MOXA RKS-G4028 Series Industrial Rackmount Switch Installation Guide
- June 4, 2024
- MOXA
Table of Contents
MOXA RKS-G4028 Series Industrial Rackmount Switch
Technical Support Contact Information www.moxa.com/support
Package Checklist
The Moxa RKS-G4028/RKS-G4028-L3 industrial rackmount switch is shipped with
the following items. If any of these items are missing or damaged, please
contact your customer service representative for assistance.
- RKS-G4028/RKS-G4028-L3 switch
- 4 protective caps for unused SFP ports (only for RKS-G4028-GS models)
- 2 rackmount ears
- 8 round stickers for module screws
- Quick installation guide (printed)
- Warranty card
Panel Layouts
Front View
RKS-G4028-4GS Series
RKS-G4028-4GT Series
Rear View
- System status LEDs
- MicroSD card socket cover
- Reset button
- USB host (type A)
- Console port (RS-232, RJ45)
- Module 1
- Module 2 socket
- Module 3 socket
- Module 4 socket
- Relay output
- EPS (external power supply) inputs
- Power input 1 for 110/220 VDC/VAC
- Power input 2 for 110/220 VDC/VAC
- Model name
- Power input 1 for 24/48 VDC
- Power input 2 for 24/48 VDC
- Grounding connector screw
- System status LEDs
- Module 1 status LEDs
- Module 2 status LEDs
- Module 3 status LEDs
- Module 4 status LEDs
Dimensions
RM-G4000 Ethernet Interface Modules
WARNING: When end users are using Optical SFP Communications modules, these must be limited to Laser Class 1.
WARNING: Use of the controls or adjustments or the performance of procedures other than those specified herein may result in hazardous radiation exposure.
CLASS 1 LASER PRODUCT
Grounding the Moxa Industrial Rackmount Switch
Grounding and wire routing help limit the effects of noise due to
electromagnetic interference (EMI). Run the ground connection from the ground
screw to the grounding surface prior to connecting devices.
NOTE Using a shielded cable achieves better electromagnetic compatibility.
Connecting the Power Inputs
The RKS-G4028 Series switches support various types of power supply.
- LV models provide one 24/48 VDC power input
- 2LV models provide two 24/28 VDC power inputs
- HV models provide one 110/220 VDC/VAC power input
- 2HV models provide two 110/220 VDC/VAC power inputs
- PoE models provide 1 EPS (external power supplies) with 48 VDC power inputs
Wiring Requirements
WARNING
Do not disconnect modules or wires unless power has been switched off or the
area is known to be non-hazardous. The device may only be connected to the
supply voltage shown on the type plate. The device is designed for operation
with a Safety Extra-Low Voltage (SELV) or an isolated power supply, which
means that they may only be connected to the supply voltage connections and to
the signal contact with a SELV or an isolated power supply in compliance with
IEC 62368-1/EN 62368-1/UL 62368-1 or UL 61010.
Power Terminal Blocks
The connection for EPS (external power supply) / PWR1 (power supply 1) and
PWR2 (power supply 2) are located on the front panel as shown below.
PoE Models
HV Models
LV Models
PoE Models Power Terminal Blocks
- Insert the negative/positive (-/+) DC wires into the terminals.
- Insert the terminal block connector prongs into the terminal block receptor.
HV Models Power Terminal Blocks
- Insert the line/neutral/ground (L/N/Ground) AC/DC wires into the terminals.
- Insert the terminal block connector prongs into the terminal block receptor.
LV Models Power Terminal Blocks
- Insert the negative/positive (-/+) DC wires into the terminals.
- Insert the terminal block connector prongs into the terminal block receptor.
NOTE In order to have higher levels of protection against surge, it is suggested to install a surge protector in front of the power input of the PoE powered device so that it is suitable for use in IEC 61850 conditions.
NOTE When wiring the power input, we suggest using the cable type – AWG (American Wire Gauge) 16-20 (1.31-0.519 mm2) and the corresponding pin type cable terminals. The rated temperature of wiring should be at least 105°C.
NOTE When wiring the PoE power input, we suggest using the cable type – AWG (American Wire Gauge) 16 (1.31 mm2) and the corresponding pin type cable terminals. The rated temperature of wiring should be at least 105°C.
NOTE When wiring the grounding connector screw, we suggest using the cable type – AWG (American Wire Gauge) 16 (1.31 mm2) and the corresponding pin type cable terminals. The rated temperature of wiring should be at least 105°C.
