LEVITON EZ-MAX H Lighting Control Panel User Guide

June 12, 2024
Leviton

LEVITON EZ-MAX H Lighting Control Panel

PRECAUTIONS

  • READ AND FOLLOW ALL SAFETY INSTRUCTIONS
  • CAUTION – RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn off the power at the circuit breaker before installing or servicing the unit. Never wire-energized electrical components.
  • NOTICE: For installation by a licensed electrician in accordance with national and/or local electrical codes and the following instructions:
  • CAUTION: USE COPPER CONDUCTOR ONLY
  • Be sure to read and understand all instructions before installing or servicing unit
  • For Indoor use only. Do not use outdoors.
  • Do not mount near gas or electric heaters
  • A disconnect switch or a circuit breaker must be provided and marked as the disconnecting device
  • The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
  • Confirm that device ratings are suitable for application prior to installation.
  • No user-serviceable parts are contained inside the unit. Refer all service-related questions to the factory. All servicing shall be performed by qualified service personnel.
  • Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel
  • Use only approved materials and components (i.e. twist-on connectors, electrical box, etc.) as appropriate for installation
  • NOTICE: Do not install if the product appears to be damaged
  • If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired
  • Do not use this equipment for other than the intended use
  • Always use and follow installation instructions

Line Voltage Power Connections

Mount the panel enclosure –Mount the EZ-MAX H panel securely to the building structure in accordance with local code requirements

  • Remove the panel door prior to mounting the enclosure. All mounting holes are located such that no additional disassembly is required to complete mounting.
  • Mounting keyhole location and dimensions are included in the EZ-MAX H Panel Installation Instructions

Install individual relay cards as required –Panels are shipped empty without relays installed, relays must be field installed

  • Control power must be disconnected to the panel main board prior to installing relay cards
  • Once installation of all cards is complete, restore control power to main board
  • Read and follow the installation instructions provided with the individual relay cards when installing

Connect controlled lighting loads –Each relay card is provided with terminal blocks for connection to lighting circuits to be controlled

  • Each terminal will accommodate two (2)-#10-#14 copper solid or stranded wire of the same size and type
  • Relays connected to the same supply circuit may be jumpered on the line side
  • All line voltage connections should be made with the circuit breaker feeding the load in the locked off position

Test controlled lighting loads –Once circuits are connected to line and load sides of terminals, test each for shorts and proper grounding prior to energizing the circuit breaker feeding the load

Record controlled lighting loads in panel schedule –After completion of all testing, include in the panel schedule the name and/or location of the load controlled and the panel and circuit designation of the source line power

Panel Components

  1. EZ-MAX H Series Interface –The easy to use and understand color LCD Display with keypad has been designed based on input styles of commonly used devices such as cell phones

  2. Panel Door Lock –The EZ-MAX Panel is designed to be locked once the qualified electrician has completed all connections. All programming, system status, and manual controls are available via the user interface once the door is secured.

  3. Low Voltage Input Device Wiring Diagrams –Indicates point-to-point connection requirements for each type of device

  4. Line Voltage Input Leads –These leads are marked for various input supply voltages

  5. Control Power Disconnect–A disconnect
    plug is provided for low voltage input control power to allow for safe removal and replacement of relay cards

  6. Individual Relay Card–Relays are individually mounted for easy replacement, improved reliability and to allow for panels to include any mix of relay types

  7. Relay Manual Override Button–Allows for relays to be manually operated. Manual control of relays is also available through the User InterfaceLEVITON-EZ-MAX-H-Lighting-Control-Panel-fig-4

  8. Relay Status Light–Indicates relay operation status

  9. Relay Board Input Terminal Block–Any type of low-voltage input including Switches, Motion Sensors or Photocells may be connected to any relay input terminal block. These inputs are software assignable as to type and control. Any input can control any relay or group.

  10. Line Voltage Control Circuit Terminals–Lighting circuits are connected to these heavy duty screw terminals. Each terminal will accommodate two #14 – #10 stranded or solid copper wire of the same type and size.

  11. Auxiliary Inputs–The EZ-MAX Panel is supplied with additional low voltage inputs to accommodate a wide variety of control scenarios that require more than one input for a relay or group. Any type of low voltage input including Switches, Motion Sensors or Photocells may be connected to any input terminal block. These inputs are software assignable as to type and control. Any input can control any relay or group.

