DUCTABLE FAN COIL UNITS 42CT

The Carrier 42CT is available in different sizes with 2-pipe or 4-pipe coils, with an air flow range from 222 m /h to 2660 m /h, a total cooling capacity range from 1,2 kW to 14,5 kW and a heating capacity range from 1,6 kW to 16,2 kW.

GENERAL

  • Ductable fan coil units for horizontal concealed ceiling applications
  • Reliable and economical solution for buildings, hotels, hospitals, offices or any other required commercial or residential applications
  • Compact design with hydrophilic blue fin coil
  • Low height for all sizes with rear plenum
  • 3-speed AC fan motors for the right amount of conditioned air
  • Washable standard filters with easy access
  • Standard supply flange
  • Standard rear plenum
  • Optional extra extended drain pan with stainless steel alternative
  • Optional ISO Coarse %40 filter
  • Factory installed electrical box
  • Certified performance
  • User-friendly cloud base selection software for quick selections

MODEL NUMBER NOMENCLATURE

42CT is easy to configure with its standard features to speed up the ordering process. Standard washable filter, factory installed rear plenum and rectangular supply flange gives the advantage to create and track the coding easily.

TECHNICAL DESCRIPTION

CASING

The casing is made of galvanised sheet steel with high-efficiency internal lining for optimised thermal and sound insulation of the unit. The fan coil unit is available with Euroclass level B-s2-d0 insulation (in compliance with EN13501-1). To minimize the dimensions, the units are equipped with high- efficiency heat exchangers with very high cooling capacity. The condensate drain pan height is optimised. Mounting holes and slots quicken hanging operations.

Coil

Unit coil using the latest developed wide seam blue hydrophilic aluminum fin, advanced mechanical tube expanding process, ensure copper tube optimally contacts with aluminium fin. Wide seam hydrophilic aluminium fin provides sufficient heat transfer channel for heat exchanger, wide impeller provide uniformly air velocity environment for heat transfer.

It makes the heat transfer more complete, which ensures the cooling capacity per input power of 42CT outperforms other similar products. Metal sheet casing prevents any damage on header and coil connections.

  • Aluminium fins mechanically bonded by expansion onto copper tubes
  • With 7 mm copper tubes and special coil design, unit can supply high cooling and heating capacity with minimized dimensions even in bigger size models
  • ¾” threaded female water inlet and outlet connections for all sizes
  • Operating pressure of 16 bar

Maximum hot water inlet temperature

  • 4-pipe application: 90°C
  • 2-pipe application: 90°C

Fan

42CT unit equipped with newly designed wide and large diameter impeller, low speed forward multi-blade. The fan casing is strengthened with reinforcing ribs for additional strength. It adopts NSK bearings, ensuring small vibration and low noise in operation. One to four-wheel fans depending on the unit size.

Electric Motor

The 42CT has 3 speed fan motor with totally enclosed casing structure and it has great advantages in efficiency, noise and energy saving.

Fan motors of all types are

  • Asynchronous motors, 4 poles with internal overload protection
  • Permanent split capacitor
  • Power supply: 220V-240V/1Ph/50Hz
  • Level of Protection: IP20
  • Class B insulation

Electrical Box

Electrical Box is standard in 42CT for all models. The unit is factory-fitted with an electrical box with the 3 standard speeds connected to a terminal strip. With the electrical box, the installer can connect the unit to a terminal board. The electrical box can be opened with a screw driver. Electrical box can be mounted to both sides of the units thanks to its long wiring.

Condensate Drain Pan

A condensate drain pan is cold roll steel with powder coating and drain pan has its own angled surface so that condensate can be drain out smoothly. Drain pan design enhances the strength of drain pan, and avoid drain pan deformation in transportation.

  • The drain connection diameter is 3/4’’ threaded nippel
  • 6 mm flexible elastomeric rubber foam insulation
  • Fire rating B-s2-d0 in compliance with EN13501-1
  • Stainless steel and extended lenght drain pans are optional

Plenums

Factory mounted rear air plenum is standard in all sizes and models of the unit for a better quality and appearance. Along with the air plenum box, filter is also supplied in standard and ISO Coarse %40 filter (in compliance with ISO 16890) is optional for a better indoor air quality. Unit can also be supplied with bottom plenum option.