NOTE When HV models are connected with an AC power source, please make sure the Ground wire is well connected. NOTE When your purchase a device with two power modules, both power units will be activated simultaneously, which will enable power redundancy.
NOTE The reverse power input connection will not activate the device or PoE input.
Wiring the Relay Contact
Each power module has one relay output that can be used to detect user-
configured events. Two wires are attached to the relay pins with ‘Normally
Closed’ and ‘Normally Open’ options.
- Insert the wires into the terminals.
- Insert the terminal block connector prongs into the terminal block receptor.
FAULT:
The relay contact of the 2-pin terminal block connector is used to detect
user-configured events. The two wires attached to the fault contacts form an
open circuit when a user-configured event is triggered. If a user-configured
event does not occur, the fault circuit remains closed.
USB Connection
Use Moxa’s USB Automatic Backup Configurator ABC-02-USB to connect to the
USB host port to backup and restore configuration files, auto-load
configuration files, upgrade firmware, and backup system log files.
Type A
Console Port Connection
The RKS device has one RJ45 console port (RS-232), located on the front
panel. Use an RJ45-based cable to connect the RKS’s console port to your PC’s
COM port. You may then use a console terminal program, such as Moxa PComm
Terminal Emulator, to access the RKS device that has a baud rate of 115200.
Refer to the following table figure for the pin definition.
Pin | Description |
---|---|
1 | – |
2 | – |
3 | – |
4 | TxD |
5 | RxD |
6 | GND |
7 | – |
8 | – |
The Reset Button
Depress the Reset button for five continuous seconds to load the factory
default settings. Use a pointed object, such as a straightened paper clip or
toothpick, to depress the Reset button. When you do so, the STATE LED will
start to blink about once per second. Continue to depress the STATE LED until
it begins blinking more rapidly; this indicates that the button has been
depressed for five seconds and you can release the Reset button to load
factory default settings.
NOTE Do NOT power off the switch when loading default settings
Placing the Round Stickers on Module Screws
Moxa offers eight round stickers in the shipment package. These stickers are
to be placed on the screws of the modules to avoid unauthorized persons
accessing the modules. If the stickers are broken, users will know the modules
have been accessed by unauthorized persons. The figure below highlights the
locations of the screws.
Follow these steps to place the stickers.
- Use a cloth to clean the surface of the screws with 75% alcohol solution.
- We suggest you use a tweezer to place the stickers.
- Press the stickers down with 15PSI (pound per square inch) for at least 15 seconds.
- Keep the device at room temperature for 24 hours before deploying the devices in harsh environments.
NOTE
- Place the stickers carefully as they are thin and fragile.
- The ideal environment for the stickers to be stored in is 22°C (72°F) and 50% relative humidity.
- Keep the extra two stickers in a safe place so that no unauthorized persons can access them.
LED Indicators
The front/rear panels of the RKS-G4028 switch contains several LED indicators.
The function of each LED is described in the table below.
LED | Color | State | Description |
---|
System LEDs
P1 (PWR1)| Amber| On| Power is being supplied to the main module’s
power input PWR1.
Off| Power is not being supplied to the mainmodule’s power input PWR1.
P2 (PWR2)| Amber| On| Power is being supplied to the main module’s
power input PWR2.
Off| Power is not being supplied to the main module’s power input PWR2.
S (STATE)| Green| On| The system passed the self-diagnosis test on
boot up and is ready to run.
Blinking (1Hz)
|
- System service initialization.
- When pressing the reset button for 5 seconds to reset to factory default setting.
Blinking (4Hz)|
- After pressing the reset button for 5 seconds and the system is preparing to do a factory reset.
- When the external storage ABC-02 automatic backup device is connected to the switch.
Red| On| The system has initially failed in the boot-up process.
F (FAULT)| Red| On|
- Network loop is detected when loop protection is enabled.
- The relay contact is triggered.
- External storage Loading/Saving has failed.
- The port is being disabled because it has exceeded the ingress rate limit of the shutdown mode.
- Invalid Ring port connection.
| | Off| When the system has successfully booted up and no events have been
triggered.
M/H (MSTR/ HEAD)| Green| On| The switch is set as the Master of the Turbo
Ring, or as the Head of the Turbo Chain, or as the Root of the RSTP.
| | Blinking|
- The switch has become the Master of the Turbo Ring after the Turbo Ring has gone down.