  12. Dry Contact Output Terminals–Each Output Terminal allows for the EZ-MAX H Panel to signal other systems with N.O./N.C. momentary or maintained contacts

  13. Wireway Divider-Separates Line and Low Voltage wiring

Low Voltage Input/Output Connections

Always use and follow installation instructions

  1. Connect Low Voltage Inputs–There are low voltage inputs, one each on each relay card and auxiliary inputs on the main board. Any device can be connected to any input. All inputs are software assignable to any type of device, including low voltage switches, motion sensors, or photocells. Any input can control any relay, group or output. Wiring diagrams for each type of device are indicated inside the panel door and in this document. Each panel provides enough device power for one device per relay, including devices that may be wired in parallel to a single input.

  2. Inputs should be connected based on zone control. Where relays are controlled by single devices, inputs should be connected to the input terminal on that specific relay. Even though any input can be mapped to any relay or group, it is easier for programming and future modifications if inputs and relays are aligned.

  3. Switches or sensors that control the same zone should be connected in parallel to
    a single input. Low voltage switches and motion sensors can be connected in parallel for like devices when more than one device controls the same zone.

  4. Record Inputs in Panel Schedule After completion of all connections, include in the panel schedule the name, type and/or location of the input device and the relay or group controlled.

Low Voltage Device Input Wiring Diagrams

LEVITON-EZ-MAX-H-Lighting-Control-Panel-fig-8

User Interface Functions

  • Color LCD Display-Allows for most programming to be completed in a single screen. Right side scroll bars appear when more choices are available than are currently visible.
  • Function Keys– These keys provide programming choices in various screens. Key labels appear on-screen when keys are available.
  • Alpha-Numeric Keypad-This keypad is used to populate names and numeric values while programming. Tap/Scroll operation is similar to that used for cell phones.
  • Escape Key-This key takes the user to the previous screen. Warning prompts when changes have been made but not saved.
  • Help Key-This key will bring u p help screens in specific locations driven by the field that is highlighted.
  • Navigation Keys-Allows user to navigate Up/Down/Right/Left/Toggle through editable fields to select program choices
  • Enter Key-Use this key to make selections

Programming Guide

SYSTEM SETTINGS

  • From the Main Menu SELECT System Settings, and press ENTER

SET DATE/TIME

  • Use the alphanumeric keypad to enter the date
  • Use the alphanumeric keypad to enter the time
  • Use the push-button to Choose AM or PM
  • Scroll down to [SAVE] and press ENTER to finish

DATE/TIME PREFERENCES

  • SELECT Set Date/Time Preferences, and press ENTER.
  • Use the RIGHT and LEFT arrow keys to enable or disable Daylight Savings Time
  • Scroll down and use the RIGHT and LEFT arrow keys to choose a date format
  • Scroll down and use the RIGHT and LEFT arrow keys to choose the time format
  • Scroll down and use the RIGHT and LEFT arrow keys to choose a Time Zone
  • Scroll down to [SAVE] and press ENTER to finish

ASTRO CLOCK SETTINGS

  • SELECT Astro Clock Settings, and press ENTER
  • Press the ENTER key and use the alpha-numeric keypad to enter the first letter of a major City near your location. A list will appear that can be scrolled to find the city of your choice.
  • Press ENTER to auto-populate the longitude and latitude values
  • Alternately, if you know these values Scroll to each field and enter the data for your area
  • Scroll down to [SAVE] and press ENTER to finish

OPEN/CLOSE TIMES
This feature is useful if several schedules will be required and need to be keyed to a facility operating schedule that will change frequently. When schedules are keyed to the Open/Close Time rather than discrete times, it is only necessary to change the Open/Closed Time to affect the schedule change on the multiple schedules. Most basic programs will not
need to make use of this function.

  • Use the RIGHT and LEFT arrow keys to select the days of the week for this Open/Close Time
  • Scroll down and select “Not blocked by holidays” to ignore Holidays. Or select “Blocked by holidays” if the Open/Close Time will be superseded by Holiday dates.
  • Scroll down and use the RIGHT and LEFT arrow keys to SELECT OPEN time: format, fill in the appropriate fields
  • Scroll down and use the RIGHT and LEFT arrow keys to SELECT CLOSE time: format, fill in the appropriate fields
  • Scroll down and use the RIGHT and LEFT arrow keys to SELECT Date Range: format, fill in the appropriate fields
  • Scroll down to [SAVE] and press ENTER to finish

PANEL NAME

  • Use the alphanumeric keypad to enter a name for the panel. This is optional.

AFTER-HOURS SWEEP
After-hours sweeps are useful for turning off lights that may have been left on by occupants after the OFF schedule has occurred.