Air Filter

All the models are supplied with standard factory installed washable nylon mesh filter with aluminium frame. With its special design, filters can be removed on both rear or bottom side of the unit easily. The unit can also be supplied with ISO Coarse %40 filter (in compliance with ISO 16890) for a better air quality as an optional.

Filter Access

Filters can be easily removed from both the back and the bottom side of the unit without any necessity of extra equipment thanks to the clamps.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-6

  • Unit with rear plenumCarrier-42CT-Ductable-Fan-Coil-Unit-FIG-7
  • Unit with bottom plenum

DIMENSIONS & WATER COIL CONNECTIONS

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-8

SIZE

| A

(Standard)

| B

(Extended)

|

C

|

D

|

E

|

F

---|---|---|---|---|---|---
02| 703| 803| 492| 490| 460| 546
03| 843| 943| 632| 630| 600| 686
04| 923| 1023| 712| 710| 680| 766
05| 1003| 1103| 792| 790| 760| 846
06| 1163| 1263| 952| 950| 920| 1006
08| 1483| 1583| 1272| 1270| 1240| 1326
10| 1533| 1633| 1322| 1320| 1290| 1376
12| 1733| 1833| 1522| 1520| 1490| 1576
14| 2103| 2203| 1892| 1890| 1860| 1946

  • Standard 2 pipe unit with rear plenumCarrier-42CT-Ductable-Fan-Coil-Unit-FIG-10
  • Standard 4 pipe unit with rear plenum
  1. For the unit size 14, the dimension is 54 mm
  2. For the unit size 14, the dimension is 118,5 mm
  • Standard 2 pipe unit with bottom plenumCarrier-42CT-Ductable-Fan-Coil-Unit-FIG-11
  • Standard 4 pipe unit with bottom plenumCarrier-42CT-Ductable-Fan-Coil-Unit-FIG-12
  1. For the unit size 14, the dimension is 54 mm
  2. For the unit size 14, the dimension is 118,5 mm

PERFORMANCE DATA

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-13

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-14

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-15

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-16

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-18

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-19

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-20

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-21

Fan speed: L = Low, M = Medium, H = High

  • Eurovent standard cooling conditions: air inlet temperature 27°C dry bulb/19°C wet bulb, water inlet/outlet temperature 7°C/12°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 45°C/40°C,
  • Eurovent standard heating conditions: air inlet temperature 20°C dry bulb/15°C wet bulb, water inlet/outlet temperature 65°C/60°C.

ELECTRICAL DATA

Fan operation 230V/1ph/50Hz and values are given for units with standard filter.

  • 42CT 2 Pipe 3 Rows Models
  • 42CT 2 Pipe 4 Rows Models
  • 42CT 4 Pipe 3+1 Rows Models

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-22

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-23

Carrier-42CT-Ductable-Fan-Coil-Unit-FIG-24

  • 42CT 2 Pipe 3 Rows Models
  • 42CT 2 Pipe 4 Rows Models
  • 42CT 4 Pipe 3+1 Rows Models

42CT0S30S

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,39| 89,68| 584|
0,38| 87,80| 556| 10
0,38| 86,76| 542| 15
0,37| 84,47| 510| 25
0,36| 83,19| 493| 30
0,35| 80,26| 455| 40
**| 0,43| 99,35| 785|
0,42| 96,23| 741|
10
0,41| 94,68| 719|
15
0,39| 90,05| 653|
30
0,38| 86,91| 607|
40
0,36| 83,68| 562|
so
| 0,49| 113,64| 1072|
0,48| 110,13| 996|
10
0,47| 108,36| 960|
15
0,45| 102,99| 854|
30
0,42| 95,61| 722|
so
0,40| 91,78| 660|
60**

