping and components must be used in order to protect against corrosion.
- Flexible pipe elements shall be protected against mechanical damage, excessive stress by torsion, or other forces. They should be checked for mechanical damage annually.
- Piping material, routing, and installation shall be include protection from physical damage in operation and service, and be in compliance with the national and local codes and standards of the installation site.
- When setting up refrigerant piping, precautions shall be taken to avoid excessive vibration or pulsation
When outdoor unit is connected to factory–approved indoor unit, outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field–supplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover and/or in the Check Charge section of this instruction.
IMPORTANT:
- Maximum liquid–line size is 3/8–in. OD for all residential applications including long line.
- Always install the factory–supplied liquid–line filter drier. Obtain replacement filter driers from your distributor or branch.
INSTALLATION
IMPORTANT: All split system and packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate
protective clothing and gloves when handling parts.
Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged
or incomplete. Locate unit rating plate on unit corner panel. It contains
information needed to properly install unit. Check rating plate to be sure
unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down
bolts should be used and fastened through knockouts provided in unit base pan.
Refer to unit mounting pattern in Fig. 2 to determine base pan size and
knockout hole location.
For hurricane tie downs, contact distributor for details and PE Certification
(Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place unit above a
load–bearing wall and isolate unit and tubing set from structure. Arrange
supporting members to adequately support unit and minimize transmission of
vibration to building. Consult local codes governing rooftop applications.
Elevate Unit
Roof mounted units exposed to winds above 5 mph may require wind baffles.
Consult the Service Manual – Residential Split System Air Conditioners and
Heat Pumps for wind baffle construction.
Unit must be level to within ±2° (±3/8 in/ft,±9.5 mm/m) per compressor
manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring,
refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service
end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6–in.
(152.4 mm) clearance on 1 side of unit and 12–in. (304.8 mm) on all remaining
sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between
units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m). Position so
water, snow, or ice from roof or eaves cannot fall directly on unit.
18” (457.2 mm) clearance option described above is approved for outdoor units
with wire grille coil guard only. Units with louver panels require 24” (609.6
mm) between units.
On rooftop applications, locate unit at least 6 in. above roof surface.
UNIT BASE PAN
Dimension in. (mm)
| TIEDOWN KNOCKOUT LOCATIONS in. (mm)
---|---
A| B| C
31–1/2 X 31–1/2 (800 X 800)| 9–1/8 (231.8)| 6–9/16 (166.7)| 24–11/16 (627.1)
35 X 35
(889 X 889)
| 9–1/8 (231.8)| 6–9/16 (166.7)| 28–7/16 (722.3)
Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely
attached. There is a liquid header with a distributor and feeder tube going
into outdoor coil. At the end of the one of the feeder tubes, there is a 3/8
in. O.D. stub tube approximately 2 in. (50.8 mm) long (see Fig. 3). The
defrost thermostat should be located on stub tube. Note that there is only one
stub tube used with liquid header, and on most units it is the bottom circuit.
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Do not allow water and/or ice to build up in base pan.
Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.
Make Piping Connections
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final
unit disposal.
Use all service ports and open all flow–control devices, including solenoid
valves.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
If ANY refrigerant tubing is buried, provide a 6–in (152.4 mm) vertical rise
at service valve. Refrigerant tubing lengths up to 36–in (914.4 mm). may be
buried without further special consideration. Do not bury lines longer than 36
in (914.4 mm).
Outdoor units may be connected to indoor section using accessory tubing
package or field–supplied refrigerant grade tubing of correct size and
condition. For tubing requirements beyond 80 ft, substantial capacity and
performance losses can occur. Following the recommendations in the Residential
Piping and Long Line Guideline will reduce these losses. Refer to Table 3 for
accessory requirements. Refer to Table 1 for field tubing diameters.
There are no buried–line applications greater than 36 in. (914.4 mm)
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be
evacuated to 500 microns to eliminate contamination and moisture in the
system.
Outdoor Unit Connected To Factory Approved Indoor Unit
Outdoor unit contains approximate system refrigerant charge for operation with
approved AHRI rated indoor unit when connected by 15 ft (4.57 m) of
field–supplied or factory–accessory tubing, and factory supplied filter drier.
Some indoor units require additional subcooling to achieve optimal heating
performance. Using Table 5 – Additional Subcooling Required, check refrigerant
charge for maximum efficiency
Service Valves
Service valves are closed and plugged from the factory. Outdoor units are
shipped with a refrigerant charge sealed in the unit. Leave the service valves
closed until all other refrigerant system work is complete or the charge will
be lost. Leave the plugs in place until line set tubing is ready to be
inserted.