- The switch is set as the Head of the Turbo Chain and the Turbo Chain has gone down.
- The switch is set as the Turbo Ring’s Member and the corresponding Ring port is down.
- The switch is set as the Turbo Chains’ Member/Tail and the corresponding Head-end Chain port is down.
| | Off| When the switch is not the Master/Head/Root of this Turbo Ring/Turbo
Chain/RSTP Ring.
C/T (CPLR/ TAIL)| Green| On|
- The switch’s ring coupling or dual homing function is enabled.
- The switch is set as the Tail of the Turbo Chain.
| | Blinking|
- The switch is set as the Tail of Turbo Chain and the Chain has gone down.
- The switch is set as Turbo Chain’s Member/Head and the corresponding Tail-end Chain port has gone down.
| | Off| When the switch disables the coupling or the Tail of Turbo Chain.
SYNC| Amber| On| The PTP function is enabled.
| | Blinking| The switch receives sync packets but the time has not converged
yet.
| Green| On| The PTP function has successfully converged.
EPS
(External Power Supply)
| Am ber| On| Normal operation.
| | Off| No external power supply for PoE.
M1 Copper (10/100/
1000 Mbps, 4GT model only)
| Green| On| When the port is active and links at 1,000 Mbps.
| | Blinking| When the port’s data is being
transmitted at 1,000 Mbps.
| | Off| When the port is inactive or link down.
| Amber| On| When the port is active and links at 10/100 Mbps.
| | Blinking| When the port’s data is being
transmitted at 10/100 Mbps.
| | Off| When the port is inactive or link down.
M1 SFP (100/1000
Mbps, 4GS model only)
| Green| On| When the port is active and links at 1,000 Mbps.
| | Blinking| When the port’s data is being transmitted at 1,000 Mbps.
| | Off| When the port is inactive or link down.
| Amber| On| When the port is active and links at 100 Mbps.
| | Blinking| When the port’s data is being transmitted at 100 Mbps.
| | Off| When the port is inactive or link down.
LEDs for RM-G4000 Modules RM-G4000-8GTX/8GSFP
LED | Color | State | Description |
---|
Copper (10/100/ 1000
Mbps)
| ****
Green
| On| The corresponding port’s 1000 Mbps link is active.
Blinking| Data is being transmitted at 1000 Mbps.
Off| The corresponding port’s link is inactive.
Amber
| On| The corresponding port’s 10/100 Mbps link is active.
Blinking| Data is being transmitted at 10/100 Mbps.
Off| The corresponding port’s link is
inactive.
SFP (100/1000
Mbps)
| ****
Green
| On| The corresponding port’s 1000 Mbps link is active.
Blinking| Data is being transmitted at 1000 Mbps.
Off| The corresponding port’s link is inactive.
Amber
| On| The corresponding port’s 100 Mbps link is active.
Blinking| Data is being transmitted at 100 Mbps.
Off| The corresponding port’s link is inactive.
RM-G4000-8TX/8SFP/6MSC/6MST/6SSC/4MSC2TX/4MST2TX/ 4SSC2TX/2MSC4TX/2MST4TX/2SSC4TX
LED | Color | State | Description |
---|
Copper (10/100
Mbps)
| ****
Green
| On| The corresponding port’s 100 Mbps link is active.
Blinking| Data is being transmitted at 100 Mbps.
Off| The corresponding port’s link is inactive.
Amber
| On| The corresponding port’s 10 Mbps link is active.
Blinking| Data is being transmitted at 10 Mbps.
Off| The corresponding port’s link is inactive.
Fiber (10/100
Mbps)
| ****
Green
| On| The corresponding port’s 100 Mbps link is active.
Blinking| Data is being transmitted at 100 Mbps.
Off| The corresponding port’s link is inactive.
Amber
| On| The corresponding port’s 10 Mbps link is active.
Blinking| Data is being transmitted at 10 Mbps.
Off| The corresponding port’s link is inactive.
RM-G4000-8GPoE
LED | Color | State | Description |
---|
Copper (10/100/ 1000
Mbps)
| ****
Green
| On| The corresponding port’s 1000 Mbps link is active.
Blinking| Data is being transmitted at 1000 Mbps.
Off| The corresponding port’s link is inactive.
Amber
| On| The corresponding port’s 10/100 Mbps link is active.
Blinking| Data is being transmitted at 10/100
Mbps.