42CTOS40S

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,39| 89,58| 583| 0
0,38| 87,62| 554| 10
0,38| 86,53| 538| 15
0,37| 84,10| sos| 25
0,36| 82,71| 487| 30
0,35| 79,46| 445| 40
**| 0,43| 99,49| 787| 0
0,42| 96,35| 743|
10
0,41| 94,79| 721|
15
0,39| 90,05| 653|
30
0,38| 86,79| 606|
40
0,36| 83,40| 558|
so
| 0,49| 113,17| 1062|
0
0,48| 109,93| 992|
10
0,47| 108,27| 958|
15
0,45| 103,12| 857|
30
0,42| 95,74| 725|
so
0,40| 91,80| 660|
60**

42CT0S31S

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,39| 89,52| 582| 0
0,38| 87,47| 552| 10
0,38| 86,33| 535| 15
0,36| 83,72| 500| 25
0,36| 82,21| 480| 30
0,34| 78,54| 434| 40
**| 0,43| 99,13| 782| 0
0,42| 95,86| 736|
10
0,41| 94,22| 713|
15
0,39| 89,22| 641|
30
0,37| 85,73| 591|
40
0,36| 82,05| 539|
so
| 0,49| 112,03| 1037|
0
0,47| 108,65| 966|
10
0,46| 106,90| 930|
15
0,44| 101,41| 825|
30
0,41| 93,36| 685|
50
0,39| 88,97| 616|
60**

42CT0630S

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,42| 97,07| 604|
0,41| 95,36| 564| 10
0,41| 93,97| 544| 15
0,39| 90,62| 508| 25
0,39| 88,77| 490| 30
0,37| 84,85| 456| 40
**| 0,51| 116,55| 934|
0,49| 112,79| 889|
10
0,48| 110,85| 866|
15
0,45| 104,61| 792|
30
0,43| 99,99| 738|
40
0,41| 94,87| 679|
so
| 0,54| 124,72| 1176|
0,53| 120,83| 1083|
10
0,52| 118,62| 1037|
15
0,48| 111,01| 900|
30
0,43| 98,55| 720|
SO
0,40| 91,33| 632|
60**

42CT06405

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,42| 97,11| 608| 0
0,42| 95,67| 569| 10
0,41| 94,37| 550| 15
0,40| 91,16| 513| 25
0,39| 89,35| 495| 30
0,37| 85,47| 461| 40
**| 0,50| 114,88| 914| 0
0,48| 111,46| 873|
10
0,48| 109,68| 852|
15
0,45| 103,96| 784|
30
0,43| 99,71| 735|
40
0,41| 94,98| 681|
so
| 0,54| 124,26| 1164|
0
0,53| 121,44| 1097|
10
0,52| 119,86| 1062|
15
0,50| 114,38| 957|
30
0,46| 105,12| 810|
SO
0,43| 99,53| 733|
60**

42CT06315

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,42| 96,85| 594| 0
0,41| 94,96| 558| 10
0,41| 93,63| 540| 15
0,39| 90,51| 507| 25
0,39| 88,79| 490| 30
0,37| 85,13| 458| 40
**| 0,49| 112,15| 882| 0
0,47| 108,77| 841|
10
0,47| 107,01| 820|
15
0,44| 101,36| 754|
30
0,42| 97,19| 706|
40
0,40| 92,59| 654|
so
| 0,53| 121,35| 1095|
0
0,51| 118,27| 1030|
10
0,51| 116,57| 997|
15
0,48| 110,86| 897|
30
0,44| 101,65| 761|
SO
0,42| 96,31| 692|
60**

42CT0830S

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,62| 142,24| 862|
0,59| 135,19| 789| 10
0,58| 132,52| 760| 15
0,56| 128,30| 709| 25
0,55| 126,60| 686| 30
0,54| 123,78| 644| 40
**| 0,75| 172,31| 1337|
0,71| 163,17| 1253| 10
0,69|
159,33| 1215| 15
0,65|
149,97| 1108| 30
0,63|
145,11| 1042| 40
0,61| 141,06| 981|
SO
| 0,83| 191,98| 1750|
0,80| 184,57| 1674|
10
0,79| 181,19| 1635|
15
0,75| 171,97| 1513|
30
0,70| 161,01| 1332|
SO
0,68| 155,76| 1233|
60**