Heat pumps require a piston metering device in the liquid service valve for
proper heating operation. Piston is shipped in the piston body of the liquid
service valve, temporarily held in place with a plastic cap. Do not remove the
plastic cap until line set tubing is ready to be installed.
Refer to Fig. 4 and follow these steps for piston installation:
- Remove plastic cap holding piston in piston body of liquid service valve.
- Check that piston size (stamped on side of piston) matches with number listed on unit rating plate. Return piston to piston body of liquid service valve (either direction).
- Find plastic bag taped to unit containing copper adapter tube, brass nut, and plastic washer.
- Install plastic washer in the seat inside piston body.
- Fit brass nut onto adapter tube and install tube onto liquid service valve. Tighten nut finger tight, then wrench additional ½ turn only [15-ft lbs (20.3 N-m)]. Over tightening may damage the plastic washer and service valve’s piston body.
Brazing Connections
Clean line set tube ends with emery cloth or steel brush. Remove any grit or
debris.
Connect vapor tube to fitting on outdoor unit vapor service valves (see Table
1). Connect liquid tubing to adapter tube on liquid service valve. Use
refrigerant grade tubing.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Service valves must be wrapped in a heat–sinking material such as a wet cloth
while brazing.
Apply heat absorbing paste or heat sink product between service valve and
joint. Wrap service valves with a heat sinking material such as a wet cloth.
After wrapping service valve with a wet cloth, tubing set can be brazed to
service valve using either silver bearing or non–silver bearing brazing
material. Do not use soft solder (materials which melt below 800°F/427°C).
Braze joints using a Sil-Fos or Phos-copper alloy. Consult local code
requirements.
Some outdoor units contain a mechanical fitting at the liquid distributor.
This connection is not field serviceable and should not be disturbed. For
Liquid Service Valve – Braze lineset to adapter tube BEFORE bolting adapter to
valve. This helps prevent overheating and damage to plastic washer or o-ring.
For Vapor Service Valve – remove valve core from schrader port on Service
Valve BEFORE brazing. This helps prevent overheating and damage to valve seals
(refer to Fig. 5). Replace valve core when brazing is completed.
FIRE HAZARD
Failure to following this warning could result in personal injury, death
and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes and contacts
brazing torch. Make sure the refrigerant charge is properly removed from both
the high and low sides of the system before brazing any component or lines.
CAUTION
BURN HAZARD
Failure to follow this caution may result in personal injury Components will
be HOT after brazing. Wear appropriate personal protective equipment and allow
to cool before handling parts and equipment.
Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT SIZE
| LIQUID| **RATED VAPOR *
---|---|---
Connection Diameter| Tube Diameter| Connection Diameter|
Tube Diameter**
18, 24| 3/8| 3/8| 5/8| 5/8
30, 36| 3/8| 3/8| 3/4| 3/4
42, 48| 3/8| 3/8| 7/8| 7/8
60| 3/8| 3/8| 7/8| 1–1/8
*. Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.
Notes:
- Do not apply capillary tube indoor coils to these units.
- For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.09 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length, refer to the Residential Piping and Long Line Guideline – Air Conditioners and Heat Pumps using Puron refrigerant.
Mechanical Line Set Connections
If using mechanical or crimp-type line set connections, follow crimp tool manufacturer’s instructions.
NOTE: Should the use of mechanical fittings cause failure of the fittings or failure of the equipment, such would not be covered under the standard warranty.
Installing with Indoor Piston
Heat pumps may only be installed with piston metered indoor units as
replacement components in a piston system. When installing a non-rated heat
pump with a piston indoor the correct piston must be installed, which should
be listed in the indoor installation instructions or product data. Replacement
pistons can be ordered from Replacement Components.
Install Liquid Line Filter Drier Indoor
Refer to Fig. 6 and install filter drier as follows:
- Braze 5 in. (127 mm) liquid tube to the indoor coil.
- Wrap filter drier with damp cloth.
- Braze filter drier to 5 in. (127 mm) long liquid tube from step 1.
- Connect and braze liquid refrigerant tube to the filter drier.
IMPORTANT: Installation of the filter drier in liquid line is required.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
- Installation of filter drier in liquid line is required.
- Filter drier must be wrapped in a heat-sinking material such as a wet cloth while brazing.