Off| The corresponding port’s link is inactive.
PoE/ PoE+/ PoE++
| ****
Green
| On| When the port is connected to an IEEE 802.3bt powered device (PD).
Off|
- Power is not being supplied to a powered device (PD).
- The port is not connected to an IEEE 802.3bt/at/af standard powered device (PD).
Amber
| On| When the port is connected to an IEEE 802.3af/at powered device (PD).
Blinking| PoE power has been shut off because power budget is low.
Off|
- Power is not being supplied to a powered device (PD).
- The port is not connected to an IEEE 802.3bt/at/af standard powered device (PD).
RM-G4000-8PoE
LED | Color | State | Description |
---|
Copper (10/100/ 1000
Mbps)
| ****
Green
| On| The corresponding port’s 100 Mbps link is active.
Blinking| Data is being transmitted at 100 Mbps.
Off| The corresponding port’s link is inactive.
Amber
| On| The corresponding port’s 10 Mbps link is active.
Blinking| Data is being transmitted at 10 Mbps.
Off| The corresponding port’s link is inactive.
PoE/ PoE+/ PoE++| **** Green| On| When the port is connected to an
IEEE 802.3bt powered device (PD).
Off|
- Power is not being supplied to a powered device (PD).
- The port is not connected to an IEEE 802.3bt/at/af standard powered device (PD).
Amber| On| When the port is connected to an IEEE 802.3af/at powered device
(PD).
Blinking| PoE power has been shut off because
power budget is low.
Off|
- Power is not being supplied to a powered device (PD).
- The port is not connected to an IEEE 802.3bt/at/af standard powered device (PD).
Specifications
Input/Output Interface
Alarm Contact Channels| 1 relay output with current carrying capacity of 2 A @
24 VDC
Ethernet Interface
10/100/1000BaseT
(X) Ports (RJ45 connector)
| RKS-G4028-4GT Models: 4
RKS-G4028-L3-4GT Models: 4
100/1000BaseSFP)| RKS-G4028-4GS Models: 4
RKS-G4028-L3-4GS Models: 4
RKS-G4028-PoE-4GS Models: 4
RKS-G4028-L3-PoE-4GS Models: 4
Modules| There are 3 module slots on the switch. Users can select different
types of m odules to insert into the switch. The modules that can be selected
include 8- port/6-port modules with 10/100/1000BaseT(X), 10/100BaseT(X),
100/1000BaseSFP, or 100BaseFX(SC/ST connector) interfaces.
Standards| IEEE 802.1D-2004 for Spanning Tree Protocol IEEE 802.1p for Class
of Service
IEEE 802.1Q for VLAN Tagging
IEEE 802.1s for Multiple Spanning Tree Protocol IEEE 802.1w for Rapid Spanning
Tree Protocol IEEE 802.1X for Authentication
IEEE 802.3 for 10BaseT
IEEE 802.3ab for 1000BaseT(X)
IEEE 802.3ad for Port Trunk with LACP
IEEE 802.3u for 100BaseT(X) and 100BaseFX IEEE 802.3x for flow control
IEEE 802.3z for 1000BaseSX/LX/LHX/ZX
IEEE 802.3bt for Power over Ethernet
PoE Information
Total PoE Power Budget| 300 W
PoE Output Power| For each PoE port: 15.4 W in IEEE 802.3af, 30 W in IEEE
802.3at*, 90 W in IEEE 802.3bt
The power consumption tested for UL certification.