42CT08405

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,61| 141,11| 850| 0
0,59| 134,84| 785| 10
0,58| 132,38| 758| 15
0,56| 128,41| 710| 25
0,55| 126,78| 688| 30
0,54| 124,04| 648| 40
**| 0,72| 165,90| 1280| 0
0,69|
158,72| 1208| 10
0,68|
155,61| 1175| 15
0,64|
147,81| 1080| 30
0,62| 143,62|
1021| 40
0,61| 140,06| 965|
SO
| 0,80| 183,31| 1660|
0
0,77| 177,45| 1589|
10
0,76| 174,70| 1552|
15
0,73| 167,02| 1436|
30
0,68| 157,54| 1267|
SO
0,66| 152,92| 1176|
60**

42CT08315

| Current| Power Consumption| Air Flow| ESP
A| W| m 3 /h| Pa
| 0,61| 140,82| 847| 0
0,59| 134,66| 783| 10
0,57| 132,23| 756| 15
0,56| 128,32| 709| 25
0,55| 126,71| 687| 30
0,54| 124,00| 648| 40
**| 0,72| 166,27| 1283| 0
0,69|
158,84| 1210| 10
0,68|
155,66| 1175| 15
0,64| 147,73| 1079|
30
0,62|
143,51| 1019| 40
0,61| 139,95|
963| 50
| 0,80| 185,11| 1680|
0
0,78| 178,75| 1605|
10
0,76| 175,81| 1567|
15
0,73| 167,64| 1446|
30
0,69| 157,73| 1271|
SO
0,67| 152,96| 1176|
60**

  • 42CT 2 Pipe 3 Rows Models
  • 42CT 2 Pipe 4 Rows Models
  • 42CT 4 Pipe 3+1 Rows Models

42CT1030S

.| Current| Power Consumption| Air Flow| ESP
A| W| m1/h| Pa

i

3

.9

| 0,75| 173,02| 1067|
0,74| 169,10| 1034| 10
0,73| 167,30| 1016| 15
0,71| 163,76| 976| 25
0,70| 161,94| 953| 30
0,69| 157,90| 900| 40
**| 0,86| 196,72| 1487|
0,83| 190,53| 1434| 10
0,82| 187,53| 1406| 15
0,78| 178,54| 1314| 30
0,75| 172,23| 1245| 40
0,72| 165,32| 1166| SO
| 0,95| 217,38| 1992| 0
0,92| 211,72| 1907| 10
0,91| 208,96| 1863| 15
0,87| 200,83| 1733|
30
0,83| 190,13| 1555|
50
0,80| 184,74| 1465|
60**

42CT1040S

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 0,75| 172,64| 1064|
0,73| 168,99| 1033| 10
0,73| 167,30| 1016| 15
0,71| 164,00| 979| 25
0,71| 162,32| 958| 30
0,69| 158,72| 911| 40
**| 0,83| 191,74| 1445|
0,81| 186,32| 1394| 10
0,80| 183,65| 1368| 15
0,76| 175,50| 1282| 30
0,74| 169,77| 1217| 40
0,71| 163,54| 1146| SO
| 0,91| 208,35| 1854| 0
0,89| 203,73| 1780| 10
0,88| 201,44| 1743| 15
0,85| 194,62| 1630| 30
0,81| 185,48| 1477|
50
0,79| 180,84| 1400|
60**

42CT1031S

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 0,75| 173,39| 1070|
0,74| 169,48| 1037| 10
0,73| 167,69| 1020| 15
0,71| 164,21| 981| 25
0,71| 162,43| 959| 30
0,69| 168,54| 908| 40
**| 0,85| 194,97| 1473|
0,82| 189,24| 1422| 10
0,81| 186,44| 1395| 15
0,77| 177,98| 1308| 30
0,75| 172,02| 1243| 40
0,72| 165,51| 1168| SO
| 0,92| 211,68| 1906| 0
0,90| 207,00| 1832| 10
0,89| 204,67| 1795| 15
0,86| 197,70| 1681| 30
0,82| 188,28| 1524|
50
0,80| 183,44| 1443|
60**

42CT12305

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 0,97| 223,66| 1500|
0,94| 216,08| 1444| 10
0,92| 212,52| 1415| 15
0,89| 205,49| 1352| 25
0,88| 201,93| 1318| 30
0,85| 194,46| 1242| 40
**| 1,07| 246,74| 2007|
1,04| 238,90| 1929|
10
1,02| 235,17| 1890|
15
0,98| 224,43| 1769|
30
0,95| 217,50| 1687| 40
0,92| 210,64| 1604|
50**


“g

!

