LeonLite LitSafe Indoor Exit Sign User Manual

October 30, 2023
LeonLite

Lit Safe Indoor Exit Sign
User ManualLeonLite LitSafe Indoor Exit Sign -
fig

LED Emergency Exit sign User Manual

PACKAGE CONTENT

LeonLite LitSafe Indoor Exit Sign

IMPORTANT SAFETY INSTRUCTIONS

  • Do not use outdoors.
  • Do not let power supply cords touch the hot surfaces.
  • Do not mount near gas or electric heaters.
  • Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or in eyes. flush acid with fresh water and contact a physician immediately.
  • Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  • Do not use this equipment for other than intended use.
  • To prevent risk of electric shock, turn off the power at the main circuit breaker box before installation.
  • This product must be installed in accordance with the applicable installation codes by a person familiar with the construction and operation of the product and the hazards involved. Consult a qualified electrician to ensure correct branch circuit conductor.
  • This product is rated 120/277 VAC and must be connected to a suitable power source
  • The product employs non-replaceable LED light sources.
  • All servicing should be performed by a qualified personnel only.
  • This product is intended for emergency lighting applications such as stairways and hallways. During an electrical power failure. the sign automatically lights up for a minimum of 90 minutes.
  • This product is intended to be used in dry and damp indoor areas only.
  • No liability will be accepted for damages resulting from improper use or non-compliance with these instructions.

INSTALLATION

Flexible conduit only.

  1. Turn off the main power switch before installation.
  2. Push into the holes of the housing (C) to release the front panel (A).
  3. Connect the battery cable. NOTICE: This product is supplied with a battery for use when main power source Is not available. Refer to chapter ”SPECIFICATIONS” for the battery replacement date.

Wall mounting

  1. Drill through the knockouts on the mounting plate (B) for wires and screws, then feed the wires through the center hole.
  2. Use twist-on wire connectors (G) to join the wires to the electrical box. Refer to chapter “WIRING” for more details.
  3. Screw the mounting plate (B) to the electrical box using screws (I) making sure no wires are pinched.
  4. Clip on the front plate (A). Turn on main power source then press the TEST button (J). The emergency sign should dim, and the AC ON indicator goes off.
  5. Insert direction arrow (s) (F)into the front and/or back plate (A) to hide the incorrect exit direction.

Side or ceiling mounting
NOTICE: If you require EXIT signs on both sides of the housing, remove the mounting plate (B) and replace with • the spare front plate (A).

  1. Using a screwdriver, remove the top or side knockout from the housing (C), then feed the wires through the hole, mounting bracket (D) and crossbar (E).
  2. Use twist-on wire connectors (G) to join the wires to the electrical box. Refer to chapter “WIRING” for more details.
  3. Screw the crossbar (E) to the electrical box using screws (H) making sure no wires are pinched, then screw the mounting bracket (D) to the crossbar (E) using screws (I).
  4. Align the clips on mounting bracket (D) to the housing (C) and twist the housing to secure.
  5. Clip on the front plate (A). Turn on power from the mains then press the TEST button (J). The emergency sign should dim, and the AC ON indicator goes off.
  6. Insert direction arrow (s) (F) into the front and/or back plate (A) to hide the incorrect exit direction.

WIHRING

LeonLite LitSafe Indoor Exit Sign - flexible15

WARNING:
Risk of electric shock!

  •  To prevent risk of electric shock, turn off the power at the main circuit breaker box before installation.
  • Connect the black (live) and white (neutral) wires to the building utility for 120 VAC.
  • Connect the orange (live) and white (neutral) wires to the building utility for 277 VAC.
  • Cap off unused wire with wire connector (G).

MAINTENANCE

  1. Battery replacement
    This product is fitted with a Nickel-Cadmium battery which needs to be replaced as specified in chapter “SPECIFICATIONS”.

  2. Product testing
    • In accordance to NFPA 101, this product must be tested monthly for a minimum of 30 seconds and annually for 90 minutes.
    • To test, press the TEST button. The emergency sign should dim, and the AC ON indicator goes off.

SPECIFICATIONS

RATED VOLTAGE: 120/277 VAC 60 Hz
POWER INPUT: 4 W
CURRENT CONSUMPTION: 60 mA
BATTERY TYPE: 1.2 V 1000 mash, AA Nickel-Cadmium
BATTERY REPLACEMENT DATE: 30/5/2024
OPERATING CONDITIONS: 32 °F to 104 °F (0 °C to 40 °C )
NET WEIGHT: approx. 1.41 lbs. (0.64 kg)
DIMENSIONS (W x H x D): approx. 11.61 x 8.19 x 1.77″ (29.5 x 20.8 x 4.5cm)