  • Use the RIGHT and LEFT arrow keys to SELECT a source for the Sweep start time
  • Use the alphanumeric keypad to set the Time or the Offset as required for the chosen source
  • Scroll down and use the alphanumeric keypad to enter the time interval to wait between sweeps
  • Scroll down and SELECT [CHANGE] to choose the Relays or Group to Sweep
  • Scroll down to [SAVE] and press ENTER to finish

BLINK ALERT
Use this feature to warn occupants of an impending OFF by blinking the lights

  • Use the alphanumeric keypad to set the Warning period; to number of minutes before the OFF that the Blink Alert will occur
  • Scroll down and use the alphanumeric keypad to enter the Override time: to the number of minutes the OFF event will be delayed when the override switch is pressed
  • Scroll down to [SAVE] and press ENTER to finish

POWER-ON SETTINGS
This feature is used to determine what state the relays and outputs will be set to after a power outage.

  • Use the buttons to select a state for All Relays+Outputs
  • Scroll down and use the buttons to select the state of individual Relays and Outputs
  • Press the [SAVE] button to finish

RELAY FUNCTION
Use this function to name and set other specific attributes for relays

  • Use the UP and DOWN arrow keys to SELECT a Relay and press ENTER
  • Use the alphanumeric keypad to name the Relay. This is optional.
  • Scroll down and use the RIGHT and LEFT arrow keys to choose a Function:
  • – the relay ignores the Blink Alert
  • – the relay follows Blink Alert
  • – the Relay does not blink but does follow the Override time
  • – the Relay responds to OFF by blinking OFF and back ON to accommodate the function requirement of the LineV series Automatic Switch
  • Scroll down to [SAVE] and press ENTER to finish

IDLE TIME-OUT SETTINGS
Use the alphanumeric keypad to set the number of minutes the user interface screen will wait before returning to the Home screen. A value of “0” disables this function.

BACKLIGHT SETTINGS

  • Use this function to change the user interface backlight function.

CLOCK ADJUSTMENT
This feature can be used to improve the accuracy of the internal clock if necessary. Enter a value to slow the clock the amount indicated.

FACTORY DEFAULTS
Use this feature to set the panel back to factory fresh program values. Use the RIGHT and LEFT arrow keys to SELECT and press ENTER

GROUPS
To get to Groups, select Escape to get back to the main menu. Groups are useful when a control function such as a Switch, Schedule, or Photocell must control multiple loads. Groups may contain Relays and/or Dimmers (requires the optional dimming card). Creating a Group load allows the loads to be controlled together and eliminates the need for separate programming.

  • From the Main Menu SELECT Groups, and press ENTER
  • SELECT a Group, and press ENTER. The solid box next to the Group number indicates that it has been programmed.
  • Edit the name field using the alpha-numeric keypad. Press ENTER to select from name list

RELAYS

  • SELECT [CHANGE] in the Relays field
  • Select the relays to be included in the Group and Press ENTER
  • Scroll down to [SAVE] and press ENTER to finish selecting relays

SCHEDULES
Each Schedule can affect a Relay or a Group. If you need to schedule a Dimmer, the Dimmer must be included in a Group.

  • From the Main Menu SELECT Schedules, and press ENTER.
  • SELECT a Schedule, and press ENTER. The solid box next to the group number indicates that it has been programmed.
  • Edit the name field using the alpha-numeric keypad.
  • SELECT [CHANGE] in the Control field
  • Select the Relay or Group to be controlled and Press ENTER
  • SELECT [CHANGE] in the [Times] field
  • Choose which days of the week that this schedule will affect
  • Scroll down and select “Not blocked by holidays” if this schedule should ignore Holidays. Or select “Blocked by holidays” if the Schedule will be superseded by Holiday dates.
  • Input the schedule times in the appropriate fields, and Press ENTER
  • Scroll down to [SAVE] and press ENTER to finish
  • Scroll down to ON priority: and select the Priority level at which the ON event will be executed
  • Scroll down to OFF priority: and select the Priority level at which the OFF event will be executed.
  • Note that both Priority level selections should be left at for most basic programs
  • See “Working with Priorities”
  • Scroll down to [SAVE] and press ENTER to finish creating the Schedule

HOLIDAYS
The Holiday feature allows for alternate schedules to be automatically run on standard or selected holiday dates. From the Main Menu select Holidays and press ENTERLEVITON-EZ-MAX-H-Lighting-Control-Panel-
fig-15

STANDARD U.S. HOLIDAYS
Use this selection to choose from a list of standard Holidays

  • SELECT Standard U.S. Holidays and press ENTER
  • Use the UP and DOWN arrow keys to select a Holiday and press ENTER to include
  • Press SAVE to finish the selection and return to the HOLIDAYS menu

HOLIDAY SCHEDULES
Use this selection to create a Holiday Schedule

  • Use the UP and DOWN arrow keys to select one of the available Holiday Schedules and press ENTER
  • Edit the name field using the alpha-numeric keypad
  • SELECT Control: [CHANGE] and press ENTER to select a Relay or Group to control
  • Use the UP and DOWN arrow keys to select a Relay or a Group and press ENTER
  • Enter an ON time and an OFF time for the Schedule. If you choose Sunrise or Sunset you can also enter an offset time to have the control action happen before Sunrise or after Sunset.
  • Scroll down and SELECT [SAVE] to finish creating the Holiday Schedule and return to the SELECT HOLIDAY SCHEDULE screen

CLEAR EXPIRED HOLIDAYS
Use this feature to clean out Holidays that have already occurred, remove blanks, etc.

  • SELECT Clear Expired Holidays and press ENTER
  • Use the RIGHT and LEFT arrow keys to toggle selection to and press ENTER

INPUTS
Inputs are uniquely configured based on the type of device that is connected to the input. These can include Switches, Photocells, or Occupancy Sensors.

  • From the Main Menu SELECT Inputs, and press ENTER
  • SELECT an Input, and press ENTER. The solid box next to the Input number indicates that it has been programmed. MI01 would be the master panel relay card 1 input. MAX1 would be the master panel auxiliary input 1.
  • Edit the name field using the alpha-numeric keypad.
  • SELECT in the Type field
  • Use the RIGHT and LEFT arrow key to toggle to the desired input type

INPUT TYPE =

  • Scroll down and select . Leave this setting for most basic normally open switch applications.
  • Use the RIGHT and LEFT arrow keys to toggle the switch types. Momentary Switches may be set to Temporary Priority. See “Working with Priorities”

INPUT TYPE =
Use this Input setting if an Occupancy Sensor is connected to the Input

INPUT TYPE =
Use this Input setting if a photocell is connected to the Input.

  • SELECT [CHANGE] in the Settings: field
  • Select <0 – 100%> in the Input range: field and use the RIGHT and LEFT arrow key to toggle to the desired range. The 0 – 100% range selection allows generic set up without using specific foot candle levels. Other choices use a specific foot candle range based on the photocell selection. Consult the documentation included with the photocell.
  • Enter values in the On and Off threshold fields indicating at what ambient light level the load is to switch ON and OFF
  • Set the OFF delay time to determine how long the panel will wait before turning off the load after the OFF threshold is reached. The OFF delay should not be left at 0 as this could cause undesirable cycling of the lighting.
  • Scroll down to [SAVE] and press ENTER to save the photocell setup and return to the Input screen Input Type = <Timed-ON/OFF>

This input type allows an ON/OFF switch to have an automatic OFF timer

  • Scroll down to the On time field
  • Enter the desired number of minutes

Input Type =
This input type allows an ON only switch to have an automatic OFF timer

  • Scroll down to the On time: field
  • Enter the desired number of minutes

After setting up one of the above Input Types continue:

  • SELECT [CHANGE] in the Control field
  • Choose the Relay or Group to be controlled and Press ENTER
  • Scroll down to [SAVE] and press ENTER to save the selection

INPUT MASKING
Masking allows ON and/or OFF actions to be disabled during selected periods of time. This feature is commonly used to prevent timed override switches from operating during normal business hours.

  • Scroll down and SELECT Masking
  • Use the RIGHT and LEFT arrow key to toggle to the desired setting
  • NOTE: Selecting will allow OFF only and selecting will allow ON only. Selecting <On + OFF> will disable the switch
  • Scroll down and SELECT Times: [CHANGE]
  • Populate the fields to enter the time period the masking will be in affect
  • Scroll down to [SAVE] and press ENTER to return to the Edit Inputs screen ON and OFF priorities should be left at for most applications. See “Working with Priorities”.

OUTPUTS
Use this selection to program the EZ-MAX H Panel’s auxiliary low voltage outputs

  • Use the UP and DOWN arrow keys to select one of the Aux outputs and press ENTER
  • Edit the name field using the alpha-numeric keypad
  • SELECT Type: and use the RIGHT and LEFT arrow keys to toggle between the Type choices
  • SELECT Control: and choose Input or Schedule
  • Scroll down and SELECT [CHANGE] to choose an Input or a Schedule to control the Output
  • Scroll down and use the RIGHT and LEFT arrow keys to select if this Output is to follow “OFF” sweeps during after hours.
  • Scroll down and SELECT [SAVE] to finish setting up the Aux Output

PRESETS
Use this selection to program the EZ-MAX H Panel’s auxiliary low-voltage outputs

  • Presets allow a series of control actions to be associated with a single Input action such as pressing a button.
  • From the Main Menu SELECT Presets and press ENTER
  • SELECT desired Preset and press ENTER.
  • Using the keypad enter a Preset Name.
  • SELECT Action #1 [Add Action] and press ENTER. Use the RIGHT and LEFT arrow keys to toggle through options which include:
    • ON – turns a Relay or Group ON when an ON event is received
    • OFF – turns a Relay or Group OFF when an ON event is received
    • PRESET – performs another preset’s actions (this only works one level deep, and passes along the ON/OFF event status, and allows up to 64 actions from a single preset)

PRESETS

  • TOGGLE – changes the state of a Relay or Group; if this is the first action, it sets a pushbutton’s ON or OFF event state
  • OFF->ON – turns a Relay or Group ON when an OFF event is received
  • OFF->OFF – turns a Relay or Group OFF when an OFF event is received
  • SELECT Device [CHANGE] and press ENTER.
  • Select the Relay(s) or Group to be controlled and then Press ENTER
  • SELECT Action #2 [Add Action] and press ENTER. Repeat the above steps to add additional actions to the Preset
  • Scroll down and select [SAVE] and press ENTER to finish

WORKING WITH PRIORITIES
The EX-MAX H Series Panel supports an array of four priority levels for Inputs and Schedules with Master being the highest priority. The most commonly used are Low and High with Normal being the panel wide default. Think of these as a vertical array with 4 priority “slots”. Each Relay has its own “priority array” where each slot can be populated with an ON or OFF state. The current state of the Relay will always be the state in highest slot. Priorities are persistent and are continuously evaluated to determine the relay state. For example, a relay that is scheduled ON by a Schedule at Low priority will not turn ON after a photocell input with an OFF Priority set at Normal has previously turned it off. This can be very useful, especially when combining Photocell and Schedule control where the Schedule is turning outdoor lights ON near dawn in the morning.

  • Slot 1 Master N/A
  • Slot 2 High OFF
  • Slot 3 Normal ON
  • Slot 4 Low N/A

Some inputs can be set to enable Temporary Priority. This creates a priority “one shot” ON or OFF event where the priority is not persistent. A Temporary Priority controls the relay at one of the slot levels but then is immediately is cleared out.

SYSTEM TOOLS
Scroll down to System Tools and press ENTER to access the SYSTEM TOOLS menu

MANUAL CONTROL

  • Use the UP and DOWN arrow keys to make a selection and press ENTER
  • Use the UP and DOWN arrow keys to choose an item to control
  • Use the UP and DOWN arrow keys to turn the item ON and OFF
  • Press the ESC key to back out of this function

SYSTEM STATUS
This feature is useful in determining if various control features are working as expected. Choose an item from the menu and press ENTER to see the status.

SAVE/RESTORE PROGRAM
This feature is used to save the program or back up the user programming. The system allows the saving of up to three versions of panel programming in internal memory. Most useful is the ability to save the program to an SD card for safe storage away from the panel.

BACKING UP PROGRAM

  • Insert an SD card into the slot in the controller
  • Choose Export Program
  • Use the alphanumeric keypad to name the file
  • Scroll to [SAVE] and press ENTER to save the file to the SD card

RESTORING THE PROGRAM

  • Insert the SD card with the back-up panel program into the slot in the controller
  • Choose Import Program
  • Select the file and press enter to restore the program

PRIORITIES/MASKING
Use this feature to check or edit the priority and masking settings made during the programming of Inputs and Schedules

ACCESS CONTROL
Use this feature to create and manage passwords for users. User #1 is always set to Master level. Additional users can be set to Limited or View Only access.

DIAGNOSTICS
Use to check the status of the battery backup for the memory and communication status

UPDATE FIRMWARE
Can be used to install a newer firmware version in the panel. Contact factory for additional information.

CONTROLLER VERSION
Provides technical information about the panel. Contact factory for additional information.

Leviton Manufacturing Co., Inc. Lighting & Controls
10385 SW Avery Street, Tualatin, OR 97062 tel 800-736-6682 tech line (6:00AM-4:00PM PT Monday-Friday) 800-954-6004

Leviton Manufacturing Co., Inc. Global Headquarters
201 North Service Road, Melville, NY 11747-3138 tel 800-323-8920 tech line (8:00AM-10:00 PM ET Mon-Fri, 9:00 AM-7:00 PM ET Sat, 9:00 AM-5:00PM ET Sun) 800-824-3005

Visit our website at: www.leviton.com/ezmax
© 2023 Leviton Manufacturing Co. Inc. All rights reserved. Subject to change without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Leviton User Manuals

Related Manuals