:i:

| 1,17| 268,69| 2521|
1,14| 262,42| 2405| 10
1,13| 259,28| 2347| 15
1,09| 249,79| 2172| 30
1,03| 236,84| 1937| SO
1,00| 230,17| 1818| 60

42CT12405

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 0,95| 219,33| 1469|
0,92| 212,55| 1415| 10
0,91| 209,27| 1387| 15
0,88| 202,73| 1325| 25
0,87| 199,39| 1292| 30
0,84| 192,37| 1220| 40
**| 1,04| 238,61| 1926|
1,01| 231,77| 1852|
10
0,99| 228,45| 1815|
15
0,95| 218,78| 1703|
30
0,92| 212,48| 1626|
40**
0,90| 206,21| 1549| SO


“g

!

:i:

| 1,13| 259,82| 2357|
1,10| 254,06| 2250| 10
1,09| 251,17| 2197| 15
1,05| 242,45| 2037| 30
1,00| 230,57| 1826| SO
0,98| 224,49| 1720| 60

42CT1231S

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 0,95| 218,59| 1464|
0,92| 211,99| 1410| 10
0,91| 208,79| 1382| 15
0,88| 202,35| 1322| 2S
0,87| 199,04| 1289| 30
0,84| 192,06| 1217| 40
**| 1,02| 235,51| 1893|
1,00| 229,29| 1825|
10
0,98| 226,24| 1790|
1S**
0,94| 217,24| 1684| 30
0,92| 211,28| 1612| 40
0,89| 205,31| 1538| SO


“g

!

:i:

| 1,11| 254,27| 2254|
1,08| 249,35| 2164| 10
1,07| 246,86| 2118| 15
1,04| 239,21| 1979| 30
0,99| 228,53| 1790| SO
0,97| 222,94| 1693| 60

42CT1430S

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 1,26| 288,68| 1411|
1,20| 276,59| 1364| 10
1,18| 271,27| 1339| 15
1,14| 261,29| 1287| 25
1,11| 256,45| 1259| 30
1,07| 246,69| 1198| 40
**| 1,44| 332,10| 2206|
1,38| 318,10| 2080|
10
1,35| 311,41| 2018|
15
1,27| 292,17| 1831|
30
1,22| 279,86| 1708|
40
1,16| 267,79| 1584|
50**


“g

!

:i:

| 1,57| 361,85| 2683|
1,54| 355,11| 2584| 10
1,53| 351,83| 2533| 15
1,49| 342,15| 2370| 30
1,43| 328,96| 2126| SO
1,40| 321,87| 1987| 60

42CT1440S

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 1,26| 290,06| 1415|
1,21| 278,05| 1370| 10
1,19| 272,82| 1347| 15
1,14| 263,10| 1297| 25
1,12| 258,43| 1270| 30
1,08| 249,16| 1214| 40
**| 1,43| 328,89| 2178|
1,37| 315,44| 2056|
10
1,34| 309,03| 1995|
15
1,26| 290,71| 1817|
30
1,21| 279,07| 1700|
40
1,16| 267,74| 1584|
50**


“g

!