Evacuate Refrigerant Tubing and Indoor Coil
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of
500 microns and a vacuum gage capable of accurately measuring this vacuum
depth. The deep vacuum method is the most positive way of assuring a system is
free of air and liquid water. A tight dry system will hold a vacuum of 1000
microns after approximately 7 minutes. (See Fig. 7.)
Mandatory Requirements
Pressure Proof Check
- Preform a pressure check of the unit with a nitrogen charge of about 200psi.
- the Nitrogen holding charge must NOT decrease in pressure for 1 hour, as indicated by the test gauge. The measuring test gauge resolution not exceeding 5% of the holding charge.
Leak Check
This leak check requires a vacuum pump capable of pulling a vacuum of at
least 500 microns and a vacuum gage capable of accurately measuring this
vacuum depth.
WARNING
FIRE HAZARD
Failure to following this warning could result in personal injury, death
and/or property damage.
DO NOT USE FLAMES OR IGNITION SOURCES TO LEAK CHECK.
- Vacuum unit to 500 microns.
- When isolating the unit from the pump, the pressure shall not rise above 1500 microns in 10 minutes.
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, makings sure wire ties on feeder tubes are secure and tight.
Make Electrical Connections
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not supply power to unit with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE:
- Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.
- Use copper wire only between disconnect switch and unit.
- Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440–14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from
disconnect through power wiring hole provided and into unit control box.
Connect Ground and Power Wires
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize
personal injury if an electrical fault should occur. The ground may consist of
electrical wire or metal conduit when installed in accordance with existing
electrical codes.
Connect ground wire to ground connection in control box for safety.
Connect power wiring to contactor as shown in Fig. 8.
Table 2 – 3-Phase Monitor LED Indicators
LED | STATUS |
---|---|
OFF | No call for compressor operation |
FLASHING | Reversed phase |
ON | Normal |
Connect Control Wiring
Route 24v control wires through control wiring grommet and connect leads to
control wiring. See Thermostat Installation Instructions for wiring specific
unit combinations. (See Fig. 10.)
Use No. 18 AWG color–coded, insulated (35°C minimum) wire. If thermostat is
located more than 100 ft (30.5 m) from unit, as measured along the control
voltage wires, use No. 16 AWG color–coded wire to avoid excessive voltage
drop.
All wiring must be NEC Class 2 and must be separated from incoming power
leads.
Use furnace transformer, fan coil transformer, or accessory transformer for
control power, 24v/40va minimum.
Use of available 24v accessories may exceed the minimum 40va power
requirement. Determine total transformer loading and increase the transformer
capacity or split the load with an accessory transformer as required.
(See tstat Installation Instructions for specific unit combinations)
Final Wiring Check
IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24
hr before starting unit. To furnish power to heater only, set thermostat to
OFF and close electrical disconnect to outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft
(24.38 m), or when outdoor unit is 20 ft (6.10 m) below indoor unit.
Refer to the Residential Piping and Long Line Guideline.
Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when
installing.
Start–Up
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant
and observe the following:
- Front seating service valves are equipped with Schrader valves.
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Federal regulations require that you do not vent refrigerant to the
atmosphere. Recover during system repair or final unit disposal.
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury, equipment damage
or improper operation.
- Do not overcharge system with refrigerant.
- Do not operate unit in a vacuum or at negative pressure.
- Do not disable low pressure switch in scroll compressor applications.
- Compressor dome temperatures may be hot.
Follow these steps to properly start up system:
- After system is evacuated, fully open liquid and vapor service valves.
- Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow (back seated). Replace caps finger–tight and tighten with wrench an additional 1/12 turn.
- Close electrical disconnects to energize system.
- Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature for cooling mode operation.
- Set room thermostat to HEAT or COOL and fan control to ON or AUTO mode, as desired. Operate unit for 15 minutes. Check system refrigerant charge.
Sequence of Operation
Turn on power to indoor and outdoor units. Transformer is energized.
Cooling
- On a call for cooling, thermostat makes circuits R–O and R–Y, and R–G.
- Circuit R–O energizes reversing valve, switching it to cooling position.
- Circuit R–Y energizes contactor, starting outdoor fan motor and compressor circuit. R–G energizes indoor unit blower relay, starting indoor blower motor on high speed.
- When thermostat is satisfied, its contacts open, de–energizing contactor and blower relay. Compressor and motors should stop.
- If indoor unit is equipped with a time–delay relay circuit, the indoor blower will run an additional 90 seconds to increase system efficiency.
Heating
- On a call for heating, thermostat makes circuits R–Y and R–G. Circuit
- R–Y energizes contactor, starting outdoor fan motor and compressor.
- Circuit R–G energizes indoor blower relay, starting blower motor on high speed.
- Should temperature continue to fall, R–W2 is made through second–stage room thermostat. Circuit R–W2 energizes a relay, bringing on first bank of supplemental electric heat and providing electrical potential to second heater relay (if used). If outdoor temperature falls below setting of outdoor thermostat (field installed option), contacts close to complete circuit and bring on second bank of supplemental electric heat.
- When thermostat is satisfied, its contacts open, de–energizing contactor and relay. All heaters and motors should stop.
Quiet Shift-2
Quiet Shift-2 is a field selectable defrost mode (factory set to OFF),which
will reduce the occasional noise that could be heard at the start of defrost
cycle and restarting of heating cycle. It is selected by placing DIP switch 3
on defrost board in the ON position.
When Quiet Shift-2 switch is placed in ON position, and defrost is initiated, the following sequence of operation will occur:
-
The compressor will be de–energized for approximately 1 minute, then the reversing valve will be energized. A few seconds later, the compressor will be re-energized and the normal defrost cycle starts.
Once defrost termination conditions have been met, the following sequence will occur: -
The compressor will be de-energized for approximately 1 minute, then the reversing valve will be de-energized. A few seconds later,the compressor will be re-energized and the normal heating cycle starts.
Defrost
The defrost control is a time/temperature control which includes a field
selectable time period between defrost cycles (30, 60, 90, or 120). The time
period is selected using DIP switches located on the board. The setting is
initial period only then varies with defrost length.
The defrost thermostat senses coil temperature throughout the heating cycle.
When the coil temperature reaches the defrost thermostat setting of
approximately 32°F (0°C), it will close, which energizes the DFT terminal and
begins the defrost timing sequence. The timer runs only when the defrost
thermostat is closed and the contactor is energized.
Defrost mode is identical to cooling mode except that outdoor fan motor stops and second-stage heat is turned on to continue warming conditioned spaces.
Defrost Speedup
Quiet Shift-2 Models
To initiate a forced defrost, speedup pins (J1) must be shorted with a flat
head screwdriver for 5 seconds and RELEASED. If the defrost thermostat is
open, a short defrost cycle will be observed (actual length depends on Quiet
Shift-2 switch position). When Quiet Shift-2 is off, only a short 30 second
defrost cycle is observed. With Quiet Shift-2 ON, the speedup sequence is
approximately 3 minutes; 1 minute compressor off period followed by 30 seconds
of defrost with compressor operation.
When returning to heating mode, the compressor will turn off for an additional
minute.
If the defrost thermostat is closed, a complete defrost cycle is initiated. If
the Quiet Shift-2 switch is turned on, the compressor will be turned off for
two 1-minute intervals as explained previously.
If Quiet Shift 2 is enabled, the variable defrost intervals will be disabled
to provide options where using a specific setting is desired. In this case the
30, 60, 90, or 120 setting will not change unless the dipswitch is
Check Charge
Factory charge amount and desired subcooling are shown on unit rating plate.
Additional subcooling may be required to achieve optimal heating performance
based on the installed indoor unit. (see Table 5).
Charging method is shown on information plate inside unit. For TXV,use
subcooling method. For piston, use superheat method. To properly check or
adjust charge, conditions must be favorable for subcooling or superheat
charging. Favorable conditions exist when the outdoor temperature is between
70°F and 100°F (21.11°C and 37.78°C), and the indoor temperature is between
70°F and 80°F (21.11°C and 26.67°C).
Follow the procedure below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge by adding
or removing 0.6 oz/ft (.018 kg/m) of 3/8 liquid line above or below 15ft (4.57
m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow system to
operate in cooling mode at least 15 minutes. If conditions are favorable,
check system charge by super heat method for fixed metering device and
subcooling method for TXV. If any adjustment is necessary,adjust charge slowly
and allow system to operate for 15 minutes to stabilize before declaring a
properly charged system. Refer to Table 5 for additional subcooling required.
If the indoor temperature is above 80°F (26.67°C), and the outdoor temperature
is in the favorable range, adjust system charge by weight based on line length
and allow the indoor temperature to drop to 80°F (26.67°C) before attempting
to check system charge by subcooling method as described above.
If the indoor temperature is below 70°F (21.11°C), or the outdoor temperature
is not in the favorable range, adjust charge for line set length above or
below 15ft (4.57 m) only. Charge level should then be appropriate for the
system to achieve rated capacity. The charge level could then be checked at
another time when the both indoor and outdoor temperatures are in a more
favorable range.
If line length is beyond 80 ft (24.38 m) or greater than 20 ft (6.10 m)
vertical separation, See Residential Piping and Long Line Guideline for
special charging requirements.
Units with Cooling Mode TXV
Units installed with cooling mode TXV require charging by the subcooling
method.
- Operate unit a minimum of 15 minutes before checking charge.
- Measure liquid service valve pressure by attaching an accurate gage to service port.
- Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil.
- Refer to unit rating plate for required subcooling temperature.
- Refer to Table 6. Find the point where required subcooling temperature intersects measured liquid service valve pressure.
- To obtain required subcooling temperature at a specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of ?3°F.
Units with Indoor Pistons
Units installed with indoor pistons require charging by the superheat method.
The following procedure is valid when indoor airflow is within 20 percent of its rated CFM.
-
Operate unit a minimum of 15 minutes before checking charge.
-
Measure suction pressure by attaching an accurate gage to suction valve service port.
-
Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service valve.
-
Measure outdoor air dry–bulb temperature with thermometer.
-
Measure indoor air (entering indoor coil) wet–bulb temperature with a sling psychrometer.
-
Refer to Table 7. Find outdoor temperature and evaporator entering air wet–bulb temperature. At this intersection, note superheat.
Where a dash (––) appears on the table, do not attempt to charge system under these conditions or refrigerant slugging may occur.
Charge must be weighted in, adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15 ft (4.57 m) respectively. -
Refer to Table 8. Find superheat temperature located in item 6 and suction pressure. At this intersection, note suction line temperature.
-
If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
-
If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature is reached.
-
When adding refrigerant, charge in liquid form into suction service port using a flow–restricting device.
-
If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated on chart.
-
Optimum performance will be achieved when the operating charge produces 5° to 6°F suction superheat at suction service valve with 82°F outdoor ambient and 80°F (26.7°C) dry bulb 67°F (19.4°C) wet bulb indoor temperature (DOE “B” test conditions) at rated airflow.
Heating Check Chart Procedure
To check system operation during heating cycle, refer to the Heating Check
Chart on outdoor unit. This chart indicates whether a correct relationship
exists between system operating pressure and air temperature entering indoor
and outdoor units. If pressure and temperature do not match on chart, system
refrigerant charge may not be correct. Do not use chart to adjust refrigerant
charge.
Table 3 – Accessory Usage
Accessory
| REQUIRED FOR LOW–AMBIENT COOLING APPLICATIONS (Below 55°F / 12.8°C)|
**REQUIRED FOR LONG LINE APPLICATIONS ***
| REQUIRED FOR SEA COAST
APPLICATIONS (Within 2
miles / 3.22 km)
---|---|---|---
Accumulator| Standard| Standard| Standard
Ball Bearing Fan Motor| Yes†| No| No
Compressor Start Assist Capacitor and Relay| Yes| Yes| No
Crankcase Heater| Yes| Yes| No
Evaporator Freeze Thermostat| Yes| No| No
Hard Shutoff TXV| Yes| Yes| No
Isolation Relay| Yes| No| No
Liquid Line Solenoid Valve| No| See Long–Line Application Guideline| No
Motor Master® Control or Low Ambient Switch| Yes‡| No| No
Support Feet| Recommended| No| Recommended
- For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Long Line Guideline.
- Additional requirement for Low–Ambient Controller (full modulation feature) MotorMaster® Control.
- In units equipped with ECM OD motor, motor needs to be replaced per unit accessory guide to work properly. This motor kit comes with a new defrost board that also needs to be installed. Unit will not meet AHRI rated efficiency once motor and control board are replaced to use this accessory.
Table 4 – Additional Subcooling Required
Subcooling Delta from Rating Plate Value
Subcooling Delta from Rating Plate Value
Outdoor Unit Tonnage
Indoor unit | Additional Subcooling Required
18| 24| 30| 36| 42
CAP1917AL*| +5| CAP*2517AL| +5| FM(C,U)4X30AL*| +5| CAP3721AL*| +5|
CAP*4321AL| +3
CAP2517AL*| +5| FM(C,U)4X24AL*| +5| FM(C,U)4Z30*AL| +5| CAP4321AL*|
+5| CAP4821AL| +3
CSPH2412AL| +3| FJ4DNXB30L| +3| CAP3721AL*| +5| | | CAP4824AL| +3
FJ4DNXB24L| +3| FM(C,U)4X30AL*| +5| FM(C,U)4X36AL*| +5| | | |
FB4CNP025L| +3| FM(C,U)4Z30*AL| +5| FM(C,U)4Z36AL*| +5| | | |
FX4DNF019L| +3| | | | | | | |
FX4DNF025L| +3| | | | | | | |
FM(C,U)4X18AL*| +5| | | | | | | |
FM(C,U)4X24*AL| +5| | | | | | | |
FM(C,U)4Z18AL*| +5| | | | | | | |
FM(C,U)4Z24*AL| +5| | | | | | | |
Table 5 – Required Liquid Line Temperatures °F
LIQUID PRESSURE AT SERVICE VALVE (PSIG)| REQUIRED SUBCOOLING
TEMPERATURE (°F)
---|---
8| 10| 12| 14| 16| 18
251| 76| 74| 72| 70| 68| 66
259| 78| 76| 74| 72| 70| 68
266| 80| 78| 76| 74| 72| 70
274| 82| 80| 78| 76| 74| 72
283| 84| 82| 80| 78| 76| 74
291| 86| 84| 82| 80| 78| 76
299| 88| 86| 84| 82| 80| 78
308| 90| 88| 86| 84| 82| 80
317| 92| 90| 88| 86| 84| 82
326| 94| 92| 90| 88| 86| 84
335| 96| 94| 92| 90| 88| 86
345| 98| 96| 94| 92| 90| 88
354| 100| 98| 96| 94| 92| 90
364| 102| 100| 98| 96| 94| 92
374| 104| 102| 100| 98| 96| 94
384| 106| 104| 102| 100| 98| 96
395| 108| 106| 104| 102| 100| 98
406| 110| 108| 106| 104| 102| 100
416| 112| 110| 108| 106| 104| 102
427| 114| 112| 110| 108| 106| 104
439| 116| 114| 112| 110| 108| 106
450| 118| 116| 114| 112| 110| 108
462| 120| 118| 116| 114| 112| 110
474| 122| 120| 118| 116| 114| 112
486| 124| 122| 120| 118| 116| 114
499| 126| 124| 122| 120| 118| 116
511| 128| 126| 124| 122| 120| 118
Table 6 – Superheat Charging (Heat Pump Only)
OUTDOOR TEMP (°F) | EVAPORATOR ENTERING AIR TEMPERATURE (°F WB) |
---|---|
50 | 52 |
67 | 68 |
55 | 11 |
60 | 6 |
65 | – |
70 | – |
75 | – |
82 | – |
85 | – |
90 | – |
95 | – |
100 | – |
105 | – |
110 | – |
115 | – |
Optimum performance point, 82°F outdoor ambient and (80°F dry bulb),( 67°F wet bulb) indoor conditions. (DOE B Test Conditions) Where a dash (––) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in. Note: Superheat °F is at low–side service port, Allow a tolerance of ± 3°F
Note: Indoor dry bulb between 70°F and 80°F
Table 7 – Required Suction–Line Temperature
SUPERHEAT TEMP (°F) | SUCTION PRESSURE AT SERVICE PORT (PSIG) |
---|---|
107.8 | 112.2 |
138.8 | 140.8 |
0 | 35 |
2 | 37 |
4 | 39 |
6 | 41 |
8 | 43 |
10 | 45 |
12 | 47 |
14 | 49 |
16 | 51 |
18 | 53 |
20 | 55 |
22 | 57 |
24 | 59 |
26 | 61 |
28 | 63 |
30 | 65 |
Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
- Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub–through or wire pinching.
- Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers.
- Tighten service valve stem caps to 1/12–turn past finger tight.
- Leave Owner’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
- Fill out Dealer Installation Checklist and place in customer file.
Care and Maintenance
For continuing high performance and to minimize possible equipment failure,
periodic maintenance must be performed on this equipment. Frequency of
maintenance may vary depending upon geographic areas, such as coastal
applications. See Users Manual for information.
Training
My Learning Center is your central location for professional residential HVAC
training resources that help strengthen careers and businesses. We believe in
providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at
www.mlctraining.com. Please contact us a
mylearning@carrier.com with questions.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>