Power Parameters
Input Voltage| RKS-G4028-LV Models: 24/48 VDC
RKS-G4028-2LV Models: 24/48 VDC (redundant dual inputs)
RKS-G4028-HV Models: 110/220 VAC, 110/220 VDC
RKS-G4028-2HV Models: 110/220 VAC, 110/220
VDC (redundant dual inputs)
PoE Models: 48 VDC (for PoE system)
Operating Voltage| RKS-G4028-LV Models: 18 to 72 VDC
RKS-G4028-2LV Models: 18 to 72 VDC
RKS-G4028-HV Models: 85 to 264 VAC, 88 to 300 VDC
RKS-G4028-2HV Models: 85 to 264 VAC, 88 to 300 VDC
PoE Models: 46 to 57 VDC (for PoE system)
Overload Current Protection| Supported
Reverse Polarity
Protection
| Supported
Input Current| RKS-G4028-LV/2LV models:
- Max. 2.53 A @ 24 VDC
- Max. 1.25 A @ 48 VDC RKS-G4028-HV/2HV models:
- Max. 0.55 A @ 110 VDC
- Max. 0.29 A @ 220 VDC
- Max. 1.01 A @ 110 VAC
- Max. 0.62 A @ 220 VAC
- EPS (only for PoE model):
- Max. 7.50 A @ 48 VDC
Physical Characteristics
IP Rating| IP30
Dim ensions| 440 x 44 x 300 mm (17.32 x 1.73 x 11.81 in)
Weight| RKS-G4028-LV/HV Models: 4,900 g RKS-G4028-2LV/2HV Models: 5,200 g
RKS-G4028-PoE-LV/HV Models: 5,000 g
RKS-G4028-PoE-2LV/2HV Models: 5,300 g RM-G4000-8TX: 300 g
RM-G4000-8SFP: 400 g
RM-G4000-8GTX: 300 g
RM-G4000-8GSFP: 400 g
RM-G4000-6MSC: 400 g
RM-G4000-6MST: 400 g
RM-G4000-6SSC: 400 g
RM-G4000-4MSC2TX: 400 g
RM-G4000-4MST2TX: 400 g
RM-G4000-4SSC2TX: 400 gRM-G4000-2MSC4TX: 400 g
RM-G4000-2MST4TX: 400 g
RM-G4000-2SSC4TX: 400 g
RM-G4000-8PoE: 500 g
RM-G4000-8GPoE: 500 g
Installation| Rack mounting
Environmental Limits
Operating Temperature| -40 to 75°C (-40 to 167°F)
Storage
Temperature (package included)| -40 to 85°C (-40 to 185°F)
Ambient Relative Hum idity| 5 to 95% (non-condensing)
Standards and Certifications
Safety| EN 62368-1, UL 62368-1, UL 61010
EMC| EN 55032/35
EMI| CISPR 32, FCC Part 15B Class A
EMS| IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 35 V/m
IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV
IEC 61000-4-5 Surge: Power: 4 kV; Signal: 4 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
IEC 61000-4-11 DIPs
Power Substation| IEC 61850-3, IEEE 1613
Railway| EN 50121-4
Freefall| IEC 60068-2-32
Shock| IEC 60068-2-27
Vibration| IEC 60068-2-6
Warranty
Warranty Period| 5 years
Details| See www.moxa.com/warranty
Rack Mounting Instructions
-
Elevated Operating Ambient: If installed in a closed or multi- unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, . consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer.
NOTE In order to ensure reliable operations, please make sure the operating temp. of the environment does not exceed the spec. When mounting an RKS-G4028 rack-mounted switch with other operating units in a cabinet without forced ventilation, it is recommended that 1U of space is reserved between each rack-mounted switch and/or device. -
Reduced Air Flo w : Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised.
-
Mechanical Loading: Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading.
-
Circuit Overloading: Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.
-
Reliable Grounding: Reliable grounding of rack-mounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips). Make sure the grounding screw of the device has been connected by a 16 AWG (min.) green-and-yellow wire to the rack, and the protective terminal of the rack has connected to the earth ground.
ATTENTION
When installing the device onto a rack, make sure that the input terminal
block and protective terminal do not connect, or it may cause an electric
shock.
NOTE The rackmount ears can be equipped on the front or rear of Moxa RKS-G4028/RKS-G4028-L3 switch.
Restricted Access Locations
-
This equipment is intended to be used in Restricted Access Locations, such as a computer room, with access limited to SERVICE PERSONAL or USERS who have been instructed on how to handle the metal chassis of
equipment that is so hot that special protection may be needed before touching it. The location should only be accessible with a key or through a security identity system. -
External metal parts of this equipment are extremely hot!! Before touching the equipment, you must take special precautions to protect your hands and body from serious injury.
Patent
https://www.moxa.com/doc/operations/Moxa_Patent_Marking.pdf
ATTENTION
- To protect against the risk of fire, only replace the fuse with one that has the same type and rating.
- It is recommended to incorporate a readily accessible disconnect device into the building installation wiring. Importantly, ensure the power supply is disconnected before performing any maintenance.
- This equipment is designed to connect the earthed conductor of the D.C supply circuit to the equipment’s’ earthing conductor.
- It is recommended to keep the PoE network indoors when using Information Technology Equipment.
Read User Manual Online (PDF format)