:i:

| 1,57| 360,27| 2660|
1,54| 353,52| 2560| 10
1,52| 350,24| 2507| 15
1,48| 340,59| 2343| 30
1,42| 327,53| 2098| SO
1,39| 320,60| 1962| 60

42CT1431S

| Current| Power Consumption| Air Flow| ESP
A| W| m3/h| Pa
| 1,22| 280,40| 1380|
1,18| 270,40| 1335| 10
1,16| 265,78| 1311| 1S
1,12| 256,88| 1261| 2S
1,10| 252,50| 1235| 30
1,06| 243,61| 1178| 40
**| 1,34| 308,91| 1994|
1,30| 298,19| 1891|
10
1,27| 292,96| 1839|
1S
1,21| 277,64| 1685|
30
1,16| 267,66| 1583|
40
1,12| 257,78| 1482|
50**
| 1,50| 346,10| 2439|
1,48| 340,61| 2343| 10
1,47| 337,86| 2293| 1S
1,43| 329,53| 2137| 30
1,38| 317,74| 1905| SO
1,35| 311,28| 1775| 60

OPERATING LIMITS

Carrier-42CT -Ductable-Fan-Coil-Unit-FIG-1

GUIDE SPECIFICATION

General

System Description

The Carrier 42CT is a new hydraulic ductable fan coil unit suitable for all kind of applications with horizontal installation and available in 2 and 4 pipe versions. Unit should be factory assembled, horizontal type fan coil for suspended ceiling or/and ducted installations. Unit shall be complete with water coil, fan(s), motor(s), drain pan and all required electrical wiring.

Quality Assurance

The unit must be designed, manufactured and tested in a facility with an ISO 9001 certified quality assurance system, an ISO 14001 certified environmental management system, and an ISO 45001 occupational health and safety management system. The unit must be certified by Eurovent and the ongoing validity of the certificate can be checked in the Eurovent website. The unit must comply with the requirements of European regulations and must bear the CE mark. The unit must be tested in operation at the factory before shipment.

Performance

Unit can supply the air flow from 222 m³/h to 2660 m³/h and a total cooling capacity range from 1,2 kW to 14,5 kW and a heating capacity range from 1,6 kW to 16,2 kW. Sound power levels of the units shall be tested in accordance with the requirements of ISO 3741 and shall not exceed 65 dB(A) in medium speed.

Delivery, storage and handling

Each unit shall be individually packaged from point of manufacture. Unit shall be handled and stored in accordance with the manufacturer’s instructions.

Techical Details

Casing

Galvanised sheet steel casing with high efficiency insulation. The insulation used in the fan coil unit should comply with EN13501-1, Euroclass level B-s2-d0. Condensing drain pan is cold roll steel with powder coating with angled surface. Drain connection diameter is ¾” threaded nippel and the insulation is 6 mm flexible elastomeric rubber foam with fire rating B-s2-d0 incompliance with EN13501-1.

Fan and Motor

Unit is equipped with wide diameter impeller with low speed forward multi- blade and strenghtened fan casing. Unit can contain one to four wheel fans depending on size. Unit has asynchronous 3 speed fan motors, 4 poles with internal overload protection and permenant split capacitor. Power supply 220-240V/1Ph/50 Hz. Motor insulation grade is class B, level of protection is IP20. The fan motor assembly must meet the requirements up to 50 Pa of operating pressure in medium speed with standard filter.

Coil

Units coil made of 7 mm copper pipes and wide seam aluminium blue hydrophilic fins that ensures the maximum capacity within the compact design. Metal sheet casing for the protection of header and coil connections. ¾” threaded female water inlet and outlet connections for all sizes. Operating pressure of 16 bar. Maximum hot water inlet temperature is 90°C for both 2 and 4 pipe applications.

Filter

Factory installed washable nylon mesh filter with aluminium frame with standart rear air plenum. Filters can be removed on both rear or bottom side of the unit easily. ISO Coarse %40 filter is optional.

Electrical Box

Factory fitted electrical box is standard with 3 standard speed connection to a terminal strip. The electric box can be connected to the terminal board and it is easy to mount on both side of the unit with its long wiring. The protection class of the electrical box should not be lower than IP67.

  • Order No: 10011, 10.2021
  • Supersedes Order No: 10001, 09.2021

The manufacturer reserves the right to make changes to the product specifications without notice.
The illustrations in this document are for illustrative purposes only and part of any offer for sale or contract.
The manufacturer reserves the right to change the design at any time without notice.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals